Pentax 7100 Installation Manual

0 (0)
7100 Series Fire Alarm Control
Document: 9000-0447 Print Date: 6/6/07 Rev. I
P/N 9000-0447 Rev. I ECN: 06-528
Copyright © 1998
Honeywell International Inc.
All Rights Reserved
Published in U.S.A.
12 Clintonville Road, Northford, CT 06472-1610 USA • TEL: (203) 484-7161 • FAX: (203) 484-7118
www.gamewell-fci.com
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
This manual is designed for use by factory­trained installers and operators of the Gamewell­FCI, 7100 Series, Fire Alarm Control. All illustrations, functional descriptions, operating and installation procedures, and other relevant information are contained in this manual. The contents of this manual are important, and the manual must be kept with the fire alarm control panel at all times. If building ownership is changed, this manual, including any testing and maintenance information, must be passed along to the new owner(s). The fire alarm control panel is part of a system. Manuals and instructions for other devices forming part of the system should be kept together. Purchasers who install this system for use by others must leave the instructions with the user. A copy of these instructions is included with each product and is available from the manufacturer. This equipment is Listed by various listing agencies for use in fire alarm systems. Use only components which are compatible with the Gamewell-FCI System. The installation MUST be in accordance with the instructions in this manual. THEREFORE:
DO NOT deviate from the procedures described in this manual.
DO NOT assume any details not shown in the instructions.
DO NOT modify any electrical or mechanical features.
DO comply with all codes and standards set forth by the Authority Having Jurisdiction.
The term “Authority Having Jurisdiction” has become a standard term in the fire alarm industry. An acceptable definition of “Authority Having Jurisdiction” is: Fire alarm systems installed in the USA fall under the jurisdiction of some authority. In some areas this may be a local fire department; in other areas it may be a building inspector, insurance firm, etc. Different authorities may have their own local requirements for the way the fire alarm system is installed and used. Most local authorities base their requirements on the National Fire Protection Agency (NFPA) codes, but there may be important differences. You must install this system in the way in which the Authority Having Jurisdiction requires. If you do not know which authority has jurisdiction in your area, contact your local fire department or building inspector for guidance. It is important that you tell users to be aware of any requirements defined by the Authority Having Jurisdiction.
E3 Series is a trademark of Honeywell International Inc.
The installation MUST be in accordance with the following standards:
National Fire Alarm Code (NFPA 72)
National Electrical Code (NFPA 70)
Life Safety Code (NFPA 101)
NFPA 92A – Recommended Practice for
Smoke Control Systems
WARNING: Touching components which are improperly installed, applied or operated could be hazardous and possibly fatal. Short circuits could cause arcing that could result in molten metal injuries. Therefore, only qualified technicians familiar with electrical hazards should perform checkout procedures. Safety glasses should be worn, and test equipment used for voltage measurements should be designed for this purpose and be in good working order.
ENVIRONMENTAL CONSIDERATIONS:
It is important that this equipment be operated within its specifications:
Recommended operating temperature range:
Absolute maximum operating temperature range:
Operating humidity:
Operating this equipment within the recommended temperature range will extend the useful life of the system standby batteries.
