Pepperl+Fuchs KFD2-HLC-Ex1.D, KFD2-HLC-Ex1.D.4S, KFD2-HLC-Ex1.D.2W Series Manual

Page 1
ISO9001
MANUAL
HART Loop Converter KFD2-HLC-Ex1.D(.**)
PROCESS AUTOMATION
Page 2
HART Loop Converter KFD2-HLC-Ex1.D(.**)
With regard to the supply of products, the current issue of the following document is applicable:
The General Terms of Delivery for Products and Services of the Electrical Industry,
(Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version
as well as the supplementary clause: "Expanded reservation of proprietorship"
Page 3
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1 Manufacturer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Content of this Document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Target Group, Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Product Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Device Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Mounting and Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 DIN Mounting Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2 Power Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.1 Configuration via Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
4.2 Configuration via Keypad on the Device . . . . . . . . . . . . . . . . . . 26
5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
5.1 Indicators during Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.2 Fault Message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
6 Dismounting, Maintenance, and Repair . . . . . . . . . . . . . . . 56
7 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.1 Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
315702 2018-01
EN
EN - 1
Page 4
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Introduction

1Introduction

1.1 Manufacturer

Pepperl+Fuchs GmbH
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com

1.2 Content of this Document

This document contains information that you need in order to use your product throughout the applicable stages of the product life cycle. These can include the following:
Product identification
Delivery, transport, and storage
Mounting and installation
Commissioning and operation
Maintenance and repair
Troubleshooting
Dismounting
Disposal
Note!
This document does not substitute the instruction manual.
Note!
For full information on the product, refer to the instruction manual and further documentation on the Internet at www.pepperl-fuchs.com.
315702 2018-01
2 - EN
Page 5
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Introduction
The documentation consists of the following parts:
Present document
Instruction manual
Datasheet Additionally, the following parts may belong to the documentation, if applicable:
EU-type examination certificate
EU declaration of conformity
Attestation of conformity
Certificates
Control drawings
Additional documents

1.3 Target Group, Personnel

Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the plant operator.
Only appropriately trained and qualified personnel may carry out mounting, installation, commissioning, operation, maintenance, and dismounting of the product. The personnel must have read and understood the instruction manual and the further documentation.
Prior to using the product make yourself familiar with it. Read the document carefully.

1.4 Symbols Used

This document contains symbols for the identification of warning messages and of informative messages.
Warning Messages
You will find warning messages, whenever dangers may arise from your actions. It is mandatory that you observe these warning messages for your personal safety and in order to avoid property damage.
315702 2018-01
EN
EN - 3
Page 6
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Introduction
Depending on the risk level, the warning messages are displayed in descending order as follows:
Danger!
This symbol indicates an imminent danger.
Non-observance will result in personal injury or death.
Warnin g!
This symbol indicates a possible fault or danger.
Non-observance may cause personal injury or serious property damage.
Caution!
This symbol indicates a possible fault.
Non-observance could interrupt the device and any connected systems and plants, or result in their complete failure.
Informative Symbols
Note!
This symbol brings important information to your attention.
Action
This symbol indicates a paragraph with instructions. You are prompted to perform an action or a sequence of actions.
315702 2018-01
4 - EN
Page 7
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Product Specifications

2 Product Specifications

2.1 Device Versions

The following device versions described in this manual:
•HART Loop Converter KFD2-HLC-Ex1.D
HART Loop Converter KFD2-HLC-Ex1.D.2W
HART Loop Converter KFD2-HLC-Ex1.D.4S

2.2 Function

General
The HART Loop Converter is an isolated barrier suitable for intrinsically safe applications.
The device supplies field devices and can be connected in parallel to existing HART circuits.
The device analyzes up to four HART variables (PV, SV, TV, QV). Three HART variables can be transformed into varying current signals from these four HART variables. These signals are used to display the values via the analog inputs of the process control system.
The device is easily configured by the use of keypad or with the PACTware configuration software.
KFD2-HLC-Ex1.D.2W
In addition to the current outputs, the device has two changeover contacts. These changeover contacts can be programmed so that the changeover contacts function as limit values for the HART variables.
KFD2-HLC-Ex1.D.4S
In addition to the current outputs, the device has four NO contacts. These NO contacts can be programmed so that the NO contacts function as limit values for the HART variables.
315702 2018-01
EN
EN - 5
Page 8
EN

2.3 Assembly

ESC
OK
KFD2-HLC­Ex1.D.4S
RS232
PWRERR
12
3
4
OUT
19 21
15
9
13
7
20
14
8
22 24
18
121610
23
17
11
132465
3
1
2
6
7
8
9
4
5
6 - EN
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Product Specifications
Operating and indicating elements
Figure 2.1 Example front view KFD2-HLC-Ex1D.4S
315702 2018-01
Page 9
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Product Specifications
1 Removable terminals, blue
315702 2018-01
2 LC display Display for showing
3 Keypad
ESC
OK
4 Place for labeling
5 Removable terminals, green
6 Programming socket Interface for connecting a computer for parameterization and
7 yellow LEDs Outputs Out 1 to 4, indicating relay status
8 red LEDs Indicating faults
9 green LEDs Indicating power supply
•the measured values
• the current output values
• the fault messages
• the parameterization mode
Four keys for selecting the displayed values, the current output values and for setting the parameters of the device
Up
Down
Escape
Confirmation
diagnostics of the device with the PACTware operating software, using the K-ADP-USB adapter
EN
EN - 7
Page 10
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Product Specifications

2.4 Dimensions

Housing Type C2
8 - EN
40 mm (1.6 inch)
Figure 2.2
Number of terminal blocks max. 10
Dimension drawing with screw terminals
When using screw terminals with test sockets the device is 124 mm (4.9 inch) in height.
When using spring terminals the device is 131 mm (5.16 inch) in height.
115 mm (4.5 inch)
46 mm (1.82 inch)58 mm (2.28 inch)
104 mm (4.1 inch)
119 mm (4.7 inch)
315702 2018-01
Page 11
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Mounting and Installation

3 Mounting and Installation

Danger!
Explosion hazard from damaged electronic components
Premature wear of electronic components in a device that was previously used in a general electrical installation can cause sparks that can ignite the surrounding potentially explosive atmosphere.
Never install devices that have already been operated in general electrical installations in electrical installations used in combination with hazardous areas!
Danger!
Explosion hazard from pollution
An excessively polluted surface of the device can become conductive and consequently ignite a surrounding potentially explosive atmosphere.
Ensure that you install the device only in environments with a pollution degree 2 or better according to IEC/EN 60664–1.

