Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Introduction
1Introduction
1.1General Information
This manual contains information for application of the device in functional safety
related loops.
The corresponding data sheets, the operating instructions, the system
description, the Declaration of Conformity, the EC-Type-Examination Certificate,
the Functional Safety Assessment and applicable Certificates (see data sheet)
are integral parts of this document.
The documents mentioned are available from www.pepperl-fuchs.com or by
contacting your local Pepperl+Fuchs representative.
Mounting, installation, commissioning, operation, maintenance and disassembly
of any devices may only be carried out by trained, qualified personnel. The
instruction manual must be read and understood.
When a fault is detected within the device, it must be taken out of service and
action taken to protect against accidental use. Devices shall only be repaired
directly by the manufacturer. De-activating or bypassing safety functions or failure
to follow the advice given in this manual (causing disturbances or impairment of
safety functions) may cause damage to property, environment or persons for
which Pepperl+Fuchs GmbH will not be liable.
The devices are developed, manufactured and tested according to the relevant
safety standards. They must only be used for the applications described in the
instructions and with specified environmental conditions, and only in connection
with approved external devices.
1.2Intended Use
The devices are available as safe area version (KCD2-SR-*(.LB)(.SP)) where
they can be used as a signal conditioner providing isolation for non-intrinsically
safe applications. Also the devices are available as hazardous area version
(KCD2-SR-Ex*(.LB)(.SP), HiC282*) allowing use as isolated barriers for intrinsic
safety applications.
The safe area versions transfer digital signals (NAMUR sensors/mechanical
contacts) via a galvanic isolation. The hazardous area versions transfer these
signals from a hazardous to a safe area.
The proximity sensor or switch controls a normally open relay output for the safe
area load. The device output changes state when the input signal changes state.
The normal output state can be reversed via DIP switches.
In the KCD2-SR-(Ex)1.LB(.SP) versions, output II can be switched to either follow
output I or to detect faults on the input line (line break, short circuit).
Line fault detection (LFD) can be selected or disabled via a DIP switch.
During an error condition the outputs de-energize.
4
2014-09
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Introduction
A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error
message output.
The KC devices are available with screw terminals or spring terminals. The type
code of the versions of the KC-devices with spring terminals has the
extension ".SP".
The KCD2-SR-(Ex)*(.LB)(.SP) is a single device for DIN rail mounting while the
HiC282* is a plug-in device to be inserted into a specific Termination Board.
Standard of functional safety of electrical/electronic/programmable electronic
safety-related systems (product manufacturer)
Electromagnetic compatibility:
- EN 61326-1:2006
- NE 21:2006
System specific standards and directives
Functional safety IEC 61511 part 1, edition 2003:
Standard of functional safety: safety instrumented systems for the process
industry sector (user)
2014-09
5
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Planning
2Planning
2.1System Structure
2.1.1Low Demand Mode of Operation
If there are two loops, one for the standard operation and another one for the
functional safety, then usually the demand rate for the safety loop is assumed to
be less than once per year.
The relevant safety parameters to be verified are:
the PFD
value (proof test interval that has a direct impact on the PFD
the SFF value (Safe Failure Fraction)
the HFT architecture (Hardware Fault Tolerance)
2.1.2High Demand or Continuous Mode of Operation
If there is only one loop, which combines the standard operation and safety
related operation, then usually the demand rate for this loop is assumed to be
higher than once per year.
The relevant safety parameters to be verified are:
the PFH value (Probability of dangerous Failure per Hour)
Fault reaction time of the safety system
the SFF value (Safe Failure Fraction)
the HFT architecture (Hardware Fault Tolerance architecture)
2.1.3Safe Failure Fraction
The safe failure fraction describes the ratio of all safe failures and dangerous
detected failures to the total failure rate.
SFF = (
A safe failure fraction as defined in EN 61508 is only relevant for elements or
(sub)systems in a complete safety loop. The device under consideration is
always part of a safety loop but is not regarded as a complete element or
subsystem.
For calculating the SIL of a safety loop it is necessary to evaluate the safe failure
fraction of elements, subsystems and the complete system, but not of a single
device.
Nevertheless the SFF of the device is given in this document for reference.
value (average Probability of Failure on Demand) and the T
avg
+ dd) / (s + dd + du)
s
avg
proof
)
2014-09
6
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Planning
2.2Assumptions
The following assumptions have been made during the FMEDA analysis:
Only one input and one output are part of the considered safety function
(only 2-channel version).
The device shall claim less than 10 % of the total failure budget for a SIL2
safety loop.
