Pepperl+Fuchs 1001B Series, 1001B-LPS-CII Y, 1001B-LPS-CII Z Installation & Operation Manual

CLASS II APPLICATIONS
ISC * 877-602-0010 * www.iscenclosurecooling.com
50 Cubic Feet Maximum
MODEL 1001B
TYPE Y OR Z
PRESSURIZATION SYSTEM
INSTALLATION & OPERATION MANUAL
(Less Pressure Switch)
WPS Style
(With Pressure Switch)
Table of Contents
ISC * 877-602-0010 * www.iscenclosurecooling.com
Page 2 System Purpose and Description
Purpose, System Description, Important Notes
Page 3 Identifying Your System
Defines specific features of the system
Page 4 General Information
System & Material Specifications, System Accessories, Spare Parts, Tools & Test Equipment, Maintenance Procedures
Page 5 Enclosure and Device Design
Design Requirements, Adjacent Enclosures, Device Ventilation, Temperature Limitations
Page 6 Installation Overview
Installation Diagram
Page 7 Getting Started
Establishing Connection Sizes, Determining Enclosure Inlet & Outlet Connection Locations
Page 8 System Mounting
LH, RH, TM, BM & WM Configurations, FM & PM Configurations
Page 9 Hardware Mounting
Optional Enclosure Protection Vent, Warning Nameplates
Page 10 Mounting Plate Dimensions
Mounting Plate Dimension Diagrams
Page 11 Mounting Plate Dimensions (cont.)
Mounting Plate Dimension Diagrams
Page 12 Pneumatic Tubing Requirements
Protective Gas Supply Requirements, Pneumatic Connection Requirements
Page 13 Tubing Installation
LH, RH, TM, BM, WM, FM & PM Tubing Configurations
Page 14 Tubing Connection Diagrams
LH, RH, TM, BM, WM, FM, & PM Configuration Connection Points, Pneumatic Diagram
Page 15 Electrical Supply Requirements
Wiring Requirements, Enclosure Power & Alarm Signal, Enclosure Wiring Methods & Connections
Page 16 Conduit Installation
Electrical & WPS Style Conduit and Connection Parts
Page 17 Set-Up & Operating Procedures
Class II Set-up and Operation
Page 18 Trouble - Shooting Procedures
Trouble-shooting Chart
Page 19 Warranty and Liability Statement
Warranty Notes, General Terms, Limitations
Page 20 Systems Identification & Application
Information
Purpose
Pepperl+Fuchs' Bebco EPS System’s purpose is to allow the use of general purpose or nonrated electrical or electronic devices, with exception to devices which produce excessive heat, utilize combustible gas, or expose arcing contacts to the hazardous atmosphere, in Type 4 or 12 enclosures in the place of explosion proof Type 7 or 9 enclosures. Other purposes include
heat, moisture and dust contamination prevention.
Description
Model 1001B is an enclosure pressurization system that operates on a supply of compressed instrument air or inert gas. It regulates and monitors pressure within sealed (protected) enclosures to prevent combustible dust accumulation. In Class II areas, the system maintains a “safe” (1.0") pressure. This process reduces the hazardous (classified) area rating within the enclosure(s), in accordance with the NEC - NFPA 70, Article 500, NFPA 496 and ISA 12.4
Important Notes
One (1) permanent file copy and one (1) operations copy of this Manual must be studied and retained by the operator of this System. User’s Agents are responsible for transferring this Manual to the user, prior to start-up.
The contents of this manual have been arranged to allow the use of this product as a stand-alone device on equipment and enclosures supplied by the user or its agents. The Manual’s parameters encompass a combination of both National Fire Protection Association (NFPA) requirements and Pepperl+Fuchs requirements. Pepperl+Fuchs therefore acknowledges the use of NFPA 496 as a guideline, that we have enhanced certain NFPA requirements and that additional information has been compiled to complete this document. The Manual is intended as a complete guide and must be considered, unless specifically stated otherwise, that all directives contained herein are Pepperl+Fuchs requirements for safe, practical and efficient use of this product.
This System is not intended for use to protect enclosures or devices which contain ignitable concentrations of gases or vapors. This exclusion generally applies to process or product analyzing systems equipment.
All specifications are subject to change without notice.
2
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
BEBCO EPS
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: sales@us.pepperl-fuchs.com
Identifying Your System
ISC * 877-602-0010 * www.iscenclosurecooling.com
This Enclosure Protection System is offered in various styles. For proper installation and operation, examine the System Model Number Nameplate to identify the System Style, Area Classification, and Type, as noted below.
SYSTEM STYLE
SYSTEM CLASS RATING
Defines Class rating for Protection
System’s method of use
CII - Class II Pressurization system
SERIES
MODEL NUMBER
Systems are available in two styles, with or without an explosion proof differential
pressure switch, used to detect loss of
“safe” enclosure pressure
LPS - Less Pressure Switch
WPS - With Pressure Switch
MAXIMUM
TOTAL
ENCLOSURE
VOLUME
Defines total
protected
enclosure(s)
volume capacity for
this particular system. Total
enclosure(s)
volume must be
calculated without
regard for
consumed volume
To assist you through the installation and operation of your pressurization / purge system, Pepperl+Fuchs, Inc. has provided the following information boxes throughout this manual. This information is intended to clarify certain differences between the model styles and configurations and to warn the user / installer of potential dangers of electrical shock or enclosure over pressurization.
