I/O hub ICA-16DI-G60A-IO
Dimensions
Model number
ICA-16DI-G60A-IO
I/O hub with IO-Link interface for 16 digital inputs
Features
• Sturdy metallic housing
• IO-link interface for service and process data
• 16 digital inputs
• Logic level can be configured per port
• Filter time can be configured per port
• Pulse extension can be configured
per port
Accessories
MH V1-SCREWDRIVER
torque screwdriver (0.6 Nm)
MH V1-BIT M12
plug-in cap M12
214.5
Electrical connection
27 27 27M12 x1 (9x)
149.3
150.8
158.8
In-/Outputs
1
4
3
IO-Link
1
2
3
5
1 = +24 V (L+)
2 = In B
2
3 = GND (L-)
4 = In A
5 = Protection
earth
1 = +24 V (L+)
5
2 = n.c.
4
3 = GND (L-)
4 = C/Q (IO-Link)
5 = n.c.
1
4
2
3
5
40 11.5
L+
C/Q
n.c.
L-
n.c.
16.5
17.6
M4
20
30.7
30
59.6
Release date: 2019-03-25 10:07 Date of issue: 2019-03-25 313335_eng.xml
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group
1

Indicating / Operating means
5X1X
A
B
X2
X4
X6
A
DIA
B
7X3X
A
DIA
B
X8
A
DIA
B
IO-Link
X01
AuxUS
U
XE
LED channel display
LED status display
Technical data
General specifications
UL File Number E223772
Functional safety related parameters
MTTFd 2111 a
Indicators/operating means
LED IO-Link Green: module is switched on, no communication
LED A Orange: status indicator channel A
LED B White: status indicator channel B
LED U
Green: system/sensor supply voltage OK
S
Electrical specifications
Rated operating voltage Ue18 ... 30 V
Nominal voltage 24 V DC
Nominal current 4 A
Current consumption typ. 80 mA
Interface
Interface type IO-Link
Device profile Identification and Diagnosis
Tran s f e r r a t e COM 3 (230.4 kBaud)
IO-Link Revision 1.1
Min. cycle time 2 ms
Process data witdh Input 4 Byte
SIO mode support no
Device ID 0x0F0201 (983553)
Compatible master port type A
Input
Number/Type 16 digital inputs 5-wire PNP, DC, supply from US Ty p e 1 a c co r-
Sensor supply Depending on the IO-Link master, max. 500 mA per module
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011
Sta nd a rd c onfor m it y
Degree of protection EN 60529:2000
Fieldbus standard Type 1 according to IEC 61131-2
Emitted interference EN 61000-6-2:2005
Noise immunity EN 61000-6-4:2007+A1:2011
Ambient conditions
Ambient temperature -20 ... 70 °C (-4 ... 158 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Cold start temperature
Relative humidity max. 95 %
Altitude 0 ... 2000 m
Shock and impact resistance 50 g, 11 ms, all axes
Vibration resistance 15 g / 5 ... 500 Hz
Pollution degree 3
Mechanical specifications
Degree of protection IP65/IP67/IP69K
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
2
Pepperl+Fuchs Group
Flashing green: communication OK
Red: signal line overload
Red: peripheral error
Red: peripheral error
Red: system/sensor supply voltage < 18 V
Flashing red: sensor supply voltage overload
Output 4 Byte
ding to IEC 61131-2
ICA-16DI-G60A-IOI/O hub
Release date: 2019-03-25 10:07 Date of issue: 2019-03-25 313335_eng.xml