Pepperl+Fuchs KFD2-HLC-Ex1.D, KFD2-HLC-1.D.2W, KFD2-HLC-Ex1.D.2W, KFD2-HLC-1.D.4S, KFD2-HLC-1.D User Manual

...
MANUAL
HART LOOP CONVERTER KFD2-HLC-(EX)1.D(.**)
PROCESS AUTOMATION
HANDBUCH
ISO9001
PROZESSAUTOMATION
With regard to the supply of products, the current i ssue of the following document is applicable:
by the central association of the "Elektrot echnik und Elektroindustrie (ZVEI) e.V.",
including the supplementary clause "E xtended reservation of title".
Date of issue 11/30/07 805639
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Table of contents
1 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1 Range of application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Model variants. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Explosion protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5 Installation and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.1 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.2.1 Connection input (field circuit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2.2 Connection output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.3 Setting parameters of HART field device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.4 Front. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.5 Meaning of LED indication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6 Display modes and error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7 Description of HART operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 Editing device data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.1 Parameterization mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.1.1 Invocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.1.2 Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.1.3 Navigation method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8.1.4 Lowest menu level: select values, enter normal numbers . . . . . . . . . . . . . . . . . . . . . . 19
8.1.5 Lowest menu level: enter floating decimal numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.2 Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Table of contents
8.3 HARTcom. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.3.1 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.3.2 TimeOut . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.3.3 ShortAddress and LocateMethod . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.3.4 Rebuild . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.4 Current outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8.4.1 Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.4.2 Characteristic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.4.3 Start value and end value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
8.4.4 Error current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
8.5 Relay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
8.5.1 Trip value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.5.2 Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
8.5.3 Switching characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
8.5.4 Trip point and hysteresis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8.5.5 Restart inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
8.5.6 Response delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
8.5.7 Fault indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
8.6 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.7 Default settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Date of issue 11/30/07 805639
2
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Symbols used

1 Symbols used

This symbol warns of possible danger. Failure to heed this warning may result in personal injury or death, or property damage, including destruction.
Warning
This symbol warns the user of a possible fault. Failure to heed this warning can lead to total failure of the device and any other connected equipment.
Attention
Note
This symbol draws attention to important information.

2 Overview

2.1 Range of application

The K-System devices from Pepperl+Fuchs are used for transmitting signals between field devices and a process control system/control system.
The devices marked with "Ex" in the type designation are suitable for the connection of field devices used in potentially explosive atmospheres. Safe field circuits for these devices are intrinsically safe and are galvanically isolated from non-intrinsically safe circuits. The devices thus establish an electromagnetic separation between the potentially explosive atmospheres and the safe areas in a system.
Devices without Ex-identification can be used to transmit signals between field devices and the process control system/control unit.
Date of issue 11/30/07 805639
3
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Overview
The HART system allows digital communication with HART field devices via cables for analogue 4 mA ... 20 mA field circuits.
HART
More information (for example, certificates and data sheets for the HLC and the operating manual for the K-System) can be found on our webpage www.pepperl-fuchs.com (enter *HLC* in the product search).
The HART Loop Converter KFD2-HLC-(Ex)1.D(.**) from the K-System (HLC) evaluates up to four HART variables (PV, SV, TV, QV). The information can be converted to three different 4 mA ... 20-mA current signals and conveyed to display devices or analogue inputs on the process control system/control system, for example.
In addition, two or four configurable trip values from the HART variables can be monitored via the relay outputs on the KFD2-HLC­(Ex)1.D.2W or KFD2-HLC-(Ex)1.D.4S.
HART
PV, SV, TV, QV

2.2 Model variants

The following variants of the HART Loop Converter are available:
KFD2-HLC-**1.D.**
.2W = with 2 change-over contacts
.4S = with 4 normally open contacts
no identification letters = without relay
Ex = for connection of field devices in areas exposed to danger of explosion
without identifier letters = for connection of field devices in the secure area
3x
4x
Date of issue 11/30/07 805639
4
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Safety instructions