INSTALLATION CONSIDERATIONS:
Check that you have all of the equipment you need to make the installation. Follow the field wiring diagrams and installation notes in this manual. Install the equipment in a clean, dry environment (minimal dust). Avoid installing equipment where vibrations will occur. Remove all electronic assemblies prior to drilling, filing, reaming, or punching the enclosure. When possible, make all cable entries from the sides; being careful to separate the power-limited conductors from the non power-limited conductors. Before making modifications, verify that they will not interfere with battery, transformer and printed circuit board location. Do not over-tighten screw terminals. Over­tightening may damage threads, resulting in
9000-0447 Rev. I
i
60° to 80° F (15° to 27° C) 32° to 120° F (0° to 49° C)
Not to exceed 93% Non-condensing at 90° F (32° C)
reduced terminal contact pressure and difficulty with screw terminal removal. Disconnect all sources of power before servicing, removing, or inserting any circuit boards. Control unit and associated equipment may be damaged by removing and/or inserting cards, sub-assemblies, or interconnecting cables while the unit is energized
WIRING CONSIDERATIONS:
This fire alarm control panel contains power­limited circuits. You cannot connect external sources of power to these circuits without invalidating their approval. Verify that wire sizes are adequate for all initiating device and notification appliance circuits. Most devices cannot tolerate more than a 10% drop from the specified device voltage. The installer must make sure that the wiring and devices installed in the system meet the current National Electrical Code, NFPA 70, and all applicable state and local building code requirements. Use the conductor size and type required by local codes. (See NFPA 70, Article 760). Wiring resistance must not be more than that shown on the field wiring diagrams. To reduce errors and help in servicing the system, all conductors should be tagged or otherwise coded and logged at installation to identify circuit assignment and polarity. If the conductors are logged with a code, keep the log that explains the code with the manual, so that it is available to other people working on the panel. Like all solid state electronic devices, this system may operate erratically or be damaged when subjected to lightening induced transients. Although no system is completely immune to lightening transients and interference, proper grounding will reduce susceptibility. We do not recommend the use of overhead or outside aerial wiring due to the increased susceptibility to nearby lightening strikes. Consult with the Gamewell-FCI Technical Support Department if any problems are anticipated or encountered. To prevent the spread of fire, use proper patching materials to areas where system wiring passes through the fire-rated walls or floors.
SURVIVABILITY:
Per the National Fire Alarm Code, NFPA 72, all circuits necessary for the operation of the notification appliances shall be protected until they enter the evacuation signaling zone that they serve. Any of the following methods shall be considered acceptable as meeting these requirements:
1) A 2-hour rated cable or cable system
2) A 2-hour rated enclosure
3) Performance alternatives approved by
.
Authority Having Jurisdiction
MAINTENANCE:
To keep your fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA Standards, and applicable state and local codes. At a minimum, the requirements of Chapter 7 of NFPA, the National Fire Alarm Code, shall be followed. A preventative maintenance agreement should be arranged through the manufacturer’s local representative. Though smoke detectors are designed for long life, they may fail at any time. Any smoke detector, fire alarm system, or any component of that system shall be repaired or replaced immediately.
OTHER CONSIDERATIONS:
The equipment was tested according to EC directive 89/336/EEC for Class A equipment and was verified to the limits and methods of EN
55022. An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association NFPA Standard 72, manufacturer’s recommendations, State and local codes. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not into alarm in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
9000-0447 Rev. I
ii
Smoke particles may be blown away from detectors by air outlets.
Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photo-electronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the
9000-0447 Rev. I
iii
signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals. In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 -2002-1999 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, a fire alarm system is not a substitute for insurance. Property owners should continue to act prudently in protecting the premises and the people in the premises and should properly insure life and property and buy sufficient amounts of liability insurance to meet their needs.
Limit-C-9-2005
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power
before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system
operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment Listed for service with this control panel.
This system meets Underwriter’s Laboratories requirements for operation at 0-49º C/32-120º F and at a relative humidity (non condensing) of 85% at 30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C (89.6°F ± 1.1°F) per UL 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all
initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightening induced transients. Although no system is completely immune from lightening transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightening strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in­lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau -D1-9 -2005
FCC Warning: This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for Class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at the user’s expense. If these instructions are not clear, or if additional information or clarification is needed, please consult your local authorized Gamewell-FCI distributor. Because of design changes and product improvements, the information in this manual is subject to change without notice. Gamewell-FCI reserves the right to change hardware and/or software design, which may subsequently affect the contents of this manual. Gamewell-FCI assumes no responsibility for any errors that may appear in this manual. Neither this manual nor any part of it may be reproduced without the advance written permission of Gamewell-FCI.
