FACTORY AUTOMATION
Operating instructions
DA6-IU-2K-V
DA6-IU-2K-C
Process Controllers
for analogue input signals with Totaliser function
for analogue input signals 0…10 V
2…10 V
-10…+10 V 0…20 mA 4…20 mA
SENSING YOUR NEEDS
DA6-IU-2K-V
DA6-IU-2K-C
Table of Contents (German is the original version.) |
|
|||
1 |
Preface |
|
3 |
|
2 |
Safety instructions and Warnings |
3 |
||
|
2.1 |
Use according to the intended purpose |
3 |
|
|
2.2 |
Mounting in a control panel |
3 |
|
|
2.3 |
Electrical Installation |
4 |
|
3 |
2.4 |
Cleaning and maintenance |
4 |
|
Description |
|
5 |
||
4 |
Display/Operating elements |
5 |
||
5 |
Block diagram |
6 |
||
6 |
Connections |
6 |
||
7 |
Operating concept (Operating mode) |
7 |
||
8 |
Programming |
8 |
||
9 |
Function Groups |
10 |
||
|
9.1 |
Help Texts (running text) |
10 |
|
|
9.2 |
Signal inputs |
10 |
|
|
9.3 |
User Linearisation |
11 |
|
|
9.4 |
Function Multifunction Key (MP-Key) and Multifunction inputs (MP-INP) |
13 |
|
|
|
9.4.1 |
Multifunction Key |
14 |
|
|
9.4.2 |
Multifunction Inputs |
14 |
|
9.5 |
Totaliser function |
15 |
|
10 |
9.6 |
Limit Value (Alarm) Monitoring |
16 |
|
Monitoring of Measuring Circuit |
18 |
|||
11 |
Technical Data |
19 |
||
|
11.1 |
General Data |
19 |
|
|
11.2 |
Measuring signal inputs |
19 |
|
|
11.3 |
Control Inputs MPI 1 / MPI 2 |
19 |
|
|
11.4 |
Alarm outputs |
19 |
|
|
11.5 |
Supply voltage |
19 |
|
|
11.6 |
Sensor Supply voltage |
19 |
|
|
11.7 |
Climatic Conditions |
19 |
|
|
11.8 |
EMC |
|
19 |
|
11.9 |
Device Safety |
19 |
|
|
11.10Mechanical Data |
19 |
||
|
11.11Connections |
20 |
||
12 |
Dimensional Drawings |
20 |
||
13 |
Help Texts |
|
21 |
Page 2
DA6-IU-2K-V
DA6-IU-2K-C
1 |
Preface |
|
voltages at the terminals of the device must be kept |
||
|
within the limits of Over-voltage Category II. |
||||
|
|
Please read this instruction manual |
|
The device must only be operated when mounted |
|
|
|
entirely and carefully before installation |
|
in a panel in the correct way and in accordance |
|
|
|
and start-up. Please observe all |
|
with the section “Technical Data”. |
|
|
|
warnings and advice, both for your own |
|
The device is not suitable for use in hazardous |
|
|
|
safety and for general plant safety. If |
|
||
|
|
the device is not used in accordance |
|
areas and for areas excluded in EN 61010 Part 1. If |
|
|
|
with this instruction manual, then the |
|
the device is used to monitor machines or |
|
|
|
intended protection can be impaired. |
|
processes in which, in the event of a failure of the |
|
2 |
Safety instructions and |
|
device or an error made by the operator, there |
||
|
might be the risk of damaging the machine or |
||||
|
Warnings |
|
causing an accident to the operators, it is your |
||
|
|
responsibility to take the appropriate safety |
|||
|
|
Please use the device only if its |
|
measures. |
|
|
|
technical condition is perfect. It should |
|
|
|
|
|
be used only for its intended purpose. |
|
The device has been designed for indoor operation. |
|
|
|
Please bear in mind safety aspects and |
|
||
|
|
|
It may nevertheless be used outdoors, provided the |
||
|
|
potential dangers and adhere to the |
|
||
|
|
|
technical data is adhered to. In this case, take care |
||
|
|
operating instructions at all times. |
|
||
|
|
|
to provide suitable UV protection. |
||
|
|
Defective or damaged devices should |
|
||
|
|
|
|
|
|
|
|
be disconnected from the mains |
|
|
|
|
|
immediately and taken out of operation. |
2.2 |
Mounting in a control panel |
|
|
|
The device shall not be opened. Use |
|
|
|
|
|
the repair service of the manufacturer. |
|
|
Mount the device away from heat |
|
|
Only connect the device to the |
|
|
sources and avoid direct contact with |
|
|
electricity networks provided to that |
|
|
corrosive liquids, hot steam or similar. |
