Pepperl+Fuchs IPT FP, IDENT-I system P IPT FP Series, IDENT-I system P IPT1-FP, IDENT-I system P U-P6-B5-V Series Manual

Page 1
MANUAL
IPT*-FP WITH U-P6-B5
Read/write station with INTERBUS interface
FACTORY AUTOMATION
Page 2
IPT*-FP WITH U-P6-B5
1 Introduction..................................................................4
2 Declaration of conformity ...........................................5
3 Safety............................................................................6
3.1 Symbols relevant to safety ...................................................................... 6
3.2 Intended use.............................................................................................. 6
3.3 General safety instructions...................................................................... 6
3.4 Operational reliability and monitoring.................................................... 7
4 Product description.....................................................8
4.1 Product family........................................................................................... 9
4.1.1 Code/data carrier ........................................................................................ 9
4.2 Range of application ...............................................................................10
4.3 Delivery package......................................................................................10
4.4 Device characteristics.............................................................................10
4.5 Display and controls ...............................................................................11
4.6 Diagnostic LEDs ......................................................................................11
4.7 Interfaces and connections ................................................................... 12
5 Installation..................................................................13
5.1 Storage and transport ............................................................................ 13
5.2 Unpacking ............................................................................................... 13
5.3 EMC concept ........................................................................................... 13
5.4 Device connection .................................................................................. 15
5.4.1 Voltage supply .......................................................................................... 15
5.4.2 Earth connection....................................................................................... 16
5.4.3 INTERBUS Ring termination .................................................................... 17
5.4.4 Cable lengths............................................................................................ 17
5.4.5 Cable ........................................................................................................ 17
5.4.6 Transfer rate changeover.......................................................................... 18
2
Page 3
IPT*-FP WITH U-P6-B5
6 Commissioning ......................................................... 19
6.1 Installation check ....................................................................................19
6.2 Preliminary considerations ....................................................................20
6.3 Self test ....................................................................................................20
7 Operation on the INTERBUS.................................... 21
7.1 General information on INTERBUS........................................................21
7.2 Outline of the commands and data on the INTERBUS ........................21
7.3 General command information ..............................................................21
7.3.1 Software information .................................................................................21
7.3.2 Command overview...................................................................................23
7.4 System commands..................................................................................25
7.5 Read/write commands ............................................................................29
7.5.1 Read data..................................................................................................29
7.5.2 Write data ..................................................................................................33
7.6 Read only code........................................................................................37
7.7 Special command modes .......................................................................41
7.7.1 IPC03 configuration...................................................................................41
7.7.2 Password mode with IPC03 ......................................................................51
7.7.3 Write fixed code IPC10 ..............................................................................54
7.8 Legend......................................................................................................58
7.9 Error/Status messages ...........................................................................59
8 Technical specifications .......................................... 60
8.1 Read/write station IPT*-FP......................................................................60
8.2 Read/write distances IPT*-FP.................................................................61
8.3 U-P6B5 lower section..............................................................................62
3
Page 4
IPT*-FP WITH U-P6-B5
Introduction

1 Introduction

Congratulations
You have chosen a device manufactured by Pepperl+Fuchs. Pepperl+Fuchs develops, produces and distributes electronic sensors and interface modules for the market of automation technology on a worldwide scale.
Before you install this device and put it into operation, please read the operating instructions thoroughly. The instructions and notes contained in this operating manual will guide you step­by-step through the installation and commissioning to ensure the trouble-free usage of this product. This is useful to you, because with this you:
support the safe operation of the device
can utilize the devices entire range of functions
reduce faulty operation and the associated errors
reduce costs from downtime and incidental repairs
increase the effectiveness and operating efficiency of your plant.
Store this operating manual somewhere safe in order to have it available for future work on the device.
Directly after opening the packaging, please ensure that the device is intact and that the package is complete.
Symbols used
The following symbols are used in this manual:
Note!
This symbol draws your attention to important information.
Handling instructions
You will find handling instructions beside this symbol
Contact
If you have any questions about the device, its functions, or accessories, please contact us at:
Pepperl+Fuchs GmbH Lilienthalstraße 200 68307 Mannheim Telephone: +49 621 776-4411 Fax: +49 621 776-274411 E-Mail: fa-info@pepperl-fuchs.com
102696 2009-03
4
Page 5
IPT*-FP WITH U-P6-B5
Declaration of conformity

2 Declaration of conformity

2.1 CE conformity

This product was developed and manufactured under observance of the applicable European standards and guidelines.
Note!
A declaration of conformity can be requested from the manufacturer.
102696 2009-03
5
Page 6
IPT*-FP WITH U-P6-B5
Safety

3 Safety

3.1 Symbols relevant to safety

Danger!
This symbol indicates a warning about a possible danger.
In the event the warning is ignored, the consequences may range from personal injury to death.
Warning!
This symbol indicates a warning about a possible fault or danger.
In the event the warning is ignored, the consequences may course personal injury or heaviest property damage.
Caution!
This symbol warns of a possible fault.
Failure to observe the instructions given in this warning may result in the devices and any connected facilities or systems develop a fault or fail completely.

3.2 Intended use

Together, the devices IPT*-FP and U-P6-B5 of the inductive identification system IDENT-I system P comprise a read/write station..
Always operate the device as described in these instructions to ensure that the device and connected systems function correctly. The protection of operating personnel and plant is only guaranteed if the device is operated in accordance with its intended use.

3.3 General safety instructions

Only instructed specialist staff may operate the device in accordance with the operating manual.
Independent interventions and separate modifications are dangerous and will void the warranty and exclude the manufacturer from any liability. If serious faults occur, stop using the device. Secure the device against inadvertent operation. In the event of repairs, send the device to Pepperl+Fuchs.
The connection of the device and maintenance work when live may only be carried out by a qualified electrical specialist.
The operating company bears responsibility for observing locally applicable safety regulations.
Store the not used device in the original packaging. This offers the device optimal protection against impact and moisture.
Note!
Electronic waste is hazardous waste. Observe local disposal regulations.
6
102696 2009-03
Page 7
IPT*-FP WITH U-P6-B5
Safety

3.4 Operational reliability and monitoring

The devices IPT*-FP and U-P6-B5 of the inductive identification system IDENT-I System P operate on a microprocessor level. Device status is reported via LEDs on the front side on the IPT*-FP read station and in the U-P6-B5 lower section terminal compartment.
In addition, the INTERBUS functionality can be tested by querying the status information or via specific commands to test the device. Device error or the failure of a read/write station, for example, can be recognized and reported by the INTERBUS master in this way.
102696 2009-03
7
Page 8
IPT*-FP WITH U-P6-B5
Product description

4 Product description

The brand name IDENT-I System P represents a complete identification system. The read/write station consists of the read/write head IPT*-FP (standard version: IPT1-FP) and the lower section U-P6-B5 with INTERBUS interface. With the use of 125 kHz technology, the system is extensively open for the implementation of other components.
The lower section operates as a passive node (Slave). It is therefore restricted to use on the cyclically read process data channel. The device assigns 5 words to each 16 bits (10 bytes). The acyclically read parameter channel of the INTERBUS protocol is not assigned.
102696 2009-03
8
Page 9
IPT*-FP WITH U-P6-B5
2
1
3
Product description

4.1 Product family

The inductive identification system IDENT-I system P from Pepperl+Fuchs offers various possible combinations of individual components.
1 Read/write station
2 Lower sections
3 Code/data carrier
Note!
Detailed information on the components of the identification system IDENT-I system P can be found in the sensor systems 1 catalog.

