TO ENTER PROGRAMMING MODE (using an alpha keypad connected to the control):
A. POWER UP, then press [✱] and [#] at the same time, within 50 seconds of powering up (this method must be used if ✱98
was used to exit program mode). OR
B. Initially, key: Installer Code (4 + 1 + 1 + 2) plus 8 + 0 + 0.
PROGRAMMING MODE COMMANDS
TaskCommand/Explanation
Go to a Data Field
Entering Data
Press [∗∗∗∗] + [Field Number], followed by the required entry.
When the desired field number appears, simply make the required entry. When the last entry
for a field is entered, the keypad beeps three times and automatically displays the next data
field in sequence. If the number of digits that you need to enter in a data field is less than the
maximum digits available (for example, the phone number fields *41, *42), enter the desired
data, then press [∗ ] to end the entry. The next data field number is displayed.
Review a Data FieldPress [#] + [Field Number].
Deleting an Entry
Initialize Download ID
Reset Factory Defaults
Zone Programming
Function Key Programming
Zone Programming
(Expert Mode)
Output Device Mapping
Output Programming
Zone List Programming
Alpha Programming
Exit Program Mode with
installer code lockout
Data will be displayed for that field number. No changes will be accepted in this mode.
Press [∗∗∗∗] + [Field Number] + [∗∗∗∗]. (Applies only to fields ∗40 thru *46, *94, and pager fields)
Press ∗∗∗∗96. Initializes download ID and subscriber account number.
Press ∗∗∗∗97. Sets all data fields to original factory default values.
Press ∗∗∗∗56. Zone characteristics, report codes, alpha descriptors, and serial numbers for 5800
RF transmitters.
Press ∗∗∗∗57. Unlabeled keypad keys (known as ABCD keys) for special functions
Press ∗∗∗∗58. Same options as *56 mode, but with fewer prompts. Intended for those familiar
with this type of programming, otherwise *56 mode is recommended.
Press ∗∗∗∗79. Assign module addresses and map individual relays/powerline carrier devices
Press ∗∗∗∗80. 4229 or 4204 Relay modules, Powerline Carrier devices, or on-board triggers
Press ∗∗∗∗81. Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc.
Press ∗∗∗∗82. Zone alpha descriptors
Press ∗∗∗∗98. Exits programming mode and
prevents
re-entry by: Installer Code + 8 + 0 + 0.
To reenter programming mode, the system must be powered down, then powered up. Then
use method A above. See field *88 for other *98 Program mode lockout options.
Exit Program Mode
Press ∗∗∗∗99. Exits programming mode and
method A above.
allows
re-entry by: Installer Code + 8 + 0 + 0 or
SPECIAL MESSAGES
OC = OPEN CIRCUIT (no communication between Keypad and Control).
EE or ENTRY ERROR = ERROR (invalid field number entered; re-enter valid field number).
After powering up, AC, dI (disabled) or Busy Standby and NOT READY will be displayed after approximately 4 seconds.
This will revert to a “Ready” message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this
delay by pressing [#] + [0].
If E4 or E8 appears, more zones than the expansion units can handle have been programmed. The display will clear after
you correct the programming.
TABLE OF DEVICE ADDRESSES
This Device Uses Address Reports as †† Enabled By…
RF Receiver 00 100 *56 zone programming: input device type entry
AUI 1 01 101 Automatic if AUI enable field *189 enabled for AUI 1
AUI 2 02 102 Automatic if AUI enable field *189 enabled for AUI 2
Long Range Radio 03 103 automatic if output to long range radio field *29 enabled
4286 Voice Module 04 104 automatic if phone module access code field *28 enabled
Zone Expanders (4219/4229):
module 1 (for zones 09 - 16)
module 2 (for zones 17 - 24)
module 3 (for zones 25 - 32)
module 4 zones 33 - 40
module 5 zones 41 - 48
** These module addresses apply to VISTA-20P only.
†† Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable device
reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad display options.
07
08
09**
10**
11**
12
13
14**
15**
16
17
18
19
20
21
22
23
107
108
109
110
111
112
113
114
115
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
*56 zone programming: input device type entry, then:
automatic if zone no. 9-16 entered as AW type or relay assigned
automatic if zone no. 17-24 entered as AW type or relay assigned
automatic if zone no. 25-32 entered as AW type or relay assigned
automatic if zone no. 33-40 entered as AW type or relay assigned
automatic if zone no. 41-48 entered as AW type or relay assigned
entered at device address prompt
entered at device address prompt
entered at device address prompt
entered at device address prompt
data field programming as listed below:
always enabled, all sounds enabled.
data field *190
data field *191
data field *192
data field *193
data field *194
data field *195
data field *196
– 2 –
PROGRAMMING FORM
Entries apply to the ADEMCO VISTA-15P/VISTA-15PSIA and ADEMCO VISTA-20P/VISTA-20PSIA controls, except entries shown in dashed
boxes, which apply only to the VISTA-20P/VISTA-20PSIA (partition entries) and are not applicable to the VISTA-15P/VISTA-15PSIA. In addition,
where noted, certain fields have special settings when used with the VISTA-20PSIA/VISTA-15PSIA (indicated by V20PSIA/V15PSIA with heavy
borders and reverse type throughout for easy identification).
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
SIA Guidelines: Notes in certain fields give instructions for programming the VISTA-20P/VISTA-15P for False Alarm Reduction.
UL: must be “0”
[00,00,00]
[4112] | | |
[0,0]
[0]
[0,0]
Part. 1 Part. 2
| | |
[0]
[0]
|
(Partition 1 only)
[60,60] | |
[30,30] | |
Part. 1 Part. 2
[0]
[0]
[0]
[1]
∗∗∗∗20Installer Code
4 digits, 0–9
∗∗∗∗21Quick Arm Enable
0 = no; 1 = yes Part. 1 Part.2
∗∗∗∗22RF Jam Option
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
∗∗∗∗23Quick (Forced) Bypass
0 = no quick bypass
1 = allow quick bypass (code + [6] + [#] )
∗∗∗∗24RF House ID Code
00 = disable all wireless keypad usage Part. 1 Part. 2 Common
01–31 = using 5827, 5827BD or 5804BD keypad
∗∗∗∗26Chime By Zone
0 = no; 1 = yes (list chime zones on zone list 3 using *81 Menu mode)
NOTE: Entries less than 45 will result in a 45-second delay.
UL: see inst. instr. for requirements. Common zones use part. 1 delay.
∗∗∗∗35Entry Delay #1
Common zones use same delay as partition 1.
00 - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
SIA Guidelines: minimum entry delay is 30 seconds
V20PSIA/V15PSIA:
30-96 = 30 - 96 secs; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result in a 30-second delay.