|
|
purpose. |
|
CAUTION Provide a free space of 10mm all |
|
|
|
The safety of the system in which the |
|
|
around the device for its ventilation. |
|
|
device is integrated is the responsibility |
|
|
|
|
|
of the installer. |
|
|
The device should be mounted so |
|
|
Disconnect all electricity networks prior |
|
|
|
|
|
|
|
that the terminals are out of the reach |
|
|
|
to any installation or maintenance |
|
|
|
|
|
|
|
of the operator and cannot be |
|
|
|
work. |
|
|
|
|
|
|
|
touched by him. When mounting the |
|
|
|
Use exclusively cables approved in |
|
|
|
|
|
|
|
device, consider the fact that only the |
|
|
|
your country and designed for your |
|
|
|
|
|
|
|
front side is classified as accessible |
|
|
|
temperature and power ranges. |
|
|
|
|
|
|
|
for the operator. |
|
|
|
Installation and service work shall be |
|
|
|
|
|
|
|
|
|
|
|
carried out exclusively by qualified |
|
Mounting instructions |
|
|
|
personnel. |
|
||
|
|
The device must compulsorily be |
|
1. Remove the mounting clip from the device. |
|
|
|
protected with approved external fuses. |
|
2. Insert the device from the front into the panel |
|
|
|
The value of these fuses can be found |
|
|
cut-out, ensuring the front-panel gasket is |
|
|
in the technical information. |
|
|
correctly seated. |
|
|
|
|
3. Slide the fixing clip from the rear onto the |
|
|
|
This symbol is used on the device to |
|
|
housing, until the spring clamps are under |
|
|
remind of the existence of dangers, |
|
|
tension and the upper and lower latching lugs |
|
|
which are referred to in this manual. |
|
|
have snapped into place. |
2.1 |
Use according to the intended |
|
Note: In case of proper installation, IP65 can be |
||
|
reached on the front side. |
purpose
The purpose of the Process Control devices is to display measured values, as well as to monitor limit values (alarms). The application areas for this device lie in industrial processes and controls.
The application area for this device lies in industrial processes and controls, in the fields of manufacturing lines for the metal, wood, plastics, paper, glass, textile and other like industries. Over-
<![endif]>english
Page 3
DA6-IU-2K-V DA6-IU-2K-C
2.3Electrical Installation
|
The device must be disconnected |
|
from any power supply prior to any |
|
installation or maintenance work. |
DANGER |
Make sure that no more voltages |
|
LIABLE TO CAUSE AN ELECTROCUTION |
|
are present. |
|
AC-powered devices must only be |
|
connected to the low-voltage network |
|
via a switch or circuit breaker installed |
|
close to the device and marked as |
|
their disconnecting device. |
|
Installation or maintenance work must |
|
only be carried out by qualified |
|
personnel and in compliance with the |
|
applicable national and international |
|
standards. |
|
Take care to separate all extra-low |
|
voltages entering or exiting the device |
|
from hazardous electrical conductors |
|
by means of a double or reinforced |
|
insulation (SELV circuits). |
|
|
|
The device must be protected |
|
externally for its proper operation. |
|
Information about the prescribed |
DANGER |
fuses can be found in the technical |
|
information. |
|
The relay outputs are not protected |
|
internally in the device. Without |
|
suitable protection of the relay |
|
outputs, undesired heat development |
|
or even fire may occur. The relay |
|
outputs must be protected externally |
|
by the manufacturer of the plant. It |
|
must also be made sure that, even in |
|
case of a malfunction, the values |
|
stated in the technical data are under |
|
no circumstances exceeded. |
•During installation, make sure that the supply voltage and the wiring of the output contacts are both fed from the same mains phase, in order not to exceed the maximum permitted voltage of 250V.
