Before installing this product, read and follow all warning notices and instructions accompanying
this filter. Failure to follow safety warnings and instructions can result in severe injury, death, or
property damage. Call (800) 831-7133 for additional free copies of these instructions.
SECTION I. FILTER INSTALLATION
1. The filter should be mounted on a level concrete slab.
Position the filter so that the instructions, warnings
and pressure gauge are visible to the operator. Also,
position the filter so that the piping connections,
control valve and drain port are convenient and
accessible for servicing and winterizing.
Figure 1.
Pentair Pool Products
1620 Hawkins Ave., Sanford, NC 27330 • (919) 774-4151
10951 West Los Angeles Ave., Moorpark, CA 93021 • (805) 523-2400
REV. D 6-8-011P/N 98725500
2. Install electrical controls (e.g., on/off switches, timers control systems, etc.) at least five (5) feet
from the filter. This will allow you enough room to stand clear of the filter during system start
up.
3. Provide sufficient clearance around the filter to permit visual verification that the clamp is
properly installed, see Figure 1.
4. Provide sufficient space above the filter to remove the filter lid or control valve for cleaning and
servicing. This distance will vary with the model of filter you are using. See Table 1 for the
required vertical clearance.
WARNING
Risk of electrical shock or electrocution. Position the filter and High Flow™ manual air
relief valve to safely direct water drainage and purged air or water. Water discharged
from an improperly positioned filter or valve can create an electrical hazard that can
cause severe personal injury as well as damage property.
TABLE 1
ModelSizeVertical Clearance Req.
5640860044 GPM36 in.
5640870066 GPM46 in.
5640880088 GPM68 in.
5. When installing the High Flow™ manual air relief valve use the O-ring only, there is no need for
thread sealing compounds. Position the filter to safely direct water drainage. Rotate the High
Flow™ manual air relief valve to safely direct purged air or water. Water discharged from an
improperly positioned filter or valve can create an electrical hazard as well as damage property.
6.Make all plumbing connections in accordance with local plumbing and building codes. Filter
plumbing connections are provided with an O-ring seal. Use only a silicone base lubricant on the
O-rings. Do not use pipe joint compound, glue or solvent on the bulkhead connections.
7.The base of this filter is provided with two (2) mounting bosses for the purpose of anchoring the
filter to the concrete.
8.The maximum working pressure of this filter is 50 psi. Never subject this filter to pressure in
excess of this amount, even when conducting hydrostatic pressure tests. Pressures above 50 psi
can cause the lid to be blown off, which can result in severe injury, death or property damage.
P/N 987255002REV. D 6-8-01
When performing hydrostatic pressure tests or when testing for external leaks of the
completed filtration and plumbing system, insure that the Maximum Pressure that the
filtration system will be subjected to DOES NOT EXCEED THE MAXIMUM WORKING
PRESSURE OF ANY OF THE COMPONENTS CONTAINED WITHIN THE SYSTEM. In
most cases, the maximum pressure will be stated on each component of the system.
If doubt exists as to the pressure to which the system will be subjected, install an ASME
approved automatic Pressure Relief or Pressure Regulator in the circulation system for the
lowest working pressure of any of the components in the system.
REV. D 6-8-013P/N 98725500
SECTION II. FILTER OPERATION
THIS FILTER OPERATES UNDER HIGH PRESSURE. WHEN ANY PART OF THE
CIRCULATING SYSTEM (e.g., LOCK RING, PUMP, FILTER, VALVES, ETC.) IS
SERVICED, AIR CAN ENTER THE SYSTEM AND BECOME PRESSURIZED.
PRESSURIZED AIR CAN CAUSE THE LID TO BLOW OFF WHICH CAN RESULT IN
SEVERE INJURY, DEATH, OR PROPERTY DAMAGE. TO AVOID THIS POTENTIAL
HAZARD, FOLLOW THESE INSTRUCTIONS.
1.BEFORE REPOSITIONING VALVES AND BEFORE BEGINNING THE ASSEMBLY,
DISASSEMBLY, OR ADJUSTMENT OF THE LOCK RING OR ANY OTHER
SERVICE OF THE CIRCULATING SYSTEM: (A) TURN THE PUMP OFF AND SHUT
OFF ANY AUTOMATIC CONTROLS TO ASSURE THE SYSTEM IS NOT
INADVERTENTLY STARTED DURING THE SERVICING. (B) OPEN AIR RELIEF
VALVE, AND (C) WAIT UNTIL ALL PRESSURE IS RELIEVED -PRESSURE GAUGE
MUST READ ZERO (0).
2. WHENEVER INSTALLING THE FILTER LOCK RING, FOLLOW THE FILTER LOCKRING INSTALLATION INSTRUCTIONS EXACTLY.
WARNING
3.ONCE SERVICE ON THE CIRCULATING SYSTEM IS COMPLETE, FOLLOW
SYSTEM RESTART INSTRUCTIONS EXACTLY.
4.MAINTAIN CIRCULATION SYSTEM PROPERLY. REPLACE WORN OR DAMAGED
PARTS IMMEDIATELY (e.g., lock ring, pressure gauge, relief valve, O-rings, etc.)
5.BE SURE THAT THE FILTER IS PROPERLY MOUNTED AND POSITIONED
ACCORDING TO INSTRUCTIONS PROVIDED.
P/N 987255004REV. D 6-8-01
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.