9000-0447 Rev. I
iv
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
Product name and version number (if applicable)
Printed manual or online Help
Topic Title (for online Help)
Page number (for printed manual)
Brief description of content you think should be improved or corrected
Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
9000-0447 Rev. I
v
TABLE OF CONTENTS
1.0
System Overview................................................................................................................ 4
1.1 Description ........................................................................................................................ 4
1.2 Features ............................................................................................................................ 4
1.2.1 Standard Features ..................................................................................................... 4
1.2.2 Optional Features ...................................................................................................... 5
1.3 Control and Indicators ....................................................................................................... 5
1.3.1 Switch Controls .......................................................................................................... 5
1.3.2 LED Indicators ........................................................................................................... 5
1.3.3 Audible Sounder ........................................................................................................ 5
1.4 Optional Modules .............................................................................................................. 5
1.4.1 Digital Alarm Communicator (DACT)......................................................................... 5
1.4.2 Class A Option Module (CAOM)................................................................................ 5
1.4.3 Municipal Circuit Option Module (MCOM) ................................................................. 6
1.4.4 Printer Transient Module (PTRM).............................................................................. 6
1.4.5 LCD-7100 Remote Serial Annunciator Module ......................................................... 6
1.4.6 LDM-7100 Remote LED Driver Module ..................................................................... 6
1.4.7 INI-7100-UTP, Intelligent Network Interface, Unshielded, Twisted-Pair.................... 6
1.4.8 INI-7100-FO, Intelligent Network Interface, Fiber-Optic ............................................ 6
1.5 Specifications .................................................................................................................... 6
2.0 Installation........................................................................................................................... 9
2.1 General.............................................................................................................................. 9
3.0 Basic System Module (BSM)............................................................................................ 11
Table 3-1 Field Wiring Connections...................................................................................... 11
Table 3-2 LEDs Jumpers ...................................................................................................... 12
3.1 Power .............................................................................................................................. 12
3.1.1 AC Input ................................................................................................................... 12
3.1.2 Battery Connections................................................................................................. 12
3.1.3 Auxiliary Power Output, Resettable/Non-resettable (Special Application) .............. 12
3.1.4 Earth Ground Connection ........................................................................................ 12
3.2 Relay Connections .......................................................................................................... 13
Table 3-3 Battery Standby Chart .......................................................................................... 14
3.3 Notification Appliance Circuits......................................................................................... 15
3.4 Signaling Line Circuits..................................................................................................... 15
3.4.1 Style 7 Signaling Line Circuit Installation................................................................. 16
3.5 Analog Sensors ............................................................................................................... 17
3.5.1 Address Switches .................................................................................................... 17
3.5.2 Drift Compensation .................................................................................................. 17
3.6 Addressable Modules...................................................................................................... 17
3.6.1 Address Switches .................................................................................................... 17
3.7 Deleted. ........................................................................................................................... 17
3.8 Deleted. ........................................................................................................................... 17
3.9 Optional Modules ............................................................................................................ 18
3.9.1 Class A Option Module (CAOM).............................................................................. 18
3.9.2 Municipal Circuit Option Module (MCOM) ............................................................... 18
3.9.3 Printer Transient Module (PTRM)............................................................................ 18
Table 3-4 Optional Module Wiring Connections ................................................................... 18
3.10 Digital Communicator Operation (7100-D Model) ................................................... 19
3.11 Central Station Reporting ........................................................................................ 19
Table 3-5 UL Listed Receivers Compatible with the 7100.................................................... 19
3.12 7100-D DACT Event Reporting Codes .................................................................... 20