4.1.1 Code/data carrier

A wide assortment of designs is available for the inductive 125 kHz code and data carriers. Data carriers are available for temperatures up to 300 °C (max. 5 min) in chemical-resistant housings for installation in metal and in protection class IP68/IP69K. IPC02-... code carriers offer 40-bit fixcode. IPC03-... data carriers have 928 bits of freely programmable memory and a non-variable fixcode of 32 bits. The storage area of the IPC03- can be protected against unauthorized read and write. 40-bit fixcodes that can be freely determined can be generated with IPC11-... code carriers. These fixcodes can be generated one time permanently or they
102696 2009-03
can be modifiable.
9
Page 10
IPT*-FP WITH U-P6-B5
Product description

4.2 Range of application

The system is suited for the following applications:
Automation
Material flow control in production
Acquisition of operating data
Access control
Identification of e.g. storage vessels, pallets, work piece carriers, refuse containers, tanks, containers, etc.

4.3 Delivery package

IPT*-FP contains:
1 Read/write head
CD with documentation (incl. this manual)
1
U-P6-B5
contains:
Lower section
1 cover
2 ring terminals
1 earthing screw
1 serrated lock washer
1 sticker
1
The lower section must be ordered separately.

4.4 Device characteristics

The lower section U-P6-B5 is the interface with the INTERBUS remote bus.
Supply voltage with galvanic isolation
Bus interfaces with functional isolation accordant with EN 50178.
Connection of the field bus via EMV-PG9 and screw terminals
Addressing by means of physical position of the station in the system
Display LEDs (on the front of the read/write station IPT*-FP)
Diagnostic LEDs
The lower section operates as a passive node (Slave). It is therefore restricted to use on the cyclically read process data channel. The device assigns 5 words to each 16 bits (10 bytes). The acyclically read parameter channel of the INTERBUS protocol is not assigned.
10
102696 2009-03
Page 11
IPT*-FP WITH U-P6-B5
2
1
3
Product description

4.5 Display and controls

The following displays and controls are located on the read/write head.
LED display
1 Bus error - red
2 IPC recognized - yellow,
command executed successfully (approx. 1 second)
3 Power on - green

4.6 Diagnostic LEDs

The following diagnostic LEDs are located in the terminal compartment of the lower section:
LED Color Meaning
US green "Power on"
RC green "Remote Check"
BA green "Bus Acitve"
RD yellow "Remotebus Disabled"
102696 2009-03
11
Page 12
IPT*-FP WITH U-P6-B5
Product description

4.7 Interfaces and connections

The following interfaces and connections are located on the lower section U-P6-B5:
12
102696 2009-03
Page 13
IPT*-FP WITH U-P6-B5
Installation

5 Installation

5.1 Storage and transport

For storage and transport purposes, package the unit using shockproof packaging material and protect it against moisture. The best method of protection it to package the unit using the original packaging. Furthermore, ensure that the ambient conditions are within permissible range.

5.2 Unpacking

Check the product for damages while unpacking. In the event of damage to the product, inform the post office or parcel service and notify the supplier.
Check the package contents with your purchase order and the shipping documents for:
Delivery quantity
Device type and version in accordance with the type plate
Accessories
Manual/manuals
Retain the original packaging in case the device must be stored or shipped again at a later date.
Should you have any questions, please direct them to Pepperl+Fuchs.

5.3 EMC concept

The screening of cables provides for the discharge of electromagnetic interference. When screening a cable, both sides of the screen must be connected to the earth with low resistance and low inductance.
Note!
If cables with double screening are used, e.g. wire meshing and metalized foil, the screens must be connected together at the ends, with low resistance, when making up the cable.
Power supply cables are the source of much interference, e.g. the starting current of 3-phase electric motors. For this reason, the parallel laying of power supply cables with data and signal cables should be avoided, particularly in the same cable duct.
102696 2009-03
13
Page 14
IPT*-FP WITH U-P6-B5
1
2
3
Installation
Connect screening with the PG cable gland of the lower section
In order to connect the screening with the PG cable gland on the lower section and in so doing satisfy the EMC requirements in accordance with DIN VDE 0871/6.78, the following steps must be carried out:
1. Strip the outer sheathing of the cable end over a length of approx. 10 mm.
2. Lightly flare the screen (2).
3. Slide the screen (2) over the cone (3).
4. Pull the seal insert (1) over the screen (2) and cone (3).
5. Screw on the PG cable gland.
14
102696 2009-03
Page 15
IPT*-FP WITH U-P6-B5
rt ge gn
mP1
mP2
SU PI
OUT
IN
OUT
I P T-FP
U-P6-B5
IP C
20 ... 30 VDC
IN
PELV
3
U
s
RC
BA
RD
gn gn gn ge
5
5
RBST
Installation

5.4 Device connection

5.4.1 Voltage supply

The electrical connection of the lower section is made via screw terminals. The maximum core
cross-section of the cable is 1.5 mm
Connect up the INTERBUS and the supply voltage as described in the connection diagram and in the terminal assignment list.
2
.
102696 2009-03
15
Page 16
IPT*-FP WITH U-P6-B5
12 43
Installation

5.4.2 Earth connection

The internal PE connection of the lower section is conductively connected with the housing. However, from the point of view of screening, connection to the outside of the housing is preferable.
The external earth connection of the lower section is located lower left, adjacent to the cable entries. The PE conductor is screwed to the housing with a crimp connector. In order to guarantee safe earthing, the serrated washer must be mounted between the crimp connector and the housing.
1 Housing
2 Serrated lock washer
3 Crimp connector
4 Lock screw
A cross-section of at least 4 mm
2
is recommended for the PE conductor lead.
Note!
The CMD manufacturer-independent program is available for planning, commissioning and diagnosing INTERBUS networks. Details of this program and information on the general theme of INTERBUS are available from:
INTERBUS-Club Postfach 11 08 D-32817 Blomberg Tel: +49 52 35/ 34 21 00 Fax: +49 52 35/ 34 12 34
16
102696 2009-03
Page 17
IPT*-FP WITH U-P6-B5
1
0
Bus not terminated
Bus terminated
Installation

5.4.3 INTERBUS Ring termination

A characteristic of the INTERBUS system is its physical ring structure. Each connected device lies in the bus between two other stations. If this is not the case, for example, at the end of a branch with a bus terminal, then the ring line must be closed in the respective device.
The DIP switch for the ring termination, designated “RBST”, must be set to the correct position (see Figure 5.3). The ring termination switch is located in the terminal compartment in the lower section U-P6-B5.
Ring termination switch
Note!
The ring termination must only be activated if the device is positioned at the end of an open branch! Otherwise all the following devices will be cut off from the communication.