Model 1001B-LPS-CII Type Y or Z
50 CUBIC FEET MAXIMUM ENCLOSURE VOLUME
REDUCES INTERNAL AREA CLASSIFICATION AS FOLLOWS:
TYPE Y: CL. II, DIV. 1, GR. F & G TO CL. II, DIV. 2
TYPE Z: CL. II, DIV. 2, GR. F & G TO NONHAZARDOUS
PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS. IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTIONASSOCIATION STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL EQUIPMENT NFPA 496-2003 7L93
APPROVED BY FACTORY MUTUAL AS ASSOCIATED TYPE Y & Z PRESSURIZATION CONTROL EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER 129-0201.
AREA
CLASSIFICATION
Defines the area classification for
which the system is
suitable for operation
APPROVAL MARKINGS & DEFINITIONS
Identifies the current third party approvals
for this system
SYSTEM TYPE
Type Z
Reduces the internal
enclosure area
Division rating from
Division 2 to
nonhazardous
Type Y
Reduces the internal
enclosure area
Division rating from
Division 1 to
Division 2
HELPFUL HINT
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
BEBCO EPS
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: sales@us.pepperl-fuchs.com
IMPORTANT NOTE
WARNING
3
General Information
ISC * 877-602-0010 * www.iscenclosurecooling.com
System Specifications
System Dimensions: See Pages 10 & 11 Shipping Weight ( lbs.): LPS - 7, WPS - 12 Operating Temperature Range: -20° F - 120° F Supply Pressure Range: * 5 -120 PSI max. Supply Requirements: Clean Air or Inert Gas Safe Pressure Setpoint: 1.0" Safe Pressure Flowrate: ** 0.1-3.5 SCFH/Cubic Ft. System Supply Fitting: 3/8" Tube Fitting Enclosure Supply Fitting: 3/8" Tube Fitting Enclosure Reference Fitting: 1/4" Tube Fitting Switch Setting (Decr,) 0.5" Switch Conduit Port Size: 1/2" FPT Switch Contact Rating: 120 VAC, 15 Amps
* With EPV-3 Vent - 120 PSI max. to 5 PSI minimum
Systems installed without EPV-3 must be equipped with redundant regulator set to 5 PSI maximum
** Enclosure integrity determines actual flow rate
+ .02"
Material Specifications
Regulator Body: Zinc w/ Enamel Finish Regulator Handle: Polycarbonate Enclosure Pressure Gauge: Alum. w/ Enamel Finish Tube Fittings: 316 SS Forged Body Tubing: 316 SS 1/4" .035 Welded System Nameplates: Silkscreened Lexan Fastener Hardware: Aluminum & Stainless Steel Mounting Plate: 316 14 Ga #3 Brush SS EXP Pressure Switch Body: Anodized Cast Alum. Enclosure Warning Nameplate: Silkscreened SS
Lexan® is a registered trademark of the General Electric Corporation
®
& SS
Model 1001B System Accessories
Recommended Spare Parts
Qty Description Part # (supercedes)
1 Enclosure Pressure Indicator-CII 513235 (001027) 1 Enclosure Pressure Control Regulator 513236 (002050) 1 Installation & Operation Manual 129-0201
EXP Encl Pressure Loss Alarm Switch-CII
1 1 Enclosure Warning Nameplate-CII 513009 (EWN-2)
Please call and reference the above part number for current spare parts pricing. Immediate pricing is available to all confirmed customers.
513242 (001082)
Installation Tools & Testing Equipment
1/2" chuck drill Complete set of drill bits
1.25" conduit knockout punch or 1.75" hole saw Complete set of tubing, conduit bending, instrument fitting and electrical craftsman hand tools 0 - 250 scfh flowmeter (connected upstream of the Protection System to determine air consumption and flow during set-up
procedure)
Maintenance Procedures
Regular Maintenance Procedure
Drain the Protection System Filter frequently (if equipped with a Model ILFK In-Line Filter Kit) and clean System with non-solvent cleaning agents only, such as soap and water.
Long Term Maintenance Procedures
Calibrate the enclosure pressure indicator to 0 inches by venting the purge pressure reference port and the protected enclosure to atmosphere and adjusting the calibration screw in the lower center portion of the indicator’s face.
