Pentair MiniMax CH User Manual 2

Warning:
®
MiniMax CH
POOL & SPA HEATERS
OPERATION & INSTALLATION MANUAL
WARNING
FOR YOUR SAFETY - READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, personal injury or loss of life. For additional free copies of this manual; call (800) 831-7133.
1
1
1
U.S. Patent Numbers
6,295,980 5,318,007 - 5,228,618 5,201,307 - 4,595,825
WARNING
Warning: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or death. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
For Your Safety
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
To Consumer Retain For
Future
Reference
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or other appliances.
Pentair Pool Products, Inc.
1620 Hawkins Ave., Sanford, NC 27330 (919) 774-4151
10951 W. Los Angeles Ave., Moorpark, CA 93021
Rev. B 1-17-03 P/N 472128
(805) 523-2400
Table of Contents
Introduction ............................................................................................................... 3
Important Notices ...................................................................................................................................................................... 3
Warranty Information ................................................................................................................................................................. 4
Operation .................................................................................................................... 4
Safety Rules .............................................................................................................................................................................. 4
Millivolt Lighting/Operation - Natural & Propane ........................................................................................................................ 5
Operating (Controls) .................................................................................................................................................................. 6
Maintenance ............................................................................................................... 7
Maintenance Instructions ........................................................................................................................................................... 7
Relief Valve................................................................................................................................................................................ 7
Energy Saving Tips.................................................................................................................................................................... 7
Spring and Fall Operation .......................................................................................................................................................... 7
Winter Operation ....................................................................................................................................................................... 7
Chemical Balance ...................................................................................................................................................................... 8
Installation Instructions ............................................................................................ 9
2
Specifications .......................................................................................................................... 9
Plumbing Connections ........................................................................................................... 10
Plumbing/Valves ........................................................................................................................................................................ 10
Manual Bypass .......................................................................................................................................................................... 10
Below Pool Installation .............................................................................................................................................................. 10
Water Connections.................................................................................................................. 11
Reverse Water Connections ...................................................................................................................................................... 11
Insulating High Limits when Reversing Heads ........................................................................................................................... 11
Gas Connections ..................................................................................................................... 12
Gas Line Installation .................................................................................................................................................................. 12
Pipe Sizing Chart/Gas Pressure Requirements ......................................................................................................................... 12
Pipe Sizing Chart/Propane 2 Stage Regulation ......................................................................................................................... 13
Regulated Manifold Pressure Test ............................................................................................................................................. 13
Ventilation ................................................................................................................................ 14
Outdoor Installation Requirements ............................................................................................................................................ 14
Outdoor Cap Installation ............................................................................................................................................................ 14
Indoor Installation Requirements ............................................................................................................................................... 15
Installation on Floors Constructed of Combustible Materials ..................................................................................................... 16
Indoor Draft Hood Installation .................................................................................................................................................... 16
Electrical .................................................................................................................................. 17
Millivolt Wiring Diagram ............................................................................................................................................................. 17
Trouble Shooting (General)....................................................................................... 18
MiniMax CH Parts List & Exploded View ................................................................. 19-21
MiniMax CH (150 IID Model) Appendix ..................................................................... A1-A9
MiniMax CH (150 IID Model) Parts List & Exploded View ....................................... A10-A12
Warranty Information ................................................................................................. Back Cover
P/N 472128 Rev. B 1-17-03
3
Introduction
MiniMax CH
Pool and Spa Heaters
Congratulations on your purchase of a MiniMax CH high performance heating system. Proper installation and service of your new heating system and correct chemical maintenance of the water will ensure years of enjoyment. The MiniMax CH is a compact, lightweight and efficient gas fired high performance pool and spa heater that can be directly connected to schedule 40 PVC pipe and has a built-in top. The MiniMax CH is a millivolt heater and has a self sustaining pilot and requires NO external power source.
IMPORTANT NOTICES
...For the installer and operator of the MiniMax CH pool and spa heater. The manufacturer’s warranty may be void if, for any reason, the heater is improperly installed and/or operated. Be sure to follow the instructions set forth in this manual. If you need any more information, or if you have any questions regarding to this pool heater, please contact Pentair Pool Products, Inc. at (800) 831-7133.
These heaters are designed for the heating of swimming pools and spas, and should never be employed for use as space heating boilers, general purpose water heaters, in non-stationary installations, or for the heating of salt water.
CAUTION
OPERATING THIS HEATER CONTINUOUSLY AT WATER TEMPERATURE BELOW 68° F. WILL CAUSE HARMFUL CONDENSATION AND WILL DAMAGE THE HEATER AND WILL VOID THE WARRANTY.
Do not use the heater to protect pools or spas from freezing if the final maintenance temperature desired is below 68° F. as this will cause condensation related problems.
CODE REQUIREMENTS
The installation must conform with local codes or in the absence of local codes with the latest National Fuel Gas Code, ANSI Z223.1, and the latest edition of the National Electrical Code, NFPA 70.
Installation in Canada to be made in accordance with the latest CAN/CGA-B149.1 or .2 and CSA C22.1 Canadian Electric Code, part 1.
Rev. B 1-17-03 P/N 472128
Operation (contd.)
4
This instruction manual provides operating instructions, installation and service information for the MiniMax CH high performance heater. The information in this manual applies to the MiniMax CH 150, 200, 250, 300, 350, and 400 natural gas and propane (LP) models.
It is very important that the owner/installer read and understand the section covering installation instructions, and recognize the local and state codes before installing the MiniMax CH. History and experience has shown that most heater damage is caused by improper installation practices.
Operation
WARRANTY INFORMATION
The MiniMax CH pool heater is sold with a limited factory warranty. Specific details are described on
the back cover of this manual and a copy of the warranty and warranty registration card are included with the product. Return the warranty
registration card after filling in the serial number from the rating plate inside the heater.
Pentair Pool Products’ high standards of excellence include a policy of continuous product improvement resulting in your state-of-the-art heater. We reserve the right to make improvements which change the specifications of the heater without incurring an obligation to update the current heater equipment.
SAFETY RULES
1. Spa or hot tub water temperatures should never exceed 104° F (40° C). A temperature of 100° F (38° C) is considered safe for a healthy adult. Special caution is suggested for young children.
2. Drinking of alcoholic beverages before or during spa or hot tub use can cause drowsiness which could lead to unconsciousness and subsequently result in drowning.
3. Pregnant women beware! Soaking in water above 102° F (39° C) can cause fetal damage during the first three months of pregnancy (resulting in the birth of a brain-damaged or deformed child). Pregnant women should stick to the 100° F (38° C) maximum rule.