•The cables and their insulation must be designed for the planned temperature and voltage ranges. Regarding the type of the cables, adhere to the applicable standards of the country and of the plant. The cross sections allowed for the screw terminals can be found in the technical data.
•Before starting the device, check the cables for proper wiring and tightening. The screws of unused screw terminals must be screwed to the stop, so that they cannot loosen and get lost.
•The device has been designed for overvoltage category II. If higher transient voltages cannot be excluded, additional protection measures must be taken in order to limit the overvoltage to the values of CAT II.
Advice on noise immunity
All connections are protected against external sources of interference. The installation location should be chosen so that inductive or capacitive interference does not affect the device or its connecting lines! Interference (e.g. from switchmode power supplies, motors, clocked controllers or contactors) can be reduced by means of appropriate cable routing and wiring.
Measures to be taken:
•Use only shielded cable and control lines. Connect shield at both ends. The conductor cross-section of the cables should be a minimum of 0.14 mm².
•The shield connection to the equipotential bonding should be as short as possible and with a contact area as large as possible (lowimpedance).
•Only connect the shields to the control panel, if the latter is also earthed.
•Install the device as far away as possible from noise-containing cables.
•Avoid routing signal or control cables parallel to power lines.
2.4Cleaning and maintenance
The front side of the unit should only be cleaned using a soft damp (water!) cloth. Cleaning of the embedded rear side is not planned and is the responsibility of the service personnel or of the installer.
In normal operation, this device is maintenancefree. Should the device nevertheless not operate properly, it must be sent back to the manufacturer or to the supplier. Opening and repairing the device by the user is not allowed and can adversely affect the original protection level.
Page 4
DA6-IU-2K-V
DA6-IU-2K-C
3Description
Digital panel meter for displaying measured values, as well as monitoring limit values in industrial applications.
•6-digit 14-segment LED display, 14 mm, for displaying measured values and dialogs
•Running text can be switched on as Help Text
•Language for the Help Text selectable as English or German
•Signal input for 0 – 10 V, 2 – 10 V, ±10 V, 0 – 20 mA and 4 – 20 mA
•Sampling rate 10 readings per second
•Digital filter (1st order) for smoothing display fluctuations with unstable input signals
•Customised linearisation
•MIN/MAX memory function
•Totaliser function
•2 Relay outputs (changeover contacts) for limit monitoring
•Start delay for relay outputs after Power ON
•Versions for supply voltage 10 ... 30 V DC and 100 … 240 V AC ± 10%
•Auxiliary power supply 15 V DC / 25 mA
•Additional aux. power output 24 V / 30 mA with AC supply
•Programmable via the front keys
•Multifunction key and two multifunction inputs, function programmable
4Display/Operating elements
(1)Display
-14 segment display, 6-digit, red
-Height of figures 14 mm
(2)Status display, 2 LED annunciators, red
- Switching status of Alarm 1 and Alarm 2 - Indication Function Group or Function
(3)MP-Key and Programming Keys
- Multifunction key (MP-Key)
- Return from Function Group
- Return from Function
-Select previous Function Group
-Select previous Function
-Decrement parameter value
-Select next Function Group
-Select next Function
-Increment parameter value
-Enter a Function Group
-Enter a Function
-Accept the new setting
(4)Space for unit overlay
To enter the Programming Menu |
+ |
> 3 sec |
|
|
|
||
To display Device Type and Software Version |
+ |
+ |
> 5 sec |
To restore factory default settings |
+ |
> 3 sec |
|
<![endif]>english
Page 5
DA6-IU-2K-V
DA6-IU-2K-C
5Block diagram
6Connections
Page 6
DA6-IU-2K-V
DA6-IU-2K-C
7Operating concept (Operating mode)
<![if ! IE]><![endif]>english
Page 7
DA6-IU-2K-V
DA6-IU-2K-C
8Programming
To enter the Programming menu |
+ |
> 3 sec |
|
•During programming the relays are inactive (not energised).
•When quitting the programming menu via SAVE, the minimum and maximum values and the totaliser value are all cleared.
Entering the Programming Menu / Selecting Function Group / Quitting the Programming menu
Page 8