This manual describes the installation, initial operation and handling of the device. It renders
information on the safe operation of the device, fault elimination, maintenance and disposal.
The corresponding data sheets, declarations of conformity and/or EC-Type Examination Certificates
are part of this instruction manual. The instruction manual shall be valid only if all applicable documents
are taken into consideration. These documents can be downloaded at www.pepperl-fuchs.com. For
additional information, please refer to the contact addresses on the last page of this instruction manual.
This instruction manual requires technical know-how and experience with plant installations and
explosion protection.
The devices are intended only for correct and intended use (see section 2). In case of any violation, all
guarantee and manufacturer's liability shall become void. Please observe the applicable laws and
guidelines for the use and intended purpose.
The device has been developed and manufactured under observation of all applicable European
standards and directives.
193263 09/2014
EN - 5
Temperature Converter HiC2081, HiD2081, HiD2082
Introduction
1. 2 Symbols used in this document
In order to highlight safety-related and informative notes, we have defined the following categories.
Every note is marked by a symbol.
Danger!
This symbol indicates a warning about a possible danger.
In the event the warning is ignored, the consequences may range from personal injury to
death.
Warning!
This symbol indicates a warning about a possible fault or danger.
In case of non-observation injuries or severe material damage may result.
Caution!
This symbol warns of a possible fault.
In the event the warning is ignored, the consequences may course personal injury or
heaviest property damage.
This symbol brings important information to your attention.
This symbol marks an acting paragraph.
193263 09/2014
6 - EN
2Intended use
mV
Ω
mV
Ω
The outputs can be selected as a current source, current sink, or voltage source via DIP switches.
The devices can also be configured as a signal splitter (only HiD2082).
Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. The fault
conditions are monitored via a Fault Indication Board.
The devices are easily configured by the use of the PACTwareTM configuration software.
This devices mount on HiC or HiD Termination Boards.
For more information (on certificates, data sheets and the instruction manual), please refer to our
website at www.pepperl-fuchs.com (entry in product search: HiC2081, HiD2081 or HiD2082).
193263 09/2014
Temperature Converter HiC2081, HiD2081, HiD2082
Intended use
The temperature converters HiC2081,
HiD2081 and HiD2082 are used for intrinsic
safety applications. The devices HiC2081
and HiD2081 are 1-channel devices; the
device HiD2082 is a 2-channel device.
The devices accept thermocouples (TC),
millivolts, potentiometers, or resistance
temperature detectors (RTD) from a
hazardous area and convert them to an
isolated, linearized analog output in the safe
area.
EN - 7
Temperature Converter HiC2081, HiD2081, HiD2082
Safety
3Safety
3. 1 General safety instructions
The device may be mounted, connected and operated only outside of the hazardous area. Have the
work carried out only by a trained expert in electric engineering.
Use the device for its intended use only (see section 2). Please observe the information rendered in the
instruction manual on installation, initial operation and handling of the device.
If faults can not be remedied, shut down the device. Secure the device against accidental operation.
Return the device to Pepperl+Fuchs for repair. Own interventions and modifications are potentially
hazardous, and any guarantee and manufacturer's liability shall become void.
Responsibility for adhering to local safety regulations and directives is held by the operator
3.2 Explosion Protection
PROCESSAUTOMATION
MANUAL
EXPLOSION PROTECTION
Intrinsic Safety
Explosion Protection
For matters concerning primary explosion protection, i.e. measures to
prevent or restrict formation of a potentially explosive atmosphere, please
refer to Directive 94/9/EG (ATEX) and the corresponding national
regulations.
For matters concerning secondary explosion protection, i.e. measures to
prevent ignition by electrical apparatus of a potentially explosive
atmosphere, Pepperl+Fuchs are happy to provide their "Explosion
protection manual" for a nominal fee.
In particular, please observe EN 60079-0, EN 60079-11, EN 60079-26,
EN 61241-11 as well as the corresponding national regulations.
Pepperl+Fuchs also offer a seminar on the subject of explosion
protection.
193263 09/2014
8 - EN
Temperature Converter HiC2081, HiD2081, HiD2082
Delivery, transport and storage
4Delivery, transport and storage
4. 1 Scope of delivery
The scope of delivery comprises:
•The device
• The instruction manual (this document)
4. 2 Acceptance
Please check the packaging and contents for any damage. Please check the delivery in order to ensure
that all parts are available and the delivery conforms to your order. Compare the data on the nameplate
with the ordering data.
Data on the nameplate:
• Order designation and part number
• Supply voltage
• Input and/or output data
• Data on explosion protection and intrinsic safety (if applicable)
4. 3 Transport
Pack the device for transport to protect it against damage. The original packaging offers perfect
protection for the device.
4. 4 Storage
Pack the device for storage to protect it against impact and soiling. The original packaging offers perfect
protection for the device. Store the device in a dry environment protecting it against humidity and
aggressive media. The permissible storage temperature rang es from -40 °C to 90 °C (-40 °F to 194 °F).
193263 09/2014
EN - 9
Temperature Converter HiC2081, HiD2081, HiD2082
Installation and mounting
5Installation and mounting
5.1 Mounting
Warning!
Fault or damage of the device caused by wrong mounting location.
In case of non-obser vation, the safety and function of the d evice as well as other devices or
plants are not ensured.
• Select the mounting location according to the type of protection of the device (IP30).
• Protect the device against foreign bodies of 2.5 mm or larger and against spraying
water.
• Please observe the notes on the types of housing protection (IEC 60529).
This devices mount on HiC or HiD Termination Boards. All devices can be connected to every mounting
station and can be mixed on the termination board.