For a SIL2 application operating in Low Demand Mode the total PFD
of the SIF (Safety Instrumented Function) should be smaller than 10
the maximum allowable PFD
For a SIL2 application operating in High Demand Mode of operation the total
PFH value of the SIF should be smaller than 10
maximum allowable PFH value would then be 10
Failure rate based on the Siemens SN29500 data base.
Failure rates are constant, wear out mechanisms are not included.
External power supply failure rates are not included.
The safety-related device is considered to be of type A components with a
Hardware Fault Tolerance of 0.
Since the loop has a Hardware Fault Tolerance of 0 and it is a type A
component, the SFF must be > 60 % according to table 2 of IEC 61508-2 for a
SIL2 (sub)system.
It is assumed that the device will be used under average industrial ambient
conditions, which are comparable with the classification "stationary mounted"
in MIL-HDBK-217F. Alternatively, the following ambient conditions are
assumed:
• IEC 60654-1 Class C (sheltered location) with temperature limits in the
range of the manufacturer's specifications and an average temperature
of 40 ºC over a long period. A moisture level within the manufacturer's
specifications is assumed. For a higher average temperature of 60 ºC,
the failure rates must be multiplied by a factor of 2.5 based on empirical
values. A similar multiplier must be used if frequent temperature
fluctuations are expected.
It is assumed that any safe failures that occur (e.g., output in safe condition)
will be corrected within eight hours (e.g., correction of a sensor fault).
While the device is being repaired, measures must be taken to maintain the
safety function (e.g., by using a replacement device).
The indication of a dangerous fault (via fault bus) is detected within 1 hour by
the programmable logic controller (PLC).
value would then be 10-3.
avg
-6
per hour, hence the
-7
per hour.
value
avg
-2
, hence
2014-09
7
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Planning
2.3Safety Function and Safe State
The safe state of each channel is "output de-energized", independent of the
mode of operation.
The safety function has two modes of operation:
normal operation (output follows input)
inverted operation (output inverts input)
The one channel devices have two outputs where output II may be used in safety
relevant applications if it is configured to follow output I.
Therefore the DIP switch settings for all channels used in safety relevant
applications are:
DIP Switch Settings 1-channel Devices
FunctionModeKCD2-SR-(Ex)1.LB(.SP) HiC2821
Output I normal modenormal modeS1 position IS1 position II
inverted modeS1 position IIS1 position I
Assignment output IIfollow output IS2 position IS3 position I
LB/SC detection
Line fault detectionONS3 position IS2 position I
1
This mode may not be used if output II is used for safety relevant applications.
2
This switch setting may not be used if the device is used for safety relevant applications.
Table 2.1
OFF
2
1
S2 position IIS3 position II
S3 position IIS2 position II
DIP Switch Settings 2-channel Devices
FunctionModeKCD2-SR-(Ex)2(.SP)HiC2822
Mode channel 1normal modeS1 position IS1 position II
inverted modeS1 position IIS1 position I
Mode channel 2normal modeS2 position IS3 position II
inverted modeS2 position IIS3 position I
Line fault detection
channel 1
Line fault detection
channel 2
1
This switch setting may not be used if the channel is used for safety relevant applications.
Table 2.2
ONS3 position IS2 position I
1
OFF
ONS4 position IS4 position I
1
OFF
S3 position IIS2 position II
S4 position IIS4 position II
LB/SC Diagnosis
The input loop of all versions is supervised, if the line fault detection is active
(mandatory, see data sheet). The related output goes to the safe state in case of
line fault.
8
2014-09
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Planning
Note!
The failure outputs are not safety relevant.
Reaction Time
The reaction time for all safety functions is < 20 ms.
2.4Characteristic Safety Values
Parameters acc. to IEC 61508Values
Assessment type and
documentation
Device typeA
Mode of operationLow Demand Mode or High Demand Mode
HFT0
SIL2
Safety functionOne relay output of one channelTwo relay outputs of a one
s
dd
du
no effect
total (safety function)
not part
SFF81.55 %85.4 %
1
MTBF
PFH4.68 x 10-8 1/h4.51 x 10-8 1/h
PFD
for T
avg
PFD
avg
PFD
avg
Reaction time
1
acc. to SN29500. This value includes failures which are not part of the safety function.
2
Time between fault detection and fault reaction.
= 1 year2.05 x 10
proof
for T
= 2 years4.10 x 10
proof
for T
= 5 years1.02 x 10
proof
2
Table 2.3
Full assessment
channel device in series
189 FIT216 FIT
18 FIT48 FIT
47 FIT45 FIT
89 FIT90 FIT
254 FIT309 FIT
58 FIT58 FIT
365 years311 years
-4
-4
-3
1.97 x 10
3.95 x 10
9.86 x 10
< 20 ms
-4
-4
-4
The characteristic safety values like PFD, SFF, HFT and T
SIL report/FMEDA report. Please note, PFD and T
proof
are taken from the
proof
are related to each other.
