Pepperl Fuchs KC-LCDL-48-2R-230VAC Data Sheet

Timer, Counter, Tachometer KC-LCDL-48-2R-230VAC
Model Number
KC-LCDL-48-2R-230VAC
LCD batch controller with 2 relay outputs and 90 ... 260 V
Features
• Counter/Timer/Tachometer
• Adding/subtracting via 2 separate in­puts
• Batch controller with 2 pre-selections
• Easy-to-read backlit 2-line LCD dis­play with icons for the displayed pre­selection and the status of both outputs
• Display range and preselection range from -999999 up to 999999 Overflow will be evaluated correctly up to 1 decade
• PNP and NPN sensors can be con­nected
• Degree of protection IP65 (front only)
Release date: 2016-09-12 10:30 Date of issue: 2016-09-12 214736_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
supply voltage
AC
Technical data
General specifications
Pre-selection 2-fold Data storage > 10 years, EEPROM Programming keypad-driven menu
Functional safety related parameters
MTTFd 410 a Mission Time (T Diagnostic Coverage (DC) 0 %
Indicators/operating means
Ty p e 2-line, 2 x 6-digit LC display with leading sign
Display value digit height 9 mm Pre-selection digit height 7 mm Key interlock via "high" potential at "LOCK" input Decimal point 0 to max 5 fractional digits Scale factor 0.0001 ... 99.9999 Reset manually or external
Electrical specifications
Fusing 90 260 V AC: T 0.1 A Operating voltage U Power consumption P0max. 8 VA
Input
Connection Counter inputs: A and B
Signal voltage
High 12 ... 30 V DC
Low 0 ... 4 V DC Counting frequency 30 Hz / 55 kHz Minimum pulse duration Control/reset inputs: 10 ms / 1 ms Impedance 5 kOhm Count modes
Pulse counter Counting with counting direction (cnt.dir),
Frequency counter functions for input A and input B:
Timer Time measurement via GATE input (FrErun),
Output
Relay changeover contact , Make contact
Switching voltage max. 250 V AC / 110 V DC
Switching current max. 3 A AC/DC, min. 30 mA DC,
Switching power max. 750 VA / 90 W Sensor supply 20.4 ... 27.6 V DC,
Output I Relay with make contact, NC or NO progr.
Mechanical life 2x107 switching cycles
Electrical life 1 x 10 Output II Relay with changeover contact
Mechanical life 2 x 10
Electrical life 5x104 cycles at 3 A Response time Relay: approx. 7 ms
Ambient conditions
Ambient temperature -20 ... 65 °C (-4 ... 149 °F) Storage temperature -25 ... 75 °C (-13 ... 167 °F) Relative humidity 93 % at 40 °C (noncondensing) Altitude 0 ... 2000 m Pollution degree 2
Mechanical specifications
Degree of protection IP65 (front) Mass approx. 143 g Dimensions 48 mm x 48 mm x 109.8 mm
Compliance with standards and directi­ves
Directive conformity
Low Voltage Directive 2006/95/EC EN 61010-1:2001; protection class: 2
EMC Directive 2004/108/EC EN 61000-6-2:2005, EN 50295:1999 Standard conformity
) 10 a
M
B
backlighted
90 ... 260 V AC
Control/reset inputs: LOCK, RESET, GATE, MPI
difference counting (up.dn), up/down counting (quad), Cumulative counting (up.up), up/down counting x 2 (quad 2), up/down counting x 4 (quad 4), additional functions for counter input A and counter input B:
A/B, (A-B)/A x 100%
A, A-B, A+B quad, A/B, (A-B)/A x 100 %
counter input A: Start, counter input B: Stop (InpA.InpB.), counter input B: Start/Stop (InpB.InpB.), time measuring via RESET input (auto)
max. 80 mA
5
switching cycles at 3 A
7
switching cycles
Frequency counter: 100/600 ms
1
Emitted interference DIN EN 55011:2009, Class B Mech. capacity EN 60068-2-6:2008
Shock and impact resistance EN 60068-2-27:1995
10 55 Hz / 1 mm / XYZ 30 min in each direction
100G / 2ms / XYZ 3 times in each direction
KC-LCDL-48-2R-230VACTimer, Counter, Tachometer
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Release date: 2016-09-12 10:30 Date of issue: 2016-09-12 214736_eng.xml
Loading...
+ 1 hidden pages