Pentax Ademco VISTA-20P Programming Manual

ADEMCO VISTA SERIES
VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA
Security Systems
Programming Guide
K5305-1PRV5 10/04 Rev. A
TO ENTER PROGRAMMING MODE (using an alpha keypad connected to the control):
A. POWER UP, then press [✱] and [#] at the same time, within 50 seconds of powering up (this method must be used if ✱98
was used to exit program mode). OR
B. Initially, key: Installer Code (4 + 1 + 1 + 2) plus 8 + 0 + 0.
PROGRAMMING MODE COMMANDS
Task Command/Explanation Go to a Data Field Entering Data
Press [∗∗∗] + [Field Number], followed by the required entry.
When the desired field number appears, simply make the required entry. When the last entry for a field is entered, the keypad beeps three times and automatically displays the next data field in sequence. If the number of digits that you need to enter in a data field is less than the maximum digits available (for example, the phone number fields *41, *42), enter the desired data, then press [ ] to end the entry. The next data field number is displayed.
Review a Data Field Press [#] + [Field Number].
Deleting an Entry Initialize Download ID Reset Factory Defaults Zone Programming
Function Key Programming Zone Programming
(Expert Mode) Output Device Mapping Output Programming Zone List Programming Alpha Programming Exit Program Mode with installer code lockout
Data will be displayed for that field number. No changes will be accepted in this mode.
Press [∗∗∗] + [Field Number] + [∗∗∗∗]. (Applies only to fields ∗40 thru *46, *94, and pager fields) Press ∗∗∗96. Initializes download ID and subscriber account number. Press ∗∗∗97. Sets all data fields to original factory default values. Press ∗∗∗56. Zone characteristics, report codes, alpha descriptors, and serial numbers for 5800
RF transmitters.
Press ∗∗∗57. Unlabeled keypad keys (known as ABCD keys) for special functions Press ∗∗∗58. Same options as *56 mode, but with fewer prompts. Intended for those familiar
with this type of programming, otherwise *56 mode is recommended.
Press ∗∗∗79. Assign module addresses and map individual relays/powerline carrier devices Press ∗∗∗80. 4229 or 4204 Relay modules, Powerline Carrier devices, or on-board triggers Press ∗∗∗81. Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc. Press ∗∗∗82. Zone alpha descriptors Press ∗∗∗98. Exits programming mode and
prevents
re-entry by: Installer Code + 8 + 0 + 0.
To reenter programming mode, the system must be powered down, then powered up. Then use method A above. See field *88 for other *98 Program mode lockout options.
Exit Program Mode
Press ∗∗∗99. Exits programming mode and
method A above.
allows
re-entry by: Installer Code + 8 + 0 + 0 or
SPECIAL MESSAGES
OC = OPEN CIRCUIT (no communication between Keypad and Control). EE or ENTRY ERROR = ERROR (invalid field number entered; re-enter valid field number).
After powering up, AC, dI (disabled) or Busy Standby and NOT READY will be displayed after approximately 4 seconds. This will revert to a “Ready” message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this delay by pressing [#] + [0].
If E4 or E8 appears, more zones than the expansion units can handle have been programmed. The display will clear after you correct the programming.
TABLE OF DEVICE ADDRESSES
This Device Uses Address Reports as †† Enabled By…
RF Receiver 00 100 *56 zone programming: input device type entry AUI 1 01 101 Automatic if AUI enable field *189 enabled for AUI 1 AUI 2 02 102 Automatic if AUI enable field *189 enabled for AUI 2 Long Range Radio 03 103 automatic if output to long range radio field *29 enabled 4286 Voice Module 04 104 automatic if phone module access code field *28 enabled Zone Expanders (4219/4229):
module 1 (for zones 09 - 16) module 2 (for zones 17 - 24) module 3 (for zones 25 - 32) module 4 zones 33 - 40 module 5 zones 41 - 48
Relay Modules (4204):
module 1 module 2 module 3 module 4
Keypads:
keypad 1 keypad 2 keypad 3 keypad 4 keypad 5 keypad 6 keypad 7 keypad 8
5800TM Module 28 n/a automatic
** These module addresses apply to VISTA-20P only. †† Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable device
reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad display options.
07
08 09** 10** 11**
12
13 14** 15**
16
17
18
19
20
21
22
23
107 108 109 110 111
112 113 114 115
n/a n/a n/a n/a n/a n/a n/a n/a
*56 zone programming: input device type entry, then:
automatic if zone no. 9-16 entered as AW type or relay assigned automatic if zone no. 17-24 entered as AW type or relay assigned automatic if zone no. 25-32 entered as AW type or relay assigned automatic if zone no. 33-40 entered as AW type or relay assigned automatic if zone no. 41-48 entered as AW type or relay assigned
*79 output device programming: device address prompt:
entered at device address prompt entered at device address prompt entered at device address prompt entered at device address prompt
data field programming as listed below:
always enabled, all sounds enabled. data field *190 data field *191 data field *192 data field *193 data field *194 data field *195 data field *196
2
PROGRAMMING FORM
Entries apply to the ADEMCO VISTA-15P/VISTA-15PSIA and ADEMCO VISTA-20P/VISTA-20PSIA controls, except entries shown in dashed boxes, which apply only to the VISTA-20P/VISTA-20PSIA (partition entries) and are not applicable to the VISTA-15P/VISTA-15PSIA. In addition, where noted, certain fields have special settings when used with the VISTA-20PSIA/VISTA-15PSIA (indicated by V20PSIA/V15PSIA with heavy borders and reverse type throughout for easy identification). Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults. SIA Guidelines: Notes in certain fields give instructions for programming the VISTA-20P/VISTA-15P for False Alarm Reduction.
UL: must be “0”
[00,00,00]
[4112] | | |
[0,0]
[0]
[0,0]
Part. 1 Part. 2
| | |
[0]
[0]
|
(Partition 1 only)
[60,60] | |
[30,30] | |
Part. 1 Part. 2
[0]
[0]
[0]
[1]
∗∗∗∗20 Installer Code
4 digits, 0–9
∗∗∗∗21 Quick Arm Enable
0 = no; 1 = yes Part. 1 Part.2
∗∗∗∗22 RF Jam Option
0 = no RF Jam detection; 1 = send RF Jam report UL: must be 1 if wireless devices are used
∗∗∗∗23 Quick (Forced) Bypass
0 = no quick bypass
1 = allow quick bypass (code + [6] + [#] )
∗∗∗∗24 RF House ID Code
00 = disable all wireless keypad usage Part. 1 Part. 2 Common 01–31 = using 5827, 5827BD or 5804BD keypad
∗∗∗∗26 Chime By Zone
0 = no; 1 = yes (list chime zones on zone list 3 using *81 Menu mode)
∗∗∗∗27
Powerline Carrier Device (X–10)
House Code
0 = A; 1 = B; 2 = C; 3 = D; 4 = E; 5 = F; 6 = G; 7 = H; 8 = I; 9 = J;
#10 = K; #11 = L; #12 = M; #13 = N; #14 = O; #15 = P
UL: not for fire or UL installations
∗∗∗∗28 Access Code For Phone Module [00]
00 = disable;
1st digit: enter 1–9; 2nd digit: enter # + 11 for "✱", or # + 12 for "#".
UL: must be “00” for UL Commercial Burg. installations
∗∗∗∗29 Long Range Radio Output
0 = disable; 1 = enable
∗∗∗∗31 Single Alarm Sounding Per Zone
0 = unlimited sounding; 1 = one alarm sounding per zone
V20PSIA/V15PSIA: If “0” selected, “alarm sounding per zone” will be
the same as the “number of reports in armed period” set in field *93 (1 if one report, 2 if 2 reports, unlimited for zones in zone list 7).
∗∗∗∗32 Fire Alarm Sounder Timeout
0 = sound stops at timeout; 1 = no timeout UL: must be “1” for fire install.
∗∗∗∗33 Alarm Sounder (Bell) Timeout
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min; UL: For residential fire alarm installation, must be set for a
minimum of 4 min (option 1); for UL Commercial Burglary installations, must be minimum 16 min (option 4)
∗∗∗∗34 Exit Delay
00 - 96 = 0 - 96 secs; 97 = 120 secs Part. 1 Part. 2 SIA Guidelines: minimum exit delay is 45 seconds
V20PSIA/V15PSIA: 45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result in a 45-second delay.
UL: see inst. instr. for requirements. Common zones use part. 1 delay.
∗∗∗∗35 Entry Delay #1
Common zones use same delay as partition 1. 00 - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
SIA Guidelines: minimum entry delay is 30 seconds
V20PSIA/V15PSIA:
30-96 = 30 - 96 secs; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs NOTE: Entries less than 30 will result in a 30-second delay.
For UL Residential Burglary Alarm installations, must be set for a maximum of 30 seconds; entry delay plus dial delay should not exceed 1 min. For UL Commercial Burglar Alarm, total entry delay may not exceed 45 seconds.
∗∗∗∗36 Entry Delay #2
See *35 Entry Delay 1 for entries. Part. 1 Part. 2
∗∗∗∗37 Audible Exit Warning
0 = no; 1 = yes (SIA Guidelines: must be enabled) Part. 1 Part. 2
V20PSIA/V15PSIA: feature always enabled; field does not exist
∗∗∗∗38 Confirmation Of Arming Ding
0 = no; 1 = yes (wired keypads and RF) Part. 1 Part. 2
2 = yes, RF only
UL: must be “1” for UL Commercial Burglar Alarm inst.
∗∗∗∗39 Power Up In Previous State
0 = no, always power up disarmed; 1 = yes, power up in previous state
UL: must be “1” SIA Guidelines: must be “1”
[30,30] | |
[1,1]
[0,0]
[1]
DIALER PROGRAMMING (✱40 – ✱42)
Do not fill unused spaces. Enter 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2­second pause. If fewer than the maximum digits entered, exit the field by pressing []. The next data field number is displayed.