For UL Residential Burglary Alarm installations, must be set for a
maximum of 30 seconds; entry delay plus dial delay should not
exceed 1 min. For UL Commercial Burglar Alarm, total entry delay
may not exceed 45 seconds.
∗∗∗∗36Entry Delay #2
See *35 Entry Delay 1 for entries. Part. 1 Part. 2
∗∗∗∗37Audible Exit Warning
0 = no; 1 = yes (SIA Guidelines: must be enabled) Part. 1 Part. 2
V20PSIA/V15PSIA: feature always enabled; field does not exist
UL: must be “1” for UL Commercial Burglar Alarm inst.
∗∗∗∗39Power Up In Previous State
0 = no, always power up disarmed; 1 = yes, power up in previous state
UL: must be “1” SIA Guidelines: must be “1”
[30,30] | |
[1,1]
[0,0]
[1]
DIALER PROGRAMMING (✱40 – ✱42)
Do not fill unused spaces. Enter 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2second pause. If fewer than the maximum digits entered, exit the field by
pressing [✶]. The next data field number is displayed.
∗∗∗∗40PABX Access Code or
| | | | |
Call Waiting Disable Enter up to 6 digits. To clear entries,
press ✱40✱. If call waiting is used, enter call waiting disable digits “∗
(#+11) 70” plus “# + 13” (pause).
NOTES: 1. The call waiting disable feature cannot be used on a PABX line.
2. Using Call Waiting Disable on a non-call waiting line will
prevent successful communication to the central station.
V20PSIA/V15PSIA: If call waiting is used, enter call waiting disable digits
as described above, and also set Call Waiting Disable option in field *91.
∗∗∗∗41Primary Phone No.
| | | | | | | | | | | | | | | | | | |
∗∗∗∗42Second Phone No.
Enter up to 20 digits. To clear entries, press ✱41✱ or ✱42
NOTE:
#+14 for E; #+15 for F. Enter [✱] as the fourth digit if a 3-digit account number
(for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a 4-digit
account number for Nos. 0000-0999. Exit field by pressing ✱ if only 3 digits are
used. E.g., For Acct. B234, enter: #+11 + 2 + 3 + 4
∗∗∗∗43Partition 1 Primary Acct. No.
| | | / | | | | |
| | | | | | | | | | | | | | | | | | |
✱ respectively
For fields *43 thru *46: Enter 0–9; #+11 for B; #+12 for C; #+13 for D;
[FFFFFFFFFF] Enter 4 or 10 digits, as
chosen in *48 Report Format. See box above. To clear entries, press *43
∗∗∗∗44Part. 1 Secondary Acct. No. (see field *43 for entries)
| | | / | | | | | [FFFFFFFFFF] To clear, press
∗∗∗∗45 Partition 2 Primary Acct. No. (see field *43 for entries)
| | | / | | | | | [FFFFFFFFFF] To clear, press
∗∗∗∗46Partition 2 Secondary Acct. No. (see field *43 for entries)
| | | / | | | | | [FFFFFFFFFF] To clear, press
∗∗∗∗47Phone System Select [1]
If Cent. Sta. is not on a WATS line: 0=Pulse Dial; 1=Tone Dial;
if Cent. Sta. is on
0 = Standard/backup reporting only (all to primary)
Primary Phone No.2nd Phone No.1 = Alarms, Restore, Cancel Others
2 = All except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All
4 = All except Open/Close, Test All
5 = All All
∗∗∗∗50Burglary Dialer Delay [2,0]
Delay Time: Delay Time V20PSIA/V15PSIA
0 = no delay UL: must be “0” Delay Disable
1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds
SIA Guidelines: delay must be minimum of 30 seconds
0 = use delay set in entry 1
1 = dial delay disabled for zones listed in zone list 6 (use zone list 6
to enter those zones that require dial delay to be disabled;
these zones ignore the setting in entry 1)
UL: Dial delay plus entry delay must not exceed one minute; use zone
list 6 to disable dial delay from appropriate zones, if necessary.
∗∗∗∗53SESCOA/Radionics Select [0]
0 = Radionics (0-9, B-F); enter “0” for all non-SESCOA formats
1 = SESCOA (0-9 only reporting)
∗∗∗∗54Dynamic Signaling Delay [0]
Select delay from 0 to 225 secs, in 15-sec increments.
0 = no delay (both signals sent); 1 = 15 secs; 2 = 30 secs, etc.
UL: Grade AA must be “0;” Grade A must be “15” max
∗∗∗∗55Dynamic Signaling Priority [0]
0 = Primary Dialer first; 1 = Long Range Radio first.
For UL Commercial Burglary installations that use a DACT and LRR,
this field must be “0”.
∗∗∗∗56, ∗∗∗∗57, ∗∗∗∗58Menu Modes
These are Menu Mode commands, not data fields, for Zone Programming,
Function Key Programming, and Expert Mode Zone Programming respectively.
See page 2 and respective sections later in this document.
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (∗∗∗∗59 thru
∗∗∗∗68, *70 thru ∗∗∗∗76, and ∗∗∗∗89):
For 3+1 or 4+1 Standard Format: Enter a code in the
0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.
A 0 (
not
second
For Expanded or 4+2 Format: Enter codes in
for 1–9, 0, or B–F, as described above.
A 0 (
that report. A 0 (
For Ademco Contact ID® Reporting: Enter any digit (other than 0) in the
box, to enable zone to report (entries in the
A 0 (
UL: see installation instructions for requirements
#+10) in the
box will result in automatic advance to the next field.
not
#+10) in the
not
#+10) in the
not
#+10) in
first
box will disable a report. A 0 (
second
box will eliminate the expanded message for
both
boxes will disable the report.
first
box disables the report.
second
SYSTEM STATUS REPORT CODES (
first
box: 1–9, #+10 for
not
#+10) in the
both
boxes (1st and 2nd digits)
boxes are ignored).
✱
59–✱ 68)
first
∗∗∗∗59Exit Error Alarm Report Code [0]
See above for entries. V20PSIA/V15PSIA: [1] Always enabled.
∗∗∗∗60Trouble Report Code[00] |
∗∗∗∗61Bypass Report Code[00] |
∗∗∗∗62AC Loss Report Code [00] |
∗∗∗∗63Low Bat Report Code[00] |
∗∗∗∗64Test Report Code[00] |
Use Scheduling mode to set periodic test reports, or use the following
key commands:
installer code +[#] + [0] + 0 = test report sent every 24 hours
installer code +[#] + [0] + 1 = test report sent once per week
installer code +[#] + [0] + 2 = test report sent every 28 day
Each mode sets schedule 32 (VISTA-20P) or schedule 08 (VISTA-15P)
to the stated repeat option; first test report sent 12 hours after command.
