Pepperl+Fuchs KE5D2-6H Technical Data

Safety Monitor

67.8
7 107
99
Germany: +49 621 776 1111Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0001 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com

Dimensions

Safety Monitor

KE5D2-6H/2R-S

24 V AC/DC supply
<
(6) Monitored inputs
<
DIN rail mountable
<
Dual output relay contacts
<
Internal relay monitoring
<
<

Technical Data

General specifications
UL File Number E179102
Supply
Rated voltage U
Rated current I
Power consumption < 12 W
Indicators/operating means
LED green power
LED red sensor status (one per channel/two per input)
LED red/green relay : ( 2 ) red , ( 2 ) green
Switching state LED red flashing: fault signal
Input
Input type (6) dedicated input devices for 50FY41-.. series
Input voltage 12 V DC , (2 channel, sink/source)
Output
Current 5 mA to 5 A (NO contact)
Release date: 2020-03-24 Date of issue: 2020-03-26 Filename: 235639_eng.pdf
24 V AC/V DC ( for AC, 45 ... 62 Hz )
r
< 0 . 5 A
r
1
CON 1
CON 2
R 21
W 22
B 23
O 24
R 31
W 32
B 33
O 34
R 41
W 42
B 43
O 44
R 51
W 52
B 53
O 54
R 61
W 62
B 63
O 64
R 11
W 12
B 13
O 14
71
72
L/+ 73
N/- 74
81
828384
C1
C2
Relay 1 (SR1)
Relay 2 (SR2)
Relay Control & Fault
Monitoring Circuit
Power Supply
Input Control & Fault Monitoring Circuit
Input1 Input2 Input3 Input4 Input5 Input6
Power
Safety Monitor KE5D2-6H/2R-S
Germany: +49 621 776 1111Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0001 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com

Technical Data

Relay
Switching voltage 20 ... 230 V AC/DC
Switching current See Specifications in manual for details of currents and cycles
Mechanical life > 1,000,000 operations
Output I 2 relay outputs , NO Contact
Response time 20 ms (switch open to contact open)
Transfer characteristics
Time delay before availability 3 s
Compliance with standards and directives
Directive conformity
Machinery Directive 2006/42/EC EN/ISO 13849-1:2008 / AC : 2009
Low Voltage Directive 2006/95/EC EN 60664-1:2007
EMC Directive 2004/108/EC EN 61326-1:2006
Standard conformity
Electromagnetic compatibility EN 61326-1:2006
Standards EN 61496-1:2008
Approvals and certificates
UL approval UL 508
Ambient conditions
Ambient temperature -20 ... 50 °C (-4 ... 122 °F)
Mechanical specifications
Degree of protection IP20
Connection screw connection, max. 2.5 mm
Mass approx. 545 g
Mounting DIN mounting rail
category 3 PL d
EN 61000-6-3:2007+A1:2011 or EN 61000-6-4:2007/A1:2011
IEC 61496-2:2006 EN 50178:1998
2

Connection

Matching system components

50FY41-12
50FY41-50
Release date: 2020-03-24 Date of issue: 2020-03-26 Filename: 235639_eng.pdf
2
Safety Monitor KE5D2-6H/2R-S
Germany: +49 621 776 1111Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0001 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com

Matching system components

50FY41-6

Accessories

50FY41-SIMMOD-1 Sensor simulator device
50FY41-SIMMOD Sensor simulator device
Release date: 2020-03-24 Date of issue: 2020-03-26 Filename: 235639_eng.pdf
3
Germany: +49 621 776 1111Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0001 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com
Safety Monitor
KE5D2-6H/2R-S
Documentation
See instruction manual for complete product information and installation requirements.
Installation
Improper installation
This product is designed to conform to the technical requirements of ISO 13849-1:2008. To ensure compliance with these requirements, 50FY41 series sensors and 52FY31 series actuators must be used with the KE5D2-6H/2R-S and KE5A5-6H/2R-S safety monitors. Consult with the local safety agency and its requirements when designing a machine control system, interface, and all control elements that affect safety. Strictly adhere to all installation instructions. Failure to comply with these instructions could result in death or serious injury.
Release date: 2020-03-24 Date of issue: 2020-03-26 Filename: 235639_eng.pdf