∗∗∗∗40 PABX Access Code or
| | | | |
Call Waiting Disable Enter up to 6 digits. To clear entries,
press 40. If call waiting is used, enter call waiting disable digits “ (#+11) 70” plus “# + 13” (pause). NOTES: 1. The call waiting disable feature cannot be used on a PABX line.
2. Using Call Waiting Disable on a non-call waiting line will prevent successful communication to the central station.
V20PSIA/V15PSIA: If call waiting is used, enter call waiting disable digits
as described above, and also set Call Waiting Disable option in field *91.
∗∗∗∗41 Primary Phone No.
| | | | | | | | | | | | | | | | | | |
∗∗∗∗42 Second Phone No.
Enter up to 20 digits. To clear entries, press ✱41✱ or ✱42
NOTE: #+14 for E; #+15 for F. Enter [✱] as the fourth digit if a 3-digit account number
(for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a 4-digit account number for Nos. 0000-0999. Exit field by pressing ✱ if only 3 digits are used. E.g., For Acct. B234, enter: #+11 + 2 + 3 + 4
∗∗∗∗43 Partition 1 Primary Acct. No.
| | | / | | | | |
| | | | | | | | | | | | | | | | | | |
respectively
For fields *43 thru *46: Enter 0–9; #+11 for B; #+12 for C; #+13 for D;
[FFFFFFFFFF] Enter 4 or 10 digits, as
chosen in *48 Report Format. See box above. To clear entries, press *43
∗∗∗∗44 Part. 1 Secondary Acct. No. (see field *43 for entries)
| | | / | | | | | [FFFFFFFFFF] To clear, press
∗∗∗∗45 Partition 2 Primary Acct. No. (see field *43 for entries)
| | | / | | | | | [FFFFFFFFFF] To clear, press
∗∗∗∗46 Partition 2 Secondary Acct. No. (see field *43 for entries)
| | | / | | | | | [FFFFFFFFFF] To clear, press
∗∗∗∗47 Phone System Select [1]
If Cent. Sta. is not on a WATS line: 0=Pulse Dial; 1=Tone Dial; if Cent. Sta. is on
a WATS line: 2 = Pulse Dial ; 3 = Tone Dial
∗∗∗∗48 Report Format [77]
0 = 3+1, 4+1 ADEMCO L/S STANDARD primary secondary 1 = 3+1, 4+1 RADIONICS STANDARD 2 = 4+2 ADEMCO L/S STANDARD 3 = 4+2 RADIONICS STANDARD 5 = 10-digit ADEMCO CONTACT ID® REPORTING 6 = 4+2 ADEMCO EXPRESS 7 = 4-digit ADEMCO CONTACT ID® REPORTING 8 = 3+1, 4+1 ADEMCO L/S EXPANDED 9 = 3+1, 4+1 RADIONICS EXPANDED
*44*.
*45*.
*46*.
– 3 –
.
*.
∗∗∗∗49 Split/Dual Reporting [0]
0 = Standard/backup reporting only (all to primary) Primary Phone No. 2nd Phone No. 1 = Alarms, Restore, Cancel Others 2 = All except Open/Close, Test Open/Close, Test 3 = Alarms, Restore, Cancel All 4 = All except Open/Close, Test All 5 = All All
∗∗∗∗50 Burglary Dialer Delay [2,0]
Delay Time: Delay Time V20PSIA/V15PSIA
0 = no delay UL: must be “0” Delay Disable 1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds
SIA Guidelines: delay must be minimum of 30 seconds
V20PSIA/V15PSIA:
Delay Time: 1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds Delay Disable:
0 = use delay set in entry 1 1 = dial delay disabled for zones listed in zone list 6 (use zone list 6
to enter those zones that require dial delay to be disabled; these zones ignore the setting in entry 1)
UL: Dial delay plus entry delay must not exceed one minute; use zone list 6 to disable dial delay from appropriate zones, if necessary.
∗∗∗∗53 SESCOA/Radionics Select [0]
0 = Radionics (0-9, B-F); enter “0” for all non-SESCOA formats 1 = SESCOA (0-9 only reporting)
∗∗∗∗54 Dynamic Signaling Delay [0]
Select delay from 0 to 225 secs, in 15-sec increments. 0 = no delay (both signals sent); 1 = 15 secs; 2 = 30 secs, etc. UL: Grade AA must be “0;” Grade A must be “15” max
∗∗∗∗55 Dynamic Signaling Priority [0]
0 = Primary Dialer first; 1 = Long Range Radio first.
For UL Commercial Burglary installations that use a DACT and LRR, this field must be “0”.
∗∗∗∗56, ∗∗∗∗57, ∗∗∗∗58 Menu Modes
These are Menu Mode commands, not data fields, for Zone Programming, Function Key Programming, and Expert Mode Zone Programming respectively. See page 2 and respective sections later in this document.
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (∗∗∗59 thru
∗∗∗∗68, *70 thru ∗∗∗∗76, and ∗∗∗∗89):
For 3+1 or 4+1 Standard Format: Enter a code in the 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F. A 0 (
not
second
For Expanded or 4+2 Format: Enter codes in for 1–9, 0, or B–F, as described above. A 0 ( that report. A 0 ( For Ademco Contact ID® Reporting: Enter any digit (other than 0) in the box, to enable zone to report (entries in the A 0 ( UL: see installation instructions for requirements
#+10) in the
box will result in automatic advance to the next field.
not
#+10) in the
not
#+10) in the
not
#+10) in
first
box will disable a report. A 0 (
second
box will eliminate the expanded message for
both
boxes will disable the report.
first
box disables the report.
second
SYSTEM STATUS REPORT CODES (
first
box: 1–9, #+10 for
not
#+10) in the
both
boxes (1st and 2nd digits)
boxes are ignored).
59–✱ 68)
first
∗∗∗∗59 Exit Error Alarm Report Code [0]
See above for entries. V20PSIA/V15PSIA: [1] Always enabled.
∗∗∗∗60 Trouble Report Code [00] |
∗∗∗∗61 Bypass Report Code [00] |
∗∗∗∗62 AC Loss Report Code [00] |
∗∗∗∗63 Low Bat Report Code [00] |
∗∗∗∗64 Test Report Code [00] |
Use Scheduling mode to set periodic test reports, or use the following
key commands: installer code +[#] + [0] + 0 = test report sent every 24 hours installer code +[#] + [0] + 1 = test report sent once per week installer code +[#] + [0] + 2 = test report sent every 28 day Each mode sets schedule 32 (VISTA-20P) or schedule 08 (VISTA-15P)
to the stated repeat option; first test report sent 12 hours after command.
∗∗∗∗65 Open Report Code [0,0,0]
Part. 1 Part. 2 Common
∗∗∗∗66 Arm Away/Stay Rpt Code
Away Stay Away Stay Away Stay
Part. 1 Part. 2 Common
[0,0,0,0,0,0]
∗∗∗∗67 RF Trans. Low Bat Report Code [00] |
UL: must be enabled if wireless devices are used
∗∗∗∗68 Cancel Report Code [00] |
V20PSIA/V15PSIA: [10] Report enabled.
∗∗∗∗69 Recent Closing Report Code [11] |
V20PSIA/V15PSIA: Always enabled.
Field does not apply to other controls.
RESTORE REPORT CODES (✱70 – ✱76)
∗∗∗∗70 Alarm Restore Rpt Code [0]
∗∗∗∗71 Trouble Restore Rpt Code [00] |
∗∗∗∗72 Bypass Restore Rpt Code [00] |
∗∗∗∗73 AC Restore Rpt Code [00] |
∗∗∗∗74 Low Bat Restore Rpt Code [00] |
∗∗∗∗75 RF Trans. Lo Bat Rst Rpt Code [00] |
UL: must be enabled if wireless devices are used
∗∗∗∗76 Test Restore Rpt Code [00] |
OUTPUT AND SYSTEM SETUP (✱77 – ✱93)
∗∗∗∗77 Daylight Savings Time [4][10] |
Start/End Month
0 = Disabled 1-12 = January-September (1 = Jan, 2 = Feb, etc) #+10 = October; #+11 = November; #+12 = December
∗∗∗∗78 Daylight Savings Time [1][5] |
Start/End Weekend
0 = disabled; 1 = first; 2 = second; 3 = third; 4 = fourth; 5 = last; 6 = next to last; 7 = third to last
∗∗∗∗79, *80, *81, *82 Menu Modes
These are Menu Mode commands, not data fields, for Output Device Mapping, Output Programming, Zone List Programming, and Alpha Programming respectively. See page 2 and their respective sections in the Installation and Setup Guide for procedures.
∗∗∗∗84 Auto Stay Arm [3]
0 = no; 1 = partition 1 only; 2 = partition 2 only; 3 = both partitions
∗∗∗∗85 Cross Zone Timer [0]
This option not for use in UL installations. (assign cross zones on zone list 4, using *81 Menu mode) 0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min 1 = 30 seconds 7 = 3 min #+13 = 10 min 2 = 45 seconds 8 = 4 min #+14 = 12 min 3 = 60 seconds 9 = 5 min #+15 = 15 min 4 = 90 seconds #+10 = 6 min 5 = 2 minutes #+11 = 7 min
∗∗∗∗86 Cancel Verify Keypad Display [1]
0 = no “alarm canceled” display 1 = display “Alarm Canceled” when system is disarmed after an alarm
has occurred. (To clear the “ALARM CANCELED” display, the user must enter the security code + OFF again.)
∗∗∗∗87 Misc. Fault Delay Time [0]
(used with Configurable Zone Types “digit 6”) 0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min 1 = 30 seconds 7 = 3 min #+13 = 10 min 2 = 45 seconds 8 = 4 min #+14 = 12 min 3 = 60 seconds 9 = 5 min #+15 = 15 min 4 = 90 seconds #+10 = 6 min 5 = 2 minutes #+11 = 7 min
UL: may only be used on non-burglar alarm/ non-fire alarm zones when used in fire and/or UL burglar alarm installation
– 4 –
∗∗∗∗88 Program Mode Lockout Options [0]
0 = standard *98 installer code lockout (reentry only by [] + [#] within
50 seconds after power up)
1 = lockout [] + [#] reentry after *98 exit (reenter via installer code or
downloader only) 2 = not used 3 = lockout local programming after *98 exit (reenter by downloader only)
∗∗∗∗89 Event Log Full Report Code [00] |
See box above field *59 for report code entries.