0 = disabled; 1 = first; 2 = second; 3 = third; 4 = fourth;
5 = last; 6 = next to last; 7 = third to last
∗∗∗∗79, *80, *81, *82Menu Modes
These are Menu Mode commands, not data fields, for Output Device Mapping,
Output Programming, Zone List Programming, and Alpha Programming
respectively. See page 2 and their respective sections in the Installation and
Setup Guide for procedures.
This option not for use in UL installations.
(assign cross zones on zone list 4, using *81 Menu mode)
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min
1 = 30 seconds 7 = 3 min #+13 = 10 min
2 = 45 seconds 8 = 4 min #+14 = 12 min
3 = 60 seconds 9 = 5 min #+15 = 15 min
4 = 90 seconds #+10 = 6 min 5 = 2 minutes #+11 = 7 min
∗∗∗∗86Cancel Verify Keypad Display [1]
0 = no “alarm canceled” display
1 = display “Alarm Canceled” when system is disarmed after an alarm
has occurred. (To clear the “ALARM CANCELED” display, the
user must enter the security code + OFF again.)
∗∗∗∗87Misc. Fault Delay Time [0]
(used with Configurable Zone Types “digit 6”)
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min
1 = 30 seconds 7 = 3 min #+13 = 10 min
2 = 45 seconds 8 = 4 min #+14 = 12 min
3 = 60 seconds 9 = 5 min #+15 = 15 min
4 = 90 seconds #+10 = 6 min
5 = 2 minutes #+11 = 7 min
UL: may only be used on non-burglar alarm/ non-fire alarm zones
when used in fire and/or UL burglar alarm installation
– 4 –
∗∗∗∗88Program Mode Lockout Options [0]
0 = standard *98 installer code lockout (reentry only by [∗] + [#] within
50 seconds after power up)
1 = lockout [∗] + [#] reentry after *98 exit (reenter via installer code or
downloader only)
2 = not used
3 = lockout local programming after *98 exit (reenter by downloader only)
∗∗∗∗89Event Log Full Report Code [00] |
See box above field *59 for report code entries.
∗∗∗∗90 Event Log Enables [3]
NOTE: System messages are logged when any non-zero entry is made.
“Open/Close”, enter 9 (1 + 8); To select all, enter #15.
∗∗∗∗91Option Selection[8, 0]
Example:
To select “Alarm/Alarm Restore”, and
Options: 0 = NoneOptions V20PSIA/V15PSIA
4 = AAV UL: must use ADEMCO UVCM module Call Wait Disable
8 = Exit Delay Restart/Reset UL: must be disabled
#+12 = AAV and Exit Delay Restart/ResetSIA Guidelines: Exit Delay should be enabled.
V20PSIA/V15PSIA:
Options: Same as listed above.
Call Waiting Disable:
0 = call waiting not used1 = call waiting disable digits (*70) entered in field *40; (when
selected, the system dials the entry in field *40 only on
alternate dial attempts; this allows proper dialing in the event
call waiting service is later canceled by the user).
∗∗∗∗92Phone Line Monitor Enable[0,0]
UL: see Inst. Instructions for requirements 1 2
NOTE: Output Device must either be programmed to be STOPPED in
field ✱80 or STOPPED by Code + # + 8 + output number.
Entry 1:: 0 = disabled, 1-15 = 1 min - 15 min
(#+10 = 10 min; #+11 = 11 min; #+12 = 12 min; #+13 = 13 min; #+14
Entry 2:
0 = Keypad display when line is faulted
1 = Keypad display plus keypad trouble sound
2 = Same as “1”, plus programmed output device STARTS. If either
= 14 min; #+15 = 15 min)
partition is armed, external sounder activates also.
∗∗∗∗93Reports In Armed Period [1,0]
Per Zone(Swinger Suppression)RestrictV20PSIA/V15PSIA
1 = unlimited reports for zones listed in zone list 7; (use zone list 7
to enter those zones that require unlimited reporting; these
zones ignore the setting in entry 1)
DOWNLOAD INFORMATION (✱94, ✱95)
∗∗∗∗94 Download Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits, 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-
second pause. Do not fill unused spaces. If fewer than 20 digits, exit
field by pressing ✱. To clear entries from field, press ✱94✱.
UL: downloading may be performed only if a technician is at the site.
∗∗∗∗95 Ring Count For Downloading [15]
NOTE: Do not enter “0” if using 4285/4286 Phone Module.
0 = Disable Station Initiated Download;
1–14 = number of rings (1–9, # +10 =10, # +11 =11,
# +12 =12, # +13 =13, # +14 =14);
15 = answering machine defeat (# +15 =15).
∗∗∗∗96, ∗
∗97 Initialize/Reset Defaults
∗∗
This is a command, not a data field. See page 2.
∗∗∗∗98, *99 Exit Commands
This is a command, not a data field. See page 2.
PAGER OPTIONS (✱160- ✱172)
∗∗∗∗160 Pager 1 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-sec pause
∗∗∗∗161Pager 1 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
∗∗∗∗162Pager 1 Report Options
[0,0,0]
Part. 1 Part. 2 common
For each partition, select from the following options:
0 = no reports sent
1 = Opens/closes all users
4 = All alarms and troubles
5 = All alarms / troubles, and opens/closes for all users
12 = Alarms / troubles for zones entered in zone list 9
13 = Alarms / troubles for zones entered in zone list 9, and
∗∗∗∗163Pager 2 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = 'Q'; #+12 = '#'; #+13 = 2-sec pause
∗∗∗∗164Pager 2 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
∗∗∗∗165Pager 2 Report Options
[0,0,0]
Part. 1 Part. 2 common
See field *162 for reporting options. Select for each partition (use zone
list 10 if using options 12 or 13).
∗∗∗∗166Pager 3 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-sec pause
∗∗∗∗167Pager 3 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
∗∗∗∗168Pager 3 Report Options
0,0,0]
Part. 1 Part. 2 common
See field *162 for reporting options. Select for each partition (use zone
list 11 if using options 12 or 13).
∗∗∗∗169Pager 4 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-sec pause
∗∗∗∗170Pager 4 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
∗∗∗∗171Pager 4 Report Options
[0,0,0]
Part. 1 Part. 2 common
See field *162 for reporting options. Select for each partition (use zone
list 12 if using options 12 or 13).
∗∗∗∗172Pager Delay Option For Alarms[3]
0 = none; 1 = 1 minute; 2 = 2 minutes; 3 = 3 minutes
This delay is for ALL pagers in the system.
opens/closes for all users
– 5 –
MISCELLANEOUS SYSTEM FIELDS (*174-*181)
∗∗∗∗174Clean Me Reporting Options[0]
(for ESL smoke detectors)
0 = disable; 1 = Clean Me signal reports;
NOTE: If Clean Me is enabled, you must enter “3” in field ✱56
programming for zone 1 response time.
