Pepperl+Fuchs KFD2-RSH-1.2D.FL2, KFD2-RSH-1.2D.FL3 Original Instructions Manual

ISO9001
PL e
3
Functional Safety
Relay Module KFD2-RSH-1.2D.FL2, KFD2-RSH-1.2D.FL3
PROCESS AUTOMATION
ORIGINAL INSTRUCTIONS
With regard to the supply of products, the current issue of the following document is applicable: The General Terms of
Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical
Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the
supplementary clause: "Expanded reservation of proprietorship"
Functional Safety KFD2-RSH-1.2D.FL2, KFD2-RSH-1.2D.FL3
Functional Safety KFD2-RSH-1.2D.FL2, KFD2-RSH-1.2D.FL3
Content
2018-06
3
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Content of this Document. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.4 Standards and Directives for Functional Safe. . . . . . . . . . . . . . . . . . . . 8
3 Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 System Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2 Assumptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.3 Safety Function and Safe State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4 Characteristic Safety Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.5 Useful Lifetime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4 Mounting and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.1 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.3 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.1 Internal Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.2 Proof Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.3 Application Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6 Maintenance and Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7 List of Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2018-06
4
Functional Safety KFD2-RSH-1.2D.FL2, KFD2-RSH-1.2D.FL3
Introduction
1Introduction
1.1 Content of this Document
This document contains safety-relevant information for usage of the device. You need this information to use your product throughout the applicable stages of the product life cycle. These can include the following:
Product identification
Delivery, transport, and storage
Mounting and installation
Commissioning and operation
Maintenance and repair
Troubleshooting
Dismounting
Disposal
The documentation consists of the following parts:
Present document
Instruction manual
•Manual
•Datasheet
Additionally, the following parts may belong to the documentation, if applicable:
EU-type examination certificate
EU declaration of conformity
Attestation of conformity
Certificates
Control drawings
FMEDA report
Assessment report
Additional documents
For more information about Pepperl+Fuchs products with functional safety, see www.pepperl­fuchs.com/sil.
Note!
For full information on the product, refer to the further documentation on the Internet at www.pepperl-fuchs.com.
Functional Safety KFD2-RSH-1.2D.FL2, KFD2-RSH-1.2D.FL3
Introduction
2018-06
5
1.2 Safety Information
Target Group, Personnel
Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the plant operator.
Only appropriately trained and qualified personnel may carry out mounting, installation, commissioning, operation, maintenance, and dismounting of the product. The personnel must have read and understood the instruction manual and the further documentation.
Intended Use
The device is only approved for appropriate and intended use. Ignoring these instructions will void any warranty and absolve the manufacturer from any liability.
The device is developed, manufactured and tested according to the relevant safety standards.
Use the device only
for the application described
with specified environmental conditions
with devices that are suitable for this safety application
Improper Use
Protection of the personnel and the plant is not ensured if the device is not used according to its intended use.
2018-06
6
Functional Safety KFD2-RSH-1.2D.FL2, KFD2-RSH-1.2D.FL3
Introduction
1.3 Symbols Used
This document contains symbols for the identification of warning messages and of informative messages.
Warning Messages
You will find warning messages, whenever dangers may arise from your actions. It is mandatory that you observe these warning messages for your personal safety and in order to avoid property damage.
Depending on the risk level, the warning messages are displayed in descending order as follows:
Informative Symbols
Action
This symbol indicates a paragraph with instructions. You are prompted to perform an action or a sequence of actions.
Danger!
This symbol indicates an imminent danger.
Non-observance will result in personal injury or death.
Warning!
This symbol indicates a possible fault or danger.
Non-observance may cause personal injury or serious property damage.
Caution!
This symbol indicates a possible fault.
Non-observance could interrupt the device and any connected systems and plants, or result in their complete failure.
Note!
This symbol brings important information to your attention.
Functional Safety KFD2-RSH-1.2D.FL2, KFD2-RSH-1.2D.FL3
Product Description
2018-06
7
2 Product Description
2.1 Function
General
This signal conditioner provides the galvanic isolation between field circuits and control circuits.
The de-energized to safe (DTS) function is permitted for SIL 3 and PL e applications.
An internal fault or a line fault is signalized by the impedance change of the relay contact input and an additional relay contact output.
A fault is signalized by LEDs and a separate collective error message output.
The output must be protected against contact welding by an internal fuse or an external current limitation.
KFD2-RSH-1.2D.FL2
The device is a relay module that is suitable for safely switching applications of a load circuit. The device isolates load circuits up to 60 V DC and the 24 V DC control circuit.
KFD2-RSH-1.2D.FL3
The device is a relay module that is suitable for safely switching applications of a load circuit. The device isolates load circuits up to 230 V AC and the 24 V DC control circuit.
2.2 Interfaces
The device has the following interfaces:
Safety-relevant interfaces: input, output (DTS)
Non-safety relevant interfaces: fault indication output
2.3 Marking
Note!
For corresponding connections see datasheet.
Pepperl+Fuchs GmbH Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
KFD2-RSH-1.2D.FL2, KFD2-RSH-1.2D.FL3 Up to SIL 3 and PL e
2018-06
8
Functional Safety KFD2-RSH-1.2D.FL2, KFD2-RSH-1.2D.FL3
Product Description
2.4 Standards and Directives for Functional Safe
Device-specific standards and directives
Functional safety IEC/EN 61508, part 1 – 2, edition 2010:
Functional safety of electrical/electronic/programmable electronic safety-related systems (manufacturer)
Machinery Directive 2006/42/EC
• EN/ISO 13849, part 1, edition 2015: Safety-related parts of control systems (manufacturer)
• IEC 62061, edition 2005 + A1:2012 + A2:2015 EN 62061, edition 2005 + Cor. 2010 + A1:2013 + A2:2015:
Safety of machinery – Functional safety of safety-related
electrical, electronic and programmable electronic control systems