The function of the devices has to be checked within the proof test interval
).
(T
proof
2014-09
9
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Safety Recommendation
3Safety Recommendation
3.1Interfaces
The device has the following interfaces. For corresponding terminals see data
sheet.
Safety relevant interfaces:
KCD2-SR-(Ex)1.LB(.SP), HiC2821: input I, output I, output II
KCD2-SR-(Ex)2(.SP), HiC2822: input I, input II, output I, output II
Non-safety relevant interfaces: output ERR
3.2Configuration
The device must be configured through the user accessible DIP switches for the
required output function before the start-up. During the functionality any change
of the operating function (DIP switch modification) can invalidate the safety
function behavior and must be avoided.
The KCD2 devices provide a suitable cover to protect against accidental changes
while on the HiC devices the access to the DIP switch is permitted only through a
small window on the side and by a small screw driver.
3.3Useful Life Time
Although a constant failure rate is assumed by the probabilistic estimation this
only applies provided that the useful life time of components is not exceeded.
Beyond this useful life time, the result of the probabilistic calculation is
meaningless as the probability of failure significantly increases with time. The
useful life time is highly dependent on the component itself and its operating
conditions – temperature in particular (for example, the electrolytic capacitors can
be very sensitive to the working temperature).
This assumption of a constant failure rate is based on the bathtub curve, which
shows the typical behavior for electronic components.
Therefore it is obvious that failure calculation is only valid for components that
have this constant domain and that the validity of the calculation is limited to the
useful life time of each component.
It is assumed that early failures are detected to a huge percentage during the
installation period and therefore the assumption of a constant failure rate during
the useful life time is valid.
However, according to IEC 61508-2, a useful life time, based on experience,
should be assumed. Experience has shown that the useful life time often lies
within a range period of about 8 ... 12 years.
As noted in DIN EN 61508-2:2011 note NA4, appropriate measures taken by the
manufacturer and operator can extend the useful lifetime.
10
2014-09
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
1
I (A)
10050
U (V)
30
0.5
0.3
Resistive load DC
Electrical life
max. 1 x 10
5
switching cycles
Electrical life
max. 2.5 x 10
5
switching cycles
1
I (A)
2
4
40
10030 50
200
115 253
U (V)
20
Electrical life
max. 1 x 10
5
switching cycles
0.5
0.4
0.15
Resistive load DCResistive load AC
Safety Recommendation
Our experience has shown that the useful life time of a Pepperl+Fuchs product
can be higher
if there are no components with reduced life time in the safety path (like
electrolytic capacitors, relays, flash memory, opto coupler) which can
produce dangerous undetected failures and
if the ambient temperature is significantly below 60 °C.
Please note that the useful life time refers to the (constant) failure rate of the
device.
Maximum Switching Power of Output Contacts
The useful life time is limited by the maximum number of switching cycles under
load conditions. The maximum number of switching cycles is depending on the
electrical load and may be higher when reduced currents and voltages are
applied. You can see the relationship between the maximum switching power and
the load conditions in the diagrams below.
2014-09
Figure 3.1Maximum switching power of HiC282*
Figure 3.2Maximum switching power of KCD2-SR-(Ex)*(.LB)(.SP)
11
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Safety Recommendation
3.4Installation and Commissioning
During installation all aspects regarding the SIL level of the loop must be
considered. The safety function must be tested to ensure the expected outputs
are given. When replacing a device, the loop must be shut down. In all cases,
devices must be replaced by the same type.
12
2014-09
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Proof Test
4Proof Test
4.1Proof Test Procedure
According to IEC 61508-2 a recurring proof test shall be undertaken to reveal
potential dangerous fails that are otherwise not detected by diagnostic test.
The functionality of the subsystem must be verified at periodic intervals
depending on the applied PFD
manual. See chapter 2.4.
It is under the responsibility of the operator to define the type of proof test and the
interval time period.
The ancillary equipment required:
Digital multimeter with an accuracy better than 0.1 %
For the proof test of the intrinsic safety side of the devices, a special digital
multimeter for intrinsically safe circuits must be used.
Intrinsically safe circuits that were operated with non-intrinsically safe
circuits may not be used as intrinsically safe circuits afterwards.
Power supply set at nominal voltage of 24 V DC
The settings have to be verified after the configuration by means of suitable tests.