∗∗∗∗177Device Duration 1, 2[0] [0]
(used in *80 Menu mode-Device Actions 5/6) 1 20 = 15 seconds 6 = 2-1/2 min #+11 = 7 min
1 = 30 seconds 7 = 3 min #+12 = 8 min
2 = 45 seconds 8 = 4 min #+13 = 10 min
3 = 60 seconds 9 = 5 min #+14 = 12 min
4 = 90 seconds #+10 = 6 min #+15 = 15 min
5 = 2 minutes
∗∗∗∗181 50/60 Hertz AC Operation[0]
0 = 60 Hz; 1 = 50 Hz
CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)
(see Configurable Zone Type Worksheet on page 7)
∗∗∗∗182Configurable Zone Type 90
1 2 3 4 5 6 7 8 9 10
Enter the appropriate value for each entry, 1-10, based on the charts
provided on the next page. Each entry is the sum of the values of its
Enter the desired 3-digit Contact ID® report codes for alarms and
troubles occurring on zones assigned to this zone type. Enter the
codes sequentially (all 6 digits). When entering digits, [#] moves
cursor back, [∗] moves forward. Press [∗] when done to continue.
∗∗∗∗189AUI Device 1 and 2 Enable[1] [1]
(for Touch Screen Style Keypads)
System supports up to two touch screen style keypads (e.g., Symphony
Advanced User Interface, and 6270 Touch Screen Keypad).
AUI Compatibility Note: To ensure proper AUI device operation,
connect only to controls having microprocessor version 3.0 or higher,
and use AUI devices with the following rev levels: 6270 series use
version 1.0.9 or higher; 8132/8142 (Symphony) series use version
1.1.175 or higher.
Touch Screen (AUI) device 1: Must set AUI device address to 1
Touch Screen (AUI) device 2: Must set AUI device address to 2
VISTA-20P: Enter each touch screen keypad’s home partition
0 = disable; 1 = partition 1; 2 = partition 2; 3 = partition 3 (common)
VISTA-15P: 0 = disable; 1 = enable
NOTE: Use of touch screen style keypads does not affect the number
of standard keypads supported.
AUI 1 AUI 2
– 6 –
Configurable Zone Types Worksheets
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182*185. Configurable zone types 92 and 93 (VISTA-20P only) can only be programmed using the downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for
zone type 91, where each entry represents the sum of the values of the various options shown in the tables below. Use fields
*183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1 (See note 5 for RF zones) ENTRY 2 (See note 5 for RF zones)
Response when system disarmed and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
Shorted
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
Entry 1 = EOL + Open Entry 2 = Short + auto restore + vent zone
Auto
Restore
0 = no
4 = yes
Vent Zone
0 = no
8 = yes
ENTRY 3 (See note 5 for RF zones) ENTRY 4 (See note 5 for RF zones)
Response when armed STAY and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
Shorted
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
Entry 3 = EOL + Open Entry 4 = Short + byp. disarmed + byp. armed
Byp. when
disarmed
0 = no
4 = yes
Byp. when
armed
0 = no
8 = yes
ENTRY 5 (See note 5 for RF zones) ENTRY 6 (See note 5 for RF zones)
Response when armed AWAY and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
Shorted
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
Entry 5 = EOL + Open Entry 6 = Short + dial delay + fault delay
Dial Delay
(see field *50)
0 = no
4 = use delay
Fault Delay
(see field *87)
0 = no
8 = use delay
see note 1
ENTRY 7ENTRY 8
Display Faults Power Reset/
Verification
0 = show alarms
when armed
& disarmed
1 = don’t show
alarms when
armed
alarms, trbles,
faults when
disarmed)
0 = no
4 = power reset
12 = verification
(see zone
(show
after fault
(by code + OFF)
type 16)
3 = never show
any alarms,
trbles, faults
Entry 7 = fault display + power
reset/verification
and keypad
Entry 9 = alarm sounds + bell timeout + fire zone Entry 10 = trouble sounds + chime
Respond as
Fire Zone
0 = no
8 = yes
see zone type
09; see note 4
Trouble
Sounds
0 = none
1 = periodic
beep
2 = trouble
beeps
Chime when
Chime Mode On
0 = no
4 = yes
Entries for Fields *182 and *184
Entry Zone Type 90 Zone Type 91
(field *182) (field *184)
1
2
3
4
5
6
7
8
9
10
To calculate the value for each entry:
Simply add the values of the selected options
in each of the entry’s columns (one option per
column). For example, to program Entry 2 for
“alarm response to short,” “auto restore on,”
but not a “vent zone,” enter 5 (“1” for alarm
short + “4” for auto restore yes + “0” for vent
zone no).
EOL
Zone Conditions Represented
NOTES:
1. Do not use the “fault delay” option with a
configurable zone type if it is set for an
entry or exit delay, otherwise
unpredictable results may occur.
2. To create an interior type zone, select
“respond as interior zone type” (entry 8,
interior type = yes), and set zone
response to “fault” in entries 3-4 to ensure
fault displays; do not set as “normal,”
“alarm,” or “trouble.”
3. Do not set fire zones to respond as a
“fault” (entries 1-6), otherwise faults will
not display unless the [∗] key is pressed.
4. 4219/4229 modules must use EOLRs or
unpredictable results may occur.
5. RF Zones: The “open” option in entries 1,
3, and 5 is not applicable for RF zones.
Use the “intact EOL” option for normal RF
zone conditions and “shorted” for offnormal RF zone conditions.
6. a. Zone-Doubling/Double-Balanced: A
short on either zone of a zone-doubled
pair or on a double-balanced zone
causes a tamper condition.
b. For double-balanced zones, this entry
must be “0.”
c. For zone-doubled zones, both zones
of the doubled pair must be assigned
the same response to a short.
OPENSHORTEDINTACT
in Entries 1-6
ZONE-003-V0
– 7 –
*56 Zone Programming Menu Mode
(press *56 while in Program mode)
The Zone Programming Worksheet is on page 13.
For each of the following prompts, make the desired entry, followed by the [∗] key to accept the entry.
Refer to the Installation and Setup Guide for detailed explanations for each prompt.
SET TO CONFIRM?
0 = no; 1 = yes (See XMIT TO CONFIRM prompt later in this section.) We
recommend that you confirm the programming of every transmitter.
ENTER ZN NUM.
01-64, 91, 92, 95, 96, 99
To quit, enter 00 to quit (returns to data field mode).
SUMMARY SCREEN:
System displays a summary of the entered zone’s current programming.
Press [∗] to continue.
