Pepperl Fuchs KFA6-DU-Ex1.D Users Guide

Switch Amplifier, Timer Relay

Zone 0, 1, 2 Div. 1, 2

KFA6-DU-Ex1.D

3-
1+
10 11 12
I
230 V AC
23 24
II
19+
20-
13+ 14-
10 k
10 k
400 Ω ≤ R 2 k
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
KFA6-DU-Ex1.D
1-channel isolated barrier
<
230 V AC supply
<
Dry contact or NAMUR inputs
<
Relay contact and transistor output
<
Adjustable output timer functions from 10 ms ... 60 min
<
<
Reset function
<
Configurable by keypad
<
Line fault detection (LFD)
<

Function

This isolated barrier is used for intrinsic safety applications. It is a highly configurable timer that accepts a digital signal (NAMUR sensor/mechanical contact) from a hazardous area and is commonly used in applications requiring on-delay, off-delay, one-shot, or pulse lengthening. The output relay switch duration is easily adjusted, and a pulse divider function allows step-down ratios from 1:1 to 9999:1. A reset can be activated via dry contact switch and used to terminate a particular time function. The unit is easily programmed by the use of a keypad located on the front of the unit. Line fault detection of the field circuit is indicated by a red LED. For additional information, refer to the manual and www.pepperl-fuchs.com.

Connection

Technical Data

General specifications
Signal type Digital Input
Supply
Connection terminals 23, 24 Rated voltage U Rated current I Power consumption 4 VA
Input
Connection side field side Connection Input I: terminals 1+, 3- ; input II: terminals 13+, 14-
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231211_eng.pdf
r
r
230 V AC ± 10 % 15 mA
1
Switch Amplifier, Timer Relay KFA6-DU-Ex1.D
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com

Technical Data

Input I acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit current 8.2 V / 10 mA Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA Pulse duration min. 75 µs / 1 ms see instruction manuals; the maximum input frequency has to be
Input frequency 0 ... 80 Hz , pulse divider 0 ... 1 kHz Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II reset
Active/Passive I > 3 mA / I < 1.5 mA Open circuit voltage/short-circuit current 12 V / 3.5 mA Pulse duration min. 10 ms
Output
Connection side control side Connection output I: terminals 10, 11, 12 ; output II: terminals 19+, 20­Output I signal , Relay output
Contact loading 253 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A Mechanical life 5 x 107 switching cycles Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output II signal , electronic unit, isolated
Contact loading 40 V / 50 mA Energized/De-energized delay after rising input flank 3 ms ; after falling input flank 2 ms Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof)
Transfer characteristics
Input I
Resolution < 0.1 % of the set value, min. 10 ms Accuracy 2 ms Influence of ambient temperature 0.003 %/K (50 ppm)
Galvanic isolation
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Output I/power supply and reset reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Output I, II against eachother reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Output II/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V Output II/reset basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V Reset/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Indicators/settings
Display elements LEDs , display Control elements Control panel Configuration via operating buttons Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EU EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006 Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20 Connection screw terminals Mass approx. 300 g
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231211_eng.pdf
observed.
0-signal: blocked output (off-state current ≤ 10 µA)
eff
eff
eff
eff
eff
eff
2
Switch Amplifier, Timer Relay KFA6-DU-Ex1.D
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com

Technical Data

Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination Certificate TÜV 99 ATEX 1408
Marking 1 II (1)G [Ex ia Ga] IIC
Supply
Maximum safe voltage U
Input I terminals 1+, 3-: Ex ia
Voltage U Current I Power P
o
o
o
Input II terminals 13+, 14- non-intrinsically safe
Maximum safe voltage U
m
Output I terminals 10, 11, 12 non-intrinsically safe
Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1408)
Maximum safe voltage U
Output II terminals 19+, 20- non-intrinsically safe
Maximum safe voltage U
Certificate TÜV 02 ATEX 1885 X
Marking 1 II 3G Ex nA nC IIC T4 Gc
Output I
Contact loading 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Galvanic isolation
Input I/other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing 116-0305 UL approval E223772 IECEx approval IECEx TUN 03.0000
Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals
1 II (1)D [Ex ia Da] IIIC 1 I (M1) [Ex ia Ma] I
253 V AC (Attention! The rated voltage can be lower.)
m
10.1 V
13.5 mA 34 mW (linear characteristic)
40 V (Attention! The rated voltage can be lower.)
50 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 02 ATEX 1885 X) 253 V (Attention! The rated voltage can be lower.)
m
40 V (Attention! The rated voltage can be lower.)
m
where applicable. For information see www.pepperl-fuchs.com.
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231211_eng.pdf
3
ESC
OK
KFA6-DU­Ex1.D
PWR1
1
2
IN/ CHK
OUT
19 21
15
9
13
7
20
14
8
22 24
18
12
16
10
23
17
11
132 465
Front view
Removable terminals green
Removable terminal blue
Keypad
LC display
LED green: Power supply
LED yellow/red: Input pulses/ fault signal
LED yellow: Output I
LED yellow: Output II
Place for labeling
Switch Amplifier, Timer Relay KFA6-DU-Ex1.D
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com

Assembly

Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231211_eng.pdf
4
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
Switch Amplifier, Timer Relay
0.1
1
0.2
0.15
2
0.3
3
0.4
4
0.5
0 50 150 200 250100
I (A)
U (V)
1
Characteristic Curve
Maximum Switching Power of Output Contacts
Resistive load DC
Resistive load AC
1 max. 105 switching cycles
KFA6-DU-Ex1.D
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 231211_eng.pdf
5