Table 3-6 DACT-E3 Event Reporting Codes ........................................................................ 20
3.13 Telephone Requirements ........................................................................................ 21
3.14 Digital Communicator............................................................................................... 21
3.15 Telephone Company Rights and Warnings ............................................................. 21
9000-0447 Rev. I
Page 1 of 42
3.16 FCC Required Information ....................................................................................... 21
3.17 Repairs..................................................................................................................... 21
3.18 Optional Accessories ............................................................................................... 22
3.18.1 LCD-7100 Serial Remote Annunciator ................................................................ 22
Table 3-7 Resistance Limitations.......................................................................................... 22
3.18.2 LDM-7100 LED Driver Module ............................................................................ 22
Table 3-8 Resistance Limitations.......................................................................................... 22
4.0 Programming/Operation Instructions................................................................................ 23
4.1 LED Indicators................................................................................................................. 23
Table 4-1 LED Indicators ...................................................................................................... 23
4.2 Panel Switches................................................................................................................ 24
Table 4-2 Switches ............................................................................................................... 24
5.0 System Programming ....................................................................................................... 25
5.1 MAIN Menu Selections.................................................................................................... 25
5.1.1 Addresses/Default settings after Autoconfiguration................................................. 25
5.2 CONFIG. Menu Selections.............................................................................................. 27
Table 5-1 7100 Series Menu System ................................................................................... 28
Table 5-2 Sensor Sensitivity Settings ................................................................................... 29
5.3 WALK / DRILL Menu Selections ..................................................................................... 34
5.4 I/O Menu Selections ........................................................................................................ 34
5.5 CLOCK Menu Selections ................................................................................................ 36
5.6 LOG Menu Selections ..................................................................................................... 38
5.7 INFO Menu Selection ...................................................................................................... 38
6.0 Power Up Procedure ........................................................................................................ 40
6.1 General............................................................................................................................ 40
6.2 To set the system time (Keyswitch must be engaged). .................................................. 40
6.3 Automatic Configuration.................................................................................................. 40
Table 6-1 7100 Series Device Types and Functions............................................................ 41
Figure 11 Power-Limited/Non Power-Limited Wiring............................................................ 42
9000-0447 Rev. I
Page 2 of 42
Figure 1 Basic System Module (BSM)
9000-0447 Rev. I
Page 3 of 42
1.0 System Overview
1.1 Description
The Gamewell-FCI 7100 is a multiprocessor-based analog/addressable system, de­signed for commercial, industrial and institutional fire alarm applications. It is available with either one or two signaling line circuits. The 7100 Series is Listed by Underwriter’s Laboratories, Standard UL 864, 9th Edition. It is suitable for the following signaling services:
Automatic Fire Detector Alarm
Manual Fire Alarm
Waterflow Alarm
Supervisory
Automatic Smoke Alarm, non-coded and master coded operation
Releasing Device Service
The 7100 Series complies with the requirements of the following National Fire Protection Association (NFPA) Standards:
NFPA 13 - Installation of Sprinkler Systems
NFPA 16 - Deluge Foam-Water Sprinkler Systems
NFPA 72 - National Fire Alarm Code:
- Central Station Fire Alarm Systems
- Local Fire Alarm Systems
- Auxiliary Fire Alarm Systems
- Remote Station Fire Alarm Systems
- Proprietary Fire Alarm Systems
1.2 Features
1.2.1 Standard Features
Two (2) Class B, Style 4 Signaling Line Circuits
Two (2) Class B, Style Y Notification Appliance Circuits
Alarm and Trouble dry contacts
Accommodates 99 Gamewell-FCI Approved, UL Listed compatible analog
sensors per SLC
Accommodates 98 Gamewell-FCI Approved, UL Listed compatible addressable monitor/control devices per SLC
80-character alphanumeric LCD display
280 event history buffer (non-volatile)
Power-limited
Resettable/Non-resettable 1.0 amp. @ 24 VDC power output, FWR
Alarm verification
Walk test
Multi-level alarm processing
Positive alarm Sequence (PAS) operation
NAC coding
Trouble reminder
Integral RS-232 port
Key Switch - keyed alike with the door lock and renders the key pad
inoperative until activated.
9000-0447 Rev. I
Page 4 of 42
1.2.2 Optional Features
g
Class A Module (CAOM) with Disconnect Switches for NACs and SLCs
Digital Alarm Communicator (DACT) (Model 7100-D)
RS-232 Printer Transient Module (PTRM), Supervised
Municipal Circuit Option Module (MCOM)
1.3 Control and Indicators
1.3.1 Switch Controls
Alarm Acknowledge
Trouble Acknowledge
Signal Silence
System Reset/Lamp test
Programming buttons
- Menu/Back
- Back Space/Edit
- OK
1.3.2 LED Indicators
12 button keypad
AC Power On
Alarm
Supervisory
System Trouble
Power Fault
Fi
(green) (red) (yellow) (yellow)
Ground Fault
NAC 1 Silenced
NAC 2 Silenced
System Silenced
(yellow) (yellow) (yellow) (yellow)
(yellow)
ure 2
1.3.3 Audible Sounder
An Alarm/Trouble sounder is located on the Basic System Module (BSM).
