Pentair SHURFLO 4008 RV REVOLUTION Installation & Operation Manual

SHURFLO® 4008 RV REVOLUTION™ By-pass pUmp
INSTALLATION & OperATION MANuAL
Switch
Connector
Ground
Black
Flexible Braided High Flow Hose
Fuse
Surface Solide
Strainer
Typical Pump Installation
INSTALLATION GUIDELINES
Solid Surface within 6' of tank. Minimize flow restrictions in the
system.
No Accumulator needed. Flexible hose on inlet and outlet. Minimize plumbing elbows and valves. Accessible location. Strainer on pump inlet. Properly Sized wiring. Properly electrical protection. Properly sized plumbing.
INSTALLATION PREPARATION
The goal of installation is to provide a quiet, easy-to-maintain installation with good flow and low backpressure. This can be accomplished with the following guidelines:
Mount on a solid surface in an accessible location for strainer cleaning
and pump maintenance. Use flexible high-pressure hose
on the pump inlet and outlet [such as SHURFLO Kit 94-591-01]. The pumps ports and strainer should
not be connected to plastic or rigid pipe, or the pump's normal motion will transmit through rigid plumbing causing noise, and possibly loosening or cracking components.
Pump must use an adequate 50-mesh strainer [such as SHURFLO 255 series strainers].
Use a minimum of 1/2" [13mm] Inner Diameter plumbing. Smaller ID
plumbing will cause cavitation, high back pressure, low flow and noise.
No need for an accumulator with by- pass pumps.
Pump is designed for intermittent duty only: Do not use these pumps
for running a Reverse-Osmosis [RO] Filtration System. High pressure­continuous duty usage will shorten the life of the pump and is not covered under warranty.
Wire Size is 16 GA MINIMUM, 12GA is recommended —See Wire Chart in Electrical Section for minimum sizing.
Minimum power requirement is a 10 Amp circuit.
Reduce restrictions on inlet and outlet. This includes small inner
diameter shut-off valves, winterizing valves and elbows.
If the RV has an Intellitec Pump Controller, it must be rated at 10 or 15
amps; If the controller is rated at 7.5 Amps, a new controller or a high-amp relay must be used.
MOUNTING
Mount the pump within 6 feet of the tank for best performance and pump life. The pump will pull farther, but the farther it pulls the more work it does, increasing vibration and noise, and reducing the output and pump life.
Mount pump in a space of at least 1 cubic foot for adequate ventilation to prevent overheating.
Pump may be mounted in any position. Mount pump for easy access for
cleaning strainer, maintenance and service.
Mount pump on a solid surface to prevent vibration and noise.
WATER PURFICATION 911-1008 REV.H 1
ELECTRICAL
ABOUT THE BY-PASS
The pump works best on an individual filtered circuit, protected by the recom­mended fuse or breaker specified on the label.
A 15-Amp switch is recommended and should be on the positive lead (red wire).
Wire Sizing: Proper wire sizing is required for good pump operation. If the wire is too small, low voltage will affect the pump performance and can create a fire hazard. SHUT OFF POWER TO THE PUMP
WHEN LEAVING THE RV UNATTENDED.
Ft. [m] AWG [mm2]
0-25 [0-7.6] 16 [1.3]
25-50 [7.6-15.2] 14 [2.1]
50-70 [15.2-21.3] 12 [3.3]
70-110 [21.3-33.5] 10 [5.3]
Minimum Wire Size for a 10% voltage drop on a 12VDC, 15 Amp Circuit. Length is the distance from the power source to pump and back to ground.
PLUMBING
Installation of a strainer is required to prevent debris from entering the pump. For noise and vibration reduction we recommend at least 18 in. [.5 M] of 1/2" [13mm] I.D. flexible high-pressure hose to both ports. The pump ports and strainer should not be connected to plastic or rigid pipe. This hose should be anchored where it meets the hard plumbing to reduce plumbing vibration.
OPERATION
NOTE: By-pass adjustment should only be performed by a professional techni­cian with proper gauges and equipment.
