© 2014 Pentair Equipment Protection www.pentairprotect.com
89113977
- 2 -
NOTE: Refer to the instruction manual for all other installation and safety
information
HANDLING AND TESTING THE AIR CONDITIONER
Inspect the air conditioner and verify correct functionality before mounting the air
conditioner.
Do not attempt to operate the air conditioner while it is horizontal
or on its side, back or front. The refrigeration compressor is filled
with lubricating oil. This will cause permanent damage to the air
conditioner and voids the warranty.
CAUTION
If the air conditioner has been in a horizontal position, be certain it is placed in
an upright, vertical or mounting position for a minimum of five (5) minutes before
operating.
ELECTRICAL INSTALLATION
Refer to the nameplate for proper electrical current requirements, and then wire the
unit to a properly grounded power supply using copper conductors only. Power supply
wiring should be restrained after field installation to ensure no contact with internal
fan.
Minimum circuit ampacity should be at least 125% of the amperage, and +/- 10% of
the voltage, shown on the unit nameplate.
No other equipment should be connected to this circuit to prevent overloading.
Use a higher ampere rated circuit breaker, or time-delay fuse, that is closest to the
nominal ampere rating of the air conditioner, or sum of the individual component
ampere ratings, to protect system electrical circuits from short circuit or overload.
1. Loosen the screw on the evaporator access panel and remove the power
access panel, see Figure 1
2. Route the power supply wire through the strain relief.
3. Connect the wire to the terminal block per the label.
4. Reinstall the power access panel and screw.
5. Tighten the screw on the strain relief to secure the supply wire, see Figure 2.
6. For optional 3-phase operation, ensure the proper phase connection order by
observing the phase monitor green light.
Figure 1 Figure 2