WARNING
4. Before entering the spa or hot tub, the user should check the water temperature with an accurate thermometer. Spa or hot tub thermostats may err in regulating water temperatures by as much as 4° F (2.2° C).
5. Persons with a medical history of heart disease, circulatory problems, diabetes or blood pressure problems should obtain their physician's advice before using spas or hot tubs.
6. Persons taking medication which induce drowsiness, such as tranquilizers, antihistamines or anticoagulants should not use spas or hot tubs.
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance. Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of control system and gas control which has been under water.
P/N 472128 Rev. B 1-17-03
Operation (contd.)
MINIMAX CH MILLIVOLT LIGHTING/OPERATION-NATURAL GAS & PROPANE
FOR YOUR SAFETY: READ BEFORE LIGHTING
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing personal injury, loss of life and property damage.
Since propane gas is heavier than air, escaping propane will accumulate and remain at ground level. Do not attempt to light the heater. If you suspect a propane leak, lighting the heater can result in a fire or explosion which can cause personal injury, death, and property damage.
A. This heater is equipped with a pilot which must be
lighted manually. When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the heater
area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle
on the floor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any heater.
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
- If you cannot reach your gas supplier, call the Fire Department.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it. Call a qualified service technician. Forced or attempted repair may result in a fire or explosion.
D. Do not use this heater if any part has been under
water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
5
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off electric power to the heater.
4. Push in gas control knob slightly and turn clock­wise to “OFF”.
Robertshaw Millivolt Gas Valve Honeywell Millivolt Gas Valve
Figure 1. Figure 2.
Gas control knobs shown in “OFF” position.
NOTE
Knob cannot be turned from “Pilot to “OFF”” unless knob is pushed in slightly. DO NOT FORCE.
5. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in the safety informa­tion above. If you don't smell gas, go to the next step.
6. Push in gas control knob slightly and turn counter­clockwise to “Pilot”.
7. Push the control knob all the way and hold in. Immediately light the pilot with Presslite matchless ignition system by pressing the red igniter button (located at the panel next to the gas valve). Continue to hold the control knob in for about one (1) minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 4 through 7.
If knob does not pop up when released, stop and immediately call your service technician or gas supplier.
If the pilot will not stay lit after several tries, turn the gas control knob to “OFF” and call your service technician or gas supplier.
8. Turn knob on gas control counterclockwise to “ON”.
9. Replace the control access door.
10. Set the thermostat to the desired setting.
Figure 3.
Figure 4.
Pilot
TO TURN OFF GAS TO HEATER
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the heater if service is to be performed.
3. Remove control access door.
Rev. B 1-17-03 P/N 472128
4. Push in gas control knob slightly and turn clockwise to "OFF". Do not force.
5. Replace control access door.
Operation (contd.)
SPAPOOL
COLD COLDHOT HOT
OFF
POOL TEMP SPA TEMP
6
OPERATING (CONTROLS)
Dual Temperature Control System
For convenience and economy all MiniMax CH heaters are equipped with two thermostats on the front of the heater control panel; see Figure 5.
THERMOSTAT KNOB STOPPER
Each thermostat is equipped with a mechanical stop that can be locked or unlocked with use of a screwdriver to prevent temperatures in excess of that desired by the user; see Figure 6.
The maximum setting can be adjusted by loosening the screw "A" and turning the stopper dial to desired maximum setting. Lock the setting by tightening the screw. The Mechanical stop is under the knob. Ensure that the knob is stopping at the correct position when the knob is rotated clockwise from a lower temperature position. (See Thermostat Adjustment.)
Figure 5.
NOTE To eliminate error due to piping heat losses, measure pool temperature with an accurate thermometer directly at the pool or spa.
THERMOSTAT ADJUSTMENT
The knob with locking feature eliminates the need for constant thermostat adjustments. Set the knob pointer to the desired pool or spa temperature.
If further adjustment is needed, rotate the knob until the desired temperature is obtained. This knob position corresponding to your desired maximum pool or spa temperature may now be preset (locked) by the knob stopper which prevents the knob from being turned beyond the maximum temperature you set.
POWER (THERMOSTAT SELECT) SWITCH
Figure 6.
Screw A
The Pool/Off/Spa switch allows the heater to be turned off when heating is not desired.
1. “Pool” position - Maintains selected pool temperature.
Knob Stopper
2. “Off” position - Heater will not come on regardless of drop in pool or spa temperature.
3. “Spa” position - This allows separate control of spa water temperature or an alternate lower pool temperature.
P/N 472128 Rev. B 1-17-03
Maintenance
7
MAINTENANCE INSTRUCTIONS
It is recommended that you check the following items at least every six months and at the beginning of every swimming season.
1. Examine the venting system. Make sure there are no ob­structions in the flow of combustion and ventilation air.
2. Visually inspect the main burner and the pilot burner flame. The normal color of the flame is blue. When flame appears yellow, burners should be inspected and cleaned; see Figure 8.
3. Keep the heater area clear and free from combustibles and flammable liquids.
Blue Flame
Figure 7.
Figure 8.
ENERGY SAVING TIPS
1. If possible, keep pool or spa covered when not in use. This will not only cut heating costs, but also keep dirt and debris from settling in the pool and conserve chemicals.
2. Reduce the pool thermostat setting to 78° F. or lower. This is accepted as being the most healthy temperature for swimming by the American Red Cross.
3. Use an accurate thermometer.
4. When the proper maximum thermostat settings have been determined, tighten the thermostat knob stopper.
CAUTION
REMOVE THE FLOW VALVE ASSEMBLY WHEN DRILLING THE HOLE TO INSTALL A PRV. OTHERWISE, YOU WILL DRILL INTO THE VALVE ASSEMBLY.
Pressure Relief Valve
In some installations, a pressure relief valve (PRV) is required on the MiniMax CH heater. To install a PRV, carefully drill a 3/8 in. hole in center of 3/4 in. NPT port (on main header) being careful to drill only thru wall at bottom of 3/4 in. NPT port and no deeper—now thread in the 3/4 NPT PRV. (Sold separately.)
5. Set time clock to start circulation system no earlier than daybreak. The swimming pool loses less heat at this time.
6. For pools that are only used on the weekends, it is not necessary to leave the thermostat set at 78° F. Lower the temperature to a range that can be achieved easily in one day. Generally, this would be 10° F. to 15° F., if pool heater is sized properly.
7. During the winter or while on vacation, turn the heater off.
8. Set up a regular program of preventative maintenance for the heater each new swimming season. Check heat exchanger, controls, burners, operation, etc.
Figure 9.