ZONE TYPE
00 = Not used 07 = 24-Hr Audible 20 = Arm–STAY*
01 = Entry/exit #1 08 = 24-Hr Aux 21 = Arm–AWAY*
02 = Entry/exit #2 09 = Fire 22 = Disarm*
03 = Perimeter 10 = Interior w/Delay
04 = Interior Follower 12 = Monitor Zone 24 = Silent Burglary
05 = Trouble Day/Alarm Night 14 = Carbon Monoxide 77 = Keyswitch
06 = 24-Hr Silent 16 = Fire w/Verify 81 = AAV Monitor
Zone
*5800 button-type transmitters only 90-91 = Configurable
23 = No Alarm Resp
PARTITION
1, 2, or 3-common (VISTA-20P)
REPORT CODE
1-9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F
For Contact ID®, enter any non-zero entry as the first digit to enable
reporting for this zone.
To disable the report code for this zone, enter 00.
HARDWIRE TYPE
Appears only for zones 02-08. Zone 1 is automatically set for EOL
operation. Enter the desired hardwire type:
0 = EOL; 1 = NC; 2 = NO; 3 = zone doubling (ZD)†; 4 = double-balanced
(DB)† († VISTA-20P)
RESPONSE TIME
For hardwired zones 01-08. Enter the desired response time for this zone:
0 = 10mSec; 1 = 350mSec; 2 = 700mSec; 3 = 1.2 secs (see field ∗174).
NOTE: If zone doubling is being used, the response time selected for zones
02-08 automatically applies to each zone’s associated doubled zone.
INPUT TYPE
Skipped for zones 2-8, and for zones 10-16 if zone-doubling enabled. Enter
the input type: 2 = AW (Aux wired zone); 3 = RF (supervised RF);
4 = UR (unsupervised RF); 5 = BR (unsupervised button type)
NOTE: To change the input type of a previously programmed wireless
device to a wired zone, you must first delete the transmitter’s serial number.
INPUT S/N
Enroll the transmitter’s serial number and loop number as follows:
1. a. Transmit two open/close sequences (for button-type transmitters,
press and release the button twice, waiting about 4 seconds before
pressing the button the second time).
OR
b. Manually enter the 7-digit serial number printed on the label of the
transmitter. Press the [∗] key to move to the “L” position, then enter
the loop number.
Use the [A] (Advance) and [B] (Back) keys to move the cursor forward
and back within the screen. Pressing the [C] (Copy) key will insert the
previously enrolled serial number, if desired (used when programming
a transmitter with several input loops).
To delete an existing serial number, enter 0 in the loop number
field. The serial number will change to 0's. If 0 was entered in error,
simply re-enter the loop number or press [#], and the serial number
will return to the display.
2. Press [∗] to continue. The system now checks for a duplicate serial/loop
number.
If no duplicate is found, the display shows the serial number and loop
number.
3. Press [∗] to continue to confirmation screen.
(prompts continued in next column)
XMIT TO confirm
Appears if you answered “Yes” at the “Set to Confirm” prompt.
Activate the loop input or button that corresponds to this zone.
Press [∗] to continue.
If the serial/loop number transmitted does not match the serial number
entered, a display showing the entered and the received serial/loop numbers
appears.
If so, activate the loop input or button on the transmitter once again. If a
match is not obtained, press the [#] key twice and then enter (or transmit)
the correct serial number.
Press [∗] to continue
If the serial number transmitted matches the serial number entered,
the keypad will beep 3 times and a summary display will appear,
showing that zone's programming. An “s” indicates that a
transmitter’s serial number has been enrolled.
Press [∗] to accept the zone information and continue.
PROGRAM ALPHA?
Press 1 if you want to program descriptors for the zone now, and refer to the
*82 Descriptor Programming section for procedure. To program descriptors
later, enter 0 (no).
Press [∗] to return to the ENTER ZN NUM prompt.
∗∗∗∗58 Expert Zone Programming Mode
(press ∗∗∗∗58 while in Data Programming mode)
SET TO CONFIRM?
Select whether you want confirmation of wireless device enrollment. (See
“XMIT TO CONFIRM” prompt later in this section.) We recommend that
you confirm the programming of every transmitter.
SUMMARY SCREEN
Zn ZT P RC HW: RT
01 09 1 10 EL 1
(Typical for Zone 1, initial summary screen)
Zn ZT P RC IN: L
10 00 1 10 RF: –
(Typical for entered zone number; zone 10 in this example)
System displays summary of zone 1’s current programming.
Enter the zone number being programmed, then press [∗]. A summary
screen for that zone is displayed, along with any current programming
values, and the cursor moves to the Zone Type location. The cursor then
automatically moves to the next locations after each entry is made.
Special Function Keys:
• [A] (Advance) and [B] (Back) keys on the keypad move the cursor
within the screen.
• [C] (Copy) key will insert the previous zone’s attributes, if desired.
• [D] key starts the Wireless Key Programming Templates menu
(see Wireless Key Programming Templates section that follows this
section).
Sequentially enter Zone Type (ZT), Partition (P)†, and Report Code (RC),
then Hardwire Type (HW) and Response Time (RT) for basic wired zones 1-8
or Input Device Type (IN) for zones 9 and higher (Loop Number [L] is
programmed at the INPUT S/N prompt).
See *56 Zone Programming Menu Mode section described earlier for entry
values.
† applies to VISTA-20P
Press [∗] to save the programming and continue. If needed, press the [#]
key to back up without saving.
• For wireless devices (input types RF, UR, BR), continue to the INPUT
S/N (serial number/loop number) and XMIT TO CONFIRM prompts
described earlier in the *56 Zone Programming Menu Mode section.
When done, the display returns to the initial summary screen prompt to
let you program the next zone.
• For wired devices, the display returns to the initial summary screen
prompt to let you program the next zone.
To Quit, enter 00 at the zone number location and press [∗].
– 8 –
Wireless Key Programming Templates(press the [D] key from *58 Menu mode Summary Screen)
0
This procedure programs the wireless keys, but a key is not active for arming/disarming until it is assigned to a user number (see
System Operation
TEMPLATE ?
Enter desired template number 1–6 (see chart below), then press [∗] to
continue.
To exit the Template screen, press [#]. The system returns to the *58 Menu
mode Summary Screen.
TEMPLATE SUMMARY
L 01 02 03 04
T 23 22 21 23
The selected template is displayed.
The top line represents loop numbers, the bottom line represents each
loop’s zone type.
Press [∗] to accept template and continue.
PARTITION (VISTA-20P)
Enter the partition (1, 2, or 3-common) in which the key is to be active.
Press [∗] to continue.
Wireless Key Predefined Default Templates
For 5804
TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23
2 Disarm 22 2 No Response 23
3 Arm Away 21 3 Arm Away 21
4 No Response 23 4 Disarm 22
TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23
2 Disarm 22 2 Arm Stay 20
3 Arm Away 21 3 Arm Away 21
4 Arm Stay 20 4 Disarm 22
TEMPLATE 3 1 24-hour audible 7 TEMPLATE 6 1 24-hour audible 7
2 Disarm 22 2 Arm Stay 20
3 Arm Away 21 3 Arm Away 21
4 Arm Stay 20 4 Disarm 22
5800 Series Transmitter Input Loop Identification
All of the transmitters illustrated have one or more unique
factory assigned input (loop) ID numbers. Each of the inputs
requires its own programming zone
require four programming zones).
