Switch Amplifier, Timer Relay
Zone 0, 1, 2
Div. 1, 2
KFA6-DU-Ex1.D
3-
1+
10
11
12
I
230 V AC
23
24
II
19+
20-
13+
14-
10 kΩ
10 kΩ
400 Ω ≤ R ≤ 2 kΩ
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
KFA6-DU-Ex1.D
1-channel isolated barrier
<
230 V AC supply
<
Dry contact or NAMUR inputs
<
Relay contact and transistor output
<
Adjustable output timer functions from 10 ms ... 60 min
<
Input frequency up to 80 Hz; pulse divider up to 1 kHz
<
Reset function
<
Configurable by keypad
<
Line fault detection (LFD)
<
Function
This isolated barrier is used for intrinsic safety applications. It is a highly configurable timer that accepts a digital signal (NAMUR
sensor/mechanical contact) from a hazardous area and is commonly used in applications requiring on-delay, off-delay, one-shot, or pulse
lengthening.
The output relay switch duration is easily adjusted, and a pulse divider function allows step-down ratios from 1:1 to 9999:1.
A reset can be activated via dry contact switch and used to terminate a particular time function. The unit is easily programmed by the use of a
keypad located on the front of the unit. Line fault detection of the field circuit is indicated by a red LED.
For additional information, refer to the manual and www.pepperl-fuchs.com.
Connection
Technical Data
General specifications
Signal type Digital Input
Supply
Connection terminals 23, 24
Rated voltage U
Rated current I
Power consumption 4 VA
Input
Connection side field side
Connection Input I: terminals 1+, 3- ; input II: terminals 13+, 14-
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231211_eng.pdf
r
r
230 V AC ± 10 %
15 mA
1

Switch Amplifier, Timer Relay KFA6-DU-Ex1.D
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
Technical Data
Input I acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit current 8.2 V / 10 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Pulse duration min. 75 µs / 1 ms see instruction manuals; the maximum input frequency has to be
Input frequency 0 ... 80 Hz , pulse divider 0 ... 1 kHz
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II reset
Active/Passive I > 3 mA / I < 1.5 mA
Open circuit voltage/short-circuit current 12 V / 3.5 mA
Pulse duration min. 10 ms
Output
Connection side control side
Connection output I: terminals 10, 11, 12 ; output II: terminals 19+, 20Output I signal , Relay output
Contact loading 253 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A
Mechanical life 5 x 107 switching cycles
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output II signal , electronic unit, isolated
Contact loading 40 V / 50 mA
Energized/De-energized delay after rising input flank 3 ms ; after falling input flank 2 ms
Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof)
Transfer characteristics
Input I
Resolution < 0.1 % of the set value, min. 10 ms
Accuracy 2 ms
Influence of ambient temperature 0.003 %/K (50 ppm)
Galvanic isolation
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output I/power supply and reset reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output I, II against eachother reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output II/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output II/reset basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V
Reset/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Indicators/settings
Display elements LEDs , display
Control elements Control panel
Configuration via operating buttons
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EU EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 300 g
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231211_eng.pdf