REMOVE FLOW VALVE BEFORE DRILLING THE NPT PORT
FOR PRV INSTALLATION DRILL THRU THE NPT PORT
SPRING AND FALL OPERATION
If the pool is being used occasionally, do not turn the heater completely off. Set the thermostat down to 65° F. This will keep the pool and the surrounding ground warm enough to bring the pool up to a comfortable swimming temperature in a
shorter period of time.
WINTER OPERATION
CAUTION
OPERATING THIS HEATER CONTINUOUSLY AT WATER TEMPERATURE BELOW 68° F. WILL CAUSE HARMFUL CONDENSATION AND WILL DAMAGE THE HEATER AND WILL VOID THE WARRANTY.
If the pool won't be used for a month or more, turn the heater off at the main gas valve. For areas where there is no danger of water freezing, water should circulate through the heater all year long, even though you are not heating your swimming pool. The MiniMax CH should not be operated out doors at temperatures below 0° F. for propane and -20° F. for natural gas. Where freezing is possible, it is necessary to drain the water from the heater. This may be done by opening the drain valve located at the inlet/outlet header (see Figure 9.) allowing all water to drain out of the heater. It would be a good practice to use compressed air to blow the water out of the heat exchanger. (See additional notes under Important Notices in Introduction
on page 3.)
Rev. B 1-17-03 P/N 472128
Maintenance (contd.)
8
CHEMICAL BALANCE
POOL AND SPA WATER
Your Pentair Pool Products pool heater was designed specifically for your spa or pool and will give you many years of trouble free service provided you keep your water chemistry in proper condition.
Three major items that can cause problems with your pool heater are improper pH, disinfectant residual, and total alkalinity. These items, if not kept properly balanced, can shorten the life of the heater and cause permanent damage.
CAUTION
Heat exchanger damage resulting from chemical imbalance is not covered by the warranty.
WHAT A DISINFECTANT DOES
Two pool guests you do not want are algae and bacteria. To get rid of them and make pool water sanitary for swimming - as well as to improve the water's taste, odor and clarity - some sort of disinfectant must be used.
Chlorine and bromine are universally approved by health authorities and are accepted disinfecting agents for bacteria control.
RULE: 7.4 to 7.6 is a desirable pH range. It is essential to maintain correct pH, see Table 2.
If pH becomes too high (over alkaline), it has these effects:
1. Greatly lowers the ability of chlorine to destroy bacteria and algae.
2. Water becomes cloudy.
3. There is more danger of scale formation on the plaster or in the heat exchanger.
4. Filter elements may become blocked.
If pH is too low (over acid) the following conditions may occur:
1. Excessive eye burn or skin irritation.
2. Etching of the plaster.
3. Corrosion of metal fixtures in the filtration and recirculation system, which may create brown, blue, green, or sometimes almost black stains on the plaster.
4. Corrosion of copper in the heater, which may cause leaks.
5. If you have a sand and gravel filter, the alum used as a filter aid may dissolve and pass through the filter.
WHAT IS A DISINFECTANT RESIDUAL?
When you add chlorine or bromine to the pool water, a portion of the disinfectant will be consumed in the process of destroying bacteria, algae and other oxidizable materials. The disinfectant remaining is called chlorine residual or bromine residual. You can determine the disinfectant residual of your pool water with a reliable test kit, available from your local pool supply store.
You must maintain a disinfectant residual level adequate enough to assure a continuous kill of bacteria or virus introduced into pool water by swimmers, through the air, from dust, rain or other sources.
It is wise to test pool water regularly. Never allow chlorine residual to drop below 0.6 ppm (parts per million). The minimum level for effective chlorine or bromine residual is 1.4 ppm.
pH - The term pH refers to the acid/alkaline balance of water expressed on a numerical scale from 0 to 14. A test kit for measuring pH balance of your pool water is available from your local pool supply store; see Table 1.
Table 1.
Strongly Acid Neutral Strongly Alkaline
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Muriatic Acid has a pH of about 0. Pure water is 7 (neutral). Weak Lye solution have a pH of 13-14.
pH Chart
CAUTION: Do not test for pH when the chlorine residual is 3.0 ppm or higher, or bromine residual is 6.0 ppm or higher. See your local pool supply store for help in properly balancing your water chemistry.
RULE: Chemicals that are acid lower pH. Chemicals that are alkaline raise pH.
Table 2.
6.8 7.0
Add Soda, Ash or Sodium Bicarbonate
pH Control Chart
7.4 7.6
7.2
7.8 8.0 8.2 8.4
Add AcidMarginalIdealMarginal
ALKALINITY High - Low:
"Total alkalinity" is a measurement of the total amount of alkaline chemicals in the water, and control pH to a great degree. (It is not the same as pH which refers merely to the relative alkalinity/acidity balance.) Your pool water's total alkalinity should be 100 - 140 ppm to permit easier pH control.
A total alkalinity test is simple to perform with a reliable test kit. You will need to test about once a week and make proper adjustments until alkalinity is in the proper range. Then, test only once every month or so to be sure it is being maintained. See your local pool dealer for help in properly balancing the water chemistry.
P/N 472128 Rev. B 1-17-03
Installation Instructions
SPECIFICATIONS
IMPORTANT NOTICE: These installation instructions are designed for use by qualified personnel only, trained especially for installation of this type of heating equipment and related components. Some states require installation and repair by licensed personnel. If this applies in your state, be sure your contractor bears the appropriate license.
Outdoor installation - stackless
9
ledoMmiD"A"miD"B"
051.ni8/771.ni½6
002.ni8/702.ni½9
052.ni8/732.ni½21
003.ni8/762.ni½51
053.ni8/792.ni½81
004.ni8/333.ni8/322
Table 3.
Outdoor installation - with vent kit
ledoMmiD"A"miD"B"miD"C"miD"D"
051.ni8/771.ni½6.ni¾7.ni¾93
002.ni8/702.ni½9.ni01.ni¾24
052.ni8/732.ni½21.ni01.ni¾24
003.ni8/762.ni½51.ni¼01.ni¾34
SPAPOOL
OFF
COLD COLDHOT HOT
POOL TEMP SPA TEMP
32
1
"B" DIM.
2
"A" DIM.
FRONT VIEW SIDE VIEW
SPAPOOL
OFF
COLD COLDHOT HOT
POOL TEMP SPA TEMP
"D"
DIM
5
"C"
DIM.
28"
HIGH PERFORMANCE HEATER
TM
CH
"E" DIM.
HIGH PERFORMANCE HEATER
7
13
8
1
21
4.875
TM
CH
2
1
053.ni8/792.ni½81.ni31.ni¾74
004.ni8/333.ni8/322.ni71.ni¾15
Table 4.
"B" DIM.