The by-pass is a spring loaded dia­phragm that opens up allowing water from the discharge side back to the inlet side. The by-pass is set to begin opening at about 40 psi and creating full by-pass at about 62 psi (lower pressure pumps will vary depending on the by-pass and pressure shut-off settings). The pres­sure switch on the pump is set to shut off at 55 psi. If the switch or by-pass are adjusted too much, the by-pass and switch shut-off can overlap and THE
PUMP WILL NOT SHUT OFF. Screw-
SANITIZING
Potable water systems require periodic maintenance to keep components work­ing properly and deliver a consistent flow of fresh water. Sanitizing is recom­mended: prior to storing, after a period of storage, or any time the system is opened or contaminated, as follows:
NOTE: Check your Vehicle Owner’s Manual for specific instructions. By-pass any filters or remove filter cartridges.
1. Determine the amount of common
household bleach needed to sanitize the tank.
A) 2 ounces of bleach per 15 gallons tank size: 60 gallon tank [15 x 4] = 4 x 2 ounces = 8 ounces of bleach.
B) I ml bleach per 1 liter tank size: 300 liter tank = 300 milliliters of bleach.
ing the switch screw in clockwise will raise the shut-off pressure. Unscrew­ing the switch screw counterclockwise will lower the pump shut-off pressure. Screwing the by-pass screw in will raise the pressure at which the by-pass starts and raise the full by-pass pressure. Unscrewing the by-pass screw coun­terclockwise will lower the pressure at which by-pass starts and lower the full by-pass pressure.
WARNING: If full by-pass is reached before the shut-off setting, the pump will not shut off. Full by-pass pressure
setting should be at least 10 psi higher than pump shut off pressure.
2. Mix the bleach with water in a con­tainer such as a gallon jug. If tank is filled through a pressurized fitting, pour the bleach into the hose before attach­ing the hose to the city water entry.
3. Pour the bleach solution into the tank and fill the tank with potable water. Rock the RV back and forth to coat top and sides of potable water tank.
4. Open all faucets (Hot & Cold) al­lowing the water to run until the odor of chlorine is detected. Allow four (4) hours of contact time to disinfect com­pletely. Doubling the solution concentra­tion allows for a contact time of one (1) hour.
5. Drain the tank. Refill the tank and flush the system once or twice until the odor has decreased. The residual chlo­rine odor and taste is not harmful.
This pump is designed for intermittent duty only. The pump operates normally up to about 40-psi, where a spring-load­ed by-pass valve opens, allowing flow back from the output side to the input side, providing smooth, steady flow with virtually no cycling, all the way down to a trickle. As a faucet is opened back up, the pressure will drop, the by-pass will close and full flow is again ob­tained. This allows good flow, even with today’s restrictive showers and pullout sprayer faucets. Performance will vary, of course, depending on the voltage to the pump; lower voltage = lower flow, higher voltage = higher flow. Remember your electrical safety: It is always best to shut power to the pump OFF when leav­ing the RV unattended.
2
WINTERIZING
Refer to the vehicle owner’s manual for specific winterizing instructions.
If water is allowed to freeze in the system, serious damage to the plumb­ing and pump may occur. Failures of this type will void the warranty. The best guarantee against damage is to com­pletely drain the pump and perform the following:
1. Drain the water tank. If the tank doesn't have a drain valve, open all fau­cets allowing the pump to operate until the tank is empty.
2. Open all the faucets (including the low­est valve or drain in the plumbing), allow the pump to purge the water from the plumbing, and then turn the pump OFF.
3. Using a pan to catch the remain­ing water, remove the plumbing at the pump's inlet/outlet ports. Turn the pump ON, allowing it to operate until the water is expelled. Turn OFF power to the pump once the plumbing is emptied. Do not reconnect the pump plumbing. Make a note at tank filler as a reminder: "Plumbing is disconnected".
4. All faucets must be left open to guard against any damage.
5. Potable anti-freeze may be poured down drains and toilets to protect p-traps and toilet seals. Sanitize the plumbing system before putting the plumbing system back in service.