∗∗∗∗90 Event Log Enables [3]
NOTE: System messages are logged when any non-zero entry is made.
0 = None; 1 = Alarm/Alarm Restore 2 = Trouble/Trouble Restore; 4 = Bypass/Bypass Restore; 8 = Open/Close.
“Open/Close”, enter 9 (1 + 8); To select all, enter #15.
∗∗∗∗91 Option Selection [8, 0]
Example:
To select “Alarm/Alarm Restore”, and
Options: 0 = None Options V20PSIA/V15PSIA
4 = AAV UL: must use ADEMCO UVCM module Call Wait Disable
8 = Exit Delay Restart/Reset UL: must be disabled
#+12 = AAV and Exit Delay Restart/Reset SIA Guidelines: Exit Delay should be enabled.
V20PSIA/V15PSIA:
Options: Same as listed above. Call Waiting Disable: 0 = call waiting not used 1 = call waiting disable digits (*70) entered in field *40; (when
selected, the system dials the entry in field *40 only on alternate dial attempts; this allows proper dialing in the event call waiting service is later canceled by the user).
∗∗∗∗92 Phone Line Monitor Enable [0,0]
UL: see Inst. Instructions for requirements 1 2
NOTE: Output Device must either be programmed to be STOPPED in
field 80 or STOPPED by Code + # + 8 + output number. Entry 1:: 0 = disabled, 1-15 = 1 min - 15 min (#+10 = 10 min; #+11 = 11 min; #+12 = 12 min; #+13 = 13 min; #+14
Entry 2: 0 = Keypad display when line is faulted 1 = Keypad display plus keypad trouble sound 2 = Same as “1”, plus programmed output device STARTS. If either
= 14 min; #+15 = 15 min)
partition is armed, external sounder activates also.
∗∗∗∗93 Reports In Armed Period [1,0]
Per Zone (Swinger Suppression) Restrict V20PSIA/V15PSIA
Restrict Report Pairs: Report Pairs Unlimited 0 = Unlimited Reports Reports Enable 1 = 1 report pair
2 = 2 report pairs SIA Guidelines: Must be set for option 1 or 2.
V20PSIA/V15PSIA:
Restrict Report Pairs: 1 = 1 report pair; 2 = 2 report pairs
Unlimited Reports Enable:
0 = restrict reports to the setting in entry 1
1 = unlimited reports for zones listed in zone list 7; (use zone list 7
to enter those zones that require unlimited reporting; these zones ignore the setting in entry 1)
DOWNLOAD INFORMATION (✱94, ✱95)
∗∗∗∗94 Download Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits, 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-
second pause. Do not fill unused spaces. If fewer than 20 digits, exit
field by pressing ✱. To clear entries from field, press ✱94✱.
UL: downloading may be performed only if a technician is at the site.
∗∗∗∗95 Ring Count For Downloading [15]
NOTE: Do not enter “0” if using 4285/4286 Phone Module.
0 = Disable Station Initiated Download;
1–14 = number of rings (1–9, # +10 =10, # +11 =11,
# +12 =12, # +13 =13, # +14 =14);
15 = answering machine defeat (# +15 =15).
∗∗∗∗96, ∗
97 Initialize/Reset Defaults
∗∗
This is a command, not a data field. See page 2.
∗∗∗∗98, *99 Exit Commands
This is a command, not a data field. See page 2.
PAGER OPTIONS (✱160- ✱172)
∗∗∗∗160 Pager 1 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-sec pause
∗∗∗∗161 Pager 1 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
∗∗∗∗162 Pager 1 Report Options
[0,0,0]
Part. 1 Part. 2 common For each partition, select from the following options: 0 = no reports sent 1 = Opens/closes all users 4 = All alarms and troubles 5 = All alarms / troubles, and opens/closes for all users 12 = Alarms / troubles for zones entered in zone list 9 13 = Alarms / troubles for zones entered in zone list 9, and
∗∗∗∗163 Pager 2 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = 'Q'; #+12 = '#'; #+13 = 2-sec pause
∗∗∗∗164 Pager 2 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
∗∗∗∗165 Pager 2 Report Options
[0,0,0]
Part. 1 Part. 2 common See field *162 for reporting options. Select for each partition (use zone
list 10 if using options 12 or 13).
∗∗∗∗166 Pager 3 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-sec pause
∗∗∗∗167 Pager 3 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
∗∗∗∗168 Pager 3 Report Options
0,0,0]
Part. 1 Part. 2 common See field *162 for reporting options. Select for each partition (use zone
list 11 if using options 12 or 13).
∗∗∗∗169 Pager 4 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-sec pause
∗∗∗∗170 Pager 4 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
∗∗∗∗171 Pager 4 Report Options
[0,0,0]
Part. 1 Part. 2 common See field *162 for reporting options. Select for each partition (use zone
list 12 if using options 12 or 13).
∗∗∗∗172 Pager Delay Option For Alarms [3]
0 = none; 1 = 1 minute; 2 = 2 minutes; 3 = 3 minutes This delay is for ALL pagers in the system.
opens/closes for all users
5
MISCELLANEOUS SYSTEM FIELDS (*174-*181)
∗∗∗∗174 Clean Me Reporting Options [0]
(for ESL smoke detectors) 0 = disable; 1 = Clean Me signal reports;
NOTE: If Clean Me is enabled, you must enter “3” in field ✱56
programming for zone 1 response time.
∗∗∗∗177 Device Duration 1, 2 [0] [0]
(used in *80 Menu mode-Device Actions 5/6) 1 2 0 = 15 seconds 6 = 2-1/2 min #+11 = 7 min 1 = 30 seconds 7 = 3 min #+12 = 8 min 2 = 45 seconds 8 = 4 min #+13 = 10 min 3 = 60 seconds 9 = 5 min #+14 = 12 min 4 = 90 seconds #+10 = 6 min #+15 = 15 min 5 = 2 minutes
∗∗∗∗181 50/60 Hertz AC Operation [0]
0 = 60 Hz; 1 = 50 Hz
CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)
(see Configurable Zone Type Worksheet on page 7)
∗∗∗∗182 Configurable Zone Type 90
1 2 3 4 5 6 7 8 9 10
Enter the appropriate value for each entry, 1-10, based on the charts
provided on the next page. Each entry is the sum of the values of its
selected options (0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
∗∗∗∗183 Zone Type 90 Report Codes
IMPORTANT: Use existing Contact ID® codes, if appropriate, or
define unique codes in CID code range 750-789. See important note
in installation instructions.
90 ALARM ID: XXX TROUBLE ID: XXX
Enter the desired 3-digit Contact ID® report codes for alarms and
troubles occurring on zones assigned to this zone type. Enter the
codes sequentially (all 6 digits). When entering digits, [#] moves
cursor back, [∗] moves forward. Press [∗] when done to continue.
∗∗∗∗184 Configurable Zone Type 91
1 2 3 4 5 6 7 8 9 10
Enter the appropriate value for each entry, 1-10, based on the charts
provided on the next page. Each entry is the sum of the values of its
selected options (0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
∗∗∗∗185 Zone Type 91 Report Codes
IMPORTANT: Use existing Contact ID® codes, if appropriate, or
define unique codes in CID code range 750-789. See important note
in installation instructions.
KEYPAD OPTIONS *190-*196
NOTES: 1. Options for keypad address 16 are set by the factory and cannot
2. Each keypad must be assigned a unique address. Keypads
be changed.)
programmed with the same address will give unpredictable results.
∗∗∗∗190 Keypad 2 Device Address 17 [0] [0]
†Partition/Enable: Part./ Sound VISTA-20P: Enter partition where: Enable
0 = keypad disabled; 1-3 = part. no. (3 = com) VISTA-15P: 1 = enable; 0 = disable
Sound: 0 = no suppression 1 = suppress arm/disarm and E/E beeps 2 = Suppress chime beeps only 3 = suppress arm/disarm, E/E, and chime beeps
∗∗∗∗191 Keypad 3 Device Address 18 [0] [0]
See field ∗190 for entries. Partition/ Sound Enable
∗∗∗∗192 Keypad 4 Device Address 19 [0] [0]
See field ∗190 for entries. Partition/ Sound Enable
∗∗∗∗193 Keypad 5 Device Address 20 [0] [0]
See field ∗190 for entries. Partition/ Sound Enable
∗∗∗∗194 Keypad 6 Device Address 21 [0] [0]
See field ∗190 for entries. Partition/ Sound Enable
∗∗∗∗195 Keypad 7 Device Address 22 [0] [0]
See field ∗190 for entries. Partition/ Sound Enable
∗∗∗∗196 Keypad 8 Device Address 23 [0] [0]
See field ∗190 for entries. Partition/ Sound Enable
∗∗∗∗197 Exit Time Display Interval [0]
0 = no display; 1-5 = seconds between display refresh NOTE: If enabled and using only 2-digit fixed-word keypads (e.g.,
6150RF), do not set exit delay time greater than 96 seconds. See Inst. Instr. for explanation.
∗∗∗∗198 Display Partition Number [0]
(VISTA-20P; for Alpha Display Keypads) 0 = no; 1 = yes (partition no. appears on Alpha Display)
∗∗∗∗199 ECP Fail Display [0]
0 = 3-digit display (“1” + device address) 1 = 2-digit fixed-display as “91”
91 ALARM ID: XXX TROUBLE ID: XXX
Enter the desired 3-digit Contact ID® report codes for alarms and
troubles occurring on zones assigned to this zone type. Enter the
codes sequentially (all 6 digits). When entering digits, [#] moves
cursor back, [∗] moves forward. Press [∗] when done to continue.
∗∗∗∗189 AUI Device 1 and 2 Enable [1] [1]
(for Touch Screen Style Keypads)
System supports up to two touch screen style keypads (e.g., Symphony
Advanced User Interface, and 6270 Touch Screen Keypad).