3.1 DIN Mounting Rail

The devices are mounted on a 35 mm DIN mounting rail according to EN 60715.
Figure 3.1 Example: DIN mounting rail UPR-MR (35 mm x 15 mm)
315702 2018-01
EN
EN - 9
Page 12
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
1
2
34
Mounting and Installation

3.2 Power Rail

To reduce wiring and installation costs, Power Rail is the optimum solution. The Power Rail is a DIN mounting rail with plastic insert, that delivers power to the devices (24 V DC) and transfers bus signals and a collective error message.
The Power Rail is factory-equipped with cover and end caps. These parts cover empty and open segments of the Power Rail. Thus, the Power Rail is protected from contamination. Additionally the cover and end caps prevent that electrically conductive parts come in contact with the Power Rail.
Power Rail UPR-03
The Power Rail UPR–03 has 3 conductors.
2 conductors for power
1 conductor for collective error messaging
10 - EN
Figure 3.2 Example: Power Rail UPR-03
1 Cover UPR-COVER
2 Insert UPR-INS-03
3 DIN mounting rail UPR-MR (35 mm x 15 mm)
4 End cap UPR-E
315702 2018-01
Page 13
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Mounting and Installation

3.3 Mounting

Danger!
Danger to life from electric shock
Absent or insufficient insulation can result in electric shock.
Only connect supplies that provide protection against electric shock to power feed modules (e. g. SELV or PELV).
Caution!
Property damage from use of isolators for Power Rail supply
Using the isolators for Power Rail supply can damage the isolators and make the Power Rail fail.
Do not supply the Power Rail via isolators.
Mounting in the Non-Hazardous Area
Mounting the Device
Snap the device onto the DIN mounting rail in a vert ical downward movement. See figure below.
Mounting in Areas that Require the Equipment Protection Level Gc
Danger!
Explosion hazard from live wiring of non-intrinsically safe circuits
If you connect or disconnect energized non-intrinsically safe circuits in a potentially explosive atmosphere, sparks can ignite the surrounding atmosphere.
Only connect or disconnect energized non-intrinsically safe circuits in the absence of a potentially explosive atmosphere.
315702 2018-01
EN
EN - 11
Page 14
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Mounting and Installation
Danger!
Explosion hazard from wrong mounting
The device safety can be impaired by external environmental influences and by mechanical stress. This can lead to sparking that can ignite a surrounding potentially explosive atmosphere.
Mount the device in a surrounding enclosure that complies with IEC/EN 60079–0and that is rated with the degree of protection IP54 according to IEC/EN 60529.
Mounting the Device
Snap the device onto the DIN mounting rail in a vert ical downward movement. See figure below.
CORRECT: Device snapped on vertically. INCORRECT: Device snapped on from the side.
Figure 3.3
Can damage the contacts and cause the device to fail.
315702 2018-01
12 - EN
Page 15
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Mounting and Installation
Mounting the Terminal Blocks
Connect the terminal blocks or disconnect the terminal blocks.