5
2
"A" DIM.
"E" DIM.
4.875
1
21
2
Indoor installation - stack (USA only) Outdoor shelter installation (Canada)
ledoMmiD"A"miD"B"miD"C"miD"D"miD"E"
"C"
051.ni8/771.ni½6.ni31.ni¾25.ni6
002.ni8/702.ni½9.ni31.ni8/735.ni7
052.ni8/732.ni½21.ni31.ni8/735.ni7
003.ni8/762.ni½51.ni31.ni55.ni8
053.ni8/792.ni½81.ni31.ni65.ni9
004.ni8/333.ni8/322.ni71.ni¾06.ni01
Table 5.
Rev. B 1-17-03 P/N 472128
"D"
DIM
GAS LINE OPENING
28
DIM.
SPAPOOL
OFF
COLD COLDHOT HOT
POOL TEMP SPA TEMP
7
10
8
1
"B" DIM.
5
2
"A" DIM.
HIGH PERFORMANCE HEATER
TM
CH
7
13
8
1
21
4.875
2
Installation (contd.)
T H
E
P
R M
O
O S
O
T A T
L
S
E L E C T
S
O
P
F
A
F
C O L D
P O O
L T E M P
H O T
C O L D
S P A T E M
P
H O T
10
MANUAL BY-PASS
POOL HEATER
1
Optional.
2
Required when installation is below water level. Required when flow rates exceed 120 gpm.
3
3
MANUAL BY-PASS
1
CHECK VALVE
TO POOL
ISOLATION VALVE
ISOLATION VALVE
FILTER
FROM POOL
CHECK VALVE
PUMP
2
Figure 10.
PLUMBING CONNECTIONS
The MiniMax CH heater has the unique capability of direct schedule 40 PVC plumbing connections.
CAUTION
Before operating the heater on a new installation, turn on the circulation pump and bleed all the air from the filter using the air relief valve on top of the filter. Water should flow freely through the heater.
Do not operate the heater unless water in the pool/ spa is at the proper level.
Where the flow rate exceeds the maximum 120 GPM, a manual bypass should be installed and adjusted. After adjustments are made, the valve handle should be removed to avoid tampering.
ledoM.niM*.xaM
05102021
00202021
05203021
00303021
05304021
00404021
dednemmocermumixamehtdeecxetonoD*
.gnipipgnitcennocehtrofetarwolf
Table 6.
BELOW POOL INSTALLATION
PLUMBING
VALVES
When any equipment is located below the surface of the pool or spa, valves should be placed in the circulation piping system to isolate the equipment from the pool or spa.
Check valves are recommended to prevent back siphon.
CAUTION
Exercise care when installing chemical feeders so as to not allow back siphoning of chemical into the heater, filters or pump. When chemical feeders are installed in the circulation of the piping system, make sure the feeder outlet line is down stream of the heater, and is equipped with a positive seal non-corrosive “Check Valve”, (P/N R172288), between the feeder and heater.
If the heater is below water level, the pressure switch should be adjusted. This adjustment must be done by a qualified service technician. See following CAUTION.
CAUTION
BELOW OR ABOVE POOL INSTALLATION
The water pressure switch is set in the factory at 1½ PSI. This setting is for a heater installed at pool level or within 3’ above or 3’ below. If the heater is to be installed more that 3’ above or 3’ below, the water pressure switch must be adjusted by a qualified service technician.
FLOW SWITCH
If the heater is installed more the 6’ above the pool or more than 10’ below the pool level, you will be beyond the limits of the pressure switch and a flow switch must be installed. Locate and install the flow switch externally on the outlet piping from the heater, as close as possible to the heater. Connect the flow switch wires in place of the water pressure switch wires.
P/N 472128 Rev. B 1-17-03
Installation (contd.)
11
WATER CONNECTIONS
Reversible Inlet/Outlet Connection
The MiniMax CH heater is factory assembled with right side inlet/outlet water connections. The inlet/ outlet header can be reversed for left side water connections without removing the heat exchanger.
Reversing Water Connections Disassembly Tools needed:
1/4 in Nut Driver 9/16 in. Socket and Wrench 1/2 in. & 9/16 in. Open Wrench Screw Driver(s) - (Flathead & Phillips)
1. Remove the inspection plates.
2. Disconnect all wires from the high-limit switches except the short jumper wire. The exact order of the disconnection is not important.
INSULATING THE HIGH LIMITS
When Reversing Heads on the MiniMax CH Heater
On the MiniMax CH heater there is insulation installed by the factory on the return head side of the heaters. This insulation is there so that if the heads are reversed in the field, during initial installation of the heater, the reflected heat from the flue collector will be insulated from the high limits.
Return head in position before removal. This view shows the insulation installed by the factory.
NOTE
There is no reason to remove the high-limit and pressure switches or the thermister from the front header during the reversing procedure, as they will be in the proper location when installed on the left side.
3. Disconnect the pressure switch wiring.
4. Disconnect the thermostat thermister leads from the control board.
5. Exchange the in/out header with the return header. Replace the heat exchanger tube seals with new seals provided in the Quick-Flange Accessory Bag.
6. Install the temperature sensing bulb by passing the wires through the hole provided on the left side of the brace panel. Route wires through the support bracket.
7. Reconnect all the high limit wires. Reconnect the pressure switch wiring. Route the wires through the same hole as the thermostat sensor wires and reconnect thermister to the board.
Return head removed and new tube seals installed. Now ready to accept the installation of the main head.
Lift the installation to allow the main head to be installed. When head is placed into position, release the insulation; it will now shield the high limits from the heat produced by the flue collector.
8. Reinstall the inspection plates.
Rev. B 1-17-03 P/N 472128
Installation (contd.)
12
GAS CONNECTIONS
GAS LINE INSTALLATIONS
Before installing the gas line, be sure to check which gas the heater has been designed to burn. This is important because different types of gas require different gas pipe sizes. The rating plate on the heater will indicate which gas the heater is designed to burn. Tables 7-9, on pages 12 and 13, shows which size pipe is required for the distance from the gas meter to the heater. The table is for natural gas at a specific gravity of .65 and propane at specific gravity of 1.5.
When sizing gas lines, calculate three (3) additional feet of straight pipe for every elbow used.
When installing the gas line, avoid getting dirt, grease or other foreign material in the pipe as this may cause damage to the gas valve, which may result in heater failure.
The gas meter should be checked to make sure that it will supply enough gas to the heater and any other appliances that may be used on the same meter.
The gas line from the meter will usually be of a larger size than the gas valve supplied with the heater. Therefore a reduction of the connecting gas pipe will be necessary. Make this reduction as close to the heater as possible.
