Basic Segment Coupler
PROFIBUS PA
-
S+
-
S+
-
S+
PROFIBUS DP
Bulk
Power
Rail
PSGW
T
T
FE
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
KFD2-BR-1.PA.1500
Output: 24 ... 26 V/400 mA
<
Couples PROFIBUS PA devices transparently to PROFIBUS DP
<
High-power trunk for high device count and long cable lengths
<
Installation in Zone 2/Class I, Div. 2
<
Up to 1.5 MBit auto-adapting
<
PROFIBUS DP terminator selectable
<
Power Rail support
<
Function
The FieldConnex® basic Segment Coupler is an all-in-one gateway and fieldbus power supply for connecting PROFIBUS PA to PROFIBUS DP
transparently. The power output suits long cable lengths and high device counts. Device couplers provide explosion protection for live work at the
spur where needed.
Communication is transparent between DP and PA. The gateway of the Segment Coupler makes each PA device appear as if it was connected
to DP: This relates to addressing, cyclic/acyclic data exchange, and the transfer rate. Segment design is clear and easy to understand without
subnetworks. The gateway itself is confguration-free. All in all, these features significantly reduce engineering work.
Availability and a long service life are achieved through a passive impedance filter and a design optimized for low heat dissipation. The fieldbus
diagnostic handheld (FDH‑1) connects directly to test plug sockets located on the plug-in terminal.
Connection
Technical Data
General specifications
Design / Mounting Cabinet installation
Supply
Connection Power Rail or terminals 11 (L+), 12 (L-)
Rated voltage U
Ripple ≤ 10 %
Rated current I
Power dissipation max 2.5 W
Fieldbus interface
Release date: 2021-01-12 Date of issue: 2021-01-12 Filename: 277830_eng.pdf
20 ... 30 V DC
r
640 mA ... 365 mA
r
1

Basic Segment Coupler KFD2-BR-1.PA.1500
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
Technical Data
PROFIBUS PA
Connection 3+, 6+, 2-, 5-, 1 shield, 4 shield
Rated voltage 24 ... 26 V
Rated current max. 400 mA
Terminating impedance 100 Ω , integrated
PROFIBUS DP PROFIBUS with RS-485 transmission technology
Connection terminals 7 RxD/TxD-P, 8 RxD/TxD-N, 9 shield, 10 FE
Baud rate 1.5 MBit/s max.
Indicators/operating means
Switch PROFIBUS DP terminator
LED PWR green: Power on
LED DP/ERR red 2 Hz flashing: DP error red on: Hardware error red off: DP communication detected
LED PA red 2 Hz flashing: No PA communication or overload Off: PA communication OK
Galvanic isolation
PROFIBUS DP/PROFIBUS PA functional insulation acc. to IEC 62103, rated insulation voltage 50 V AC /70 V DC
PROFIBUS DP/Supply basic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V
PROFIBUS PA/Supply basic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013
Standard conformity
Electromagnetic compatibility NAMUR NE 21
Degree of protection IEC/EN 60529
Fieldbus standard EN 50170/2
Climatic conditions DIN IEC 721
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Ambient conditions
Ambient temperature -40 ... 60 °C (-40 ... 140 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Relative humidity < 95 % non-condensing
Shock resistance 15 g 11 ms
Vibration resistance 1 g 10 ... 150 Hz
Pollution degree max. 2, according to IEC 60664
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection type Terminals
Core cross-section up to 2.5 mm
Housing material Polycarbonate
Degree of protection IP20
Mass 180 g
Mounting DIN rail mounting
Data for application in connection with hazardous areas
Statement of conformity TÜV 16 ATEX 7831 X
Group, category, type of protection,
temperature class
Directive conformity
Directive 2014/34/EU EN 60079-0:2012 , EN 60079-7:2015
International approvals
CSA approval CSA 16.70064204
Approved for Class I, Division 2, Groups A, B, C, D
Release date: 2021-01-12 Date of issue: 2021-01-12 Filename: 277830_eng.pdf
DC
DC
2
1 II 3G Ex ec IIC T4 Gc
Class I, Zone 2, Ex nA IIC T4 Gc
2