3.4 Connection

Danger!
Danger to life from incorrect installation
Incorrect installation of cables and connection lines can compromise the function and the electrical safety of the device.
Observe the permissible core cross section of the conductor.
When using stranded conductors, crimp wire end ferrules on the conductor ends.
Use only one conductor per terminal.
When installing the conductors the insulation must reach up to the terminal.
Observe the tightening torque of the terminal screws.
Danger!
Explosion hazard from live wiring of non-intrinsically safe circuits
If you connect or disconnect energized non-intrinsically safe circuits in a potentially explosive atmosphere, sparks can ignite the surrounding atmosphere.
Only connect or disconnect energized non-intrinsically safe circuits in the absence of a potentially explosive atmosphere.
315702 2018-01
EN
EN - 13
Page 16
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Mounting and Installation
Danger!
Explosion hazard from wrong separation distances
If you do not observe the minimum separation distances between intrinsically safe circuits of associated apparatus and non-intrinsically safe circuits, this can lead to added currents or voltages. This can result in a current/voltage flashover generating sparks. The sparks can ignite the surrounding potentially explosive atmosphere.
Ensure that you observe the compliance of the separation distances to all non–intrinsically safe circuits according to IEC/EN 60079–14.
Danger!
Danger to life from electric shock
Absent or insufficient insulation can result in electric shock.
Maintain sufficient distance between the connection lines, terminals, housing, and the environment.
Insulate connection lines, terminals, and the housing from the environment.
Danger!
Danger to life from electric shock
Absent or insufficient insulation can result in electric shock.
Only connect supplies that provide protection against electric shock (e. g. SELV or PELV).
315702 2018-01
14 - EN
Page 17
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Mounting and Installation
Danger!
Danger to life from electric shock
Working on live parts at voltages higher than 50 V AC or 120 V DC can result in electric shock.
1. De-energize the device.
2. Secure the circuit against reconnection.
3. Verify that the device is de-energized at all poles.
4. Provide protection from adjacent live parts, if present.
The removable terminal blocks simplify connection and control cabinet construction significantly. These terminal blocks offer adequate space for the connection of leads with
core cross-sections of up to 2.5 mm2 (14 AWG). The terminal blocks are coded with red coding pins so misconnection of terminal blocks are eliminated.
Connecting Circuits
1. Connect the field circuit.
2. Connect the control circuit.
315702 2018-01
EN
EN - 15
Page 18
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Mounting and Installation
3.4.1 Input Connection (Field Circuit)
Danger!
Explosion hazard from wrong separation distances
If you do not observe the minimum separation distance between 2 intrinsically safe circuits, this can lead to added currents or voltages. This can result in a current/voltage flashover generating sparks. The sparks can ignite the surrounding potentially explosive atmosphere.
Ensure that you observe all separation distances between 2 adjacent intrinsically safe circuits according to IEC/EN 60079-14.
Connecting the Field Circuit
1. Connect the field circuit to the blue terminals.
2. Observe the tightening torque of the terminal screws. The tightening torque is
0.5 Nm to 0.6 Nm.
The intrinsically safe field circuit may be routed in the hazardous area with connection lines in accordance with DIN EN 60079-14. You can connect the following field devices:
1. any separately supplied HART current circuit with transmitter or positioner connected in parallel Connection to terminals 2 and 3
2. a HART-capable active current source, e. g., a separately supplied HART measuring transmitter Connection to terminals 2 and 3 with bridge between terminals 5 and 6
3. a 2-wire HART measuring transmitter, e. g., HART measuring transmitter with an analog output signal of 4 mA to 20 mA The HART measuring transmitter is supplied by the isolated barrier Connection to terminals 1 and 3 with bridge between terminals 4 and 5
315702 2018-01
16 - EN
Page 19
Power Ra il
24 V DCFau lt
Zone 0, 1, 2 Div. 1, 2
HART
+
-
HART
+
-
+
­HART
mA
1+
2+
3-
4
5
6
250 Ω
315702 2018-01
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Mounting and Installation
Figure 3.4
EN
EN - 17
Page 20
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
KFD2-HLC-Ex1.D
7 8+ 9-
14+ 15-
13
20+ 21-
19
Zone 2
Div. 2
24 V DC
23+ 24-
22
Power Ra il
24 V DCFau lt
HART
II
III
I
mA
mA
mA
+
-
V
+
-
V
+
-
V
250 Ω
Mounting and Installation
3.4.2 Output Connection (Control Circuit)
Connecting the Control Circuit
1. Connect the control circuit to the green terminals.
2. Note the tightening torque of the terminal screws. The tightening torque is
0.5 Nm to 0.6 Nm.
Connection KFD2-HLC-Ex1.D
The following connections are available:
Terminals 7 to 9: output I, current output as source (7/8) or sink (7/9)
Terminals 13 to 15: output II, current output as source (13/14) or sink (13/15)
Terminals 19 to 21: output III, current output as source (19/20) or sink (19/21)
Terminals 22/24: connection of HART handheld
Terminals 23/24: power supply 24 VDC
18 - EN
Figure 3.5
315702 2018-01
Page 21
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Mounting and Installation
Connection KFD2-HLC-Ex1.D.2W
Danger!
Danger to life from electric shock
Working on live parts at voltages higher than 50 V AC or 120 V DC can result in electric shock.
1. De-energize the device.
2. Secure the circuit against reconnection.
3. Verify that the device is de-energized at all poles.
4. Provide protection from adjacent live parts, if present.
The following connections are available:
Terminals 10 to 12: output I (relay 1 (change-over contact))
Terminals 16 to 18: output II (relay 2 (change-over contact))
Terminals 7 to 9: output III, current output as source (7/8) or sink (7/9)
Terminals 13 to 15: output IV, current output as source (13/14) or sink (13/15)
Terminals 19 to 21: output V, current output as source (19/20) or sink (19/21)
Terminals 22/24: connection of HART handheld
Terminals 23/24: power supply 24 VDC
315702 2018-01
EN
EN - 19
Page 22
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
KFD2-HLC-Ex1.D.2W
7 8+ 9-
14+ 15-
13
20+ 21-
19
Zone 2
Div. 2
I
II
10 11 12 16 17 18
24 V DC
23+ 24-
22
Power Ra il
24 V DCFau lt
HART
+
IV
V
III
-
mA
mA
mA
V
+
-
V
+
-
V
250 Ω
Mounting and Installation
Figure 3.6
20 - EN
315702 2018-01
Page 23
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Mounting and Installation
Connection KFD2-HLC-Ex1.D.4S
Danger!
Danger to life from electric shock
Working on live parts at voltages higher than 50 V AC or 120 V DC can result in electric shock.
1. De-energize the device.
2. Secure the circuit against reconnection.
3. Verify that the device is de-energized at all poles.
4. Provide protection from adjacent live parts, if present.
The following connections are available:
Terminals 10/11: output I (relay 1 (NO contact))
Terminals 11/12: output II (relay 2 (NO contact))
Terminals 16/17: output III (relay 3 (NO contact))
Terminals 17/18: output IV (relay 4 (NO contact))
Terminals 7 to 9: output V, current output as source (7/8) or sink (7/9)
Terminals 13 to 15: output VI, current output as source (13/14) or sink (13/15)
Terminals 19 to 21: output VII, current output as source (19/20) or sink (19/21)
Terminals 22/24: connection of HART handheld
Terminals 23/24: power supply 24 VDC
315702 2018-01
EN
EN - 21
Page 24
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
KFD2-HLC-Ex1.D.4S
7 8+ 9-
14+ 15-
13
20+ 21-
19
Zone 2
Div. 2
10 11 12 16 17 18
I
III
24 V DC
23+ 24-
22
Power Ra il
24 V DCFau lt
HART
IV
II
VI
VII
V
mA
mA
mA
+
-
V
+
-
V
+
-
V
250 Ω
Mounting and Installation
Figure 3.7
22 - EN
315702 2018-01
Page 25
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Mounting and Installation
3.4.3 Connecting a HART Handheld to the Field Device
You have two options for connecting a HART handheld to the field device:
Connection to terminals 22/24 of the isolated barrier, see chapter 3.4.2
Connection to the field cables from the isolated barrier to the field device
Danger!
Risk of explosion
Danger of explosion when using a non-certified HART handheld in a hazardous area.
Use a HART handheld certified for use in hazardous areas if the field cables lead into a hazardous area.
Transmitting the HART signal using the current outputs of the isolated barrier is not possible.
3.4.4 Description of HART Operations
Dynamic Query of Variables
Universal HART command 3 is used to query dynamic variables from the field device. This query is done either directly or by activating burst mode.
Burst Mode
Burst mode is the preferred method because this mode guarantees the fastest signal transmission. The isolated barrier always tries to set the connected field device to burst mode. See chapter 4.2.6.
The command for burst mode activation is sent to the field device under the following conditions:
after a restart or
after resetting the isolated barrier after restarting the field device. In the process, communication between the field device and isolated barrier must have been reestablished again after a time-out.
315702 2018-01
EN
EN - 23
Page 26
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Mounting and Installation
Polling Mode (Command and Answer)
The isolated barrier deactivates the burst configuration of the field device. The isolated barrier performs the field device query using HART command 3. See chapter 4.2.6.
Procedure to Restore Burst Mode
If the isolated barrier does not receive any more data from the field device in burst mode, the following actions are taken:
The isolated barrier switches to polling mode.
The isolated barrier checks whether another HART master has started in the query signal circuit. If the isolated barrier has detected a HART master, the restoring of burst mode is interrupted.
If the isolated barrier does not detect any other HART masters, the isolated barrier attempts to activate burst mode.
As soon as the isolated barrier receives a burst message from the field device, the isolated barrier switches from polling mode to burst mode.
This process enables other HART masters to deactivate burst mode momentarily for service work.
Time-out (Communication Loss)
When the time-out time has been exceeded in the absence of communication, all outputs switch to the defined safe state. Time-out can be adjusted.
315702 2018-01
24 - EN
Page 27
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration

4 Configuration

4.1 Configuration via Software

Danger!
Explosion hazard from sparking when plugging or pulling the adapter
Plugging or pulling the adapter in a potentially explosive atmosphere can cause sparks that can ignite the surrounding atmosphere.
Only plug or pull the adapter in the absence of a potentially explosive atmosphere.
Caution!
Fault in the plant
Changing the device data changes the device function.
Before entering new device data, make sure the plant is not endangered by changing the device data.
The devices can configured using the PACTwareTM operating software.
Connection between Device and Computer
Connect the device and the computer using the K-ADP-USB adapter. This adapter can be ordered as an accessory.
Connecting the Device to the Computer via the USB Interface
1. Mount the device.
2. Connect the device to the power supply.
3. Connect the device to the PC via the adapter.
- Connection on the device: front programming socket
- Connection on the PC: USB interface
4. Refer to the "Installation and Configuration DTM Collection Conventional Interface Introduction" manual for further steps.
315702 2018-01
EN
EN - 25
Page 28
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Configuration
The operating software and the necessary device and communication DTMs can be downloaded from our internet page www.pepperl-fuchs.com (product search, enter PACTware). The manual "Installation and Configuration DTM Collection Conventional Interface Introduction" guides you through the installation steps necessary to install the software. The manual can be found on our internet page www.pepperl-fuchs.com (product search, enter PACTware).
Note!
The configuration and operation of the device via software is not described in this manual.