The heater and any other gas appliances must be disconnected from the gas supply piping system during any pressure testing on that system, (greater that ½ PSIG).
The heater and its gas connection must be leak tested before placing the heater in operation. Do not use
flame to test the gas line. Use soapy water or another nonflammable method.
A manual main shut-off valve must be installed externally to the heater.
WARNING
Do not install the gas line union inside the heater cabinet. This will void your warranty.
Pipe Sized For Length Of Run In Equivalent Feet
2/1”4/3”1”4/1-1”2/1-1”2”2/1-2
TANORPTANORPTANORPTANORPTANORPTANORPTANORP
LEDOM
001&57’02’05’05’051’051’006 --------
051’01’04’05’051’051’006 --------
002-’02’03’08’521’052’054’006 ------
052-’01’02’05’07’051’052’005’006 -----
003--’01’03’05’001’002’053’004’006 ----
053--’01’02’03’07’521’052’052’005’005 ---
004 --- ’01’02’06’001’051’002’054’004 ---
525 --- ’5’51’53’56’051’031’063’093’007--
057 ----- ’02’53’08’57’081’062’006--
009 ----- ’51’02’05’54’08’051’063’004-
SNOITCENNOCENILSAGROFGNIZISEPIP
HTGNELEPIPTNELAVIUQEMUMIXAM
tooFcibuCrep.U.T.B0001tasaglarutaN
tooFcibuCrep.U.T.B0052tasaGenaporP
Table 7.
P/N 472128 Rev. B 1-17-03
Installation (contd.)
13
Pipe Sized For Length Of Run In Equivalent Feet, (cont’d.)
PROPANE 2 STAGE REGULATION
In many “RESIDENTIAL” Propane gas line installations, the gas supplier and or installer will utilize a two stage regulation process where by at the supply tank they will install the first stage gas regulator, which would be at a higher pressure, usually 10 psi and can be for longer distance and in a smaller pipe size. Then within a short distance from the heater they will install a second regulator, which is the second stage, and this would be set at the reguired inlet pressure of 11 inches of W.C. for all the Pentair Pool Heaters.
gniziSepiPsaG"erusserPhgiH"enOegatS
HTGNELEPIPTNELAVIUQEMUMIXAM
ledoMteeF05ot0teeF001ot05teeF051ot001
001&57.ni2/1.ni2/1.ni2/1
051.ni2/1.ni2/1.ni2/1
002.ni2/1.ni2/1.ni2/1
052.ni2/1.ni2/1.ni2/1
003.ni2/1.ni2/1.ni2/1
053.ni2/1.ni2/1.ni2/1
004.ni2/1.ni2/1.ni2/1
Table 8.
REGULATED MANIFOLD PRESSURE TEST
1. Attach the manometer to the heater jacket.
2. Shut off the main gas valve.
3. Remove 1/8 in. NPT plug on the outlet side of
the valve and screw in the fitting from the manometer kit.
4. Connect the manometer hose to the fitting.
5. Fire the heater.
6. The manometer must read 4 in. WC for natural
gas, 11 in. WC for propane gas, while the heater is operating.
7. For adjustment, remove the Regulator
Adjustment Cap and using a screwdriver turn the screw clockwise to increase - counterclockwise to decrease gas pressure.
CAUTION
The use of Flexible Connectors (FLEX) is NOT recommended as they cause high gas pressure drops.
gniziSepiPsaG"erusserPwoL"owTegatS
HTGNELEPIPTNELAVIUQEMUMIXAM
ledoMteeF01ot0teeF02ot01
001&57.ni2/1.ni2/1
051.ni2/1.ni2/1
002.ni2/1.ni4/3
052.ni2/1.ni4/3
003.ni4/3.ni4/3
053.ni4/3.ni4/3
004.ni4/3.ni4/3
Table 9.
REGULATOR
ADJUSTMENT CAP
PILOT
HONEYWELL
Figure 11.
1/2 P.S.I.
PILOT ADJ.
PRESS TAP
MINIMAX CH GAS PRESSURE REQUIREMENTS*
Natural
Maximum inlet gas pressure 10 in. WC 14 in. WC Minimum inlet gas pressure **5 in. WC 12 in. WC Normal manifold pressure 4 in. WC 11 in. WC ** 6 WC for 400 model
*All Readings are taken with the heater fired. Any adjustments made with heater off will give incorrect readings.
Table 10.
Propane
Rev. B 1-17-03 P/N 472128
Installation (contd.)
14
VENTILATION
OUTDOOR INSTALLATION ONLY
For outdoor installation with built in vent top, the heater must be placed in a suitable area on a level, noncombustible surface. Do not install the heater under an overhang with clearances less than 3 feet from the top of the heater. The area under an overhang must be open on three sides.
IMPORTANT!
In an outdoor installation it is important to protect your heater from water damage. Ensure water is diverted from overhanging eves with a proper gutter/ drainage system. The heater must be set on a level
foundation for proper rain drainage.
Maintain minimum clearances as indicated below. Install a minimum of 4 feet below, and 4 feet horizontally from any opening to a building.
The heater should not be installed closer than 6 inches to any fences, walls or shrubs at any side or back, or any combustible material, nor closer than 18 inches at the plumbing side. A minimum clearance of 24 inches must be maintained at the front of the heater.
STACK TYPE OUTDOOR VENT KIT
ledoMpaCtneV.oNtcudorP.aiDtneV
05151VO732064.ni6
00202VO222064.ni7
05252VO322064.ni7
00303VO422064.ni8
05353VO522064.ni9
00404VO622064.ni01
Outdoor Stack
Top Cover
Flue Adaptor
Inner Panel
Flue Collector
Table 11.
DOOR
24"
Figure 12.
6"
6"
18"
IMPORTANT!
When locating the heater, consider that high winds can roll over or deflect off adjacent buildings and walls. Normally, placing the heater at least three feet from any wall will minimize downdraft.
Unusually high prevailing wind conditions and downdrafts may require the use of a stack type outdoor vent kit (available at additional cost).
NOTE
This unit shall not be operated outdoors at temperatures below 0o F. for propane and -20o F. for natural gas.
Figure 14.Figure 13.
OUTDOOR VENT CAP INSTALLATION
The MiniMax CH heater is shipped standard as an outdoor stackless unit. To install the outdoor vent kit:
1. Take out the louvered outer top after first removing all 1/4 in. sheet metal screws attaching it along its perimeter to the cabinet. Set it aside.
2. Place the flue adaptor over the flue collector opening. Temporarily, put the top cover, from the kit, on with the label to the front of the heater. Center the flue adaptor evenly inside the top cover flue stack opening. Remove the top cover and secure the centered flue adaptor to the inner panel with the provided #8 x 1/2 in. drill qwik screws.