5.4.4 Cable lengths

5.4.5 Cable

102696 2009-03
Depending on the type of cable used and the magnitude of the external interference, the distance between two devices can be up to 400 meters. The total expansion of an INTERBUS­System can be up to 12.8 kilometers. The number of devices connected to the bus is limited to
512.
The following INTERBUS remote bus cables should be used:
Parameter Standard Highly flexible
Cable construction Twisted pairs/i.e. 2-core, common screening
Conductor cross­section
Operating capacity 60 pF/m
Impedance 120 Ω at 64 KHz/100 Ω at 1 MHz
Use only screened cables constructed as twisted pairs. The best possible EMC interference immunity can only be achieved by using screened cables.
3 x 2 x 0.22 mm
2
3 x 2 x 0.25 mm
Suitable for laying underground
2
3 x 2 x 0.22 mm
2
17
Page 18
IPT*-FP WITH U-P6-B5
2 MBit/s
500 kBit/s
Installation

5.4.6 Transfer rate changeover

An internal slide switch enables the transfer rate to be adjusted to match that of the bus. This allows the two values of 500 kbit/s and 2 Mbit/s to be set.
Schiebeschalter
The status is preset at 2 MBit/s on delivery.
102696 2009-03
18
Page 19
IPT*-FP WITH U-P6-B5
Commissioning

6 Commissioning

Warning!
Before commissioning, ensure that the plant is not in danger relating to device malfunction, e.g. from uncontrollable triggered processes.

6.1 Installation check

Caution!
Before commissioning, check once again that the connections are correct.
Before commissioning, familiarize yourself with the system of communication between your INTERBUS and the read/write station. Commissioning requires accurate knowledge of INTERBUS and the programming of your master device.
After connecting the supply voltage the "power on" LED on the read station and the green "US" LED on the lower section must light. Configure the read/write station with the described system commands. Autodetect is set as the data carrier type.
The transfer speed on the INTERBUS is 500 kbit/s or 2 Mbit/s.
102696 2009-03
19
Page 20
IPT*-FP WITH U-P6-B5
Commissioning

6.2 Preliminary considerations

Due to the complexity of field bus programming with the INTERBUS it is very difficult to make generally valid statements about commissioning.
A very important aspect of the operation of an inductive identification system with the lower section on the INTERBUS is the time response of the overall system. The question, "How long after the positioning of a data carrier in front of a read/write station will the read data be available in my computer?" is answered with the aid of knowledge of the INTERBUS protocol structure and the following formula:
= [182 + 1,5 x m] x t
t
ü
t
= Transfer time
ü
m = Number of remote bus stations
installed
= Bit duration t
t
B
it
= Soft ware run time
t
s
w
On large projects, or if you have little experience of programming an INTERBUS system, you should, in any case, construct a laboratory set up of your application and test the data transfer to the INTERBUS master before installing the system in the plant.
+ t
Bit
sw
=2μs corresponding to 500 kBit/s or
B
it
t
=0.5μs corresponding to 2 MBit/s
B
it
= 200 μs
t
s
w
Note!
The CMD manufacturer-independent program is available for planning, commissioning and diagnosing INTERBUS networks. Details of this program and information on the general theme of INTERBUS are available from:
INTERBUS-Club Postfach 11 08 D-32817 Blomberg Tel: +49 52 35/ 34 21 00 Fax: +49 52 35/ 34 12 34

6.3 Self test

When the power supply is switched on the device executes a self test in its internal memory. If the error "RAM defect" or "ROM defect" occurs, the communication is not activated. If no error occurs, then the connection to the INTERBUS master is established automatically.
Note!
When the bus connection with the device is established, the green "BA" LED illuminates and remains on.
20
102696 2009-03
Page 21
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS

7 Operation on the INTERBUS

7.1 General information on INTERBUS

The INTERBUS is a standardized field bus, which enables data exchange between PLCs, PCs, operating and observation devices and also sensors and actuators.
For detailed information, reference should be made to the INTERBUS standard DIN 19258 and to the current literature on the subject.
Note!
The INTERBUS Club publishes informational brochures and an INTERBUS product catalog.

7.2 Outline of the commands and data on the INTERBUS

The lower section assigns 5 words to each 16 bits (10 bytes) in the framework protocol of the INTERBUS in both communication directions. It is restricted in this to the cyclic transfer of the process data channel. This means:
Even the instructions for the adjustment of the device are updated on every cycle.
The parameter channel of the INTERBUS is not used.
The control interface unit is designed as a remote bus station. The ID code is 03.

7.3 General command information

7.3.1 Software information

A command consists of the command code, a specified number of parameters, the toggle flag and the data relating to the command. The command is entered in the output data field of the master.
A response is read from the input data field of the master and consists of the echo of the command code, a parameter, the toggle flag, the status, an execution counter and the read data.
102696 2009-03
21
Page 22
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
A number of commands do not use all the parameter and data fields. These unused data fields are then ignored by the device. The input and output fields are constructed as follows:
Output data field:
Byte 0 Command code
Byte 1 Parameter/Toggle flag
Byte 2 Parameter
Byte 3 Parameter
Byte 4 Write data
... ...
Byte N (defined by module selection)
Input data field:
Byte 0 Command code (Echo)
Byte 1 Parameter/Toggle flag (Echo)
Byte 2 Status
Byte 3 Execution counter
Byte 4 Read data
... ...
Byte N (defined by module selection)
Write data
Read data
22
In order to send a new command to the device, the INTERBUS master must write a command in the output data field. The new command is executed when the data has changed relative to the last read-in. If the same command is to be executed a number of times, the toggle flag must be inverted, so that the device recognizes that a new command has to be processed.
Upon detection of a new command “Status” is set to FFh. In addition, the execution counter is set to 00h and on every further execution of this command it counts up. If the execution counter overruns, it starts again at 00h. An overrun exists when the execution counter reading is equal to 00h and the status is not equal to FFh.
After the processing of commands by the identification system, the “Status” is output in accordance with the Status/Fault signal table (see Section 7.8).
The first two bytes of the response correspond to the first two bytes of the command call-up. Correspondingly, the toggle bit of the response is the same as the toggle bit of the command.
The commands buffered and enhanced buffered… are executed repeatedly as long as the commands remain in the output data field. The execution is terminated when a new command is written in the data.
102696 2009-03
Page 23
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS

7.3.2 Command overview

The commands in the list are described in detail on the following pages.
System commands
Command code Command description
2d 02h quit QU
4d 04h change tag CT
3d 03h version VE
Standard read/write commands
Fixcode
Command code Command description
1d 1h single read fixcode SF
8d 8h auto read fixcode AF
9d 9h buffered read fixcode BF
29d 1Dh enhanced buffered read fixcode EF
Read data
Command code Command description
16d 10 h single read words SR
32d 20h auto read words AR
48d 30h buffered read words BR
25d 19h enhanced buffered read words ER
Write data
Command code Command description
64d 40h single write words SW
80d 50h auto write words AW
96d 60h buffered write words BW
26d 1Ah enhanced buffered write words EW
Abbrevi ation
Abbrevi ation
Abbrevi ation
Abbrevi ation
102696 2009-03
23
Page 24
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Special command modes
Password mode with IPC03
Command code Command description
24d 18h password mode PM
65d 41h password change PC
66d 42h password set PS
IPC03 configuration
Command code Command description
18d 12 h single write configuration SC
19d 13 h auto write configuration AC
20d 14h buffered write configuration BC
102d 66h enhanced buffered write configuration EC
97d 61h single get configuration SG
98d 62h auto get configuration AG
99d 63h buffered get configuration BG
104d 68h enhanced buffered get configuration EG
Abbrevi ation
Abbrevi ation
24
Write fixcode
Commands for the IPC10 and IPC11
Command code Command description
31d 1Fh single write fixcode SX
100d 64h auto write fixcode AX
101d 65h buffered write fixcode BX
36d 24h enhanced buffered write fixcode EX
Abbrevi ation
102696 2009-03
Page 25
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS

7.4 System commands

Quit
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command
code
Byte 1 Reserved/
Toggle bit
Byte 2 not
relevant
.
.
.
.
.
.
Byte 9 not
relevant
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command
code
Byte 1 Reserved/
Toggle bit
Byte 2 Status <Status>
Byte 3 Execution
counter
Byte 4 not
relevant
.
.
.
.
.
.
Byte 9 not
relevant
0 0 0 0 0 0 1 0
- - - - - - - T
- - - - - - - -
- - - - - - - -
- - - - - - - -
0 0 0 0 0 0 1 0
- - - - - - - T
<ExecCounter>
- - - - - - - -
- - - - - - - -
- - - - - - - -
The running buffered, enhanced-buffered or auto command of the specified read/write head is interrupted.
102696 2009-03
25
Page 26
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Change Tag
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command
code
Byte 1 Reserved/
Toggle bit
Byte 2 Data
carrier type in ASCII
Byte 3 Data
carrier type in ASCII
Byte 4 not
relevant
.
.
.
.
.
.
Byte 9 not
relevant
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command
code
Byte 1 Reserved/
Toggle bit
Byte 2 Status <Status>
Byte 3 Execution
counter
Byte 4 not
relevant
.
.
.
.
.
.
Byte 9 not
relevant
0 0 0 0 0 1 0 0
- - - - - - - T
<TagType> (High Byte)
<TagType> (Low Byte)
- - - - - - - -
- - - - - - - -
- - - - - - - -
0 0 0 0 0 1 0 0
- - - - - - - T
<ExecCounter>
- - - - - - - -
- - - - - - - -
- - - - - - - -
26
This command tells the read head which code or data carrier to communicate with. The read head status on delivery is type “00”.
102696 2009-03
Page 27
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
The following code and data carriers are currently supported:
TagType
Description Chip Access
0 0 Autodetect
0 2 IPC02 μEM V4001 Fixcode 32
0 3 IPC03 μEM V4050/64 R/W 00...1D 928
1 0 IPC10 Nova R/W 0 96
With <TagType> = “00”, mixed operation of different code and data carriers is possible. Since the read head for the autodetect requires a significantly longer time, only static read and write is practical in this mode.
<WordA ddr>
BitsHigh Byte Low Byte
102696 2009-03
27
Page 28
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Version
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 0 0 0 1 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Parameter <Parameter>
Byte 3 not relevant - - - - - - - -
.
.
.
.
.
.
Byte 9 not relevant - - - - - - - -
Response
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 0 0 0 1 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4 Data 00 ... FF
.
Data 00 ... FF . .
Byte 9 Data 00 ... FF
h
h
h
- - - - - - - -
<VersionData> section 1
<VersionData> section ...
<VersionData> section 6
28
This command transfers the software version. The complete software version message cannot be transferred with one command due to its length. The individual parts of the software version message are transferred by repeated execution of the command with the appropriate parameters.
<Parameter> Meaning <VersionData> Beispiel 0; > 8 Incorrect parameter, Status “04h” Data = 0 000000
1 Identification system - Type IPT*-FP
2 Identification system - Part number 095725
3 Identification system - software number 01I040
4 Identification system - software date 170399
5 Bus system - type U-P6B5
6 Bus system - part number 099100
7 Bus system - software number 01K034
8 Bus system - software date 170399
102696 2009-03
Page 29
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS

7.5 Read/write commands

7.5.1 Read data

Single Read Words
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 0 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Word address <WordAddr> (High Byte)
Byte 3 Word address <WordAddr> (Low Byte)
Byte 4 not relevant - - - - - - - -
. . .
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 0 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
. . .
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
- - - - - - - -
a)
h
a)
h
a)
h
a)
h
<Data3>
<Data2>
<Data1>
<Data0>
One attempt is made to read a 32-bit word (<WordNum> = “0001) from the address <WordAddr>.
102696 2009-03
29
Page 30
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Auto Read Words
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 1 0 0 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Word address <WordAddr> (High Byte)
Byte 3 Word address <WordAddr> (Low Byte)
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 1 0 0 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4
Byte 5
Byte 6
Byte 7
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
a)
h
a)
h
a)
h
a)
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
- - - - - - - -
<Data3>
<Data2>
<Data1>
<Data0>
30
Repeated attempts are made until a 32-bit word (<WordNum> = “0001) is read from the address <WordAddr>.
102696 2009-03
Page 31
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Buffered Read Words
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 1 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Word address <WordAddr> (High Byte)
Byte 3 Word address <WordAddr> (Low Byte)
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
- - - - - - - -
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 1 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4
Byte 5
Byte 6
Byte 7
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
a)
h
a)
h
a)
h
a)
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
0 1
0 1
<Data3>
<Data2>
<Data1>
<Data0>
An attempt is made to read a 32-bit word (<WordNum> = “0001) from the address until successful <WordAddr>. Only changed data is transferred via the interface, i.e. when the next data carrier is read, or if previously no data carrier was found in the read range, the new data carrier.
102696 2009-03
31
Page 32
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Enhanced buffered Read Words
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 1 1 0 0 0 1
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Word address <WordAddr> (High Byte)
Byte 3 Word address <WordAddr> (Low Byte)
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 1 1 0 0 0 1
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4
Byte 5
Byte 6
Byte 7
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
a)
h
a)
h
a)
h
a)
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
- - - - - - - -
<Data3>
<Data2>
<Data1>
<Data0>
32
An attempt is made to read a 32-bit word (<WordNum> = “0001) from the address until successful <WordAddr>. Only changed data is transferred via the interface. When a data carrier leaves the read range, the status “05h” is output.
102696 2009-03
Page 33
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS

7.5.2 Write data

Single Write Words
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 0 0 0 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Word address <WordAddr> (High Byte)
Byte 3 Word address <WordAddr> (Low Byte)
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 0 0 0 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Status <Status>)
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
Byte 9 not relevant - - - - - - - -
h
h
h
h
- - - - - - - -
<Data 3>
<Data 2>
<Data 1>
<Data 0>
One attempt is made to write a 32-bit word (<WordNum> = “0001) from the address <WordAddr>. A maximum of 1 word = 4 bytes can be written.
102696 2009-03
33
Page 34
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Auto Write Words
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 0 1 0 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Word address <WordAddr> (High Byte)
Byte 3 Word address <WordAddr> (Low Byte)
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
h
h
h
h
<Data 0>
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 0 1 0 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Status <Status>)
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
- - - - - - - -
Byte 9 not relevant - - - - - - - -
<Data 3>
<Data 2>
<Data 1>
34
Repeated attempts are made until a 32-bit word (<WordNum> = “0001) is written from the address <WordAddr>. A maximum of 1 word = 4 bytes can be written.
102696 2009-03
Page 35
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Buffered Write Words
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Word address <WordAddr> (High Byte)
Byte 3 Word address <WordAddr> (Low Byte)
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
h
h
h
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 0 0 0
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Status <Status>)
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
- - - - - - - -
Byte 9 not relevant - - - - - - - -
<Data 3>
<Data 2>
<Data 1>
<Data 0>
An attempt is now made to write a 32-bit word (<WordNum> = “0001”) from the address <WordAddr>. After successfully writing, the response is sent and then continuous reading ensues. Then the same carrier data is read, until the data carrier has left the read/write range or a new data carrier appears in front of the read/write head. The command then starts again with write attempts.
A maximum of 1 word = 4 bytes can be written.
102696 2009-03
35
Page 36
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Enhanced Buffered Write Words
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 1 0 0 1
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Word address <WordAddr> (High Byte)
Byte 3 Word address <WordAddr> (Low Byte)
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
h
h
h
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 1 0 0 1
Byte 1 Word count/Toggle bit <WordNum> - - - T
Byte 2 Status <Status>)
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
- - - - - - - -
Byte 9 not relevant - - - - - - - -
<Data 3>
<Data 2>
<Data 1>
<Data 0>
36
An attempt is now made to write a 32-bit word (<WordNum> = "0001) from the address <WordAddr> . After successfully writing, the response is sent and then continuous reading ensues. Then the same carrier data is read, until the data carrier has left the read/write range or a new data carrier appears in front of the read/write head. The command then starts again with write attempts. The status “05h” is output if the data carrier leaves the read range.
A maximum of 1 word = 4 bytes can be written.
102696 2009-03
Page 37
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS

7.6 Read only code

Single Read Fixcode
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 0 0 0 0 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 not relevant - - - - - - - -
. . .
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 0 0 0 1 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Byte 9 not relevant - - - - - - - -
. . .
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
- - - - - - - -
a)
h
a)
h
a)
h
a)
h
a)
h
<ID-Code 4>a)/<ID-Code 3>
<ID-Code 3>a)/<ID-Code 2>
<ID-Code 2>a)/<ID-Code 1>
<ID-Code 1>a)/<ID-Code 0>
<ID-Code 0>
a)
a) only with IPC02
A fixed code is read once.
102696 2009-03
37
Page 38
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Auto Read Fixcode
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 0 1 0 0 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 not relevant - - - - - - - -
.
. .
. .
.
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 0 1 0 0 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
a)
h
a)
h
a)
h
a)
h
a)
h
Byte 9 not relevant - - - - - - - -
- - - - - - - -
<ID-Code 4>a)/<ID-Code 3>
<ID-Code 3>a)/<ID-Code 2>
<ID-Code 2>a)/<ID-Code 1>
<ID-Code 1>a)/<ID-Code 0>
<ID-Code 0>
a)
38
a) only with IPC02
An attempt is made to read until a fixed code has been read.
102696 2009-03
Page 39
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Buffered Read Fixcode
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 0 1 0 0 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 not relevant - - - - - - - -
.
. .
. .
.
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 0 1 0 0 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
a)
h
a)
h
a)
h
a)
h
a)
h
Byte 9 not relevant - - - - - - - -
- - - - - - - -
<ID-Code 4>a)/<ID-Code 3>
<ID-Code 3>a)/<ID-Code 2>
<ID-Code 2>a)/<ID-Code 1>
<ID-Code 1>a)/<ID-Code 0>
<ID-Code 0>
a)
a) only with IPC02
The fixcode continues to be read. Only changed data is transferred via the interface.
102696 2009-03
39
Page 40
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Enhanced Buffered Read Fixcode
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 1 1 0 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 not relevant - - - - - - - -
.
. .
. .
.
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 1 1 0 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
ID-Code 00 ... FF
a)
h
a)
h
a)
h
a)
h
a)
h
Byte 9 not relevant - - - - - - - -
- - - - - - - -
<ID-Code 4>a)/<ID-Code 3>
<ID-Code 3>a)/<ID-Code 2>
<ID-Code 2>a)/<ID-Code 1>
<ID-Code 1>a)/<ID-Code 0>
<ID-Code 0>
a)
40
a) only with IPC02
The fixcode continues to be read. Only changed data is transferred via the interface. If the code or data carrier leaves the read range, the status “05h” is output.
102696 2009-03
Page 41
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS

7.7 Special command modes

7.7.1 IPC03 configuration

Note!
These commands can only be used when data carrier type 03 (IPC03) is set. They cannot be used in the autodetect mode (mixed operation, data carrier type 00)!
The storage of a type IPC03 data carrier is organized by word. Every “word is made up of 32 bits. For the normal data range, 29 words from addresses 3 through 31 (<WordAddr> = 00
) are available.
1C
h
The storage of the data carrier IPC03 is constructed in the following way:
Address Meaning <WordAddr> <ConfAddr> Note
Word 0 Password - - Write on ly
Word 1 Protection word - "1" Read/write
Word 3 Control word - "2" Read/write
Word 3...31 Data range "00"..."1C" - Read/write
Word 32 Device Serial
Word 33 Device
Number
identification
"1D" - Read only
"1E" - Read only
h
The IPC03 has one protection word and one control word”. With the protection word”, a read- protected and a write-protected range can be defined. For this, each start and end of a read­protected and a write-protected range can be defined. With the control word”, various operating modes and the read range for the default read operating mode are set. Both words can only be accessed with the correct password.
The bits of the individual words have the following meaning:
Control word
Bit Meaning Byte
0...7 Read range start 0
8 ... 15 Read range end 1
16 Password protection on/off 2 17 Read after write operating
18 ... 23 Open
24 ... 31 Open 3
102696 2009-03
mode on/off
41
Page 42
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Protection word
Bit Meaning Byte
0 ... 7 First read-protected word 0
8 ... 15 Last read-protected word 1
16 ... 23 First write-protected word 2
24 ... 31 Last write-protected word 3
With the control and protection word, it should be noted that when communicating a word, the highest value byte is transferred first and the lowest value byte last. With the entry of the read and write-protected words, the words are counted as follows:
00 Password
01 Protection word
02 Control word
03 1. Data word
04 2. Data word
... ...
1F 29. Data word
IPC03 password mode
It is possible to protect the control word and the protection word from being overwritten. Then the configuration can no longer be changed. The password mode serves this purpose.
With password mode active in the data carrier, the data range of a data carrier can only be read or written after the correct password is sent to the data carrier from the read/write head. The following must apply for this:
The correct password is set once with the command PS set password and
the password mode is activated with the command PM set password mode”.
The password in the read/write head and on the data carrier can be changed with the command PC.
42
If the password mode is deactivated, every word on the data carrier can be read and written as necessary.
In the factory default condition of the read heads and the data carrier IPC03, the password is 00000000
IPC03 in a non-volatile manner.
"Default read"
In the default read operating mode 1 or 2, words can be read very quickly, because the memory to be read is already defined on the data carrier and does not need to be communicated to the data carrier from the read/write head first.
. In the read head, the password is stored in a volatile manner and in the data carrier
h
102696 2009-03
Page 43
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
The start and end of the read range are stored in the bytes 0 and 1 of the "control word". As soon as the data carrier is supplied with energy the data carrier sends out the data from the data range, which is defined by the read range start and end. The data range between read range start and end can be read with the read commands SR (single read words) and ER (enhanced buffered read words) when <WordAddr> is set to 0000h and <WordNum> is set to 00h.
The advantages of the default read operating mode lie in the readout speed. The readout of one data word (4 bytes) is twice as fast in this mode. The readout of 2 words takes approx. 1/3 less time. Starting at 3 data words there is no more time advantage since this mode is only intended for the reading of a maximum of 2 words (=8 bytes). Reading larger data ranges can lead to error messages when the read head does not respond within the planned reaction time.
Single Write Configuration
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 0 0 1 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 not relevant - - - - - - - -
Byte 3 Address in the configuration
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
range
h
h
h
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
<RegAddr>
<Data>
<Data>
<Data>
<Data>
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 0 0 1 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
. . .
. . .
- - - - - - - -
Byte 9 not relevant - - - - - - - -
One attempt is made to write a word in the configuration range from the address <RegAddr>. In order to write in the configuration range, the password mode must be active.
102696 2009-03
43
Page 44
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Auto Write Configuration
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 0 0 1 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 not relevant - - - - - - - -
Byte 3 Address in the
configuration range
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
h
h
h
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 0 0 1 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
- - - - - - - -
Byte 9 not relevant - - - - - - - -
<RegAddr>
<Data>
<Data>
<Data>
<Data>
44
An attempt is made to write a word in the configuration range from the address until successful. <RegAddr>. In order to write in the configuration range, the password mode must be active.
102696 2009-03
Page 45
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Buffered Write Configuration
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 0 1 0 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 not relevant - - - - - - - -
Byte 3 Address in the
configuration range
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
h
h
h
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 0 1 0 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
- - - - - - - -
Byte 9 not relevant - - - - - - - -
<RegAddr>
<Data>
<Data>
<Data>
<Data>
One attempt is made to write a word in the configuration range from the address <RegAddr> . After each successful write, the response is sent and the system waits until a new data carrier is within the detection range. The command then starts again from the beginning. In order to write in the configuration range, the password mode must be active.
102696 2009-03
45
Page 46
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Enhanced Buffered Write Configuration
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 1 1 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 not relevant - - - - - - - -
Byte 3 Address in the
configuration range
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
h
h
h
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 1 1 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
- - - - - - - -
Byte 9 not relevant - - - - - - - -
<RegAddr>
<Data>
<Data>
<Data>
<Data>
46
One attempt is made to write a word in the configuration range from the address <RegAddr>. After each successful write, the response is sent and the system waits until a new data carrier is within the detection range. The command then starts again from the beginning. In order to write in the configuration range, the password mode must be active. When the data carrier leaves the read range, the status 05
is output.
h
102696 2009-03
Page 47
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Single Get Configuration
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 0 0 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Reserved 0 0 0 0 0 0 0 0
Byte 3 Register address <RegAddr>
Byte 4 not relevant - - - - - - - -
. . .
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 0 0 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution character <ExecCounter>
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
. . .
h
h
h
h
- - - - - - - -
<Data>
<Data>
<Data>
<Data>
One attempt is made to read a word in the configuration range (protection word or “control word) from the address <RegAddr>.
102696 2009-03
47
Page 48
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Auto Get Configuration
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 0 1 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Reserved 0 0 0 0 0 0 0 0
Byte 3 Register address <RegAddr>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 0 1 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution character <ExecCounter>
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
h
h
h
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
- - - - - - - -
<Data>
<Data>
<Data>
<Data>
48
Repeated attempts are made until successful, to read a word in the configuration range from the address <RegAddr> .
102696 2009-03
Page 49
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Buffered Get Configuration
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 0 1 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Reserved 0 0 0 0 0 0 0 0
Byte 3 Register address <RegAddr>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 0 1 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution character <ExecCounter>
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
h
h
h
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
- - - - - - - -
<Data>
<Data>
<Data>
<Data>
An attempt is made to write a word in the configuration range from the address until successful. <RegAddr>. Only changed data is transferred via the interface.
102696 2009-03
49
Page 50
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Enhanced Buffered Get Configuration
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 1 0 0 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Reserved 0 0 0 0 0 0 0 0
Byte 3 Register address <RegAddr>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 1 0 0 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 Execution character <ExecCounter>
Byte 4 Data 00 ... FF
Byte 5 Data 00 ... FF
Byte 6 Data 00 ... FF
Byte 7 Data 00 ... FF
h
h
h
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
- - - - - - - -
<Data>
<Data>
<Data>
<Data>
50
An attempt is made to write a word in the configuration range from the address until successful. <RegAddr>. Only changed data is transferred via the interface. When the data carrier leaves the read range, the status “05h” is output.
102696 2009-03
Page 51
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS

7. 7. 2 P a s s w o r d m od e w i t h I P C 0 3

Note!
The password is a 32-bit word that is set to "0" before a new IPC03 data carrier leaves the factory. The password cannot be read. In order to write the passwords for the "Control Word" and the "Protection Word", the processing must always be in password mode.
Password Mode
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 1 0 0 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Mode (on:<F>=1, off:<F>=0) 0 0 0 0 0 0 0 <F>
Byte 3 not relevant - - - - - - - -
. . .
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 1 0 0 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 not relevant - - - - - - - -
. . .
Byte 9 not relevant - - - - - - - -
. . .
. . .
- - - - - - - -
- - - - - - - -
Activates (Mode <F> = “1”) and deactivates (Mode <F> = “0”) the password mode of the read head. In the password mode, the password is transferred to the data carrier before each read/write access. If a data carrier is addressed with the wrong password, then even the data range, for which no password protection is set, cannot be accessed.
102696 2009-03
51
Page 52
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Password Change
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 0 0 0 0 0 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Old password 00 ... FF
Byte 3 Old password 00 ... FF
Byte 4 Old password 00 ... FF
Byte 5 Old password 00 ... FF
Byte 6 New password 00 ... FF
Byte 7 New password 00 ... FF
Byte 8 New password 00 ... FF
Byte 9 New password 00 ... FF
h
h
h
h
h
h
h
h
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 0 0 0 0 0 1
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 not relevant - - - - - - - -
. . .
. . .
- - - - - - - -
Byte 9 not relevant - - - - - - - -
<PSW 3>
<PSW 2>
<PSW 1>
<PSW 0>
<PSW 3>
<PSW 2>
<PSW 1>
<PSW 0>
52
Changes the password in a data carrier. Here, first the old and then the new password has to be entered. If the password has been successfully written, then the password in the read/write head is also changed. The command password set is no longer necessary. The IPC03 password can also be changed when the password mode is deactivated.
102696 2009-03
Page 53
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Password Set
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 0 0 0 0 1 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 not relevant - - - - - - - -
Byte 3 not relevant - - - - - - - -
Byte 4 Password 00 ... FF
Byte 5 Password 00 ... FF
Byte 6 Password 00 ... FF
Byte 7 Password 00 ... FF
h
h
h
h
Byte 8 not relevant - - - - - - - -
Byte 9 not relevant - - - - - - - -
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 0 0 0 0 1 0
Byte 1 Reserved/Toggle bit - - - - - - - T
Byte 2 Status <Status>
Byte 3 not relevant - - - - - - - -
. . .
. . .
- - - - - - - -
Byte 9 not relevant - - - - - - - -
<PSW 3>
<PSW 2>
<PSW 1>
<PSW 0>
Sets the password, which the read/write head communicates to the data carrier in the password mode.
102696 2009-03
53
Page 54
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS

7.7.3 Write fixed code IPC10

Single Write Fixcode
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 1 1 1 1
Byte 1 FixLen/Toggle bit <FixLen> - - - T
Byte 2 Fixtype <FixType> (High Byte)
Byte 3 Fixtype <FixType> (Low Byte)
Byte 4 Data 00 ... FF
. . .
Byte 9 Data 00 ... FF
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 0 1 1 1 1 1
Byte 1 FixLen/Toggle bit <FixLen> - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
. . .
Byte 9 not relevant - - - - - - - -
Data 00 ... FF
. . .
h
h
h
<Data>
<Data>
<Data>
- - - - - - - -
54
One attempt is made to write a fixed code. This <FixType> is always “02” and <FixLen> “05
since 5 bytes must always be written.
,
h
102696 2009-03
Page 55
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Auto Write Fixcode
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 1 0 0
Byte 1 FixLen/Toggle bit <FixLen> - - - T
Byte 2 FixType <FixType> (High Byte)
Byte 3 FixType <FixType> (Low Byte)
Byte 4 Data 00 ... FF
.
Data 00 ... FF . .
Byte 9 Data 00 ... FF
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 1 0 0
Byte 1 FixLen/Toggle bit <FixLen> - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
Byte 9 not relevant - - - - - - - -
h
h
h
- - - - - - - -
<Data>
<Data>
<Data>
An attempt is made to write a fixcode until successful.
102696 2009-03
55
Page 56
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Buffered Write Fixcode
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 1 0 1
Byte 1 FixLen/Toggle bit <FixLen> - - - T
Byte 2 FixType <FixType> (High Byte)
Byte 3 FixType <FixType> (Low Byte)
Byte 4 Data 00 ... FF
.
Data 00 ... FF . .
Byte 9 Data 00 ... FF
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 1 1 0 0 1 0 1
Byte 1 FixLen/Toggle bit <FixLen> - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
Byte 9 not relevant - - - - - - - -
h
h
h
- - - - - - - -
<Data>
<Data>
<Data>
56
One attempt is made to write a fixcode. After each successful write, the response is sent and the system waits until a new data carrier is within the detection range. The command then starts again from the beginning.
102696 2009-03
Page 57
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS
Enhanced buffered write fixed code; write ID code
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 1 0 0 1 0 0
Byte 1 FixLen/Toggle bit <FixLen> - - - T
Byte 2 Fixtype <FixType> (High Byte)
Byte 3 Fixtype <FixType> (Low Byte)
Byte 4 Data 00 ... FF
.
Data 00 ... FF . .
Byte 9 Data 00 ... FF
h
h
h
Response:
Byte Content B7 B6 B5 B4 B3 B2 B1 B0
Byte 0 Command code 0 0 1 0 0 1 0 0
Byte 1 FixLen/Toggle bit <FixLen> - - - T
Byte 2 Status <Status>
Byte 3 Execution counter <ExecCounter>
Byte 4 not relevant - - - - - - - -
.
. .
. .
.
- - - - - - - -
Byte 9 not relevant - - - - - - - -
<Data>
<Data>
<Data>
One attempt is made to write a fixcode. After each successful write, the response is sent and the system waits until a new data carrier is within the detection range. The command then starts again from the beginning. When the data carrier leaves the read range, the status “05
output.
102696 2009-03
is
h
57
Page 58
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS

