
Sensor output interface terminals KCD2-EL
Technical data
Functional safety related parameters
MTTFd 1612 a
Indicators/operating means
Model Number
KCD2-EL
Sensor output interface terminal with
lead breakage monitoring
Features
• 1-channel terminal amplifier
•NAMUR sensor input
• DC 24 V supply voltage
• Standard interface for prevention of signal transmission errors
• Switching status indicator, yellow LED
• Lead breakage monitoring: The lead
breakage monitoring can be disconnected by bridging terminals 1 and 3
• Short-circuit proof electronic output
• Low noise sensitivity
• Compact terminal housing
• Clips onto standard 35 mm rail to DIN
EN 50 022
• Degree of protection IP20
LED yellow switch output
Electrical specifications
Operating voltage UB10 ... 30 V DC
Ripple ≤ 10 %
Operating current I
Input
Connection terminals 1+, 2Connectable sensor types NAMUR
Pulse length/pulse interval ≥ 0.5 ms / ≥ 0.5 ms
Short-circuit current approx. 8 mA
Sensor supply 8 V DC
Switching point 1.2 ... 2.1 mA hysteresis approx. 0.2 mA
Line fault detection with
Trip value 1 kHz
Output
Connection terminal 4Current 200 mA short-circuit protected
Transistor NPN
Signal level UB - 1.8V
Transfer characteristics
Mode of operation NO contact
Switching frequency 1 kHz
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013
Standard c on fo rm ity
Degree of protection EN 60529:2000
Noise immunity EN 61326-1:2013
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protection IP20
Connection self-opening apparatus connection terminals, max. core cross-
Mass 60 g
Dimensions 20x60x40
lead breakage: LED off, output locked
approx. 22 mA
B
section 0.34 ... 2.5 mm
(in mm)
2
Release date: 2016-09-26 10:48 Date of issue: 2016-09-26 018357_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
1

Dimensions
KCD2-ELSensor output interface terminals
Electrical connection
546
60
LED
213
4020
Input
Sensor
1+
1+
1+ 2- 3
I ≤
0.1 mA
2-
Lead breakage
monitoring
Output
3
5+6-4-
Supply
voltage
For lead break monitoring you must switch a resistance of 10 kOhm parallel to the contact locally, if you use a mechanical contact as an emitter.
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Release date: 2016-09-26 10:48 Date of issue: 2016-09-26 018357_eng.xml