AUI Compatibility Note: To ensure proper AUI device operation,
connect only to controls having microprocessor version 3.0 or higher,
and use AUI devices with the following rev levels: 6270 series use
version 1.0.9 or higher; 8132/8142 (Symphony) series use version
1.1.175 or higher.
Touch Screen (AUI) device 1: Must set AUI device address to 1 Touch Screen (AUI) device 2: Must set AUI device address to 2 VISTA-20P: Enter each touch screen keypad’s home partition 0 = disable; 1 = partition 1; 2 = partition 2; 3 = partition 3 (common) VISTA-15P: 0 = disable; 1 = enable
NOTE: Use of touch screen style keypads does not affect the number
of standard keypads supported.
AUI 1 AUI 2
6
Configurable Zone Types Worksheets
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182­*185. Configurable zone types 92 and 93 (VISTA-20P only) can only be programmed using the downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1 (See note 5 for RF zones) ENTRY 2 (See note 5 for RF zones)
Response when system disarmed and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault
Open
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
Shorted
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault see note 6
Entry 1 = EOL + Open Entry 2 = Short + auto restore + vent zone
Auto
Restore
0 = no 4 = yes
Vent Zone
0 = no 8 = yes
ENTRY 3 (See note 5 for RF zones) ENTRY 4 (See note 5 for RF zones)
Response when armed STAY and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault
Open
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
Shorted
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault see note 6
Entry 3 = EOL + Open Entry 4 = Short + byp. disarmed + byp. armed
Byp. when
disarmed
0 = no 4 = yes
Byp. when
armed
0 = no 8 = yes
ENTRY 5 (See note 5 for RF zones) ENTRY 6 (See note 5 for RF zones)
Response when armed AWAY and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault
Open
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
Shorted
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault see note 6
Entry 5 = EOL + Open Entry 6 = Short + dial delay + fault delay
Dial Delay
(see field *50)
0 = no 4 = use delay
Fault Delay
(see field *87)
0 = no 8 = use delay
see note 1
ENTRY 7 ENTRY 8
Display Faults Power Reset/
Verification
0 = show alarms
when armed & disarmed
1 = don’t show
alarms when armed
alarms, trbles, faults when disarmed)
0 = no 4 = power reset
12 = verification (see zone
(show
after fault
(by code + OFF)
type 16)
3 = never show
any alarms,
trbles, faults Entry 7 = fault display + power reset/verification
Use Entry
Delay 1/2
0 = no 1 = delay 1 2 = delay 2
Use Exit
Delay
0 = no 4 = use exit
delay
Respond as
Interior Type
0 = no 8 = yes
see note 2
Entry 8 = entry delay 1/entry delay 2 + exit delay +
interior zone type
ENTRY 9 ENTRY 10
Alarm Sounds Use Bell
Timeout
0 = none 1 = steady
keypad 2 = steady bell
and keypad
0 = no 4 = yes
see fields *32, *33
3 = pulsing bell
and keypad Entry 9 = alarm sounds + bell timeout + fire zone Entry 10 = trouble sounds + chime
Respond as
Fire Zone
0 = no 8 = yes
see zone type 09; see note 4
Trouble Sounds
0 = none 1 = periodic
beep
2 = trouble
beeps
Chime when
Chime Mode On
0 = no 4 = yes
Entries for Fields *182 and *184
Entry Zone Type 90 Zone Type 91 (field *182) (field *184)
1 2 3 4 5 6 7 8 9 10
To calculate the value for each entry: Simply add the values of the selected options in each of the entry’s columns (one option per column). For example, to program Entry 2 for “alarm response to short,” “auto restore on,” but not a “vent zone,” enter 5 (“1” for alarm short + “4” for auto restore yes + “0” for vent zone no).
EOL
Zone Conditions Represented
NOTES:
1. Do not use the “fault delay” option with a configurable zone type if it is set for an entry or exit delay, otherwise unpredictable results may occur.
2. To create an interior type zone, select “respond as interior zone type” (entry 8, interior type = yes), and set zone response to “fault” in entries 3-4 to ensure fault displays; do not set as “normal,” “alarm,” or “trouble.”
3. Do not set fire zones to respond as a “fault” (entries 1-6), otherwise faults will not display unless the [] key is pressed.
4. 4219/4229 modules must use EOLRs or unpredictable results may occur.
5. RF Zones: The “open” option in entries 1, 3, and 5 is not applicable for RF zones. Use the “intact EOL” option for normal RF zone conditions and “shorted” for off­normal RF zone conditions.
6. a. Zone-Doubling/Double-Balanced: A
short on either zone of a zone-doubled pair or on a double-balanced zone causes a tamper condition.
b. For double-balanced zones, this entry
must be “0.”
c. For zone-doubled zones, both zones
of the doubled pair must be assigned the same response to a short.
OPEN SHORTEDINTACT
in Entries 1-6
ZONE-003-V0
7
*56 Zone Programming Menu Mode
(press *56 while in Program mode)
The Zone Programming Worksheet is on page 13.
For each of the following prompts, make the desired entry, followed by the [] key to accept the entry. Refer to the Installation and Setup Guide for detailed explanations for each prompt.
SET TO CONFIRM?
0 = no; 1 = yes (See XMIT TO CONFIRM prompt later in this section.) We recommend that you confirm the programming of every transmitter.
ENTER ZN NUM.
01-64, 91, 92, 95, 96, 99 To quit, enter 00 to quit (returns to data field mode).
SUMMARY SCREEN:
System displays a summary of the entered zone’s current programming. Press [] to continue.
ZONE TYPE
00 = Not used 07 = 24-Hr Audible 20 = Arm–STAY* 01 = Entry/exit #1 08 = 24-Hr Aux 21 = Arm–AWAY* 02 = Entry/exit #2 09 = Fire 22 = Disarm* 03 = Perimeter 10 = Interior w/Delay 04 = Interior Follower 12 = Monitor Zone 24 = Silent Burglary 05 = Trouble Day/Alarm Night 14 = Carbon Monoxide 77 = Keyswitch 06 = 24-Hr Silent 16 = Fire w/Verify 81 = AAV Monitor Zone *5800 button-type transmitters only 90-91 = Configurable
23 = No Alarm Resp
PARTITION
1, 2, or 3-common (VISTA-20P)
REPORT CODE
1-9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F For Contact ID®, enter any non-zero entry as the first digit to enable reporting for this zone. To disable the report code for this zone, enter 00.
HARDWIRE TYPE
Appears only for zones 02-08. Zone 1 is automatically set for EOL operation. Enter the desired hardwire type: 0 = EOL; 1 = NC; 2 = NO; 3 = zone doubling (ZD)†; 4 = double-balanced (DB)† († VISTA-20P)
RESPONSE TIME
For hardwired zones 01-08. Enter the desired response time for this zone: 0 = 10mSec; 1 = 350mSec; 2 = 700mSec; 3 = 1.2 secs (see field ∗174).
NOTE: If zone doubling is being used, the response time selected for zones 02-08 automatically applies to each zone’s associated doubled zone.
INPUT TYPE
Skipped for zones 2-8, and for zones 10-16 if zone-doubling enabled. Enter the input type: 2 = AW (Aux wired zone); 3 = RF (supervised RF); 4 = UR (unsupervised RF); 5 = BR (unsupervised button type)
NOTE: To change the input type of a previously programmed wireless device to a wired zone, you must first delete the transmitter’s serial number.
INPUT S/N
Enroll the transmitter’s serial number and loop number as follows:
1. a. Transmit two open/close sequences (for button-type transmitters, press and release the button twice, waiting about 4 seconds before pressing the button the second time).
OR b. Manually enter the 7-digit serial number printed on the label of the
transmitter. Press the [] key to move to the “L” position, then enter the loop number.
Use the [A] (Advance) and [B] (Back) keys to move the cursor forward
and back within the screen. Pressing the [C] (Copy) key will insert the previously enrolled serial number, if desired (used when programming a transmitter with several input loops).
To delete an existing serial number, enter 0 in the loop number field. The serial number will change to 0's. If 0 was entered in error, simply re-enter the loop number or press [#], and the serial number will return to the display.
2. Press [] to continue. The system now checks for a duplicate serial/loop
number.
If no duplicate is found, the display shows the serial number and loop
number.
3. Press [] to continue to confirmation screen.
(prompts continued in next column)
XMIT TO confirm
Appears if you answered “Yes” at the “Set to Confirm” prompt. Activate the loop input or button that corresponds to this zone. Press [] to continue. If the serial/loop number transmitted does not match the serial number entered, a display showing the entered and the received serial/loop numbers appears. If so, activate the loop input or button on the transmitter once again. If a match is not obtained, press the [#] key twice and then enter (or transmit) the correct serial number. Press [] to continue If the serial number transmitted matches the serial number entered, the keypad will beep 3 times and a summary display will appear, showing that zone's programming. An “s” indicates that a transmitter’s serial number has been enrolled.
Press [] to accept the zone information and continue.
PROGRAM ALPHA?
Press 1 if you want to program descriptors for the zone now, and refer to the *82 Descriptor Programming section for procedure. To program descriptors later, enter 0 (no). Press [] to return to the ENTER ZN NUM prompt.
∗∗∗∗58 Expert Zone Programming Mode
(press ∗∗∗58 while in Data Programming mode)
SET TO CONFIRM?
Select whether you want confirmation of wireless device enrollment. (See “XMIT TO CONFIRM” prompt later in this section.) We recommend that
you confirm the programming of every transmitter.
SUMMARY SCREEN
Zn ZT P RC HW: RT 01 09 1 10 EL 1
(Typical for Zone 1, initial summary screen)
Zn ZT P RC IN: L 10 00 1 10 RF: –
(Typical for entered zone number; zone 10 in this example)
System displays summary of zone 1’s current programming. Enter the zone number being programmed, then press []. A summary screen for that zone is displayed, along with any current programming values, and the cursor moves to the Zone Type location. The cursor then automatically moves to the next locations after each entry is made.
Special Function Keys:
[A] (Advance) and [B] (Back) keys on the keypad move the cursor within the screen.