3. Place the top cover, with the hole for the stack, on the heater cabinet.
4. Install the vent stack through the hole in the top cover, over the flue adaptor top ring.
5. Using a 3/32 in. drill bit, position the “L” bracket to hold the top cover and outdoor stack. Drill the pilot holes through the “L” bracket holes to accept the screws.
6. Secure the vent stack and the inner top with the #8 x 1/4 in. sheet metal screws through the “L” brackets.
P/N 472128 Rev. B 1-17-03
Installation (contd.)
Height above any roof surface within 10 ft. horizontally
Vent Cap
Ridge
Chimney
3 ft. min.
2 ft. min.
10 ft.
Roof Jack
More Than10 ft.
INDOOR INSTALLATION (USA ONLY) OUTDOOR SHELTER INSTALLATION (CANADA)
15
All products of combustion and vent gases must be completely removed to the outside atmosphere through a vent pipe which is connected to the draft hood. A vent pipe extension of the same size must be connected to the draft hood and extended at least 2 feet higher than highest point of the roof within a 10 foot horizontal radius, and at least 3 ft. higher than the point at which it passes through the roof, or as permitted by local code; see Figures 15 and 16. The vent should terminate with an approved vent cap (weather cap) for protection against rain or blockage by snow. Double-wall vent pipe and an approved roof jack shall be employed through the roof penetration. The use of double-walled type B vent pipe is recommended.
The draft hood must be installed so as to be in the same atmospheric pressure zone as the combustion air inlet to the pool heater. The certified (factory) draft hood must not be modified in any way and must be employed in every indoor installation.
Installations in basements, garages, or underground structures where flammable liquids may be stored must have the heater elevated 18 inches from the floor using a non-combustible base. The following minimum clearances from
combustible materials must be provided.
Side Front Back Top
Water Connection 18 in. 24 in.
Remaining 6 in. 6 in.
Ceiling Clearance 36 in.*
*To ceiling or roof.
The heater must be located as close as practical to a chimney or gas vent. The heater should be installed at least 5 feet away from the pool or spa.
Figure 15.
The heater must be placed in a suitable room on a non-combustible floor or on a non-combustible base and in an area where leakage from heat exchanger or water connections will not result in damage to the area adjacent to the heater or the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan with adequate drainage, be installed under the
* Rise
heater. The pan must not restrict air flow.
Rev. B 1-17-03 P/N 472128
* 1” Rise Per Foot
Recommended
Figure 16.
Vent Cap and Riser Furnished by Installer
Air Supply Ventilation
Air Supply Gas Combustion
Installation (contd.)
Screw (2 PLC's)
HEATER
Top Cover
Adaptor
Draft Hood
16
NOTE
The heater requires two uninterrupted air supply openings; one for ventilation and one to supply oxygen
for proper gas combustion. The air supply openings should be sized according to Tables 12. and 13.
Air supply requirements below apply to all
MiniMax heaters
All opening sizes are minimum and unobstructed.
edisnImorFriAllA
ledoM
noitsubmoCrofriA
.nI.qS
noitalitneVriA
.nI.qS
051051051
002002002
052052052
003003003
053053053
004004004
Table 12.
edistuOmorFriAllA
ledoM
noitsubmoCrofriA
.nI.qS
noitalitneVriA
.nI.qS
0517373
0020505
0523636
0037777
0530909
004001001
Table 13.
I
NSTALLATION ON FLOORS CONSTRUCTED
OF COMBUSTIBLE MATERIALS
b) Construct a non-combustible base from masonry
blocks as illustrated, see Figure 17.
BASE FOR USE ON COMBUSTIBLE FLOORS
T
O
H
TM
R E T A E
H E
C N A M
R O F
R E P H G I H
T
H E R
A
M O S T A
SP
T S E L
E C T
L
O
F
F O P
O
T O H
P M
E T A P S
D L O
C T O
SHEET METAL
BLOCKS
Figure 17.
H
P M E T
L O O P
D L O C
HOLLOW MASONARY BLOCKS, NOT LESS THAN 4" THICK (LAID WITH ENDS UNSEALED AND JOINTS MATCHED FOR AIR CIRCULATION). COVER BLOCKS WITH 24 GA. (MIN.) GALVANIZED SHEET METAL.
6" Min.
.
in
" M
6
CAUTION
Chemicals should not be stored near the heater installation. Combustion air can be contaminated by corrosive chemical fumes which can void the warranty.
STACK TYPE INDOOR DRAFT HOOD KIT
The proper draft hood and adapter must be installed on the heater as shown below:
ledoMdooHtfarD.oNtcudorP.aiDtneV
05151HD722064.ni6
00202HD822064.ni7
05252HD032064.ni7
00303HD132064.ni8
05353HD332064.ni9
00404HD432064.ni01
The heater may be placed on a “combustible floor”
Table 15.
using either of the two methods listed below:
INDOOR DRAFT HOOD INSTALLATION
a) Use Listed Factory Non-combustible Base Kit
for use on combustible floors.
ledoMtiKesaBelbitsubmoC-noN
051983174
002093174
052193174
003293174
053393174
004493174
Table 14.
P/N 472128 Rev. B 1-17-03
1. Take out the louvered outer top piece after first removing the sheet metal screws, attaching it to the cabinet.
2. Install the adaptor (vent kit).
3. Install the top cover (vent kit).
4. Install the draft hood (vent kit).
Use the provided screws to secure the vent assembly.
Figure 18.
Installation (contd.)
17
ELECTRICAL
MiniMax CH Millivolt Wiring Diagram
MINIMAX WIRING DIAGRAM (MILLIVOLT) DUAL THERM (HONEYWELL ELECTRONIC)
IF ORIGINAL FACTORY WIRING MUST BE REPLACED, INSTALLER MUST SUPPLY UL OR CSA (IF CANADA) APPROVED WIRE, 18 GAUGE, 600V, 105 C˚ TEMPERATURE RATING. THERMAL FUSE WIRING MUST BE REPLACED WITH UL OR CSA (IF CANADA) APPROVED WIRE, 18 GAUGE, 600V, 125 C˚ TEMPERATURE RATING. INTERCONNECTING WIRING TO APPLIANCE MUST CONFORM TO THE NATIONAL ELECTRICAL CODE OR SUPERCEDING LOCAL (WIRING) CODES.