Procedure:
Sensor state must be simulated by a potentiometer of 4.7 k (threshold for
normal operation), by a resistor of 220 (short circuit detection) and by a resistor
of 150 k (lead breakage detection).
The input test needs to be done for each input channel individually. The threshold
must be between 1.4 mA and 1.9 mA, the hysteresis must be between 170 µA
and 250 µA.
For normal mode of operation the relay must be activated (yellow LED on), if
the input current is above the threshold.
For inverse mode of operation the relay must be activated (yellow LED on), if
the input current is below the threshold.
If the resistor R
the unit must detect an external error. The red LED shall be flashing and the relay
(220 ) or the resistor RLB (150 k) is connected to the input,
SC
of the corresponding channel shall de-activate.
Both relay outputs need to be tested with a certain current, i. e. 100 mA. To avoid
any electrical shock problems, we recommend to use 24 V DC for this test. For
the philosophy of Functional Safety it is important to test, that the relay contacts
are definitely open, if the relay is de-activated.
After the test the unit needs to be set back to the original settings for the current
application. Further the switches for the settings need to be saved against
undeliberate changes. This can be achieved by means of a (translucent)
adhesive label, for HiC units across the hole where the switches are underneath,
2014-09
for KCD2 devices by fixing the label flap.
in accordance with the data provided in this
avg
13
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Proof Test
Multimeter
(mA)
RLBR
SC
Zone 0, 1, 2
Div. 1, 2
1+
2-
KCD2-SR-Ex1.LB
Supply
5
6
7
8
9+
10-
Figure 4.1Proof test set-up for KCD2-SR-(Ex)1.LB(.SP)
Usage in Zone 0, 1, 2/Div. 1, 2 only for KCD2-SR-Ex1.LB(.SP).
Multimeter
(mA)
RLBR
SC
Multimeter
(mA)
RLBR
SC
Zone 0, 1, 2
Div. 1, 2
1+
2-
3+
4-
Figure 4.2Proof test set-up for KCD2-SR-(Ex)2(.SP)
KCD2-SR-Ex2
Supply
5
6
7
8
9+
10-
Usage in Zone 0, 1, 2/Div. 1, 2 only for KCD2-SR-Ex2(.SP).
240 R / 2.5 W
240 R / 2.5 W
Multimeter
(mA)
I supply
240 R / 2.5 W
240 R / 2.5 W
Multimeter
(mA)
I supply
Multimeter
Multimeter
24 V DC
Power
supply
Multimeter
Multimeter
24 V DC
Power
supply
(mA)
(mA)
(mA)
(mA)
24 V DC
24 V DC
24 V DC
24 V DC
Zone 2
Div. 2
Zone 2
Div. 2
14
2014-09
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
HiC2822
Termination Board
Zone 0, 1, 2
Div. 1, 2
Zone 2
Div. 2
11
14
12
15
1+
4-
2+
5-
Multimeter
(mA)
Multimeter
(mA)
Multimeter
( mA )
RLBR
SC
Multimeter
( mA )
RLBR
SC
240 R / 2.5 W
24 V DC
Multimeter
( mA )
240 R / 2.5 W
24 V DC
Supply +
Supply -
24 V DC
Power
supply
I supply
Supply
Bus
Proof Test
Figure 4.3Proof test set-up for HiC2821, HiC2822
Channel 2 only for HiC2822.
Tip
Normally the easiest way to test H-System modules is by using a stand-alone
HiCTB08-UNI-SC-SC Termination Board. The tester then has no need to
disconnect wires in the existing application, so subsequent miswiring of the
module is prevented.
2014-09
15
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Abbreviations
5Abbreviations
DCSDistributed Control System
ESDEmergency Shutdown
FITFailure In Time in 10
FMEDAFailure Mode, Effects and Diagnostics Analysis
s
dd
du
no effect
not part
total (safety function)
Probability of safe failure
Probability of dangerous detected failure
Probability of dangerous undetected failure
Probability of failures of components in the safety path that have
no effect on the safety function
Probability of failure of components that are not in the safety path
Safety function
HFTHardware Fault Tolerance
MTBFMean Time Between Failures
MTTRMean Time To Repair
PFD
avg
Average Probability of Failure on Demand
PFHProbability of dangerous Failure per Hour
PTCProof Test Coverage
SFFS afe Failure Fraction
SIFSafety Instrumented Function
SILSafety Integrity Level
SISSafety Instrumented System
T
proof
Proof Test Interval
-9
1/h
16
ERRError
LBLead Breakage
LFDLine Fault Detection
SCShort Circuit
2014-09
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Notes
2014-09
17
Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Notes
18
2014-09