[C] (Copy) key will insert the previous zone’s attributes, if desired.
[D] key starts the Wireless Key Programming Templates menu
(see Wireless Key Programming Templates section that follows this section).
Sequentially enter Zone Type (ZT), Partition (P)†, and Report Code (RC), then Hardwire Type (HW) and Response Time (RT) for basic wired zones 1-8 or Input Device Type (IN) for zones 9 and higher (Loop Number [L] is programmed at the INPUT S/N prompt). See *56 Zone Programming Menu Mode section described earlier for entry values. † applies to VISTA-20P
Press [] to save the programming and continue. If needed, press the [#] key to back up without saving.
For wireless devices (input types RF, UR, BR), continue to the INPUT S/N (serial number/loop number) and XMIT TO CONFIRM prompts described earlier in the *56 Zone Programming Menu Mode section. When done, the display returns to the initial summary screen prompt to let you program the next zone.
For wired devices, the display returns to the initial summary screen prompt to let you program the next zone.
To Quit, enter 00 at the zone number location and press [∗].
8
Wireless Key Programming Templates (press the [D] key from *58 Menu mode Summary Screen)
0
This procedure programs the wireless keys, but a key is not active for arming/disarming until it is assigned to a user number (see
System Operation
TEMPLATE ?
Enter desired template number 1–6 (see chart below), then press [] to continue. To exit the Template screen, press [#]. The system returns to the *58 Menu mode Summary Screen.
TEMPLATE SUMMARY
L 01 02 03 04 T 23 22 21 23
The selected template is displayed. The top line represents loop numbers, the bottom line represents each loop’s zone type. Press [] to accept template and continue.
PARTITION (VISTA-20P)
Enter the partition (1, 2, or 3-common) in which the key is to be active. Press [] to continue.
Wireless Key Predefined Default Templates
For 5804
TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23 2 Disarm 22 2 No Response 23 3 Arm Away 21 3 Arm Away 21 4 No Response 23 4 Disarm 22 TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22 TEMPLATE 3 1 24-hour audible 7 TEMPLATE 6 1 24-hour audible 7 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22
5800 Series Transmitter Input Loop Identification
All of the transmitters illustrated have one or more unique factory assigned input (loop) ID numbers. Each of the inputs requires its own programming zone require four programming zones).
For information on any transmitter not shown, refer to the instructions accompanying that transmitter for details regarding loop numbers, etc.
UL NOTE: The following transmitters are not intended for
use in UL installations: 5802MN, 5802MN2, 5804, 5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.
The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.
*57 Function Key Programming (press
The Function Key Worksheet is on page 14.
PRESS KEY TO PGM
Press the desired function key to be programmed, A-D, then press [] to continue. When done, press 0 to exit this mode and return to data field mode. NOTE: A key programmed as a function key is no longer available to be used as an end-user macro key or panic key.
PARTITION
Enter the partition (1-3) in which this function key will be active.
KEY "A" FUNC
Enter the desired function for this key: 00 = For the Function key selected, the function will be as follows (default): If A selected = Zone 95 (emergency key, same as [1] [] pair) If B selected = Zone 99 (emergency key, same as [] [#] pair) If C selected = Zone 96 (emergency key, same as [3] [#] pair) If D selected = Single-button paging (continued in next column)
section, Assigning Attributes Command in the Installation Instructions).
ENTER START ZONE
The system displays the lowest zone number of the highest available consecutive 4-zone group. To start at a different zone number, enter the zone desired, and press [∗]. If the system has four consecutive zones beginning with that zone, the zone number is displayed. If not, the system will again display a suggested zone that can be used. If the required number of consecutive zones is not available at all, the system will display “00”.
Press [] to accept.
Continue to the INPUT S/N (serial number/loop number) and XMIT TO CONFIRM prompts described earlier in the *56 Menu Mode section.
IMPORTANT: When confirmed, the key is not active for arming/disarming until it is assigned to a user number (using the assigning attributes command, attribute “4”). See System Operation section in Installation Instructions.
When done, the keypad beeps three times and the display returns to the ENTER START ZONE prompt to let you enter the starting zone for the next wireless key.
Loop Function Zone Type
(e.g., a 5804's four inputs
∗∗∗∗
57 while in Data Programming mode)
For 5804BD
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
ENROLL AS
"UR" OR "RF"
LOOP 1
ENROLL AS
LOOP 1
ENROLL AS
LOOP 2 (REED)
LOOP 3
(TERMINALS)
ENROLL AS
KEY "A" FUNC (continued)
01 = Single-button paging (sends a 999-9999 message to pager) 02 = Display time 03 = Arm AWAY (reports as User 00 if closing reports are enabled) 04 = Arm STAY (reports as User 00 if closing reports are enabled) 05 = Arm NIGHT-STAY (reports as User 00 if closing reports enabled) 06 = Step Arming (arms STAY, then NIGHT-STAY if enabled, then
07 = Output Device Command (for device programmed as system
08 = Communication Test (sends Contact ID code 601) 09 -12= Macro Keys 1-4 respectively (defined by [#] [6] [6] command) NOTE: Macros 11-12 apply to VISTA-20P only
Press [] to continue; returns to key number prompt with the next function key letter displayed.
Loop Function Zone Type
5801
5808
5809
5819
"RF"
"RF"
"RF"
LOOP 3
LOOP 2
LOOP 1
LOOP 1 (TERMINALS)
ENROLL AS
"UR" OR "RF"
ENROLL AS
LOOP 2 (REED)
LOOP 3
(TERMINALS)
5802MN
5816
5819S (WHS & BRS)
ENROLL AS
LOOP 2 (REED)
LOOP 1 (TERMINALS)
"RF"
LOOP
LOOP 4
YOU MUST
ENROLL
THIS
1
BUTTON
ENROLL AS "BR"
ALTERNATE
POSITION
FOR LOOP 2
LOOP 1 (INTERNAL SHOCK SENSOR
"RF"
AWAY)
operation type 66 in *80 Menu Mode)
ON
OFF
5804
5816MN
ENROLL AS
"RF"
5850 (GBD)
ENROLL AS
LOOP 3
LOOP 2
LOOP 1
LOOP 2 (REED)
LOOP 1 (TERMINALS)
"RF"
(Green)
(Red)
(Yellow)
LOOP 3
5804BD
ENROLL AS
ENROLL AS
ENROLL AS
"RF" OR "RM"
LOOP 2
5817
5890
"BR"
"RF"
LOOP 4 YOU MUST ENROLL THIS BUTTON
LOOP 1
SET
HOUSE
CODE
LOOP 1 (PRIMARY)
LOOP 2 (AUX. CENTER)
LOOP 3 (AUX. RIGHT)
LOOP
1
MOTION
V20P-006-V
– 9 –
∗∗∗∗79 Menu Mode
∗∗∗∗
(press
The *79 Device Mapping Worksheet is on page 14.
79 while in Programming mode)
ENTER OUTPUT NO.
01-18 = VISTA-20P relays/X-10; 01-08, 17, 18 = VISTA-15P relays/X-10 [] to continue
OUT NORM LOW (appears only for triggers 17/18)
0 = no (standard default); sets the output level normally high 1 = yes; sets the output normally low (can be used for resetting 4-wire
smoke detectors)
[] to return to Output Number prompt
OUTPUT TYPE
0 = delete; 1 = relay (skip to “B” prompt); 2 = Powerline Carrier device (skip to “A” prompt) [] to continue.
A (if X-10 was selected) UNIT No.
Enter the unit code (01-16, set at the device). [] to return to the Output Number prompt continue
B (if relay was selected) MODULE ADDR
Enter the predefined address for this module (07-15; see Table of Device Addresses on page 2). Make sure the module’s DIP switches are set to the selected address. [] to continue
REL POSITION (actual relay number on module)
For 4204 modules, relay numbers are 1-4. For 4229 modules, relay numbers are 1-2. [] to return to the Output Number prompt for programming the next device
∗∗∗∗80 Menu Mode
∗∗∗∗
(press
The Output Definition Worksheet is on page 15.
OUTPUT FUNCT. #
Enter the output function number to be defined (VISTA-20P: 01-48; VISTA-15P: 01-24)). [] to continue; 00 = exit
SUMMARY SCREEN
This screen displays a summary of the current output programming A = Output Action; E = Triggering event; P = Partition; Trig = Trigger type Question mark indicates the device shown has not been mapped. Use *79 Menu mode to map the device. [] to continue
ACTIVATED BY
0 = delete (deletes the output function and any previous programming); a
1 = zone list (go to “A” prompt); 2 = zone type (go to “B” prompt); 3 = zone
Press [] to continue
A” (if zone list was selected)
ZN LIST
Enter the desired zone list number (01-08). At the ENTER EVENT prompt, enter the zone list event that will activate this output (0 = restore; 1 = alarm; 2 = fault; 3= trouble)
Press [] to continue and skip to the “Output Action” prompt.
B” (if zone type was selected)
ENTER ZN TYPE
Enter the desired zone type. See list below *80 Worksheet for zone types. At the PARTITION prompt, enter the partition in which this zone type will occur (0 = any partition; 1 = partition 1; 2 = partition 2; 3 = partition 3). Press [] to continue and skip to the “Output Action” prompt.
C (if zone number was selected)
ENTER ZN NO.
Enter the desired zone number, then press [] to continue. At the ENTER EVENT prompt, enter the zone event that will activate this output (0 = restore; 1 = alarm/fault/trouble). Press [] to continue to the OUTPUT ACTION prompt
OUTPUT ACTION
0 = off; 1 = Close for 2 seconds; 2 = Close and Stay Closed; 3 = Continuous Pulse 1 sec on and 1 sec off 4 = Change Device State; 5 = Duration 1 (see data field *177); 6 = Duration 2 (see data field *177) Press [] to continue.
80 while in Programming mode)
01 A E P Trig ?00 0 0 – ZL=00
confirmation prompt appears. To delete this output definition, press 1. If you do not want to delete this output, press 0.
number (go to “C” prompt)
∗∗∗∗80 Menu Mode (continued)
ENTER OUTPUT NO.
