Pepperl Fuchs KFD0-RO-Ex2 Datasheet

Pepperl Fuchs KFD0-RO-Ex2 Datasheet

Relay Module

KFD0-RO-Ex2

<2-channel isolated barrier

<24 V DC supply (loop powered)

<Logic input 15 V DC ... 30 V DC, non-polarized

<Relay contact output

<Up to SIL 3 acc. to IEC 61508

Function

This isolated barrier is used for intrinsic safety applications.

The device switches intrinsically safe circuits on the field side. Typical applications for the use of the device are remote reset, fire alarm testing or remote calibration of strain gauges.

The outputs are galvanically isolated to the inputs. The inputs are not polarized and share a common reference potential. Each input of the device is protected by a fuse and an electronic current limiting.

Connection

 

 

KFD0-RO-EX2

 

 

1

7

 

I

3

 

I

 

2

V

 

 

 

4

8 (+/-)

 

 

 

II

II

6

 

9

 

 

5

 

 

 

 

<![if ! IE]>

<![endif]>Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 038975_eng.pdf

 

 

ZONE 0, 1, 2

 

ZONE 2

 

 

DIV. 1, 2

 

DIV. 2

 

 

 

Technical Data

 

 

 

 

 

General specifications

 

 

Signal type

 

Digital Output

Functional safety related parameters

 

 

Safety Integrity Level (SIL)

 

SIL 3

Supply

 

 

Rated voltage

Ur

loop powered

Power dissipation

 

0.8 W

Input

 

 

Connection side

 

control side

Connection

 

terminals 7, 8, 9

Input voltage

 

15 ... 30 V DC

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

Pepperl+Fuchs Group

USA: +1 330 486 0002

Germany: +49 621 776 2222

Singapore: +65 6779 9091

1

www.pepperl-fuchs.com

pa-info@us.pepperl-fuchs.com

pa-info@de.pepperl-fuchs.com

pa-info@sg.pepperl-fuchs.com

 

Relay Module

 

KFD0-RO-Ex2

 

 

Technical Data

 

 

 

 

 

 

 

 

 

Input current

 

≤ 21 mA per channel

 

 

Output

 

 

 

 

Safety note

 

Attention! Combination of output Ex i with output not Ex i is not permitted.

 

 

 

 

If load voltage > 50 V, de-energize before removing the terminals.

 

 

Connection side

 

field side

 

 

Connection

 

terminals 1, 2, 3; 4, 5, 6

 

 

Contact loading

 

230 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load

 

 

Energized/De-energized delay

 

approx. 10 ms / approx. 5 ms

 

 

Mechanical life

 

5 x 106 switching cycles

 

 

Transfer characteristics

 

 

 

 

Switching frequency

 

< 10 Hz

 

 

Galvanic isolation

 

 

 

 

Input/Output

 

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

 

 

Output/Output

 

basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

 

 

Indicators/settings

 

 

 

 

Display elements

 

LEDs

 

 

Labeling

 

space for labeling at the front

 

 

Directive conformity

 

 

 

 

Electromagnetic compatibility

 

 

 

 

Directive 2014/30/EU

 

EN 61326-1:2013 (industrial locations)

 

 

Low voltage

 

 

 

 

Directive 2014/35/EU

 

EN 61010-1:2010

 

 

Conformity

 

 

 

 

Electromagnetic compatibility

 

NE 21:2006

 

 

Degree of protection

 

IEC 60529:2001

 

 

Ambient conditions

 

 

 

 

Ambient temperature

 

-20 ... 65 °C (-4 ... 149 °F)

 

 

Mechanical specifications

 

 

 

 

Degree of protection

 

IP20

 

 

Connection

 

screw terminals

 

 

Mass

 

approx. 100 g

 

 

Dimensions

 

20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2

 

 

Mounting

 

on 35 mm DIN mounting rail acc. to EN 60715:2001

 

 

Data for application in connection with hazardous areas

 

 

EU-Type Examination Certificate

 

DMT 00 ATEX E 016

 

 

Marking

 

1 II (1)G [Ex ia Ga] IIC

 

 

 

 

1 II (1)D [Ex ia Da] IIIC

 

 

 

 

1 I (M1) [Ex ia Ma] I

<![if ! IE]>

<![endif]>eng.pdf

 

Output

 

Ex ia

 

Voltage

Ui

60 V

<![if ! IE]>

<![endif]>038975

 

Current

Ii

2 A

 

 

<![if ! IE]>

<![endif]>Filename:

 

Input

 

 

 

Maximum safe voltage

Um

40 V DC (Attention! Um is no rated voltage.)

 

 

<![if ! IE]>

<![endif]>-09-23

 

Output

 

 

 

Contact loading

 

50 V AC/2 A ; 40 V DC/2 A (TÜV 00 ATEX 1621 X)

<![if ! IE]>

<![endif]>2020

 

Certificate

 

TÜV 00 ATEX 1621 X

<![if ! IE]>

<![endif]>of issue:

 

Marking

 

1 II 3G Ex nA nC IIC T4

 

Galvanic isolation

 

 

<![if ! IE]>

<![endif]>Date

 

Input/Output

 

safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V

<![if ! IE]>

<![endif]>-23

 

 

 

 

 

Output/Output

 

safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 60 V

<![if ! IE]>

<![endif]>-09

 

 

 

 

 

Directive conformity

 

 

<![if ! IE]>

<![endif]>2020

 

 

 

 

Directive 2014/34/EU

 

EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010

<![if ! IE]>

<![endif]>date:

 

 

 

International approvals

 

 

<![if ! IE]>

<![endif]>Release

 

 

 

 

FM approval

 

 

 

 

 

 

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

Pepperl+Fuchs Group

USA: +1 330 486 0002

Germany: +49 621 776 2222

Singapore: +65 6779 9091

2

www.pepperl-fuchs.com

pa-info@us.pepperl-fuchs.com

pa-info@de.pepperl-fuchs.com

pa-info@sg.pepperl-fuchs.com

 

Loading...
+ 2 hidden pages