Fieldbus module ICE1-16DIO-G60L-V1D
Dimensions
R
Model number
ICE1-16DIO-G60L-V1D
Ethernet IO module with 16 configurable
digital inputs/outputs
Features
• Multiprotocol-compatible
•M12 power connector
• Sturdy metallic housing
• Web-based configuration
• 16 digital inputs/outputs can be configured
Function
The ICE1-16DIO-G60L-V1D is a multiprotocol
fieldbus module with 16 digital in- or outputs.
The G60L design in fully cast metal housing is
resistant to mechanical damage and environmental influences.
The G60L has protection class IP65/IP67.
The fieldbus module serves as an interface
between the controller of a fieldbus system
and the field level. Thanks to its multiprotocol
capability, the fieldbus module supports the
Ethernet communication protocols PROFINET, EtherNet/IP, and EtherCAT.
An L-coded M12 connector plug used for
supplying power enables a current rating of
up to 2 x 16 A. The inputs are equipped with
A-coded M12 connector plugs. Connection to
the fieldbus is achieved using a D-coded M12
connector plug.
The communication protocols are configured
either manually via a rotary switch or automatically. The diagnostics display status information for each channel via LEDs. An
integrated web server enables access to the
fieldbus module. Information regarding the
status of the module is also displayed and
network parameters such as the IP address
and subnet mask can be configured.
214.5
27 27 27 M12 x1 (10x) 27 11.5
Electrical connection
190.3
191.8
200
In-/Outputs
1
4
3
Ethernet
1
4
3
Power supply
1
5
4
1
2
3
4
30.7
17.6
16.5
M4
20
30
59.6
2
1 = +24 V (US)
2 = In B/Out B
3 = GND (US)
5
4 = In A/Out A
5 = Functional earth
1 = TD+
2 = RD+
2
3 = TD4 = RD-
2
1 = +24 V (US)
2 = GND (UL)
3 = GND (US)
3
4 = +24 V (UL)
5 = Functional earth
1 = +24 V (US)
2 = GND (UL)
3 = GND (US)
5
4 = +24 V (UL)
5 = Functional earth
Release date: 2019-09-06 09:36 Date of issue: 2019-09-17 308626_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group
1

ICE1-16DIO-G60L-V1DFieldbus module
Indicating / Operating means
5X1X
A
DIA
B
MS
BF
RUN ERR C
0
x10
X6
A
DIA
B
7X3X
A
DIA
B
X8
A
DIA
B
NS
DIA
FM
U
SUL
0
x1
20X10X
X04
XE
X2
X4
E/IP:
Lnk/Act
P:
X01
EC:
X02
0
E/IP
P
EC
x100
X03
LED channel display
LED status display
Rotary switch
Technical data
General specifications
UL File Number E223772
Indicators/operating means
LED indication see manual
Rotary switch Setting the fieldbus protocol
Electrical specifications
Rated operating voltage Ue18 ... 30 V
Nominal voltage 24 V DC
Current consumption 120 mA
Current loading capacity Max. 2 x 16 A per module
Interface 1
Interface type Industrial Ethernet
Physical M12, D-coded
Protocol PROFINET IO with media redundancy protocol (MRP)
Transfer rate 10/100 Mbps
Inputs/Outputs
Number/Type 16 digital inputs/outputs, configurable
Sensor supply max. 500 mA Per port (X1 - X8) via US
Output rated operating current I
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011
Sta nd a rd c onfor m it y
Degree of protection EN 60529:2000
Emitted interference EN 61000-6-4:2007+A1:2011
Noise immunity EN 61000-6-2:2005
Shock resistance EN 61131-2:2004
Ambient conditions
Ambient temperature -20 ... 70 °C (-4 ... 158 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Cold start temperature -40 °C (-40 °F)
Relative humidity max. 95 %
Altitude 0 ... 2000 m
Shock and impact resistance 50 g, 11 ms, all axes
Vibration resistance 15 g at 5 - 500 Hz
Pollution degree 3
Mechanical specifications
Contact elements PA
Degree of protection IP65/IP67/IP69K
Connection Power Supply M12, L-coded
Material
Contacts CuSn, gold-plated
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Pepperl+Fuchs Group
(Loop-through current via L-coded power supply)
Total current: max. 9 A per module
EtherNet/IP with Device Level Ring (DLR)
EtherCAT
Inputs: 2-, 3-, 4-wire PNP, DC, supply from U
Outputs: 2-wire PNP, DC, supply from U
No galvanic isolation between US and U
short-circuit protected
max. 2 A per channel (X1 - X8) / 4 A Per port via UL
e
Fieldbus M12, D-coded
Inputs M12, A-coded
CuNi, gold-plated
S
L
L
Accessories
V15L-G-5M-PUR-U
Single-ended female cordset, M12, L-coded, 5-pin, PUR cable
V15L-G-0,6M-PUR-U-V15L-G
Cordset, M12 to M12, L-coded, 5-pin,
PUR cable
V15L-G-1M-PUR-U-V15L-G
Cordset, M12 to M12, L-coded, 5-pin,
PUR cable
V15L-G-2M-PUR-U-V15L-G
Cordset, M12 to M12, L-coded, 5-pin,
PUR cable
V1SD-G-2M-PUR-ABG-V45-G
Connection cable, M12 to RJ-45, PUR
cable 4-pin, CAT5e
V1SD-G-2M-PUR-ABG-V1SD-G
Ethernet bus cable, M12 to M12, PUR cable 4-pin, CAT5e
V1SD-G-ABG-PG9
Cable connector, M12, 4-pin, D-coded,
shielded, non pre-wired
V1-G-BK1M-PUR-A-T-V1-G
Y connecting cable, M12 to 2xM12, 4-pin,
PUR cable
V1S-T-V1
Y-splitter, M12 connector on M12 socket/socket
VAZ-V1-B3
Blind plug for M12 sockets
V15L-G-BK
Single-ended female cordset, M12, L-coded, field attachable
MH V1-SCREWDRIVER
torque screwdriver (0.6 Nm)
MH V1-BIT M12
plug-in cap M12
Release date: 2019-09-06 09:36 Date of issue: 2019-09-17 308626_eng.xml