Enter the device output number (programmed in *79 Menu Mode) you want associated with this output. 01-16 = VISTA-20P output no.; 01-08 = VISTA-15P output no.; 17-18 = on­board triggers Press [] to continue.
SUMMARY SCREEN
A summary screen appears showing the programmed settings. Press [] to return to OUTPUT FUNCTION NUMBER prompt.
*81 Menu Mode
(press *81 while in Programming mode)
The Zone List Worksheet is on page 14.
ZONE LIST NO.
Enter the zone list number (01-12) to program (or 00 to exit this mode). Press [] to continue.
ENTER ZN NUM.
Enter each zone number (01-64†) to add to the zone list, followed by pressing [] (example, 01, 02, 03∗). Press 00 to continue.
† VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56. IMPORTANT: Do not include fire zones in zone lists that are used to STOP device actions.
DEL ZN LIST?
0 = don’t delete list; current zone list remains saved 1 = delete this zone list; All zones in the zone list will be deleted. [] to continue
DELETE ZONE?
0 = don’t delete zones; save the entire zone list and return to the Zone List No. prompt 1 = go to next prompt to delete zones [] to continue
ZN TO DELETE?
Enter each zone (01-64†) to be deleted from the list, following each with [∗]. 00 when done to return to the Zone List No. prompt. † VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56.
*82 Alpha Descriptor Programming
PRE-DEFINED DESCRIPTORS
PROGRAM ALPHA
0 = no (quit Alpha mode) 1 = yes Press [] or [#] to continue.
CUSTOM WORDS
0 = no (continue to descriptor programming) 1 = yes (go to custom word programming) Press 0 to program standard alpha descriptors. The system will then display the descriptor for zone 1. To program custom words, press 1 (custom words are described later). Press [] to continue.
∗∗∗∗ ZN 01
Descriptor screen for zone 1 appears. To program a descriptor (up to 3 words) for a zone, do the following:
1. Press [] plus the desired zone number (existing descriptor, if any, is displayed), then press [] plus the zone number again (flashing cursor appears).
2. a. Press [#] plus the 3-digit number from the Alpha Vocabulary List on
page 11 for the first word.
b. Press [6] to accept the word and move the cursor for the next word.
3. Repeat steps 2a and 2b for the second and third words (if used).
4. When all words have been entered, press [8] to save the descriptor for that zone. The flashing cursor disappears.
5. Repeat steps 1-4 to assign a descriptor for the next zone.
6. When all descriptors have been entered, press [] + 0 + 0 (or simply press [#]) after the last descriptor has been saved to return to the PROGRAM ALPHA? prompt.
Enter 0 (no) at the prompt to exit this mode and return to Data Field mode.
10
*82 Alpha Descriptor Programming (continued)
ADDING CUSTOM WORDS (up to 10 words)
For custom words, the keys have the following functions:
[4] moves cursor one space to the left. [6] moves cursor one space to the right. [8] saves the new word in the system's memory.
1. Select Custom Word mode (enter 1) when the prompt “CUSTOM WORD ?” is displayed.
2. Enter the number (01–10, or 11, 12, 13 for partition descriptors– see below) of the custom word or word string to be created, corresponding to index numbers 245 - 254 respectively. A cursor appears at the beginning of the second line.
NOTE: Custom words 8, 9, and 10 are “reminder words” that can be
programmed to display using Scheduling Mode.
3. Refer to the Character (ASCII) Chart on the next page.
Press [#], followed by the two-digit entry for the first letter you would like
to display (e.g., # 6 5 for “A”). The cursor moves to the right, in position for the next character.
To delete a character, simply enter the SPACE character (#32) at the
unwanted character’s location.
4. Repeat Step 3 to create the desired word(s). Each word can be a maximum of 10 characters (except custom message/partition descriptor word numbers 11, 12, and 13, which can be a maximum of 16 characters).
5. When the word is complete, press the [8] key to save the custom word(s) in the vocabulary list and return to the “CUSTOM WORD ?” display.
6. Repeat Steps 1–5 for other custom words to be entered. To change a custom word, just overwrite it. When all words have been programmed, enter 0 at the “CUSTOM WORD ?” prompt to return to the Program Alpha prompt. Enter 0 again to exit Descriptor mode.
To Assign Partition/Custom Message Descriptors, use Adding Custom Words procedure, but: VISTA-15P: Use word number 11 in step 2. The custom message replaces
VISTA-20P: Use the following word numbers in step 2: 11 = partition 1; 12 = partition 2; 13 = common lobby
the standard “DISARMED Ready to Arm” message.
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
000
– A –
001 AIR
002 ALARM
004 ALLEY 005 AMBUSH
006 AREA
007 APARTMENT
009 ATTIC
010 AUDIO – B –
012 BABY
013 BACK
014 BAR
016 BASEMENT
017 BATHROOM
018 BED
019 BEDROOM
020 BELL
021 BLOWER
022 BOILER
023 BOTTOM 025 BREAK
026 BUILDING
C – 028 CABINET
029 CALL 030 CAMERA 031 CAR 033 CASH 034 CCTV 035 CEILING 036 CELLAR
037 CENTRAL
038 CIRCUIT
040 CLOSED
046 COMPUTER
047 CONTACT D
048 DAUGHTERS
049 DELAYED
050 DEN
051 DESK
052 DETECTOR
053 DINING
054 DISCRIMINATOR 055 DISPLAY
Note: Bulleted () words in boldface type are those that are also available for use by the 4285/4286 Phone Module. If using a Phone
(Word Space)
057 DOOR
059 DOWN
060 DOWNSTAIRS
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
061 DRAWER
062 DRIVEWAY
064 DUCT E
065 EAST
066 ELECTRIC
067 EMERGENCY
068 ENTRY
069 EQUIPMENT
071 EXIT
072 EXTERIOR F
∗∗∗∗
073 FACTORY
∗∗∗∗
075 FAMILY
076 FATHERS
∗∗∗∗
077 FENCE
079 FIRE
080 FLOOR
081 FLOW 082 FOIL
083 FOYER
084 FREEZER
085 FRONT
G
089 GARAGE
090 GAS
091 GATE
092 GLASS
093 GUEST 094 GUN – H –
095 HALL
096 HEAT
098 HOLDUP 099 HOUSE 100 INFRARED
101 INSIDE
102 INTERIOR 103 INTRUSION J – 104 JEWELRY
∗∗∗∗
K
105 KITCHEN
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
L
106 LAUNDRY
107 LEFT
108 LEVEL
109 LIBRARY
110 LIGHT
111 LINE
113 LIVING
114 LOADING
∗∗∗∗
115 LOCK 116 LOOP 117 LOW
118 LOWER M
119 MACHINE
121 MAIDS
122 MAIN
123 MASTER
125 MEDICAL
126 MEDICINE 128 MONEY 129 MONITOR
130 MOTHERS
131 MOTION
132 MOTOR N
134 NORTH
135 NURSERY O
136 OFFICE
138 OPEN
139 OPENING
140 OUTSIDE
142 OVERHEAD P – 143 PAINTING
144 PANIC
145 PASSIVE
146 PATIO
147 PERIMETER
148 PHONE 150 POINT
151 POLICE 152 POOL
153 POWER
∗∗∗∗
R
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
155 RADIO
156 REAR
157 RECREATION 159 REFRIGERATION 160 RF
161 RIGHT
162 ROOM
163 ROOF S – 164 SAFE 165 SCREEN 166 SENSOR
167 SERVICE
168 SHED
169 SHOCK
170 SHOP
171 SHORT
173 SIDE
174 SKYLIGHT
175 SLIDING
176 SMOKE
178 SONS
179 SOUTH
180 SPRINKLER
182 STATION 184 STORE
185 STORAGE
186 STORY
190 SUPERVISED
191 SUPERVISION 192 SWIMMING 193 SWITCH T – 194 TAMPER 196 TELCO 197 TELEPHONE
199 TEMPERATURE
200 THERMOSTAT
201 TOOL
202 TRANSMITTER
U
205 UP
206 UPPER
207 UPSTAIRS
208 UTILITY
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
V – 209 VALVE 210 VAULT 212 VOLTAGE W – 213 WALL 214 WAREHOUSE
216 WEST
217 WINDOW
219 WING
220 WIRELESS X – 222 XMITTER Y – 223 YARD Z – 224 ZONE (No.)
225 ZONE
226 0
227 1
228 1ST
229 2
230 2ND
231 3
232 3RD
233 4
234 4TH
235 5
236 5TH
237 6
∗∗∗∗
238 6TH
239 7
240 7TH
241 8
242 8TH
243 9
244 9TH
245 Custom Word #1 246 Custom Word #2 247 Custom Word #3 248 Custom Word #4 249 Custom Word #5 250 Custom Word #6 251 Custom Word #7 252 Custom Word #8 253 Custom Word #9 254 Custom Word #10
module, and words other than these are selected for Alpha descriptors, the module will not provide annunciation of those words.
Italicized
32 (space) 33 ! 34 " 35 # 36 $ 37 % 38 & 39 ' 40 (
words followed by an asterisk indicate those words supported by the 6160V/6150V Voice Keypads
CHARACTER (ASCII) CHART (For Adding Custom Words)
41 ) 42 * 43 + 44 , 45 – 46 . 47 / 48 0 49 1
50 2 51 3 52 4 53 5 54 6 55 7 56 8 57 9 58 :
59 ; 60 <
61 = 62 > 63 ? 64 @ 65 A 66 B 67 C
68 D 69 E 70 F 71 G 72 H 73 I 74 J 75 K 76 L
77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
∗∗∗∗
86 V 87 W 88 X 89 Y 90 Z
11
Setting Schedules (Installer Code + [#] + [6] [4])
ENTER SCHED NO.
VISTA-20P: 01-16 = end-user schedules; 17-32 = installer-only schedules VISTA-15P: 01-04 = end-user schedules; 05-08- = installer-only schedules [] to continue.
To Quit, enter 00.