1.4 Optional Modules
The following optional modules and features are available:
1.4.1 Digital Alarm Communicator (DACT)
The Model 7100-D provides an integral digital communicator (DACT), fully programmable from the keypad, which is compatible with Digital Alarm Receivers (DACRs) that can receive the following formats:
SIA DC8
SIA DCS20
Ademco Contact ID
3+1 1400 Hz
3+1 2300 Hz
4+2 1400 Hz
4+2 2300 Hz
1.4.2 Class A Option Module (CAOM)
All 7100 Models are supplied with Class B Notification Appliance Circuits and Class B Signaling Line Circuits. For Class A operation, the addition of a CAOM Module is required. This module operates with all 7100 Models and enables the signaling line circuits to operate as Class A, Style 6 or 7 and notification appliance circuits to operate as Class A, Style Z. It supplies the additional terminals for these circuits.
9000-0447 Rev. I
Page 5 of 42
1.4.3 Municipal Circuit Option Module (MCOM)
The MCOM Module can trip a Local Energy City Master Box, or operate in reverse polarity mode for leased line connection. It can also energize a solenoid for releasing.
1.4.4 Printer Transient Module (PTRM)
The serial output on the BSM is connected via an existing RS-232 RJ-11 connector, J3. This can be used to communicate to the control with a laptop computer while at the panel. The PTRM module is intended for systems where a permanent connection is required. This type of connection requires that the RS­232 port have sufficient transient protection to comply with the applicable codes for wiring leaving the confines of the control box, as well as the proper isolation of the signal to prevent damage or interference caused by the connection to certain EDP devices. Connections are limited to the same room. The PTRM supplies supervision and transient protection as well as the necessary isolation.
1.4.5 LCD-7100 Remote Serial Annunciator Module
The LCD-7100 Serial Remote Annunciator provides an 80-character display and function keys for “Alarm Acknowledge”, “Trouble Acknowledge”, “Signal Silence”, “System Reset/Lamp Test” and “System Drill Test”. The 80-character display shows all pertinent information except for menus.
1.4.6 LDM-7100 Remote LED Driver Module
Each LDM-7100 LED Driver Module provides 7100 Control Panel output for thirty-three (33) remote LEDs. Three (3), LDM-7100 modules may be mounted in a single annunciator for a maximum total of 99 points per annunciator. The annunciator may be located up to 4,000 feet from the panel and up to four (4), additional annunciators can be connected, configured identically with the first.
1.4.7 INI-7100-UTP, Intelligent Network Interface, Unshielded, Twisted-Pair
E3 Broadband terminations only. It occupies one node on the E3 Series
1.4.8 INI-7100-FO, Intelligent Network Interface, Fiber-Optic
E3 Broadband Network interface connection to the 7100 FACP using either fiber­optic cable or copper wire network terminations. It occupies one node on the E3 Broadband Network.
Note: The Network Graphic Annunciator Module (NGA) is required when more than seven (7), 7100 Series panels are networked. See the E3 Broadband Installation/Operating Manual Part Number: 9000-0575 for details.
1.5 Specifications
Power Supply Output
Supervisory current 1.0 amp. (max.) (24 VDC nominal) Alarm current 3.335 amp. (max.) (24 VDC nominal)
9000-0447 Rev. I
Network interface to the 7100 FACP using copper wire network
Broadband Network.
OR
Page 6 of 42
Notification Appliance Circuits (TB1)
Two (2) regulated power outputs
Power-limited
Supervised
Non-coded
Max. alarm load 1.5 amp. /circuit
Special application: See Compatibility Addendum/ P/N 9000-0427 for a list of Gamewell-FCI Approved, UL Listed notification appliances.