4.2 Configuration via Keypad on the Device

Danger!
Explosion hazard from sparking when using operating elements
Using operating elements in a potentially explosive atmosphere can cause sparks that can ignite the surrounding atmosphere.
Only use operating elements (e.g., switch, slider, button, etc.) in the absence of a potentially explosive atmosphere.
Caution!
Fault in the plant
Changing the device data changes the device function.
Before entering new device data, make sure the plant is not endangered by changing the device data.
315702 2018-01
26 - EN
Page 29
HART Loop Converter KFD2-HLC-Ex1.D(.**)
OK →
← ESC
← ESC
← ESC
← ESC
← ESC
OK →
← ESC
▼ ▲
▼ ▲
▼ ▲
▼ ▲
Iout1
4 - 20 NE43
Assignment
Characteristic
Start Value
End Value
Fault Current
Lowest menu level
Configuration
Configuring the Device
Configure the device using the buttons on the front side. Use the , , ESC, and OK buttons for navigation. The following chapters contain more detailed information about the menus.
The navigation principle is shown using the following example:
The menu items from the lowest menu level are outlined in bold.
EN
315702 2018-01
EN - 27
Page 30
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
▼ ▲
▼ ▲
▼ ▲
HARTcom
Unit
Main menu
parameterization mode
Output
Service
Display mode
OK + ESC (simultaneously for 1 s) →
← ESC
Configuration
4.2.1 Parameterization Mode
After being switched on, the device is in display mode. If you have password protection enabled, you must enter the password every time you transition from display mode to parameterization mode.
Calling up Parameterization Mode
Press the OK and ESC buttons simultaneously for approx. 1 second.
The device changes from display mode to parameterization mode.
Exiting Parameterization Mode
1. Press the ESC once or multiple times. The number of times depends on which menu level you are in.
2. If you have not pressed a button for 10 minutes in parameterization mode, the device switches back automatically to display mode.
28 - EN
The device changes from parameterization mode to display mode.
315702 2018-01
Page 31
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
4.2.2 Password Protection
You can activate password protection to protect parameterization from unauthorized changes. If password protection is enabled, you can view the parameter settings but not change them. Password protection is deactivated during delivery. The password is preset and cannot be changed by the operator. The password is 1234. Information about enabling password protection see chapter 4.2.9.
Entering the Password
1. As soon as you try to change the parameterization, the device switches automa tically to the input window for password access.
The first digit of the password flashes.
2. Set the first digit of the password using the and buttons.
3. Confirm your entry with OK.
The next digit flashes.
4. Repeat steps 2 and 3, until all digits have been entered.
5. Confirm your entry with OK.
If the password was correct, the device changes to parameterization mode. The device can now be parameterized. If the password was not correct, cancel password access and begin password entry again using step 1.
Canceling Password Entry
You can cancel password entry at any time.
Press the ESC button.
The device switches to display mode.
315702 2018-01
EN
EN - 29
Page 32
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
OK →
← ESC
OK ↓
← ESC
← ESC
▼ ▲
Parameter Current value, flashing
New value, flashing,
not stored
New value, not flashing,
stored
Configuration
4.2.3 Entering Numbers
At the lowest menu level of the Paramete r menu, you have the option of selecting or entering a numerical value.
Selecting a Numerical Value
1. Select the parameter for which you want to change the numerical value.
2. Press the OK button.
The current value flashes.
3. Select a value from the list of values using the and buttons.
The new value flashes. The value is not stored.
4. Confirm your selection with OK.
The new value does not flash. The value is stored.
Entering a Numerical Value
1. Select the parameter where you want to enter the numerical value.
2. Press the OK button.
The current value flashes.
3. To change the value in steps, press the or button. or To change the value more quickly, press and hold the or button.
30 - EN
The new value flashes. The value is not stored.
4. Confirm your selection with OK.
The new value is stored.
315702 2018-01
Page 33
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
4.2.4 Entering Floating Point Figures
At the lowest menu level of the Paramete r menu, you have the option of entering floating point figures.
The floating point figures can have the following structure:
Positive number Input Negative number Input
43210000 43.21 E06 -3210000 -3.21 E06
4321000 4321 E03 -321000 -321 E03
432100 4 32.1 E03 -32100 -32.1 E03
43210 43.21 E03 -3210 -3.21 E03
4321 4321 E00 -321 -321 E00
432.1 4 32.1 E00 -32.1 -32.1 E00
43.21 43.21 E00 -3.21 -3.21 E00
1.234 1 .234 E00
0.1234 123.4 E-03 -0.123 -123 E-03
0.01234 12.34 E-03 -0.0123 -12.3 E-03
0.001234 1.234 E-03 -0.00123 -1.23 E-03
0.0001234 123.4 E-06 -0.00 0123 -123 E-06
Table 4.1
For a floating point figure, you must enter the following parameters:
four digits of the mantissa (decimals) for positive numbers
a minus sign and three digits for the mantissa for negative numbers
the position of the decimal point in or after the mantissa
the exponents
315702 2018-01
EN
EN - 31
Page 34
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Configuration
Entering a Numerical Value
1. Select the parameter for which you want to enter the numerical value.
2. Press the OK button.
The current value from the mantissa and exponent flashes.
3. Press the OK button.
With positive numbers, the first digit of the mantissa flashes.
With negative numbers, the minus sign flashes.
4. To change the value in steps from 0 to 9, press the or button. To enter a minus sign, press the button until the first digit is less than 0.
5. Confirm your selection with OK.
The next digit of the mantissa flashes.
6. Repeat steps 4 and 5, until all digits have been entered.
7. Confirm your entry with OK.
The position of the decimal point flashes.
8. Press the or button to specify the position of the decimal point.
9. Confirm your entry with OK.
The exponent flashes.
10. To specify the value of the exponent, press the or button. You can select the exponents from E-33 to E33 in increments of three.
11. Confirm your entry with OK.
The new value is stored.
315702 2018-01
32 - EN
Page 35
HART Loop Converter KFD2-HLC-Ex1.D(.**)
OK →
← ESC
← ESC
← ESC
← ESC
OK →
← ESC
▼ ▲
▼ ▲
▼ ▲
auto
OK →
← ESC
OK →
← ESC
OK →
← ESC
OK →
← ESC
custom
Custom Tag
▼ ▲ ▼ ▲
PV
SV
OK →
← ESC
TV
QV
see below
Unit
same as PV
same as PV
same as PV
Ty p e
Configuration
4.2.5 Unit
At the lowest menu level of the Unit menu, you have the option of selecting the unit type for the HART variables.
auto The device displays the unit which is transferred from connected HART field devices
for the HART variables PV, SV, TV, QV.
custom The device displays the unit which was defined by you for the HART variables
PV, SV, TV, QV in the Custom Tag menu.
EN
315702 2018-01
EN - 33
Page 36
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Configuration
Changing the Custom Tag of HART Variables
1. Select the HART variable for which you would like to change the custom tag.
2. Press the OK button.
3. Select the Custom Tag menu.
The device displays: if a value has not been defined: the insert mark and the symbol  If a value is defined: the insert mark on the first character, the following character, and the symbol  .
4. To select one of eight possible positions for the insert mark before the symbol , press the or button.
5. Confirm your selection with OK.
The insert mark flashes.
6. To select a character, press the or button.
7. Confirm your entry with OK.
8. Repeat steps 4 and 7, until all characters have been entered. You can also define spaces.
9. To select the symbol , press the or button.
10. Confirm your entry with OK.
The new value for Custom Tag has been stored.
Canceling the Value Input for HART Variables
You can cancel the value entry at any time.
Press the ESC button.
315702 2018-01
34 - EN
Page 37
HART Loop Converter KFD2-HLC-Ex1.D(.**)
OK →
← ESC
← ESC
← ESC
← ESC
OK →
← ESC
▼ ▲
▼ ▲
▼ ▲
secondary
OK →