For information on any transmitter not shown, refer to the
instructions accompanying that transmitter for details regarding
loop numbers, etc.
UL NOTE: The following transmitters are not intended for
use in UL installations: 5802MN, 5802MN2, 5804, 5804BD,
5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.
The 5827BD and 5800TM can be used in UL Listed
Residential Burglar installations.
*57 Function Key Programming(press
The Function Key Worksheet is on page 14.
PRESS KEY TO PGM
Press the desired function key to be programmed, A-D, then press [∗] to
continue.
When done, press 0 to exit this mode and return to data field mode.
NOTE: A key programmed as a function key is no longer available to be
used as an end-user macro key or panic key.
PARTITION
Enter the partition (1-3) in which this function key will be active.
KEY "A" FUNC
Enter the desired function for this key:
00 = For the Function key selected, the function will be as follows (default):
If A selected = Zone 95 (emergency key, same as [1] [∗] pair)
If B selected = Zone 99 (emergency key, same as [∗] [#] pair)
If C selected = Zone 96 (emergency key, same as [3] [#] pair)
If D selected = Single-button paging (continued in next column)
section, Assigning Attributes Command in the Installation Instructions).
ENTER START ZONE
The system displays the lowest zone number of the highest available
consecutive 4-zone group.
To start at a different zone number, enter the zone desired, and press [∗]. If
the system has four consecutive zones beginning with that zone, the zone
number is displayed. If not, the system will again display a suggested zone
that can be used.
If the required number of consecutive zones is not available at all, the
system will display “00”.
Press [∗] to accept.
Continue to the INPUT S/N (serial number/loop number) and XMIT TO
CONFIRM prompts described earlier in the *56 Menu Mode section.
IMPORTANT: When confirmed, the key is not active for arming/disarming
until it is assigned to a user number (using the assigning attributes command,
attribute “4”). See System Operation section in Installation Instructions.
When done, the keypad beeps three times and the display returns to the
ENTER START ZONE prompt to let you enter the starting zone for the next
wireless key.
Loop Function Zone Type
(e.g., a 5804's four inputs
∗∗∗∗
57 while in Data Programming mode)
For 5804BD
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
ENROLL AS
"UR" OR "RF"
LOOP 1
ENROLL AS
LOOP 1
ENROLL AS
LOOP 2
(REED)
LOOP 3
(TERMINALS)
ENROLL AS
KEY "A" FUNC (continued)
01 = Single-button paging (sends a 999-9999 message to pager)
02 = Display time
03 = Arm AWAY (reports as User 00 if closing reports are enabled)
04 = Arm STAY (reports as User 00 if closing reports are enabled)
05 = Arm NIGHT-STAY (reports as User 00 if closing reports enabled)
06 = Step Arming (arms STAY, then NIGHT-STAY if enabled, then
07 = Output Device Command (for device programmed as system
08 = Communication Test (sends Contact ID code 601)
09 -12= Macro Keys 1-4 respectively (defined by [#] [6] [6] command)
NOTE: Macros 11-12 apply to VISTA-20P only
Press [∗] to continue; returns to key number prompt with the next function key letter
displayed.
0 = no (standard default); sets the output level normally high
1 = yes; sets the output normally low (can be used for resetting 4-wire
smoke detectors)
[∗] to return to Output Number prompt
OUTPUT TYPE
0 = delete; 1 = relay (skip to “B” prompt); 2 = Powerline Carrier device (skip
to “A” prompt)
[∗] to continue.
“A”(if X-10 was selected)
UNIT No.
Enter the unit code (01-16, set at the device).
[∗] to return to the Output Number prompt continue
“B”(if relay was selected)
MODULE ADDR
Enter the predefined address for this module (07-15; see Table of Device
Addresses on page 2).
Make sure the module’s DIP switches are set to the selected address.
[∗] to continue
REL POSITION(actual relay number on module)
For 4204 modules, relay numbers are 1-4. For 4229 modules, relay
numbers are 1-2.
[∗] to return to the Output Number prompt for programming the next device
∗∗∗∗80 Menu Mode
∗∗∗∗
(press
The Output Definition Worksheet is on page 15.
OUTPUT FUNCT. #
Enter the output function number to be defined (VISTA-20P: 01-48;
VISTA-15P: 01-24)). [∗] to continue; 00 = exit
SUMMARY SCREEN
This screen displays a summary of the current output programming
A = Output Action; E = Triggering event; P = Partition; Trig = Trigger type
Question mark indicates the device shown has not been mapped. Use *79
Menu mode to map the device.
[∗] to continue
ACTIVATED BY
0 = delete (deletes the output function and any previous programming); a
1 = zone list (go to “A” prompt); 2 = zone type (go to “B” prompt); 3 = zone
Press [∗] to continue
“A” (if zone list was selected)
ZN LIST
Enter the desired zone list number (01-08). At the ENTER EVENT prompt,
enter the zone list event that will activate this output (0 = restore; 1 = alarm;
2 = fault; 3= trouble)
Press [∗] to continue and skip to the “Output Action” prompt.
“B” (if zone type was selected)
ENTER ZN TYPE
Enter the desired zone type. See list below *80 Worksheet for zone types.
At the PARTITION prompt, enter the partition in which this zone type will
occur (0 = any partition; 1 = partition 1; 2 = partition 2; 3 = partition 3).
Press [∗] to continue and skip to the “Output Action” prompt.
“C” (if zone number was selected)
ENTER ZN NO.
Enter the desired zone number, then press [∗] to continue. At the ENTER
EVENT prompt, enter the zone event that will activate this output (0 =
restore; 1 = alarm/fault/trouble).
Press [∗] to continue to the OUTPUT ACTION prompt
OUTPUT ACTION
0 = off; 1 = Close for 2 seconds; 2 = Close and Stay Closed; 3 = Continuous
Pulse 1 sec on and 1 sec off
4 = Change Device State; 5 = Duration 1 (see data field *177); 6 = Duration
2 (see data field *177)
Press [∗] to continue.
80 while in Programming mode)
01 A E P Trig
?00 0 0 – ZL=00
confirmation prompt appears.
To delete this output definition, press 1. If you do not want to delete this
output, press 0.
number (go to “C” prompt)
∗∗∗∗80 Menu Mode (continued)
ENTER OUTPUT NO.
Enter the device output number (programmed in *79 Menu Mode) you want
associated with this output.
01-16 = VISTA-20P output no.; 01-08 = VISTA-15P output no.; 17-18 = onboard triggers
Press [∗] to continue.
SUMMARY SCREEN
A summary screen appears showing the programmed settings.