For additional information on the termination boards, please refer to system description on
our website at www.pepperl-fuchs.com (entry in product search: HiC2081, HiD2081 or
HiD2082).
If you want to use a customized Termination Board, please contact your Pepperl+Fuchs
assistant.
193263 09/2014
10 - EN
12,5 mm
(0.5")
106 mm (4.17")
128 mm (5.04")
18 mm
(0.71")
106 mm (4.17")
128 mm (5.04")
193263 09/2014
Temperature Converter HiC2081, HiD2081, HiD2082
Installation and mounting
Dimensions HiC device
Dimesnions HiD device
EN - 11
Temperature Converter HiC2081, HiD2081, HiD2082
1
2
3
Installation and mounting
Mounting the device on the Termination Board:
• Push the Quick Lok bar (1) into the upper position.
• Center the pins (2) above the contact elements of the Termination Board. Note the
connection direction of the device.
• Center the locking pins (3) above the locking elements of the Termination Board.
• Carefully push the device into the contacts and locking elements.
• Push the red Quick Lok bar (1) down on either side of the device.
The device is mounted now.
(1) Quick Lok Bar
(2)Pins
(3)Locking pins
5. 2 Connecting the device
The device is connected by means of the terminals of the Termination Board, which permits a fast and
faultfree exchange in case of failure.
The terminals are self-opening and have a spacious connecting area for a core cross-section of up to
2.5 mm².
12 - EN
193263 09/2014
Temperature Converter HiC2081, HiD2081, HiD2082
Installation and mounting
Intrinsically safe field circuits are connected to the blue Termnation Board terminals 1, 2, 5, 4
(channel I) and 7, 3, 6, 8 (channel II only HiD2082), which in keeping with DIN EN 60079-14 by means
of connecting cables can be passed into the potentially explosive area. The following sensors can be
connected (see figure):
• Potentiometer (800 ... 20 k) in 3-wire technology
•RTD (Resistance Temperature Detector) in 2-wire, 3-wire or 4-wire technology
Pt10, Pt50, Pt100, Pt500, Pt1000 according to EN 60751: 1995 or GOST6651-94
Ni 100 according to DIN 43760
Cu10, Cu50, Cu100 according to GOSTP50353-92
• Internal cold junction compensation
HiC2081: resistance thermometer for cold junction compensation H-CJC-Pt100
HiD2081, HiD2082: esistance thermometer for cold junction compensation H-CJC-SC-8,
H-CJC-SP-8
• Thermocouples
Type B, E, J, K, N, R, S, T according to IEC584-1: 1995
Type L according to DIN 43710
Type TXA, TXK, TXKH according to GOSTP8.585-2001
• Sources for voltage signals between -100 mV and +100 mV
193263 09/2014
I
II
Zone 0, 1, 2
Div. 1, 2
CJC
+-+
T
+
-
SL2
5a
1
+
1a
2
V
5
-
-
41b5b
737a
+
3a
+
V
6
-
-
83b7b
Termination Board
1a, 1b
2a, 2b
SL1
11
8a
14+-
7a
12
10a
15+-
9a
+
6b
24 V DC
FAULT
I
V
II
V
EN - 13
Temperature Converter HiC2081, HiD2081, HiD2082
Termination Board
Zone 0, 1, 2Div. 1, 2
I
+-+
-
V
T
V
11
14+-
+
1
2
SL2
5a
1a
-
5
41b5b
SL1
8a
7a
II
+
-
+
-
V
V
12
15+-
+
737a
3a
-
6
83b7b
10a
9a
CJC
+
-
24 V DC
FAULT
1a, 1b
2a, 2b
6b
Installation and mounting
Non-intrinsically safe current circuit can be connected to the black Termination Board terminals, which
have the following function:
• Terminals 11, 14 (channel I) and 12, 15 (channel II only HiD2082): as current source, current sink or
voltage source
•Fault bus
•Power supply
• Programming socket (RS 232) for parameterisation and diagnosis using PACTware
TM
14 - EN
193263 09/2014
0
200
400
600
800
1000
1200
16202530
U [V]
Resistor range
Temperature Converter HiC2081, HiD2081, HiD2082
Installation and mounting
If a current output is operated as a sink, the voltage of the terminals has to be between 5 V and 30 V.
An additional resistance is required only, if the voltage is over 16.5 V. The resistance has to be
between (U - 16.5 V)/0.0215 A and (U - 5 V) / 0.0215 A (see diagram).
Example: U = 24 V
(24 V - 16.5 V) / 0.0215 A = 350
(24V - 5V) / 0.0215A = 880
If a current output operated as asource, the load resistance has to be between 0 and 550 .
For more information on connections (on terminal assignment and current supply, for example), please
refer to our website at www.pepperl-fuchs.com (entry in product search: HiC2081, HiD2081 or
HiD2082).
193263 09/2014
EN - 15
Temperature Converter HiC2081, HiD2081, HiD2082
PWR
CH 1CH 2
FAULTFAULT
HiD
2082
2 ch
Temperature
Converter
Serial
Config.
Installation and mounting
5.3 Operating and display elements
The following operating and display elements are located on the front
side of the device:
• Red LED CH1 FAULT (channel I) to display
a lead fault on input 1
(terminals 1, 2, 4, 5, flashing red)
of the simulation mode (flashing red)
a device failure (continuously red)
• Red LED CH2 FAULT (channel II only HiD2082) to display
a lead fault on input 2
(terminals 3, 6, 7, 8, flashing red)
of the simulation mode (flashing red)
a device failure (continuously red)
• green LED PWR ON, to indicate the presence of the supply voltage
• serial RS 232 interface for connection to a PC for programming and
diagnosis of the device using PACTware
TM
193263 09/2014
16 - EN