← ESC
OK →
← ESC
OK →
← ESC
primary
▼ ▲
Mode
ShortAddress
← ESC
▼ ▲
OK →
← ESC
TimeOut
LocateMethod
Rebuild
OFF Rebuild
▼ ▲
HARTcom
fixed
On Rebuild
search
▼ ▲
← ESC
▼ ▲
OK →
← ESC
ComControl
auto detect
polling
▼ ▲
burst
▼ ▲
5 s to 60 s
0 to 15
Configuration
4.2.6 HARTcom
The HARTcom menu offers the option of specifying the method for communication between device and field device. If available, the device activates burst mode of the HART field device for the fastest possible communication. To query variables (PV, SV, TV, QV, if present) the device uses the universal HART command 3.
EN
315702 2018-01
EN - 35
Page 38
EN
36 - EN
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
Selecting a Mode
The device functions as primary or secondary HART master according to the HART standard. The device is compatible with each HART handheld and for every other HART master.
1. Use the or buttons to select whether the device should operate as a primary or secondary HART master.
2. Confirm your selection with OK.
Defining TimeOut
If the device does not receive a valid HART message within the specified time, the communication fault fault message is output.
1. To change the time in steps, press the or buttons. Set the time from 5 s to 60 s in increments of 5 seconds.
2. Confirm your entry with OK.
Defining ComControl
You can specify the communication type between isolated barrier and field device. The change in communication type is effective immediately. It is not necessary to restart the isolated barrier. See chapter 3.4.4.
1. Select the type of communication using the or buttons.
2. Select auto detect.
If you select this type of communication, the burst configuration of the field device is
not changed.
3. Choose polling.
If you select this type of communication, the isolated barrier deactivates the burst configuration of the field device. The isolated barrier performs the field device query using HART command 3.
4. Choose burst.
If you choose this type of communication, the isolated barrier activates the burst configuration of the field device for HART command 3.
5. Confirm your entry with OK.
315702 2018-01
Page 39
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
315702 2018-01
Note!
Note that the field device can be put into burst mode, in accordance to the isolated barrier configuration. This also applies when a different HART master is in the HART circuit. If a different HART master changes the burst configuration of the field device, the isolated barrier waits until the other HART master logs out of the HART circuit. The isolated barrier assumes that the other HART master is logged off when it does not send a message for approximately 60 s. After this period of time, the isolated barrier activates the burst configuration of the field device.
Defining ShortAddress
The defined short address is needed for identification of the field device during the localization phase.
1. To enter a short address between 0 to 15, press the or buttons.
2. Confirm your entry with OK.
Selecting LocateMethod
According to the HART standard, more than one HART field device can be present in a HART circuit. But the device can communicate only with a single HART field device. This HART field device is identified during the localization phase.
1. Select the localization method with the or buttons.
2. Select fixed.
The device communicates with the field device that has a short address defined under ShortAddress.
3. Choose search.
During booting, the device searches for the field device with the smallest short address, beginning with the short address defined under ShortAdress. The address of the field device found is stored by the device under ShortAddress. This accelerates the device starting when it boots again.
4. Confirm your entry with OK.
EN
EN - 37
Page 40
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
OK → ← ESC
OK →
← ESC
▼ ▲
disabled
PV
▼ ▲ ▼ ▲
Iout1
OK →
← ESC
OK →
← ESC
4 - 20
unlimited
4 - 20 NE43
▼ ▲
SV
▼ ▲
TV
▼ ▲
QV
▼ ▲
OK →
← ESC
▼ ▲
▼ ▲
Output Assignment
Characteristic
Start Value
see section
Configuration
Activating Rebuild
If the connection to the field device has been lost, the localization phase can be performed with Rebuild without switching the device off and on again.
1. Select On Rebuild with the or buttons.
2. Confirm your selection with OK.
The display On Rebuild flashes.
3. Press the OK button.
The device searches for connected field devices when booting.
4. Press the ESC button once or multiple times to switch to display mode.
4.2.7 Current Outputs
In the Output menu, you have the option of defining current outputs 1 to 3 of the device. The menu structure is identical for the three current outputs. Current output 1 is described as an example. For information on relay contact outputs, see chapter 4.2.8.
38 - EN
315702 2018-01
Page 41
HART Loop Converter KFD2-HLC-Ex1.D(.**)
▼ ▲
Iout2
OK →
← ESC
▼ ▲
Iout3
▼ ▲
Rel1
▼ ▲
Rel2
▼ ▲
Rel3
Rel4
OK →
← ESC
down
up
▼ ▲
hold
▼ ▲
OK →
← ESC
▼ ▲
OK →
← ESC
1 2
1 2
1
1
End Value
see section
Fault Current
same as Iout1
same as Iout1
Configuration
315702 2018-01
1
Relay contact outputs for KFD2-HLC-Ex1.D.4S
2
Relay contact outputs for KFD2-HLC-Ex1.D.2W
Selecting an Assignment
The values of the selected HART v ariable (PV, SV, TV, QV) are shown on the current outp ut. The number of available variables depends on the HART field device. When selecting disabled, the downscale fault current of 0 mA or 2 mA is constantly present at the current output, depending on the characteristic.
1. Select the desired HART variable using the or buttons.
2. Confirm your selection with OK.
EN
EN - 39
Page 42
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Configuration
Defining a Characteristic
The choice of characteristic defines the limits for measuring underrange and overrange. Measuring underranges or overranges outside the specified range cannot be analyzed. If measuring ranges are undercut or exceeded, the minimum or maximum value is issued constantly.
1. Select the characteristic using the or buttons.
2. Select the characteristic 4 - 20 unlimited.
For the characteristic 4 - 20 unlimited, measuring underranges are analyzed linearly up to 0 mA, and measuring overranges are analyzed linearly up to approx. 23 mA by the device.
3. Select the characteristic 4 - 20 NE43.
For the characteristic 4 - 20 NE43, measuring underranges are analyzed linearly up to 3.8 mA, and measuring overranges are analyzed linearly up to 20.5 mA by the device.
4. Confirm your entry with OK.
Defining the Start Value
Make sure during configuration that the start value is at least 1% less than the end value. If the start value does not meet this requirement, the start value will not be accepted by the device.
1. Enter the start value as a floating point figure. For entering floating point figures, see chapter 4.2.4. The defined unit from the Unit menu is used as the unit. See chapter 4.2.5.
2. Confirm your entry with OK.
Define the End Value
Make sure during configuration that the end value is at least 1 % greater than the start value.
1. Enter the end value as a floating point figure. For entering floating point figures, see chapter 4.2.4. The defined unit from the Unit menu is used as the unit. See chapter 4.2.5.
2. Confirm your entry with OK.
315702 2018-01
40 - EN
Page 43
1.9
4.0
3.8 0
20.0
20.5
2 10 bar
10.25
mA
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
Example
Characteristic 4 - 20 NE43, start value 2 bar, end value 10 bar
Figure 4.1
Defining the Fault Current (fault message)
The type of fault current chosen will define how the current output transmits the fault message to the controller.
1. Select the type of fault current using the or buttons.
2. Select the fault current down.
The fault message is indicated by a low current value.
3. Select the fault current up.
The fault message is indicated by a high current value.
4. Select the fault current hold.
The last measured value before the fault occurred is stored.
5. Confirm your entry with OK.
315702 2018-01
EN
EN - 41
Page 44
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
▼ ▲
Iout2
▼ ▲
Iout1
OK →
← ESC
▼ ▲
Iout3
▼ ▲
Rel1
▼ ▲
Rel2
▼ ▲
Rel3
Rel4
OK →
← ESC
▼ ▲
OK →
← ESC
OK →
← ESC
OK →
← ESC
1
1 2
1 2
1
same as Rel1
same as Rel1
same as Rel1
Output
Tr i p
Faul t
Configuration
4.2.8 Relay Contact Outputs