Press [∗] to return to OUTPUT FUNCTION NUMBER prompt.
*81 Menu Mode
(press *81 while in Programming mode)
The Zone List Worksheet is on page 14.
ZONE LIST NO.
Enter the zone list number (01-12) to program (or 00 to exit this mode).
Press [∗] to continue.
ENTER ZN NUM.
Enter each zone number (01-64†) to add to the zone list, followed by
pressing [∗] (example, 01∗, 02∗, 03∗).
Press 00 to continue.
† VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56.
IMPORTANT: Do not include fire zones in zone lists that are used to STOP
device actions.
DEL ZN LIST?
0 = don’t delete list; current zone list remains saved
1 = delete this zone list; All zones in the zone list will be deleted.
[∗] to continue
DELETE ZONE?
0 = don’t delete zones; save the entire zone list and return to the Zone List
No. prompt
1 = go to next prompt to delete zones
[∗] to continue
ZN TO DELETE?
Enter each zone (01-64†) to be deleted from the list, following each with [∗].
00 when done to return to the Zone List No. prompt.
† VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56.
*82 Alpha Descriptor Programming
PRE-DEFINED DESCRIPTORS
PROGRAM ALPHA
0 = no (quit Alpha mode)
1 = yes
Press [∗] or [#] to continue.
CUSTOM WORDS
0 = no (continue to descriptor programming)
1 = yes (go to custom word programming)
Press 0 to program standard alpha descriptors. The system will then display
the descriptor for zone 1.
To program custom words, press 1 (custom words are described later).
Press [∗] to continue.
∗∗∗∗ ZN 01
Descriptor screen for zone 1 appears. To program a descriptor (up to 3
words) for a zone, do the following:
1. Press [∗] plus the desired zone number (existing descriptor, if any, is
displayed), then press [∗] plus the zone number again (flashing cursor
appears).
2. a. Press [#] plus the 3-digit number from the Alpha Vocabulary List on
page 11 for the first word.
b. Press [6] to accept the word and move the cursor for the next word.
3. Repeat steps 2a and 2b for the second and third words (if used).
4. When all words have been entered, press [8] to save the descriptor for
that zone. The flashing cursor disappears.
5. Repeat steps 1-4 to assign a descriptor for the next zone.
6. When all descriptors have been entered, press [∗] + 0 + 0 (or simply
press [#]) after the last descriptor has been saved to return to the
PROGRAM ALPHA? prompt.
Enter 0 (no) at the prompt to exit this mode and return to Data Field mode.
– 10 –
*82 Alpha Descriptor Programming (continued)
ADDING CUSTOM WORDS (up to 10 words)
For custom words, the keys have the following functions:
[4] moves cursor one space to the left.
[6] moves cursor one space to the right.
[8] saves the new word in the system's memory.
1. Select Custom Word mode (enter 1) when the prompt “CUSTOM WORD ?”
is displayed.
2. Enter the number (01–10, or 11, 12, 13 for partition descriptors– see
below) of the custom word or word string to be created, corresponding to
index numbers 245 - 254 respectively. A cursor appears at the beginning
of the second line.
NOTE: Custom words 8, 9, and 10 are “reminder words” that can be
programmed to display using Scheduling Mode.
3. Refer to the Character (ASCII) Chart on the next page.
Press [#], followed by the two-digit entry for the first letter you would like
to display (e.g., # 6 5 for “A”). The cursor moves to the right, in position
for the next character.
To delete a character, simply enter the SPACE character (#32) at the
unwanted character’s location.
4. Repeat Step 3 to create the desired word(s). Each word can be a
maximum of 10 characters (except custom message/partition descriptor
word numbers 11, 12, and 13, which can be a maximum of 16 characters).
5. When the word is complete, press the [8] key to save the custom word(s)
in the vocabulary list and return to the “CUSTOM WORD ?” display.
6. Repeat Steps 1–5 for other custom words to be entered. To change a
custom word, just overwrite it. When all words have been programmed,
enter 0 at the “CUSTOM WORD ?” prompt to return to the Program
Alpha prompt. Enter 0 again to exit Descriptor mode.
To Assign Partition/Custom Message Descriptors, use Adding Custom
Words procedure, but:
VISTA-15P: Use word number 11 in step 2. The custom message replaces
VISTA-20P: Use the following word numbers in step 2:
11 = partition 1; 12 = partition 2; 13 = common lobby
the standard “DISARMED Ready to Arm” message.
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
000
– A –
• 001 AIR
• 002 ALARM
004 ALLEY
005 AMBUSH
• 006 AREA
• 007 APARTMENT
• 009 ATTIC
010 AUDIO
– B –
• 012 BABY
• 013 BACK
• 014 BAR
• 016 BASEMENT
• 017 BATHROOM
• 018 BED
• 019 BEDROOM
020 BELL
• 021 BLOWER
• 022 BOILER
023 BOTTOM
025 BREAK
• 026 BUILDING
– C –
028 CABINET
•029 CALL
030 CAMERA
031 CAR
033 CASH
034 CCTV
035 CEILING
036 CELLAR
• 037 CENTRAL
038 CIRCUIT
• 040 CLOSED
• 046 COMPUTER
047 CONTACT
– D –
• 048 DAUGHTERS
049 DELAYED
• 050 DEN
051 DESK
• 052 DETECTOR
• 053 DINING
054 DISCRIMINATOR
055 DISPLAY
Note: Bulleted (•) words in boldface type are those that are also available for use by the 4285/4286 Phone Module. If using a Phone
– V –
209 VALVE
210 VAULT
212 VOLTAGE
– W –
213 WALL
214 WAREHOUSE
• 216 WEST
• 217 WINDOW
• 219 WING
220 WIRELESS
– X –
222 XMITTER
– Y –
223 YARD
– Z –
224 ZONE (No.)
• 225 ZONE
• 226 0
• 227 1
• 228 1ST
• 229 2
• 230 2ND
• 231 3
• 232 3RD
• 233 4
• 234 4TH
• 235 5
• 236 5TH
• 237 6
∗∗∗∗
• 238 6TH
• 239 7
• 240 7TH
• 241 8
• 242 8TH
• 243 9
• 244 9TH
245 Custom Word #1
246 Custom Word #2
247 Custom Word #3
248 Custom Word #4
249 Custom Word #5
250 Custom Word #6
251 Custom Word #7
252 Custom Word #8
253 Custom Word #9
254 Custom Word #10
module, and words other than these are selected for Alpha descriptors, the module will not provide annunciation of those words.
00 = clear event
01 = Relay On/Off
02 = User Access
03 = Latch Key Report to Pager (sent to all pagers in the user’s partition;
message sent is 777-7777. User must be enabled for paging and
system must be armed before reporting can occur.)