PILOT
TH/PP
TH
GAS VALVE
WHT
RED
PP
GENERATOR
HI-LIMIT
SAFETY
SHUT-OFF
PRESS
SWITCH
ORN
WHT
WHT
PP
TH/PP
TH
THERMOSTAT BOARD
SEN
POT
WHT
POT 1
SENSOR
POT 2
WHT
WHT
THERMAL CUT-OFF
WHT
POOL
OFF
SPA
Figure 19.
NOTE: When connecting a remote control to the MiniMax CH, you must install the low voltage
thermostat wires in separate conduit from ANY line voltage wires. Failure to follow these instructions will cause the thermostat relay to react erratically..
Rev. B 1-17-03 P/N 472128
Troubleshooting - General
Possible Cause Remedy
Heater will not come on
Pump not running Place pump in operation
Pump air locked Check for leaks
Filter dirty Clean filter
Pump strainer clogged Clean strainer
Defective wiring or connection Repair or replace wires
Defective pressure switch Replace switch
Defective gas controls Call serviceperson
On-Off switch in "OFF" position Turn switch to "ON"
18
Heater Short Cycling (Rapid On and Off Operation)
Insufficient water flow Clean filter and pump strainer
Defective wiring Repair or replace wiring
Defective flow valve or out of adjustment Call serviceperson
Defective hi-limit and/or thermostat Call serviceperson
Heater Makes Knocking Noises, Make sure all valves on system are open
Heater operating after pump has shut off Shut off gas supply and call serviceperson
Heater exchanger scaled Shut off gas supply and call serviceperson
CAUTION
Please consult the latest edition of the “MiniMax Service Manual” for complete service and repair instructions. Repairs should only be attempted by properly trained service personnel.
P/N 472128 Rev. B 1-17-03
MINIMAX CH HEATER - ALL MODELS
32
H
O
T
31
30
19
SPOTRENNI
.oNledoM.oNtraP
051420074
002520074
052620074
003720074
053820074
004920074
1a
18
36
25
28
29
37
20
15
27 23 24
22
21
5
19
2
3
4
1
16
26
7
6
9
34
35
8
17
33
14
10
11
12
13
Rev. B 1-17-03 P/N 472128
MiniMax CH Parts List
METI NOITPIRCSED YTQ 051 002 052 003 053 004
1)roodni(.yssatiktneV1722064 822064 032064 132064 332064 432064
a1)roodtuo(.yssatiktneV1732064 222064 322064 422064 522064 622064
2redaehnruteR1499070 499070 499070 499070 499070 499070
3regnahcxetaeh,tloB61199174199174199174199174199174199174
4DO"1DI"8/3rehsaW61481270 481270481270481270481270481270
5teksaglaesebuT81159070 159070 159070 159070 159070 159070
6bonktatsomrehT2481074 481074 481074481074481074 481074
7)worhtelbuod&elopelgnis(rekcorhctiwS1681074681074681074681074681074681074
8tlovilliM-)etelpmoc(.yssalenaplortnoC1571274 471274371274271274171274071274
9tlovilliM-rooD1864570 406570 884570 506570 606570 094570
01renrubdlofinaM1652070 525570 752070 625570 725570 852070
20
11
21tlovilliM-ebuttoliP480670 480670 580670 580670 680670 680670
31
41renruB032070 032070 032070 032070 032070 032070
a41tekcarbtoliphtiwrenruB)nwohston(1055074055074055074055074055074055074
51hctiwserusserP1276174 276174 276174 276174 276174 276174
61)etelpmoc(.yssarebmahcnoitsubmoC1858370 685570 758370 785570 885570 658370
71.yssaretingietilsserP1954570 954570 954570 954570 954570 954570
81retemoitnetoP2876174 876174 876174 876174 876174876174
91.yssaevlavwolF1057174 057174 057174057174 057174057174
0511tatsomrehttimiL-iH1785174785174785174 785174785174 785174
12.ni2,daehklub-rotpadA2144174144174144174144174144174144174
22gnirdaehklub-rotpadA2044472044472 044472044472044472 044472
32.yssadlofinamniaM1399174399174399174399174399174399174
tlovilliM-larutanevlavsaG1754570 754570 754570 754570 754570 754570
tlovilliM-enaporpevlavsaG1854570 854570 854570 854570 854570 854570
tlovilliM-)etelpmoc(larutan.yssayartrenruB1394570 694570 494570 794570 894570 594570
tlovilliM-)etelpmoc(enaporp.yssayartrenruB1205570 505570 305570 605570 705570 405570
.AE2.AE3.AE4.AE5.AE6.AE7
42.yssaredaehniaM1299174 299174 299174299174299174299174
52mottobdlofinamniaM1914174914174914174914174914174914174
62mottobdlofinamniam,paC1024174024174024174024174024174024174
7051tatsomrehttimiL-iH1496174 496174 496174 496174 496174 496174
82
92
elffaB
03004noselffab)2(nwoddlohelffaB1018370 018370 018370 018370 018370 018370
P/N 472128 Rev. B 1-17-03
)sdaehtuohtiw(regnahcxetaeH1131274 231274331274431274531274 631274
)sdaehhtiw(regnahcxetaeH1961274 861274761274 661274561274 461274
.ae8.ae8.ae8.ae8.ae61.ae61
772070 955570 672070 065570 772070 872070
MiniMax CH Parts List, contd.