In the Output menu, you have the option of defining relay contact outputs 1 to 4 device. The menu structure of the four relay contact outputs is identical. Relay contact output 1 is described as an example. Information on the current outputs see chapter 4.2.7.
1
Relay contact outputs for KFD2-HLC-Ex1.D.4S
2
Relay contact outputs for KFD2-HLC-Ex1.D.2W
42 - EN
1 2
of the
315702 2018-01
Page 45
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
Selecting Relay Contact Output Menus
1. Select the desired relay contact output using the or buttons.
2. Confirm your entry with OK.
The relay contact output menus Tr i p and Faul t are displayed. The active menu is
marked as On.
3. If you would like to activate the other menu, select this menu with or .
4. Press the OK button twice.
The active menu is marked as On. The submenu is displayed.
5. If you would like to cancel activation, press the ESC button after the first OK.
315702 2018-01
EN
EN - 43
Page 46
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
OK →
← ESC
disabled
PV
▼ ▲ ▼ ▲
OK →
← ESC
OK →
← ESC
min
max
▼ ▲
SV
▼ ▲
TV
▼ ▲
QV
▼ ▲
OK →
← ESC
▼ ▲
▼ ▲
Min/Max
OK →
← ESC
▼ ▲
Assignment
Tr i p
see section
Hyteresis
see section
Trip (On)
Configuration
Limit Value (Trip)
Calling up a Limit Value
1. Select the Tr i p menu with the or buttons.
2. If the Tr i p menu is activated, press the OK button once.
The Assignment submenu is displayed.
3. If the Tr i p menu is not activated, press the OK button twice.
The Assignment submenu is displayed. The Tri p menu is activated and is marked
as On.
44 - EN
315702 2018-01
Page 47
HART Loop Converter KFD2-HLC-Ex1.D(.**)
OK →
← ESC
▼ ▲ ▼ ▲
OK →
← ESC
On
OFF
▼ ▲
OK →
← ESC
▼ ▲
Mode
Delay
Restart Inhibit
passive
active
0 s to 250 s
Configuration
Selecting an Assignment
The values of the HART variables selected here (PV, SV, TV, QV) are monitored using a relay contact output. The number of available variables depends on the HART field device. When disabled is selected, the relay remains constant in a de-energized state.
1. Select the desired HART variable using the or buttons.
2. Confirm your selection with OK.
Defining Switching Characteristics
Selecting the switching characteristics defines the switching direction and the direction of operation. See applications.
1. Select the switching direction min or max with the or buttons.
2. Confirm your selection with OK.
3. Select the direction of operation passive or active with the or buttons.
4. Confirm your selection with OK.
315702 2018-01
EN
EN - 45
Page 48
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Configuration
You can implement the following applications:
Switching direction max, direction of operation active: alarm if there is a limit value overrange, e. g., sounder on
Switching direction max, direction of operation passive: switch off during limit value overrange, e. g., pump, heating, ... off, for larger hysteresis Min-Max operation (pump, heater, ... on/off)
Switching direction min, direction of operation active: alarm if there is a limit value underrange, e. g., sounder is on.
Switching direction min, direction of operation passive: switch off during limit value underrange, e. g., pump, heating, ... off, for larger hysteresis Min-Max operation (pump, heater, ... off/on)
The exact switching characteristics of the device are shown in the following illustration:
Val ue
Max
Max – hysteresis
Min + hysteresis
Min
46 - EN
Switching direction max, mode active:
de-energized
Switching direction max, mode passive:
de-energized
Switching direction min, mode active:
de-energized
Switching direction min, mode passive:
de-energized
Figure 4.2
Time
energized
energized
energized
energized
315702 2018-01
Page 49
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
Defining the Trip Point
1. Enter the starting point as a floating point figure. For entering floating point figures, see chapter 4.2.4. The defined unit from the Unit menu is used as the unit. See chapter 4.2.5.
2. Confirm your entry with OK.
Defining Hysteresis
Make sure during input that the hysteresis is at least 1 % greater than the trip point. This avoids "fluttering" of the relay.
1. Enter the hysteresis as a floating point figure. For entering floating point figures, see chapter 4.2.4. The defined unit from the Unit menu is used as the unit. See chapter 4.2.5.
2. Confirm your entry with OK.
Activating the Restart Inhibit
The restart inhibit is used to prevent momentary limit value violations from not being noticed by operating personnel.
1. Use the or buttons to select On.
2. Confirm your selection with OK.
The relay status is retained after switching the relay.
3. If you would like to reset the relay status, press the ESC or button or restart the device.
The relay is reset. Exception: there is a limit value violation.
Defining the Response Delay
Inputting a response delay > 0 s prevents momentary limit value violations from triggering an alarm.
1. To change the time in steps, press the or buttons. Set the time from 0 s to 250 s in increments of 5 seconds.
2. Confirm your entry with OK.
315702 2018-01
EN
EN - 47
Page 50
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Configuration
Response delay has the following effects:
When the value of the trip point is out of range (exceeded or not reached) for a period of time longer than the delay time, the relay switches.
When the value of the trip point ± hysteresis is in range (not reached or exceeded) for a period of time longer than the delay time, the relay switches back.
Shorter overranges/underranges do not have an effect.
The following illustration shows an example of switching characteristics with response delay
Val ue
Max – hysteresis
Max
48 - EN
Switching direction max, mode active, with delay:
Figure 4.3
energized
de-energized
Delay Delay
Time
315702 2018-01
Page 51
HART Loop Converter KFD2-HLC-Ex1.D(.**)
OK → ← ESC
On
OFF
▼ ▲
OK →
← ESC
Restart InhibitFault (On)
Configuration
Fault Message
Calling up a Fault Message
1. Use the or buttons to select the Fault message menu.
2. If the fault message menu is activated, press the OK button once.
The Restart inhibit submenu is displayed.
3. If the fault message menu is not activated, press the OK button twice.
The Restart inhibit submenu is displayed. The Fault message menu is activated
and is marked as On.
Activating the Restart Inhibit
The restart inhibit is used to prevent momentary limit value violations from not being noticed by operating personnel.
1. Use the or buttons to select On.
2. Confirm your selection with OK.
The relay status is retained after switching the relay.
3. If you would like to reset the relay status, press the ESC or button or restart the device.
The relay is reset. Exception: there is a fault message.
EN
315702 2018-01
EN - 49
Page 52
EN
OK →
← ESC
← ESC
OK →
← ESC
▼ ▲
OK →
← ESC
▼ ▲
← ESC
▼ ▲
OK →
← ESC
Reset
▼ ▲
Service
On Reset
OFF Reset
▼ ▲
← ESC
OK →
← ESC
Ver si on
ENG
DE
▼ ▲
Language
Passw ord
OFF Password
On Password
Version No.
50 - EN
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
4.2.9 Service
In the Service menu, you have the option of specifying basic device parameters.
Select language
1. Use the or buttons to select which language is used by the device display.
2. Select ENG for English.
3. Confirm your selection with OK.
4. Select DE for German.
5. Confirm your selection with OK.
315702 2018-01
Page 53
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Configuration
Activating Password Protection
To protect parameterization from unauthorized changes, you can enable password protection. Information about password protection see chapter 4.2.2.
1. Use the or buttons to select the desired setting.
2. To enable password protection, select On Password.
3. Confirm your selection with OK.
4. To disable password protection, select Off Password.
5. Confirm your selection with OK.
Resetting the Device to Factory Settings
1. Use the or buttons to select On Reset.
On Reset flashes.
2. Confirm your selection with OK.
The device is reset to factory settings. All entries you have defined in
parameterization mode will be lost.
Displaying the Software Version
Use the or buttons to display the version.
The software version of the device software is displayed.
315702 2018-01
EN
EN - 51
Page 54
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Operation