7.8 Legend

<ConfAddr> : Word start address in the configuration range of the data
<Data> : <WordNum> times 4 Bytes. When communicating a word,
<ExecCounter> : 1 byte
<FixLen> : 4 Bits <FixType> : 2 ASCII characters, for example: for IPC02 “02” (32h 30h)
<IDCode> : 4 bytes for IPC03
Mode <F> : 1 ASCII character “0” or “1”.
<Parameter>: : 1 Byte, range of values 01h to 08h
<PSW> : 4 Bytes, password
<RegAddr>: : 4 Bytes
<Status> : 1 byte
<T> : 1 Bit 0 (0b); 1(1b)
<TagType> : 2 ASCII characters, for example: '02' for IPC02
<VersionData> : 6 ASCII characters, software version message
<WordAddr> : 4 Bytes
<WordNum> : 4 Bits
carrier. 1 ASCII character range from "0" to "F", depending on data carrier type. The following applies for IPC03: "1" = Protection Word "2" = Control Word
the highest value byte is transferred first and the lowest value byte last.
5 bytes for IPC02 and IPC11
Word start address in the data carrier, range from "0000" to "FFFF", depending on data carrier type.
Number of words to be read or written, 01h (“0001”) is used as number of words. The following applies for IPC03: The number of words 00h is used with the word address 0000 to read the preset data range on the data carrier.
58
102696 2009-03
Page 59
IPT*-FP WITH U-P6-B5
Operation on the INTERBUS

7.9 Error/Status messages

Status Meaning
00h The command has been executed without error.
FFh The command is processing.
Error messages which triggered the identification system
Status Meaning
02h Switch-on message. Reset has been executed.
03h Reserved
04h Incorrect or incomplete command or parameter not in the valid
05h Read/write error. No data carrier in the detection range.
06h Hardware error,
07h Internal device error.
08h Reserved
09h Reserved
0Ah Reserved
0Bh Reserved
0Ch Reserved
0Dh Reserved
0Eh Reserved
0Fh Reserved
range.
e.g. error on self test or read head defect.
Error messages, which triggered the lower section U-P6-B5*
Status Meaning
10h Reserved
20h Reset has been executed.
40h Incorrect or incomplete command or parameter not in the valid
60h Hardware error,
70h Internal device error.
102696 2009-03
range.
e.g. no communication with the identification system.
59
Page 60
IPT*-FP WITH U-P6-B5
Technical specifications

8 Technical specifications

8.1 Read/write station IPT*-FP

IPT*-FP
General data
Operating frequency 125 kHz
Transfer rate 2 kBit/s
Operating distance max. 100 mm
Display/controls
LED green Power on
LED yellow IPC recognized
LED red Bus error (with the use of field bus
Electrical data
Rated operating voltage U
Power consumption P
Galvanic isolation
e
0
interfaces)
20 ... 30 V DC, ripple 10 %SS, PELV
max. 5 W, in connection with lower section
60
Operating voltage/Interface Functional isolation in accordance with DIN
Interface
Physical Interface type depends on the lower section
Ambient conditions
Ambient temperature -25 ... 70 °C (248 ... 343 K) Storage temperature -40 ... 85 °C (233 ... 358 K)
Mechanical data
Degree of protection IP67 in accordance with IN 60529, in
Housing material PBT (Polybutylene terephthalate)
EN 50178, rated isolation voltage 50 V
used
connection with lower section
eff
102696 2009-03
Page 61
IPT*-FP WITH U-P6-B5
20 29
80
65
80
65
Technical specifications
Dimensions of the read/write station

8.2 Read/write distances IPT*-FP

Distances Data carrier type in air
Read distance with IPC02-20W 0 mm...40 mm
Read distance with IPC02-30W 0 mm...50 mm
Read distance with IPC02-50W 0 mm...80 mm
Read distance with IPC02-C1 0 mm...80 mm
Read distance with IPC02-68-T5 0 mm...50 mm
Read distance with IPC03-20W 0 mm...30 mm
Write distance with IPC03-20W 0 mm...25 mm
Read distance with IPC03-30W 0 mm...40 mm
Write distance with IPC03-30W 0 mm...30 mm
Read distance with IPC03-50W 0 mm...60 mm
Write distance with IPC03-50W 0 mm...45 mm
Read distance with IPC03-C1 0 mm...60 mm
Write distance with IPC03-C1 0 mm...45 mm
Read distance with IPC10-20 0 mm...30 mm
Write distance with IPC10-20 0 mm...25 mm
102696 2009-03
61
Page 62
IPT*-FP WITH U-P6-B5
Technical specifications

8.3 U-P6B5 lower section

Electrical data
Rated operating voltage U
e
Current loading < 300 mA (Ue = 24 V) with read/write station
Power consumption P
Galvanic isolation
0
U-P6-B5
20 ... 30 V DC, ripple 10 %SS, PELV
max. 5 W with read/write station
Operating voltage/Interface
Functional isolation in accordance with DIN EN 50178, rated
isolation voltage 50 V
eff
Interface
BUS interface INTERBUS remote bus
BUS protocol INTERBUS remote bus
Interface RS 485
ID code 03
Transfer rate 500 kBit/s
Ring termination DIP switch
Ambient conditions
Ambient temperature -25 ... 70 °C (248 ... 343 K) Storage temperature -40 ... 85 °C (233 ... 358 K)
Mechanical data
Degree of protection IP67 according to EN 60529 with IPT*-FP
Connection BUS Screw terminals via 2 x PG9 EMC
PG9 cable glands that are not used must be sealed with the
The plugs are suitable for both the standard cable glands and for
Voltage supply Screw terminals via 2 x PG9
PE Crimp connector
provided plugs.
the EMC cable glands.
cable glands 3 x 2 x 0.22 mm
2 x 0.25 mm
twisted pairs, screened
Standard cable glands up to 3 x 1.5
mm
< 4mm
2
or 3 x
2
,
2
2
Housing material Aluminum, black anodized
62
102696 2009-03
Page 63
IPT*-FP WITH U-P6-B5
Technical specifications
U-P6B5 Lower section
+0,2
81
9
10˚
Ø9,5
43
±0,2
50
Pg9
Ø 15,5
52
22
12,5
M6
35
35
U-P6-B5 Electrical connection
Ø5,3
±0,3
32,5
65
±0,3
32,5
±0,3
32,5
±0,3
32,5
161
±0,2
121
±0,2
±0,2
80
102696 2009-03
63
Page 64
IPT*-FP WITH U-P6-B5
Technical specifications
64
102696 2009-03
Page 65
IPT*-FP WITH U-P6-B5
Technical specifications
102696 2009-03
65
Page 66
Subject to modifications Copyright PEPPERL+FUCHS • Printed in Germany
www.pepperl-fuchs.com
Worldwide Headquarters
Pepperl+Fuchs GmbH 68307 Mannheim · Germany Tel. +49 621 776-0 E-mail: info@de.pepperl-fuchs.com
USA Headquarters
Pepperl+Fuchs Inc. Twinsburg, Ohio 44087 · USA Tel. +1 330 4253555 E-mail: sales@us.pepperl-fuchs.com
Asia Pacific Headquarters
Pepperl+Fuchs Pte Ltd. Company Registration No. 199003130E Singapore 139942 Tel. +65 67799091 E-mail: sales@sg.pepperl-fuchs.com
FACTORY AUTOMATION – SENSING YOUR NEEDS
TDOCT-0109AENG 102696
03/2009
Loading...