ENTER EVENT
00 = clear event 01 = Relay On/Off 02 = User Access 03 = Latch Key Report to Pager (sent to all pagers in the user’s partition;
message sent is 777-7777. User must be enabled for paging and system must be armed before reporting can occur.)
04 = Forced Stay Arming
regardless of setting in field *23)
05 = Forced Away Arming
regardless of setting in field *23) 06 = Auto Disarm 07 = Display “Reminder” 10 = Display custom words (if selected, system displays custom words 8, 9,
and 10 at defined time. Can be used as installer’s reminder message to the end user); programmable by installer only
11 = Periodic Test Report (see key commands in Test Report Code, data
field *64, to quickly set periodic test reporting intervals); programmable by installer only
[] to continue.
(
Forced bypass is automatically enabled
(
Forced bypass is automatically enabled
DEVICE NUMBER (for event 1 relay on/off)
01-18; [] to continue.
GROUP NUMBER ( for event 2 user access)
1-8; [] to continue.
PARTITION (for events 3-7,10,12)
0 = all partitions; 1 = partition 1; 2 = partition 2; 3 = common [] to continue.
START
01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM; to select days, position the cursor under the desired days using the [] key to move forward, then press “1” to select the day. [] to continue.
STOP (for events 1 relay on/off; 2 user access; 3 latch key report)
See START for entries. [] to continue.
REPEAT
0 = do not repeat; 1 = repeat schedule weekly; 2 = repeat schedule biweekly (every other week); 3 = repeat schedule every third week; 4 = repeat schedule every fourth week [] to continue
RANDOMIZE (for events 01 and 11)
0 = no; 1 = yes If selected, the scheduled start and stop times will vary within 60 minutes of the “hour” time. For example, if a schedule is set to start at 6:15pm, it will do so the first time 6:15pm arrives, but on subsequent days it will start anytime between 6:00 and 6:59 p.m.
NOTE: Do not use the random option if the start and stop times are within
the same “hour” setting, otherwise unpredictable results may occur (e.g., the
randomized stop time may occur before the start time).
[] to continue and return to ENTER SCHED NO. prompt to program the
next schedule.
SCHEDULES WORKSHEET(installer code + [#] + [6] [4];
VISTA-15P, and events 00-07 for both controls; VISTA-15P supports up to 8 schedules, VISTA-20P supports up to 32 schedules
master code can only access schedules 01-16 for VISTA-20P, 01-04 for
)
No. Event Device No. Group No. Partition Start Time/ Stop Time/ Repeat Random
(see list below) for “01” events: for “02” events: for “04-06” events: Days Days (1-4) (yes/no) enter 01-18 enter 1-8 enter 1, 2, or 3
(VISTA-20P)
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Events: Master/Installer Installer Only 00 = clear event 04 = forced STAY arm 10 = display custom words 8-10 01 = device on/off 05 = forced AWAY arm 11 = periodic test report 02 = user access 06 = auto disarm 03 = latch key report 07 = display “reminder” Repeat Options: 0 = none; 1 = repeat weekly; 2 = repeat every other week; 3 = repeat every third week; 4 = repeat every fourth week
– 12 –
*56 ZONE PROGRAMMING WORKSHEET (VISTA-15P supports up to 32 zones: 1-6, 9-34, 49-56) [default shown in brackets]
NOTES:
Zone Type: see chart on page 12;
Report Code: enabled if any digit entered as 1st digit;
Hardwire Type (zns 1-8):
0 = EOL 3 = ZD 1 = NC 4 = DB 2 = NO
Input Type:
2 = AW (zones 9-48) 3 = RF (zones 9-48) 4 = UR (zones 9-48) 5 = BR (zones 49-64) NOTE: Zones 9-16 not available if zone doubling enabled.
Response Time:
0 = 10msec 1 = 350msec 2 = 700msec 3 = 1.2 sec
Reserved Zones
91 = addressable device
report enable/disable
default zone type =
[05].
92 = Duress report
enable/disable
Zone Zn Type Part. Report Hardwire
1 2 3 4 5 6 7 8
Zone Zn Type Part. Report Input Type Loop Serial No. Location
[09] [1] [01] [1] [03] [1] [03] [1] [03] [1] [03] [1] [03] [1] [03] [1]
Type
Rsp. Time Location
[EOL] [1] [EOL] [1] [EOL] [1] [EOL] [1] [EOL] [1] [EOL] [1] [EOL] [1] [EOL] [1]
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 95 96 99
[00] [00] [06]
[1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1]
[BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR]
N/A N/A N/A
keypad [1] / [∗] N/A N/A N/A keypad [3] / [#] N/A N/A N/A
keypad [∗] / [#]
– 13 –
*57 FUNCTION KEY WORKSHEET
Option Function
01 Paging 02 Time Display 03 Arm AWAY 04 Arm STAY 05 Arm NIGHT-STAY 06 Step Arming 07 Device Activation Device: 08 Comm. Test 09 Macro Key 1 Assign each macro key to only a single partition. 10 Macro Key 2 Assign each macro key to only a single partition. 11 Macro Key 3 Assign each macro key to only a single partition. 12 Macro Key 4 Assign each macro key to only a single partition. 00 Emergency Keys: zone 95 zone 99 zone 96 paging
Personal Emergency n/a Silent Alarm n/a Audible Alarm n/a Fire n/a
Emergency Keys: A = paired keys [1] / [] (zone 95); B = paired keys [] / [#] (zone 99); C = paired keys [3] / [#] (zone 96) † There are only four macros system-wide.
A
P1 P2 com B P1 P2 comC P1 P2 comD P1 P2 com
Comments
OUTPUT RELAYS/POWERLINE CARRIER (X-10) DEVICES WORKSHEET FOR ∗∗∗79, ∗∗∗∗80 and ∗∗∗∗81.
Applicable only if Relays and/or Powerline Carrier Devices are to be used.
∗∗∗∗79 RELAY/POWERLINE CARRIER (X-10) DEVICE MAPPING (Must program before using *80)
OUTPUT TYPE Relay X10 Output No. 01
02 03 04 05 06 07 08
81 ZONE LISTS WORKSHEET
Module Addr.
Pos
(1-4)
Unit
Description
No.
Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the data during the displays and prompts that appear in sequence.
NOTE: Record desired zone numbers below, noting that a list may include
List No. Used For Contains These Zones
01 General Purpose (GP) 02 General Purpose 03 Chime-by-Zone or GP (see field *26 for Chime-by-Zone option) 04 Cross Zones or GP (see field *85 for Cross Zone Timer option) 05 Night-Stay Zones or GP 06 Dial Delay Disable or GP V20PSIA/V15PSIA: see field *50 for Dial Delay Disable option 07 Unlimited Reports or GP V20PSIA/V15PSIA: see field *93 for Unlimited Reports option 08 General Purpose 09 Zones activating pager 1 10 Zones activating pager 2 11 Zones activating pager 3 (VISTA-20P) 12 Zones activating pager 4 (VISTA-20P)
OUTPUT TYPE (09-16 apply to VISTA-20P only) Relay X10 Output
Module
No.
Addr.
09 10 11 12 13 14 15 16
On-Board Trigger 1 norm output =
17
On-Board Trigger 2 norm output =
18
Pos
(1-4)
any
or
Unit
Description
No.
all
of system's zone numbers.
– 14 –
80 OUTPUT DEFINITIONS
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you
enter the data during the displays and prompts that appear in sequence.
1. For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
Notes:
2. For Powerline Carrier devices (plcd), field
27 must be programmed with a House Code.
3. Tampers of expansion units cannot be used to operate devices.
Function
Number (V20P=1-48) (V15P=1-24)
ZONE TYPE/SYSTEM OPERATION – Choices for Zone Types are:
00 = Not Used 05 = Trouble Day/Alarm Night 10 = Interior w/Delay 24 = Silent Burglary 01 = Entry/Exit#1 06 = 24 Hr Silent 12 = Monitor Zone 77 = Keyswitch 02 = Entry/Exit#2 07 = 24 Hr Audible 14 = Carbon Monoxide 81 = AAV Monitor Zone 03 = Perimeter 08 = 24 Hr Aux 16 = Fire w/Verification 90-91 = Configurable
04 = Interior Follower 09 = Fire 23 = No Alarm Response
Choices for System Operation are: 20 = Arming–Stay 38 = Chime 52 = Kissoff 21 = Arming–Away 39 = Any Fire Alarm 54 = Fire Zone Reset 22 = Disarming (Code + OFF) 40 = Bypassing 58 = Duress 31 = End of Exit Time 41 = **AC Power Failure 60 = AAV Trigger 32 = Start of Entry Time 42 = **System Battery Low 66 = Function key† 33 = Any Burglary Alarm 43 = Communication Failure 67 = Bell Failure
36 = **At Bell Timeout*** 68 = TELCO Line Fault 78 = Keyswitch red LED††† 79 = Keyswitch green LED†††
Activated by 0=delete 1=zn list 2=zn type 3=zn no.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
Activation Type and Detail Event (for zone list/activated by)Output
Zone List
1-8 = list
(ZL)
Zone Type
(ZT)
(see table
below)
Zone No.
(ZN)
00=none
V20P: 01-64
V15P: 01-06, 09-34, 49-56
Partition Number
(P)
(if using ZT trig)
0 = any 1 = partition 1 2 = partition 2 3 = common
By Zone List
0 = restore 1 = alarm 2 = fault 3 = trouble
Action
By Zone No.
0 = restore 1 = alrm/flt/trbl
** Use 0 (any) for Partition No. (P) entry. *** Or at Disarming, whichever occurs earlier. † Use *57 Menu mode to assign the function key. †† Duration is set in program field *177. ††† Device action not used for these choices.
