Inductive proximity switch
3RG4050-0GB05-PF |
NO |
|
|
|
Cable |
|
|
|
|
Schließer |
|
|
|
Kabel (eingegossen) |
|
||
3RG4050-7GB05-PF |
NO |
|
|
|
Connector M8 |
|
||
|
Schließer |
|
|
|
Stecker M8 |
|
|
|
3RG4050-0GA05-PF |
NC |
|
|
|
Cable |
|
|
|
|
Öffner |
|
|
|
Kabel (eingegossen) |
|
||
3RG4050-7GA05-PF |
NC |
|
|
|
Connector M8 |
|
||
|
Öffner |
|
|
|
Stecker M8 |
|
|
|
|
|
|
|
|
|
|
||
Size / Bauform |
|
|
cylindrical smooth 6,5 mm / |
|
||||
|
|
|
zylindrisch glatt 6,5 mm |
|
||||
|
|
|
|
|
|
|
||
Mounting / Einbau |
|
|
embeddable / bündig |
|
||||
|
|
|
|
|
|
|
|
|
Operating distance / Schaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Rated operating distance / |
|
sn |
1,5 mm |
|
|
|||
Bemessungsschaltabstand |
|
|
|
|
|
|
|
|
Effective operating distance / |
|
sr |
1,35 ... 1,65 mm |
|
|
|||
Realschaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Assured operating distance / |
|
sa |
1,21 mm |
|
|
|||
Gesicherter Schaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Standard target mild steel / |
|
|
8 x 8 x 1 mm |
|
|
|||
Meßplatte Stahlfahne St 37 |
|
|
|
|
|
|
|
|
Repeat accuracy / Wiederholgenauigkeit |
R |
0,10 mm |
|
|
||||
|
|
|
|
|
|
|
||
Hysteresis / Hysterese |
|
H |
0,01 ... 0,33 mm |
|
|
|||
|
|
|
|
|
|
|
||
Reduction factors / Reduktionsfaktoren |
|
Al: |
|
0,4 |
Cu: |
0,20 |
||
|
|
|
|
|
|
|
|
|
|
|
|
Ms: |
|
0,4 |
Stainl. steel / Edelst.: |
0,80 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply voltage / |
|
|
|
|
|
|
|
|
Versorgungsspannung |
|
|
|
|
|
|
|
|
Rated operational voltage / |
|
Ue |
24 V DC |
|
|
|||
Bemessungsbetriebsspannung |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Operating voltage range / |
|
UB |
15 ... 34 V DC |
|
|
|||
Betriebsspannungsbereich |
|
|
|
|
|
|
|
|
|
|
|
|
|||||
No-load supply current / Leerlaufstrom |
lo |
17mA (24 V DC); 30mA (34 V DC) |
|
|||||
max. ripple content / zul. Restwelligkeit |
|
10% |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Output / Ausgang |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
Output / Ausgangsart |
|
|
3 wire DC npn / 3 Leiter DC npn |
|
||||
|
|
|
|
|||||
Rated operational current / |
|
le |
200 mA (to / bis 50 Cel); 150 mA (to / bis 85 Cel) |
|||||
Bemessungbetriebsstrom |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Output voltage drop / Spannungsfall max. |
Ud |
2,5 V |
|
|
|
|
||
|
|
|
|
|
|
|||
Off-state current / Reststrom |
|
|
0,01 mA |
|
|
|||
|
|
|
|
|
||||
Short-circuit strength / Kurzschlußfestigkeit |
|
built-in / eingebaut |
|
|
||||
|
|
|
|
|
||||
Overload withstand capability / |
|
built-in / eingebaut |
|
|
||||
Überlastfestigkeit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Times / Zeiten |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
Frequency of operating cycles / |
f |
1500 Hz |
|
|
||||
Schaltfrequenz |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
Time delay before availability / |
tv |
40 ms |
|
|
||||
Bereitschaftsverzug |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Subject to modifications without notice |
Release: 09.09.2010 |
Copyright Pepperl+Fuchs |
1
Inductive proximity switch
Temperatures / Temperaturen |
|
|
|
Rated temperature / |
Tu |
25 Cel |
|
Bemessungstemperatur |
|
|
|
Ambient temperature range / |
Ta |
-25...+85 Cel |
|
zul. Umgebungstemperatur |
|
|
|
Storage temperature range / |
Ts |
-40...+85 Cel |
|
zul. Lagertemperatur |
|
|
|
Electrical protections / |
|
|
|
Elektrische Schutzmaßnahmen, EMV |
|
|
|
Reverse voltage protection / |
|
built-in / eingebaut |
|
Verpolungsschutz |
|
|
|
Wire breakage protection / |
|
built-in / eingebaut |
|
Drahtbruchsicherheit |
|
|
|
Inductive overvoltage / Induktionsschutz |
|
built-in / eingebaut |
|
Spurious switch-on pulse / |
|
suppressed / unterdrückt |
|
Einschaltfehlimpuls |
|
|
|
Mechanical protections / |
|
|
|
Mechanische Schutzmaßnahmen |
|
|
|
Degree of protection / Schutzart |
|
IP 67 |
|
Shock / Schockbeanspruchung |
|
30 x g; 11 ms duration / Einwirkdauer |
|
Vibration / Schwingbeanspruchung |
|
10 bis 55 Hz, 1 mm amplitude / Amplitude |
|
Indicators / Anzeigen |
|
LED (switching status / Schaltzustand) |
|
Mounting conditions / |
|
|
|
Einbaubedingungen |
|
|
|
Side-by-side mounting possibility / |
e> |
12 mm |
|
Aneinanderreihbarkeit |
r> |
4 mm |
|
Influence metallic surroundings / |
g> |
-- |
|
w> |
-- |
||
Einfluß metallischer Umgebung |
|||
c> |
3 mm |
||
|
|
|
Remarks/Bemerkungen: |
|
|
|
1) |
free space/Freiraum |
|
|
2) |
sensing face/aktive Fläche |
|
|
|
|
Max. Cable length / |
300 m |
|
|
max. zulässige Leitungslänge |
|
|
|
|
|
|
|
|
|
|
|
Design characteristics / |
|
|
|
Konstruktive Merkmale |
|
|
|
Housing material / Gehäuse |
|
stainless steel / Edelstahl 1.4305 |
|
|
|
|
|
Cable type / Leitungstyp |
|
3 x 0,25 qmm, PUR LiYY11Y |
|
|
|
|
|
Cable length / Leitungslänge, eingegossen |
|
2 m |
|
|
|
|
|
Sensing face / Ansprechfläche |
|
front side / stirnseitig |
|
|
|
|
|
Weight / Gewicht |
|
Cable / Kabel: 0,07 kg, |
|
|
|
Connector / Stecker: 0,02 kg |
|
|
|
|
|
Subject to modifications without notice |
Release: 09.09.2010 |
Copyright Pepperl+Fuchs |
2