3 Safety instructions

The HART Loop Converter KFD2-HLC-(Ex)1.D(.**) may only be operated by trained professionals in a manner corresponding to this operating manual.
Warning
The protection of operating personnel and of the system is only ensured if the devices are used in accordance with their intended purpose. Any other type of operation than that described in this manual places the safety and functionality of the devices and
Warning
Warning
Warning
Note
Date of issue 11/30/07 805639
systems connected to them in question.
The devices may only be installed, connected, and adjusted by electrical professionals
outside the hazardous area.
If faults cannot be eliminated, the devices must be taken out of operation and protected from being placed in service again inadvertently. Devices must only be repaired directly by the manufacturer Pepperl+Fuchs. Tampering with or making changes to the devices is dangerous and therefore not permitted. They render the warranty void.
The responsibility for the adherence to local safety standards lies with the operator.
5
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Explosion protection

4 Explosion protection

For primary explosion protection, that is, for measures to be taken to prevent or hinder the development of a dangerous explosive atmosphere, please observe the guideline 1999/92/EC (ATEX 137) or the corresponding national guidelines.
For secondary explosion protection, that is, for measures to hinder the ignition of a surrounding explosive atmosphere by electrical devices, Pepperl+Fuchs will gladly make the "Explosion Protection Manual" available to you for a nominal fee.
Note in particular DIN EN 60079-10, DIN EN 60079-14, DIN EN 50014 and DIN EN 50020, or the corresponding national guidelines.
Pepperl+Fuchs also offers a seminar on the topic of explosion protection.

5 Installation and connection

5.1 Installation

The HART Loop Converter KFD2-HLC-(Ex)1.D(.**) is constructed in protection degree IP20 and must therefore be protected from undesirable ambient conditions (water, small foreign objects).
Attention
The devices of the K-system from Pepperl+Fuchs and thus also the HART Loop Converter KFD2-HLC-(Ex)1.D(.**) can be mounted on a 35 mm standard rail corresponding to DIN EN 50022. The devices must be snapped onto the rail vertically, and never slanted or tipped to the side.
Additional possibilities for mounting, e. g. using the Power Rail, can be found in the K-System operating manual on our webpage www.pepperl-fuchs.com
*HLC* in the product search).
(enter
Date of issue 11/30/07 805639
6
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Installation and connection
115