Use U.L. Listed End of Line Resistor EOL-N (47K), P/N 4700-0512
Alarm Dry Contacts (TB2)
Form “C”
Rated 2 amp. @ 30 VDC Resistive
Alarm signals latch in. Supervisory and System Trouble signals do not latch in.
Trouble Dry Contacts (TB2)
Form “C”
Rated 2 amp. @ 30 VDC Resistive
Transfer Relay Control (TB2) (Special Application)
Transmit loss of AC power or brown out to Gamewell-FCI Model DRBC-1 battery charger.
Power-limited
Unsupervised
Signaling Line Circuits (TB3)
One (1) or two (2) Class “B”, Style 4 circuits
24 VDC nominal
Power-limited
Supervised
40 Ohm max. line resistance
0.5 µf max. capacitance
Capacity of 99 analog sensors and 98 addressable devices per circuit
Earth Ground Connection (TB4)
AC Input (TB6)
120/240 VAC, 50/60 Hz, 2 amp. @ 120 VAC, 1 amp. @ 240 VAC
Non-power-limited
9000-0447 Rev. I
NOTICE: Terminal TB4 must be connected to an earth ground connection per Article 760 of the National Electrical Code. Failure to make a proper earth ground connection to a metallic cold water pipe or driven ground rod to this terminal will result in loss of lightening protection, reduce the tolerance of the system to transients, and will adversely affect the operation of the system. Panel neutral or conduit ground is not acceptable; minimum wire size is 14 AWG.
24 VDC external power, system (TB4) (Special Application)
Unregulated, FWR
Resettable and non-resettable
1.0 amp. max. each circuit, 1.0 amp. max. combined
Unsupervised
Page 7 of 42
Battery Connection (TB7)
Supervised
24 VDC nominal
Maximum battery size 31 AH
Non-power-limited
0.6 A max. battery charge current
The RS-232 port, consists of an RJ11 connector which provides a standard serial port for the connection to a Listed output device for supplementary type service. Typical examples of such devices include any UL Listed EDP device (remote printer or video terminal), any UL Listed Signaling Device (such as the Keltron VS4095/5 printer), or any UL Listed Signal System Unit. Ratings: 15 VDC (max.)
.05 amp. (max.) current 9600 baud 8 bits, 1 stop bit, no parity.
Connections to the RJ11 serial connector are as follows:
Terminal Description
2 RXD 3, 4 GND 5 TXD 6 Supervision
Available cables for RS-232 connection are:
Part No. Model Description
6100-0077 RJ11-DB9PC RJ11 to 9-pin DB9
6100-0074 RJ11-DB25 RJ11 to 25-pin (DB25) (connector only-printer) 6100-0075 RJ11C-6 RJ11 to RJ11 cable, 6-inches 6100-0076 RJ11C-20 RJ11 to RJ11 cable, 20 feet NOTE: The BSM is shipped with jumpers installed on the middle three pairs of pins on J2. These jumpers must be removed when the PTRM is installed.
9000-0447 Rev. I
(Connector only - PC Laptop)
Figure 4
Page 8 of 42
1 2 3 4 5 6
Figure 3
2.0 Installation
2.1 General
Components are ordered and shipped in separate packaging for the enclosure and Basic System Module kit. The 7100 is intended for installation indoors, in a dry location. The shipping carton contains an installation drawing, backbox, Basic System Module (BSM), power transformer and door.
1) Refer to the System Assembly Drawing, P/N 9000-0457.
2) The BSM module consists of a main operating board with pluggable terminal strips, an 80-character LCD display and programming keypad. Install this module immediately unless any optional modules are to be used in the system. The optional modules are supplied separately, and should be installed on the BSM before it is mounted in the backbox. Before installing the BSM into the system backbox, refer to the installation instruction sheets shipped with each module for the proper installation procedures.
3) Install the transformer into the backbox. Connect the transformer to the BSM.
4) Install the door after the BSM is in place. Note that the door can only be installed (or removed) when it is opened at least 90° from the backbox.
9000-0447 Rev. I
Page 9 of 42
Loading...
+ 35 hidden pages