0 = off 1 = close 2 secs 2 = stay closed 3 = pulse 4 = toggle 5 = duration 1 6 = duration 2
Note: In normal operation mode:
Code + # + 7 + NN Key Entry starts Device
Code + # + 8 + NN Key Entry stops Device
V20P=1-18
V15P=1-8, 17, 18
†† ††
Output
Number
Device
Type
R = relay T = trigger X = X10
15
EOL
POWER
RED
+
_
BLK
4-WIRE SMOKE DETECTOR CONNECTIONS
RELAY
5
4
AS ZONE TYPE 54
PROGRAM RELAY
_
+
(FIRE ZONE RESET)
OUTPUT
AUX PWR
TERMINALS
SET UNIT’S
DIP SWITCH
FOR DEVICE
ADDRESSES
7 - 15
-AND/OR-
ADEMCO No. 4229
ADEMCO No. 4219
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
WIRED EXPANSION/RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
BLK
TRANSFORMER
8-PIN CONNECTOR
USED FOR 1361X10
SEE INSTRUCTIONS.
ON-BOARD TRIGGERS
CONNECTIONS AND FOR
BATTERY FUSE
FOR REPLACEMENT,
USE SAME VALUE
(e.g. ADEMCO No. 90-12)
3A
SUPERVISION
RELAY MODULE
A77-716B.
USE N.O.
CONTACT,
WHICH CLOSES
WHEN POWER
IS APPLIED.
N.O.
VIOLET
2000
OHMS
EOLR
_
+
DETECTOR
4-WIRE SMOKE
OR COMBUSTION
N.C.
TO OUTPUT 17
CONTACT OPENS MOMENTARILY
UPON FIRE ALARM RESET
(UP TO 16 DETECTORS
MAX. CURRENT = 100 mA
"OUT NORM LOW" = YES IN
PROGRAM OUTPUT 17 FOR
TYPE 54 IN 80 MENU MODE
OR
79 MENU MODE AND AS ZONE
SEE
INSTRUCTIONS.
SET
RECEIVER’S
DIP SWITCH
FOR DEVICE
AND/OR
-AND/OR-
RF RECEIVER
WIRELESS ZONES
ADEMCO 5881* Type
OUTPUT RELAYS)
(4 OUTPUT RELAYS)
ADEMCO No. 4204 RELAY MODULE
RED
GRN
YEL
BLK
OPTIONAL
TO
TRANS.
CABLE)
(USE SA4120XM-1
COM
DATA
SYNC
78
1234 5 6
GND
FLYING LEADS
FOR BATTERY
CONNECTION
(TRIG. 2)
+12 AUX
(TRIG. 1)
+
BLACK
RED
+
HEAT
DETECTOR
+
_
PLUS EOL MODULE)
TO ZONE TERM. ( )
TO ZONE TERM. ( )
(ZONES 2 - 8 ONLY)
ADDRESS
OF “0”.
SEE
INSTRUCTIONS.
5881L: UP TO 8
5881M: UP TO 16
5881H: UP TO 56
*5882 IN CANADA
RED
GRN
YEL
( FROM EITHER OR BOTH GROUPS)
FOR UP TO 40 ADDITIONAL ZONES
BLK
YEL
RED
GRN
TO TERM 4
TO TERM 5
TO TERM 6
TO TERM 7
OUTPUT 18
OUTPUT 17
RED JUMPER
CUT FOR BELL SUPERVISION.
ALSO, CONNECT 2000 OHM
RESISTOR DIRECTLY ACROSS
21 22 23 24 25
20
19
18
17
16
15
14
13
12
11
10
9
78
6
5
4
3
SOUNDER.
12
RING
TIP
RING
TIP
HI
LO
LO
HI
HI
LO
LO
HI
HI
LO
LO
HI
HI
LO
LO
HI
EARTH
(RED)
}
INCOMING
(GREEN)
(GRAY)
}
HANDSET
(BROWN)
+
}
GROUND
PHONE LINE
AUX. POWER
SEE
GROUNDING
FOR PROPER
INSTRUCTIONS
CONNECT CORD)
*CA38A IN CANADA
DOC LOAD NO.: 3
TELEPHONE WIRING
(VIA RJ31X* JACK AND DIRECT
VISTA-20P ONLY
ZONE 8
ZONE 7
ZONE 6
ZONE 5
ZONE 4
ZONE 3
ZONE 2
ZONE 1
+
)
FOR UL
OUTPUT
600mA MAX.
(500mA MAX.
10.5-13.8VDC
ALL OUTPUTS
INSTALLATIONS)
TO 110VAC
UNSWITCHED
OUTLET (24HR)
TO PREVENT RISK OF SHOCK,
COMPLIES WITH FCC RULES, PART 68.
FCC REGISTRATION NO. 5GBUSA-44003-AL-E
RINGER EQUIVALENCE: 0.1B.
DISCONNECT TELEPHONE LINE AT TELCO
JACK BEFORE SERVICING THIS UNIT.
WARNING:
FOR CONNECTION OF OPTIONAL 4285 OR 4286 VIP
MODULES TO PHONE TERMINALS, SEE INSTRUCTIONS.
2000
EOLR
OHMS
2000
EOLR
OHMS
POWER SHUTDOWN NOTE:
ZONE
MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC (PROGRAMMABLE)
MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".
1312 14
TAMPER
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
REMOTE
DEVICES
KEYPADS
AND OTHER
ADDRESSABLE
NOTE:
KEYPAD (S)
CURRENT (IN
BOTH
PARTITIONS)
AND ALL
ARE POWER
2000
EOLR
OHMS
2000
EOLR
OHMS
2000
EOLR
OHMS
2000
EOLR
OHMS
2000
EOLR
OHMS
2000
EOLR
OHMS
YELLOW: KEYPAD DATA OUT
GREEN: DATA IN FROM KEYPAD
RED: KEYPAD PWR (
BLK
LIMITED.
BLACK: KEYPAD GROUND (- ) RETURN
+
ALARM OUTPUT
USAGE, INCLUDING
(600mA MAX. FOR UL
10.5–13.8VDC, 2A MAX.
TEMPORAL PULSE
AUX POWER) STEADY
SOUNDING FOR FIRE.
FOR BURGLARY/PANIC,
CAN USE ADEMCO No. 702
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS
SYSTEM SHUTS DOWN SENSOR
DETECTION PROCESSING IF
CONTROL'S VOLTAGE DROPS
BELOW 9.6V.
PAIRS
2 / 10
3 / 11
4 / 12
5 / 13
6 / 14
7 / 15
3k
ZONE 2
10 11
2k
2k
TAMPER
CONTACTS
CONTACTS
2k
2k
4219, 4229,
4204, 5881)
(e.g. 5800TM,
4285/4286, LRR,
REMOTE KEYPADS
CAN USE 6150 OR 6160
OTHER DEVICES
DRAWING
POWER FROM
TERMS 4 & 5
MUST BE
INCLUDED IN
AUX CURRENT
FOR COMPLETE
INFORMATION, SEE
SEE INSTRUCTIONS.
SIREN, OR 12V BELL).
SYSTEM. IN ADDITION, THIS SYSTEM MUST BE CHECKED BY A QUALIFIED
TECHNICIAN AT LEAST ONCE EVERY THREE (3) YEARS.
ALL DEVICES AND ACCESSORIES
USED IN A CANADIAN INSTALLATION
MUST BE LISTED FOR USE IN CANADA
8 / 16
6.2k
ZONE DOUBLING
(VISTA-20P ONLY)
TYPICAL WIRING FOR
ZONE 10
2k
ZONE 4
(VISTA-20P ONLY)
2k
TYPICAL WIRING FOR
ZONE 3
DOUBLE BALANCED ZONE
KEYPADS. LOCAL
PROGRAMMING
MUST BE DONE WITH A
6139/6160, BUT NEED NOT
REMAIN IN THE SYSTEM
(SET TO ADDRESS 16).
DRAIN
CALCULATIONS.
INSTRUCTIONS K5305-1V2
V20P_V15P-SOC-V5
SUMMARY OF CONNECTIONS
ADEMCO VISTA-20P / VISTA-20PSIA SERIES / VISTA-15P / VISTA-15PSIA SERIES
12V, 4AH
BATTERY
SEALED LEAD-ACID TYPE.
BATTERY NORMALLY NEED NOT BE
24-HR BATTERY STANDBY REQUIRED FOR
FIRE INSTALLATIONS. USE 12V, 17.2AH
BATTERY FOR 600mA AUX POWER. SEE
INSTRUCTIONS.
CHARGING VOLTAGE
BATTERY CAPACITY FOR EMERGENCY
BURGLARY STANDBY USE AT LEAST 4 HRS
REPLACED FOR AT LEAST 3 YRS.
13.8VDC. MAXIMUM
CHARGING CURRENT
650mA.
TO DETERMINE TOTAL STANDBY LOAD
ON BATTERY, ADD 100mA TO TOTAL OF
AUX. POWER OUTPUT AND REMOTE
Copyright © 2003 Honeywell International Inc.
ÊK5305-1PRV5VŠ
K5305-1PRV5 10/04 Rev. A
16.5VAC, 25VA
(e.g. ADEMCO No. 1321).
(USE No. 1321CN IN CANADA)
USE 1361X10 TRANSFORMER
INTERFACE IN PLACE OF 1321 OR
1321CN WHEN POWER LINE CARRIER
DEVICES ARE BEING USED. (SEE
INSTRUCTIONS FOR CONNECTIONS)
THIS EQUIPMENT SHOULD BE INSTALLED
IN ACCORDANCE WITH THE NATIONAL
FIRE PROTECTION ASSOCIATION'S
STANDARD 72, CHAPTER 2 (NATIONAL
FIRE PROTECTION ASSOCIATION,
KEYPAD CURRENTS.
USE UL LISTED LIMITED ENERGY
CABLE FOR ALL CONNECTIONS
CLASS 2 PLUG-IN TRANSFORMER
165 Eileen Way, Syosset, NY 11791
www.honeywell.com/security
BATTERY-MARCH PARK, QUINCY,MA
02269).
PRINTED INFORMATION
DESCRIBING PROPER INSTALLATION,
OPERATION,TESTING, MAINTENANCE,
EVACUATION PLANNING AND REPAIR
SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT.
CONNECTION OF THE FIRE ALARM
SIGNAL TO A FIRE ALARM
HEADQUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH THE
PERMISSION OF THE LOCAL AUTHORITY
HAVING JURISDICTION. THE BURGLAR
ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY
NUMBER.
Loading...