5Operation

Danger!
Explosion hazard from live wiring of non-intrinsically safe circuits
If you connect or disconnect energized non-intrinsically safe circuits in a potentially explosive atmosphere, sparks can ignite the surrounding atmosphere.
Only connect or disconnect energized non-intrinsically safe circuits in the absence of a potentially explosive atmosphere.
Danger!
Explosion hazard from sparking when using operating elements
Using operating elements in a potentially explosive atmosphere can cause sparks that can ignite the surrounding atmosphere.
Only use operating elements (e.g., switch, slider, button, etc.) in the absence of a potentially explosive atmosphere.
315702 2018-01
52 - EN
Page 55
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Operation

5.1 Indicators during Operation

The isolated barrier displays the following operating modes and fault messages during operation.
Status Indicators
LED Status Description
315702 2018-01
Green LED Off No power supply
Red LED Flashes briefly Displays a single HART fault message received by the field device
Yellow LEDs
Table 5.1
Flashes regularly Start-up phase, self-test
On Normal function
Flashes regularly Invalid HART data (missing communica tion or fault in the
On Device self-test of isolated barrier detected a fault
On Isolated barrier is in reset state, all other LEDs are off
On For KFD2-HLC-Ex1.D.2W and KFD2-HLC-Ex1D.4S:
field device)
• Output Out 1, relay energized
• Output Out 2, relay energized
For KFD2-HLC-Ex1D.4S:
• Output Out 3, relay energized
• Output Out 4, relay energized
EN
EN - 53
Page 56
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Operation
Display Indicators
In normal operation, the display shows:
the current values of the HART variables PV, SV, TV, QV in the selected unit
the present current output values for the three current outputs in mA
•the current device status This display shows information about the device status of the field device (1 byte) and
about the response code (1 byte) of the field device. These two bytes are displayed in the first line of the display in hexadecimal form with the code RC on the left side.
the current setting of the type of communication
•LOOP Locate
The isolated barrier reestablishes the HART circuit. The isolated barrier performs the field device query using the HART command 3.
LOOP Poll
The isolated barrier performs the field device quer y using the HART command 3.
•LOOP Burst
The isolated barrier receives the HART command 3 of the field device.
LOOP Mixed
The isolated barrier performs the field device query using the HART command 3 (polling). The field device is in burst mode, however it references a different HART command than 3.
In the event of a fault, the display shows:
•Err Device Fault Displays a device fault in the isolated barrier – red LED lights up.
Err Communication Displays a communication fault – red LED flashes.
Err Field Device Malfunction Displays a field device failure – red LED flashes.
315702 2018-01
54 - EN
Page 57
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Operation
Display Options for Current Output Values and HART Variables
To select the displayed measured values or current output values, use the and buttons.
To select units for measured values, use the Unit menu. See chapter 4.2.5.
Every time the isolated barrier receives a HART command 3 message from the field device, the display is updated.
The isolated barrier displays the current output values as a four-digit number. The decimal point is set to provide the best possible resolution.
The isolated barrier shows the floating point value for HART variables as follows:
If possible, as a four-digit number with decimal point and without exponent.
Negative values are shown on the device with three digits because of the minus sign.
A digit is rounded as necessary. For example, the number 0.3456 is shown as
0.346.
If the isolated barrier cannot show the floating point value, the mantissa and
exponent are shown in alternation.