Optional Enclosure Protection Vents
EPV-3-SA-00 Straight w/ Spark Arrestor EPV-3-SA-90 Rt Angle w/ Spark Arrestor
Additional Items
SMK-1, -4 or -6 System Mounting Kit EPSK-2 Class II, Explosion Proof Switch Kit GPSK-2 Class II, General Purpose Switch Kit RAH Div. 1 Remote Alarm Horn RAB-1 Div. 1 Remote Alarm Beacon RAB-2 Div. 2 Remote Alarm Beacon LCK L Fitting Conduit Kit TCK T Fitting Conduit Kit
4
BEBCO EPS
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: sales@us.pepperl-fuchs.com
If vent is utilized, fully open the enclosure pressure control regulator, to blow out any deposits around the tip of the regulator and to ensure that the enclosure protection vent is operating properly, then carefully readjust system according to the set-up and operating procedures on page 17. Replace or tighten stem packing nut as required to prohibit stem packing leakage.
Carefully disassemble the enclosure protection vent by loosening the two bottom hex nuts that hold the unit together.
(DO NOT REMOVE CAP NUTS ON TOP OF VENT BODY)
Carefully clean the flapper valve and vent body seats with warm soap and water, being careful not to extend the vent valve beyond its normal opening point, and being careful not to exert any stress on the valve hinge.
Examine the entire Protection System and the protected enclosure(s), and replace any defective parts during routine shutdown of the protected enclosure(s). Parts are available from Pepperl+Fuchs on immediate notice as required.
Enclosure & Device Design
ISC * 877-602-0010 * www.iscenclosurecooling.com
Enclosure Design Requirements
1. All windows must be shatterproof and sized as small as possible.
2. All NFPA 496 required markings must be placed on or near all enclosure doors and covers.
3. The enclosure must withstand an internal pressure of ten (10) inches of water without sustaining permanent deformation and resist all corrosive elements in the surrounding atmosphere.
4. All lightweight objects in the enclosure, such as paper or insulation, must be firmly secured.
5. The enclosure should be constructed from materials such as metal or anti-static polycarbonate to meet or exceed Type 4 or 12 performance requirements, but does not require third party approval.
6. The installation of obstructions or other barriers which block or impede the flow of protective gas must be avoided.
7. The creation of air pockets or other areas which trap flammable gases within the enclosure or devices must be avoided.
8. The enclosure should be located in an area where impact hazards are minimal.
9. If the enclosure is nonmetallic and contains equipment which utilizes or switches power loads greater than 2500 VA, it must be constructed from substantially noncombustible materials, such as materials designed to meet or exceed ANSI/UL94 ratings of 94 V-0 or 94 5V.
Total Volume Calculation
1. The total volume of all pressurized enclosures, devices and wireways must be considered.
2. All enclosure, device and wireway volumes must be calculated without consideration of internally consumed space.
Device Ventilation
1. Enclosed devices within the protected enclosure which do not exceed 1.22 cubic inches of free volume do not require ventilation to the protected enclosure.
2. If the free volume of an internal device exceeds 1.22 cubic inches it must be protected by one of the following means:
a) ventilated on the top and bottom sides with one (1)
square inch of opening for each four hundred (400) cubic inches of volume within the internal protected enclosure, at a minimum diameter of one (1) quarter inch;
b) purged in series with the protected enclosure or be
purged separately; or
c) protected by other means; e.g. explosion proof
enclosures, hermetically sealed devices or intrinsic safe circuits.
Temperature Limitations
1. The enclosure must have no surface area which exceeds 80 percent of the flammable or ignitable substance’s auto-ignition temperature.
Adjacent Enclosures
1. Adjacent enclosures must be protected by one of the following means:
a) purged or pressurized in series with the protected
enclosure;
b) purged or pressurized separately; or
c) protected by other means; e.g. explosion proof
enclosures, hermetically sealed devices or intrinsic safe circuits.
2. Adjacent purged or pressurized enclosures must be designed to meet all construction requirements above.
2. Internal devices which exceed this temperature must be protected by one of the following manners.
a) The device is enclosed in a chamber that is cUL or
FM listed as a hermetically sealed device which prohibits the entrance of flammable or ignitable substance, and maintains a surface temperature below temperature limits.
b) It can be proven by testing that the devices will not
ignite the substance involved.
c) The device is purged in a separate enclosure that
bears an ETW (Enclosure Temperature Warning Nameplate). Devices may only be accessed after power has been removed and the device has been allowed to cool to safe temperature, or the area is positively known to be nonhazardous.
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
BEBCO EPS
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: sales@us.pepperl-fuchs.com
5
Installation Overview
ISC * 877-602-0010 * www.iscenclosurecooling.com
Typical Left Hand Configuration Installation Diagram
Model 1002-WPS-LH Shown
ENCLOSURE
PROTECTION
VENT
PROTECTED ENCLOSURE
ENCLOSURE
SUPPLY TUBING
SYSTEM
MOUNTING
BOLT
PROTECTIVE GAS SUPPLY
SERVICE
VALVE
SUPPLY TUBING
ENCLOSURE
PROTECTION
SYSTEM
SYSTEM
SUPPLY FITTING
SYSTEM
ENCLOSURE REFERENCE
TUBING
ENCLOSURE
CONNECTION
FITTINGS
ENCLOSURE
WARNING
NAMEPLATE
6
ELECTRICAL ALARM WIRING
CONDUIT & SEAL
Pepperl+Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
BEBCO EPS
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: sales@us.pepperl-fuchs.com