Relay Module
KFD0-RO-Ex2
<2-channel isolated barrier
<24 V DC supply (loop powered)
<Logic input 15 V DC ... 30 V DC, non-polarized
<Relay contact output
<Up to SIL 3 acc. to IEC 61508
This isolated barrier is used for intrinsic safety applications.
The device switches intrinsically safe circuits on the field side. Typical applications for the use of the device are remote reset, fire alarm testing or remote calibration of strain gauges.
The outputs are galvanically isolated to the inputs. The inputs are not polarized and share a common reference potential. Each input of the device is protected by a fuse and an electronic current limiting.
|
|
KFD0-RO-EX2 |
|
|
1 |
7 |
|
I |
3 |
|
I |
|
2 |
V |
|
|
|
||
|
4 |
8 (+/-) |
|
|
|
II |
|
II |
6 |
|
|
9 |
|
||
|
5 |
|
|
|
|
|
<![endif]>Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 038975_eng.pdf
|
|
ZONE 0, 1, 2 |
|
ZONE 2 |
|
|
DIV. 1, 2 |
|
DIV. 2 |
|
|
|
||
Technical Data |
|
|
||
|
|
|
||
General specifications |
|
|
||
Signal type |
|
Digital Output |
||
Functional safety related parameters |
|
|
||
Safety Integrity Level (SIL) |
|
SIL 3 |
||
Supply |
|
|
||
Rated voltage |
Ur |
loop powered |
||
Power dissipation |
|
0.8 W |
||
Input |
|
|
||
Connection side |
|
control side |
||
Connection |
|
terminals 7, 8, 9 |
||
Input voltage |
|
15 ... 30 V DC |
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group |
USA: +1 330 486 0002 |
Germany: +49 621 776 2222 |
Singapore: +65 6779 9091 |
1 |
www.pepperl-fuchs.com |
pa-info@us.pepperl-fuchs.com |
pa-info@de.pepperl-fuchs.com |
pa-info@sg.pepperl-fuchs.com |
|
Relay Module |
|
KFD0-RO-Ex2 |
|
|
|
Technical Data |
|
|
|
|
|
|
|
|
|
Input current |
|
≤ 21 mA per channel |
|
|
Output |
|
|
|
|
Safety note |
|
Attention! Combination of output Ex i with output not Ex i is not permitted. |
|
|
|
|
If load voltage > 50 V, de-energize before removing the terminals. |
|
|
Connection side |
|
field side |
|
|
Connection |
|
terminals 1, 2, 3; 4, 5, 6 |
|
|
Contact loading |
|
230 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load |
|
|
Energized/De-energized delay |
|
approx. 10 ms / approx. 5 ms |
|
|
Mechanical life |
|
5 x 106 switching cycles |
|
|
Transfer characteristics |
|
|
|
|
Switching frequency |
|
< 10 Hz |
|
|
Galvanic isolation |
|
|
|
|
Input/Output |
|
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
|
Output/Output |
|
basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
|
Indicators/settings |
|
|
|
|
Display elements |
|
LEDs |
|
|
Labeling |
|
space for labeling at the front |
|
|
Directive conformity |
|
|
|
|
Electromagnetic compatibility |
|
|
|
|
Directive 2014/30/EU |
|
EN 61326-1:2013 (industrial locations) |
|
|
Low voltage |
|
|
|
|
Directive 2014/35/EU |
|
EN 61010-1:2010 |
|
|
Conformity |
|
|
|
|
Electromagnetic compatibility |
|
NE 21:2006 |
|
|
Degree of protection |
|
IEC 60529:2001 |
|
|
Ambient conditions |
|
|
|
|
Ambient temperature |
|
-20 ... 65 °C (-4 ... 149 °F) |
|
|
Mechanical specifications |
|
|
|
|
Degree of protection |
|
IP20 |
|
|
Connection |
|
screw terminals |
|
|
Mass |
|
approx. 100 g |
|
|
Dimensions |
|
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
|
|
Mounting |
|
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
|
|
Data for application in connection with hazardous areas |
||
|
|
EU-Type Examination Certificate |
|
DMT 00 ATEX E 016 |
|
|
Marking |
|
1 II (1)G [Ex ia Ga] IIC |
|
|
|
|
1 II (1)D [Ex ia Da] IIIC |
|
|
|
|
1 I (M1) [Ex ia Ma] I |
<![if ! IE]> <![endif]>eng.pdf |
|
Output |
|
Ex ia |
|
Voltage |
Ui |
60 V |
|
<![if ! IE]> <![endif]>038975 |
|
Current |
Ii |
2 A |
|
|
|||
<![if ! IE]> <![endif]>Filename: |
|
Input |
|
|
|
Maximum safe voltage |
Um |
40 V DC (Attention! Um is no rated voltage.) |
|
|
|
|||
<![if ! IE]> <![endif]>-09-23 |
|
Output |
|
|
|
Contact loading |
|
50 V AC/2 A ; 40 V DC/2 A (TÜV 00 ATEX 1621 X) |
|
<![if ! IE]> <![endif]>2020 |
|
Certificate |
|
TÜV 00 ATEX 1621 X |
<![if ! IE]> <![endif]>of issue: |
|
Marking |
|
1 II 3G Ex nA nC IIC T4 |
|
Galvanic isolation |
|
|
|
<![if ! IE]> <![endif]>Date |
|
Input/Output |
|
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
<![if ! IE]> <![endif]>-23 |
|
|
|
|
|
Output/Output |
|
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 60 V |
|
<![if ! IE]> <![endif]>-09 |
|
|
|
|
|
Directive conformity |
|
|
|
<![if ! IE]> <![endif]>2020 |
|
|
|
|
|
Directive 2014/34/EU |
|
EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
|
<![if ! IE]> <![endif]>date: |
|
|
||
|
International approvals |
|
|
|
<![if ! IE]> <![endif]>Release |
|
|
|
|
|
FM approval |
|
|
|
|
|
|
|
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group |
USA: +1 330 486 0002 |
Germany: +49 621 776 2222 |
Singapore: +65 6779 9091 |
2 |
|
www.pepperl-fuchs.com |
pa-info@us.pepperl-fuchs.com |
pa-info@de.pepperl-fuchs.com |
pa-info@sg.pepperl-fuchs.com |
||
|