5.2 Fault Message

The following table shows which fault message the current outputs send to the controller, based on the characteristic.
Setting 4 - 20 unlimited 4 - 20 NE43
315702 2018-01
down 0 mA
up approx. 23 mA
hold Last measured value before the fault
Table 5.2
Cannot be distinguished from falling below the start value
Cannot be distinguished from the end value being exceeded
EN
2.0 mA
21.5 mA
EN - 55
Page 58
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Dismounting, Maintenance, and Repair

6 Dismounting, Maintenance, and Repair

Danger!
Explosion hazard from live wiring of circuits
If you connect or disconnect energized circuits in a potentially explosive atmosphere, sparks can ignite the surrounding atmosphere.
Only connect or disconnect energized circuits in the absence of a potentially explosive atmosphere.
Danger!
Danger to life from electric shock
Working on live parts at voltages higher than 50 V AC or 120 V DC can result in electric shock.
1. De-energize the device.
2. Secure the circuit against reconnection.
3. Verify that the device is de-energized at all poles.
4. Provide protection from adjacent live parts, if present.
Danger!
Danger to life from using damaged or repaired devices.
Using a defective or repaired device can compromise its function and its electrical safety.
Do not use a damaged or polluted device.
The device must not be repaired, changed or manipulated.
If there is a defect, always replace the device with an original device from Pepperl+Fuchs.
315702 2018-01
56 - EN
Page 59
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Dismounting, Maintenance, and Repair
Disconnecting Circuits
1. Disconnect the field circuit.
2. Disconnect the control circuit.
3. Disconnect the power supply.
Removing the Device
Use for dismounting of the device a slotted screwdriver
1. Insert the screwdriver (4) into the groove of the red mounting slider (3).
2. Turn the screwdriver (4) in the groove until the red mounting slider (3) springs back.
3. Repeat these steps on the other side of the device.
4. Remove the device (2) from the DIN mounting rail (1).
315702 2018-01
EN
EN - 57
Page 60
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
3 1
4
4
2
Dismounting, Maintenance, and Repair
Figure 6.1 Dismounting of the device from the DIN moun ting rail
1 35 mm DIN mounting rail
2 Device
3 Mounting slider
4 Slotted screwdriver
58 - EN
315702 2018-01
Page 61
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Technical Specifications

7 Technical Specifications

7.1 Default Settings

The following table provides an overview of th e default settings. Information about resetting the device to the default setting see chapter 4.2.9.
Tip
If the device parameters have changed, enter these changes in the "Custom Value" column. This provides an overview of your individual device settings.
Menu Parameters Default setting Custom value
Unit PV Type auto
HARTcom Mode secondary
Output Iout1 Assignment disabled
Output Iout2 Assignment disabled
315702 2018-01
SV Type auto
TV Type auto
QV Type auto
TimeOut 10 s
ComControl auto detect
ShortAddress 0
LocateMethod search
Characteristic 4 - 20 NE43
Start value 0.000
End value 100.0
Fault current down
Characteristic 4 - 20 NE43
Start value 0.000
End value 100.0
Fault current down
EN
EN - 59
Page 62
HART Loop Converter KFD2-HLC-Ex1.D(.**)
EN
Technical Specifications
Menu Parameters Default setting Custom value
Output Iout3 Assignment disabled
Output Rel1 1
Output Rel2
Characteristic 4 - 20 NE43
Start value 0.000
End value 100.0
Fault current down
2
Limit value (Trip) On (selected)
Limit value Assignment disabled
Limit value Min/Max min
Limit value Trip point 80.00
Limit value Hysteresis 10.00
Limit value Operating mode passive
Limit value Restart inhibit OFF
Limit value Response delay 0 s
Fault message not selected
1 2
Limit value (Trip) On (selected)
Limit value Assignment disabled
Limit value Min/Max min
Limit value Trip point 80.00
Limit value Hysteresis 10.00
Limit value Operating mode passive
Limit value Restart inhibit OFF
Limit value Response delay 0 s
Fault message not selected
315702 2018-01
60 - EN
Page 63
HART Loop Converter KFD2-HLC-Ex1.D(.**)
Technical Specifications
Menu Parameters Default setting Custom value
Output Rel3
Output Rel4
Service Language ENG
Table 7.1
1
Relay contact outputs for KFD2-HLC-Ex1.D.4S
2
Relay contact outputs for KFD2-HLC-Ex1.D.2W
315702 2018-01
1
Limit value (Trip) On (selected)
Limit value Assignment disabled
Limit value Min/Max min
Limit value Trip point 80.00
Limit value Hysteresis 10.00
Limit value Operating mode passive
Limit value Restart inhibit OFF
Limit value Response delay 0 s
Fault message not selected
1
Limit value (Trip) On (selected)
Limit value Assignment disabled
Limit value Min/Max min
Limit value Trip point 80.00
Limit value Hysteresis 10.00
Limit value Restart inhibit OFF
Limit value Response delay 0 s
Fault message not selected
Password OFF
EN
EN - 61
Page 64
PROCESS AUTOMATION – PROTECTING YOUR PROCESS
Worldwide Headquarters
Pepperl+Fuchs GmbH 68307 Mannheim · Germany Tel. +49 621 776-0 E-Mail: info@de.pepperl-fuchs.com
For the Pepperl+Fuchs representative closest to you check www.pepperl-fuchs.com/contact
www.pepperl-fuchs.com
Subject to modifications Copyright PEPPERL+FUCHS
· Printed in Germany
315702 DOCT-1377E
01/2018
Loading...