TROUBLESHOOTING
Vibration induced by driving can loosen plumbing, strainers and pump hard­ware. Check for system components that are loose. Also, refer to the chart below for trouble-shooting tips.
PUMP WILL NOT START/ BLOWS CIRCUIT
√ Electrical connections, fuse or
breaker, main switch, and ground connection.
√ Is the motor hot? Thermal breaker
may have triggered; it will reset when cool.
√ Is voltage present at the switch?
Bypass pressure sw. Does the pump operate?
√ Charging System for correct voltage
(±10%) and good ground.
√ For an open or grounded circuit, or
motor; or improperly sized wire.
√ For seized or locked diaphragm as-
sembly (water frozen?).
WILL NOT PRIME/SPUTTERS (No discharge/Motor runs)
√ Is the strainer clogged with debris? √ Is there water in the tank, or has air
collected in the hot water heater?
√ Is the inlet tubing/plumbing suck-
ing in air at plumbing connections (vacuum leak)?
√ Is inlet/outlet plumbing severely
restricted or kinked? Restrictive valves?
√ Proper voltage with the pump oper-
ating (±10%).
√ For debris in pump inlet/outlet
valves or swollen/dry valves.
√ Pump housing for cracks or loose
drive assembly screws.
RAPID CYCLING
√ For restrictive plumbing and flow
restrictions in faucets/shower heads.
√ Water filter/purifier should be on
separate feed line.
√ Shut-off pressure set too low.
PUMP WILL NOT SHUT-OFF / RUNS WHEN NOZZLE IS CLOSED
√ Output side (pressure) plumbing for
leaks, and inspect for leaky valves or toilet.
√ For air trapped in outlet side (water
heater) or pump head. √ For correct voltage to pump (±10%). √ For loose drive assembly or pump
head screws. √ Are the valves held open by debris
or is the rubber swollen? √ Pressure switch operation. By-pass
set higher than shut-off.
NOISY OR ROUGH OPERATION
√ For plumbing which may have
vibrated loose. √ For a restricted inlet (clogged
strainer, kinked hose, restrictive
valves). √ Is the pump plumbed with rigid pipe
causing noise to transmit? √ Does the mounting surface amplify
noise (flexible)? Does it bang like a
drum? √ For mounting feet that are loose or
are compressed too tight. √ For air in the system. Check all
fixtures for air and bleed system. √ The motor with pump head re-
moved. Is noise from motor or
pump head?
5
LEAKS FROM PUMP HEAD OR SWITCH
√ For loose screws at switch or pump
head.
√ Switch diaphragm ruptured or
pinched.
√ For punctured diaphragm if water is
present in drive assembly.
MAINTENANCE
Normal pump maintenance is all that is needed: Checking and cleaning of the strainer, normal sanitizing and winterizing and occasionally check­ing all plumbing hardware and fittings for tightness. Lack of sanitizing is the number one reason for premature pump failure and poor performance over time. Lack of sanitizing will cause scale build­up on the diaphragm and valves, causing low flow and leak back [occasional pump cycling with no faucets open or tank filling up when hooked up to city water].
TYPICAL PERFORMANCE
PRESSURE FLOW CURRENT
PSI BAR GPM LPM Amps
0 0 3.0 11.3 2.8
10 0.7 2.3 8.7 3.2
20 1.4 1.9 7.2 4.2
30 2.1 1.6 6.0 5.1
40 2.8 1.4 5.3 6.1
50 3.4 0.8 3.0 6.8
55 3.8 0.0 0.0 7.5
3
2
1
4
REPAIR KITS
ITEM COMPONENT PARTS KIT
1
2, 3
4 5
N/S
1, 2, 3, 4
N/S
Upper Assembly
Valve Assembly
2.5° Drive Assembly
Motor
Check Valve
Pump Head
Pressure Switch
94-800-00 94-800-01 94-800-02 94-11-302-00 94-800-03 94-800-04 94-800-05
3
Loading...
+ 5 hidden pages