04 = Forced Stay Arming
regardless of setting in field *23)
05 = Forced Away Arming
regardless of setting in field *23)
06 = Auto Disarm
07 = Display “Reminder”
10 = Display custom words (if selected, system displays custom words 8, 9,
and 10 at defined time. Can be used as installer’s reminder message
to the end user); programmable by installer only
11 = Periodic Test Report (see key commands in Test Report Code, data
field *64, to quickly set periodic test reporting intervals); programmable
by installer only
[∗] to continue.
(
Forced bypass is automatically enabled
(
Forced bypass is automatically enabled
DEVICE NUMBER (for event 1 relay on/off)
01-18; [∗] to continue.
GROUP NUMBER ( for event 2 user access)
1-8; [∗] to continue.
PARTITION (for events 3-7,10,12)
0 = all partitions; 1 = partition 1; 2 = partition 2; 3 = common
[∗] to continue.
START
01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM; to select days, position the
cursor under the desired days using the [∗] key to move forward, then press
“1” to select the day.
[∗] to continue.
0 = do not repeat; 1 = repeat schedule weekly; 2 = repeat schedule biweekly
(every other week); 3 = repeat schedule every third week; 4 = repeat
schedule every fourth week
[∗] to continue
RANDOMIZE(for events 01 and 11)
0 = no; 1 = yes
If selected, the scheduled start and stop times will vary within 60 minutes of
the “hour” time. For example, if a schedule is set to start at 6:15pm, it will do
so the first time 6:15pm arrives, but on subsequent days it will start anytime
between 6:00 and 6:59 p.m.
NOTE: Do not use the random option if the start and stop times are within
the same “hour” setting, otherwise unpredictable results may occur (e.g., the
randomized stop time may occur before the start time).
[∗] to continue and return to ENTER SCHED NO. prompt to program the
01 Paging
02 Time Display
03 Arm AWAY
04 Arm STAY
05 Arm NIGHT-STAY
06 Step Arming
07 Device Activation Device:
08 Comm. Test
09 Macro Key 1 Assign each macro key to only a single partition.†
10 Macro Key 2 Assign each macro key to only a single partition. †
11 Macro Key 3 Assign each macro key to only a single partition. †
12 Macro Key 4 Assign each macro key to only a single partition. †
00 Emergency Keys: zone 95 zone 99 zone 96 paging
Personal Emergency n/a
Silent Alarm n/a
Audible Alarm n/a
Fire n/a
Emergency Keys: A = paired keys [1] / [∗] (zone 95); B = paired keys [∗] / [#] (zone 99); C = paired keys [3] / [#] (zone 96)
† There are only four macros system-wide.
A
P1 P2 com B P1 P2 comC P1 P2 comD P1 P2 com
Comments
OUTPUT RELAYS/POWERLINE CARRIER (X-10) DEVICES WORKSHEET FOR ∗∗∗∗79, ∗∗∗∗80 and ∗∗∗∗81.
Applicable only if Relays and/or Powerline Carrier Devices are to be used.
∗∗∗∗79 RELAY/POWERLINE CARRIER (X-10) DEVICE MAPPING (Must program before using *80)
OUTPUT TYPE
Relay X10
Output
No.
01
02
03
04
05
06
07
08
✱
81 ZONE LISTS WORKSHEET
Module
Addr.
Pos
(1-4)
Unit
Description
No.
Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the
data during the displays and prompts that appear in sequence.
NOTE: Record desired zone numbers below, noting that a list may include
List No. Used For…Contains These Zones…
01 General Purpose (GP)
02 General Purpose
03 Chime-by-Zone or GP (see field *26 for Chime-by-Zone option)
04 Cross Zones or GP (see field *85 for Cross Zone Timer option)
05 Night-Stay Zones or GP
06 Dial Delay Disable or GP V20PSIA/V15PSIA: see field *50 for Dial Delay Disable option
07 Unlimited Reports or GP V20PSIA/V15PSIA: see field *93 for Unlimited Reports option
08 General Purpose
09 Zones activating pager 1
10 Zones activating pager 2
11 Zones activating pager 3 (VISTA-20P)
12 Zones activating pager 4 (VISTA-20P)
OUTPUT TYPE (09-16 apply to VISTA-20P only)
Relay X10
Output
Module
No.
Addr.
09
10
11
12
13
14
15
16
On-Board Trigger 1 norm output =
17
On-Board Trigger 2 norm output =
18
Pos
(1-4)
any
or
Unit
Description
No.
all
of system's zone numbers.
– 14 –
✱
80OUTPUT DEFINITIONS
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you
enter the data during the displays and prompts that appear in sequence.
1. For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
Notes:
2. For Powerline Carrier devices (plcd), field
✱
27 must be programmed with a House Code.
3. Tampers of expansion units cannot be used to operate devices.
Function
Number
(V20P=1-48)
(V15P=1-24)
ZONE TYPE/SYSTEM OPERATION – Choices for Zone Types are:
00 = Not Used 05 = Trouble Day/Alarm Night 10 = Interior w/Delay 24 = Silent Burglary
01 = Entry/Exit#1 06 = 24 Hr Silent 12 = Monitor Zone 77 = Keyswitch
02 = Entry/Exit#2 07 = 24 Hr Audible 14 = Carbon Monoxide 81 = AAV Monitor Zone
03 = Perimeter 08 = 24 Hr Aux 16 = Fire w/Verification 90-91 = Configurable
04 = Interior Follower 09 = Fire 23 = No Alarm Response
Choices for System Operation are:20 = Arming–Stay 38 = Chime 52 = Kissoff 21 = Arming–Away 39 = Any Fire Alarm 54 = Fire Zone Reset 22 = Disarming (Code + OFF) 40 = Bypassing 58 = Duress
31 = End of Exit Time 41 = **AC Power Failure 60 = AAV Trigger 32 = Start of Entry Time 42 = **System Battery Low 66 = Function key† 33 = Any Burglary Alarm 43 = Communication Failure 67 = Bell Failure
36 = **At Bell Timeout***68 = TELCO Line Fault78 = Keyswitch red LED††† 79 = Keyswitch green LED†††
Activated by
0=delete
1=zn list
2=zn type
3=zn no.
Activation Type and Detail Event (for zone list/activated by)Output
Zone List
1-8 = list
(ZL)
Zone Type
(ZT)
(see table
below)
Zone No.
(ZN)
00=none
V20P: 01-64
V15P: 01-06,
09-34, 49-56
Partition
Number
(P)
(if using ZT trig)
0 = any
1 = partition 1
2 = partition 2
3 = common
By Zone List
0 = restore
1 = alarm
2 = fault
3 = trouble
Action
By Zone No.
0 = restore
1 = alrm/flt/trbl
** Use 0 (any) for Partition No. (P) entry.
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu mode to assign the function key.
†† Duration is set in program field *177.
††† Device action not used for these choices.