5.2 Connection

The detachable terminals of the KF-ser ies considerably simplify the connection and the switch cabinet assembly. They make it possible to replace devices quickly and without error if a customer service becomes necessary.
Terminals are equipped with screws, are self-opening, have a large connection area for a wire cross-section up to 2.5 mm² and coded plugs, making it impossible to mix them up.
Date of issue 11/30/07 805639
Dimensions of the KFD2-HLC-(Ex)1.D(.**) in mm
11940105 7
7
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
2 2
I
Installation and connection
5.2.1 Connection input (field circuit)
The intrinsically safe field circuit is connected to the blue terminals 1 to 6 on the KFD2-HLC-Ex1.D(.**). This may be conducted using DIN EN 60079-14-compliant leads into the hazardous area.
You can connect the following three operating modes:
1. any separately powered HART loop with a transmitter or positioner in a parallel circuit (as with HART handheld terminals, terminals 2 and 3)
2. an active HART-compatible mA source, e. g. a separately powered HART transmitter (terminals 2 and 3, bridge between terminals 5 and 6)
3. a 2-wire HART transmitter (HART transmitter with analogue 4 mA ... 20 mA output signal) powered by the HLC (terminals 1 and 3, bridge between terminals 4 and 5)
12 3
HART
Zone 0, 1, 2 Div. 1, 2
+
-
HART
HART
+
1+ 2+
­3-
4 5 6
KFD2-HLC-Ex1.D
Power Rail
7- 8+
9- 13+ 14- 15+ 19 20 21
22 23+ 24-
24 V DCERR
8
+--
+--
+--
24 V DC
+
+
+
Zone
Div.
I
II
II
HART
Date of issue 11/30/07 805639
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Installation and connection
5.2.2 Connection output
The non-intrinsically safe field circuit is connected to the green terminals 1 to 6 on the KFD2-HLC-
1.D(.**).
The remaining green terminals have the following functions:
KFD2-HLC-Ex1.D
• Terminals 7 ... 9: output I, current output as source (7/8) or sink (7/9)
• Terminals 13 ... 15: output II, current output as source (13/14) or sink (13/15)
• Terminals 19 ... 21: output III, current output as source (19/20) or sink (19/21)
• Terminals 22/24: HART handheld terminal connection
• Terminals 23/24: power supply 24 V DC
Date of issue 11/30/07 805639
KFD2-HLC-Ex1.D
Power Rail
13+ 14­15+ 19 20 21
22 23+ 24-
24 V DCERR
7­8+ 9-
+--
+--
+--
24 V DC
+
+
+
Zone 2
Div. 2
I
II
III
HART
9
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Installation and connection
KFD2-HLC-Ex1.D.2W
• Terminals 10 ... 12: output I (relay 1 (change-over contact))
• Terminals 16 ... 18: output II (relay 2 (change-over contact))
• Terminals 7 ... 9: output III, current output as source (7/8) or sink (7/9)
• Terminals 13 ... 15: output IV, current output as source (13/14) or sink (13/15)
• Terminals 19 ... 21: output V, current output as source (19/20) or sink (19/21)
• Terminals 22/24: HART handheld terminal connection
• Terminals 23/24: power supply 24 V DC
KFD2-HLC-Ex1.D.2W
Power Rail
10
I
11 12 16 17
II
18
7-
+
+
+
Zone 2
Div. 2
III
IV
V
HART
Date of issue 11/30/07 805639
8+
+--
9­13+ 14-
+--
15+ 19 20
+--
21 22 23+
24 V DC
24-
24 V DCERR
10
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Installation and connection
KFD2-HLC-Ex1.D.4S
• Terminals 10/11: output I (relay 1 (change-over contact))
• Terminals 10/12: output II (relay 2 (change-over contact))
• Terminals 16/17: output III (relay 3 (change-over contact))
• Terminals 16/18: output IV (relay 4 (change-over contact))
• Terminals 7 ... 9: output V, current output as source (7/8) or sink (7/9)
• Terminals 13 ... 15: output VI, current output as source (13/14) or sink (13/15)
• Terminals 19 ... 21: output VII, current output as source (19/20) or sink (19/21)
• Terminals 22/24: HART handheld terminal connection
• Terminals 23/24: power supply 24 V DC
More information on connecting the HLC (e. g. using the power rail with collective error message) can be found in the data sheets and the K-System operating manual on our webpage www.pepperl­fuchs.com (enter
Date of issue 11/30/07 805639
*HLC* in the product search).
KFD2-HLC-Ex1.D.4S
Power Rail
10 11 12 16 17 18
7­8+
9­13+ 14­15+ 19 20 21 22 23+ 24-
24 V DCERR
I
II
III IV
+--
+--
+--
24 V DC
+
+
+
VII
Zone 2
Div. 2
V
VI
HART
11
HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Installation and connection

5.3 Setting parameters of HART field device

In order to set the parameters of the connected HART field device, you will require a HART handheld terminal which you can connect to terminals 22/24 or the field cables. Transmitting the HART signal via the current outputs of the HLC is not possible.
When connecting the field cables, use an old handheld terminal if the field cables lead through a hazardous area.
Warning

5.4 Front

The following are located on the front of the HLC:
• a display for showing the measured values, the current output values and fault messages and for displaying in parameterization mode
• four keys for selecting the displayed values/current output value and for setting the parameters of the HLC:
S (Up) T (Down) ESC (Escape) OK
• RS 232 serial interface for a connection to a PC for setting parameters and diagnosis of the HLC using PACT ware
TM
(available from 2009)
• LED ERR (red) to indicate a fault
• LED PWR (green) to indicate the presence of the supply voltage
also for KFD2-HLC-(Ex)1.D.2W and KFD2-HLC-(Ex)1.D.4S:
• LED OUT 1 (yellow) to indicate that relay 1 is active
123
KFD2-HLC­Ex1.D.4S
1 IN / CH
K
21
OUT
43
RS232
789
13 14 15
19 20 21
• LED OUT 2 (yellow) to indicate that relay 2 is active
also for KFD2-HLC-(Ex)1.D.4S:
• LED OUT 3 (yellow) to indicate that relay 3 is active
• LED OUT 4 (yellow) to indicate that relay 4 is active
PWR
456
ESC
OK
10 11 12
16 17 18
22 23 24
Date of issue 11/30/07 805639
12