METI NOITPIRCSED YTQ 051 002 052 003 053 004
13rotcelloceulF1468370 226570 368370 326570 426570 268370
23.yssapotroodtuO1174074 274074 374074 474074 574074 674074
33)ylnostinusaGenaporP(dleihskcabthgiL1387570 487570 587570 687570 787570 887570
43)sledomtlovilliM(tatsomrehtcinortcelE1776174776174776174 776174776174 776174
53)nruter(lenaP1987370987370987370987370987370987370
63)tuo/ni(lenaP1721274721274721274721274721274721274
73)sledomtlovilliM(etelpmoc)eborp(rotsimrehT1101274101274101274101274101274101274
nwohStoN*
21
*
*
*
*
*
*
*
*
*
*
*
* *
*
*
*
"4/1x6wercS617170 617170 617170 617170 617170 617170
"2/1gnihsuB155070 155070 155070 155070 155070 155070
rotareneg-toliP1515170 515170 515170 515170 515170 515170
tekcarbgnitnuomcitsalP517070 517070 517070 517070 517070 517070
ssenraheriwrofspilC772174772174772174772174772174772174
tlovilliM-tiKeriW115570 115570 115570 115570 115570 115570
HH"4/1x8wercS307170 307170 307170 307170 307170 307170
HH"2/1x8wercS896170 896170 896170 896170 896170 896170
"4/1x23-01wercS956170 956170 956170 956170 956170 956170
61/3x23-01wercS296570 296570 296570 296570 296570 296570
reppotsbonkmrehT2414074414074414074 414074414074 414074
'4/3x81-"61/5tloB2527370 527370 527370 527370 527370 527370
.ae3
ProN
larutanrenrubniamecifirO727370 727370 727370 727370 727370 727370
enaporprenrubniamecifirO827370 827370 827370 827370 827370 827370
tlovilliM-larutan-toliP1292174292174292174292174292174292174
tlovilliM-enaporp-toliP1192174192174192174192174192174192174
.ae4
ProN
.ae5
ProN
.ae6
ProN
.ae7
ProN
.ae8
ProN
*
*
*
*
*
*
*
*
Rev. B 1-17-03 P/N 472128
dleihsniartoliP1392174392174392174392174392174392174
stekcarb"L"3045470045470045470045470045470045470
repmuJ352270352270352270352270352270352270
hctalrooD042170042170042170042170042170042170
knilelbisuf-ffotuclamrehT1371570 371570 371570 371570 371570 371570
)evlav-wolf(tnemelerewoP1871074871074871074871074871074871074
)ylno(edortceletoliP1823174823174823174823174823174823174
VM,tolip973QretpadatekcarB172174172174172174172174172174172174
NOTES
22
P/N 472128 Rev. B 1-17-03
Warning:
MiniMax® CH (150 IID Model)
POOL & SPA HEATERS
OPERATION & INSTALLATION MANUAL
(APPENDIX)
WARNING
FOR YOUR SAFETY - READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, personal injury or loss of life. For additional free copies of this manual; call (800) 831-7133.
1
23
1
U.S. Patent Numbers
6,295,980 5,318,007 - 5,228,618 5,201,307 - 4,595,825
WARNING
Warning: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or death. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
For Your Safety
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or other appliances.
Pentair Pool Products, Inc.
1620 Hawkins Ave., Sanford, NC 27330 (919) 774-4151
10951 W. Los Angeles Ave., Moorpark, CA 93021
(805) 523-2400
Rev. B 1-17-03 P/N 472128
A-1
Operation
24
MINIMAX CH (150 IID) ELECTRONIC IGNITION LIGHTING/OPERATION - NATURAL GAS
FOR YOUR SAFETY: READ BEFORE LIGHTING
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing personal injury, loss of life and property damage.
Do not attempt to light the heater if you suspect a natural gas leak. Lighting the heater can result in a fire or explosion which can cause personal injury, death, and property damage.
A. This heater is equipped with an ignition device
which automatically lights the pilot. Do not try to light the pilot by hand.
B. BEFORE OPERATING smell all around the
heater area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any heater.
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
- If you cannot reach your gas supplier, call the Fire Department.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off electric power to the heater.
4. This heater is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.
5. Remove the control access door.
6. Push in gas control knob slightly and turn clock­wise to “OFF”.
7. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in the safety information above. If you don't smell gas, go to the next step.
8. Turn knob on gas control counterclockwise to “ON”; see Figure 1.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it. Call a qualified service technician. Forced or attempted repair may result in a fire or explosion.
D. Do not use this heater if any part has been under
water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
E. The MiniMax CH incorporates (9) nine
indicator lights to aid you in the operation of the heater, and to assist in diagnosing a failure in the heater’s function.
9. Replace the control access door.
10. Turn on the electrical power to the heater.
11. Set the thermostat to the desired setting.
12. If the heater will not operate, follow the instruc­tions "To Turn Off Gas To Heater" and call your service technician or gas supplier.
Gas
Inlet
ON
OFF
Gas control knob shown in “ON” position.Figure 1.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the heater if service is to be performed.
3. Remove control access door.
P/N 472128 Rev. B 1-17-03
4. Push in gas control knob slightly and turn clockwise to "OFF". Do not force.
5. Replace control access door.
A-2
Operation (contd.)
25
MINIMAX CH (150 IID) ELECTRONIC IGNITION LIGHTING/OPERATION - PROPANE
FOR YOUR SAFETY: READ BEFORE LIGHTING
NOTE
The MiniMax CH propane models have special features for additional safety and protection. Read the safety instructions for natural gas (page A-2) before proceeding.
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing personal injury, loss of life and property damage.
Since propane gas is heavier than air, escaping propane will accumulate and remain at ground level. Do not attempt to light the heater. If you suspect a propane leak, lighting the heater can result in a fire or explosion which can cause personal injury, death, and property damage.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light matches or lighter.
- Do not try to light any heater.
- Do not touch any electrical switch; do not use any phone in your building.
- Shut off gas line at propane tank.
Safety Lockout:
- Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
- If you cannot reach your gas supplier, call the Fire Department.
- Do not tamper with the heater because it is dangerous and voids all warranties.
This MiniMax CH Propane Heater is equipped with a 100% safety lockout feature. If the pilot does not light within a maximum of 90 seconds, lockout will occur.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off electric power to the heater.
4. This heater is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.
5. Remove the control access door.
6. Push in gas control knob slightly and turn clock­wise to “OFF”.
7. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in the safety information on page 5. If you don't smell gas, go to the next step.
8. Turn knob on gas control counterclockwise to “ON”; see Figure 2.
9. Replace the control access door.
10. Turn on the electrical power to the heater.
11. Set the thermostat to the desired setting.
12. If the heater will not operate, follow the instruc­tions "To Turn Off Gas To Heater" and call your service technician or gas supplier.
Gas
Inlet
ON
OFF
Gas control knob shown in “ON” position.Figure 2.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the heater if service is to be performed.
3. Remove control access door.
Rev. B 1-17-03 P/N 472128
4. Push in gas control knob slightly and turn clockwise to "OFF". Do not force.
5. Replace control access door.
A-3
Operation (contd.)
OPERATING (CONTROLS)
Dual Temperature Control System - (Electronic and Millivolt Models)
For convenience and economy all MiniMax CH heaters are equipped with two thermostats on the front of the heater control panel; see Figure 3.
Figure 3.
THERMOSTAT KNOB STOPPER
Each thermostat is equipped with a mechanical stop that can be locked or unlocked with use of a screwdriver to prevent temperatures in excess of that desired by the user; see Figure 4.
The maximum setting can be adjusted by loosening the screw "A" and turning the stopper dial to desired maximum setting. Lock the setting by tightening the screw. The Mechanical stop is under the knob. Ensure that the knob is stopping at the correct position when the knob is rotated clockwise from a lower temperature position. (See Thermostat Adjustment.)
NOTE To eliminate error due to piping heat losses, measure pool temperature with an accurate thermometer directly at the pool or spa.
THERMOSTAT ADJUSTMENT
The knob with locking feature eliminates the need for constant thermostat adjustments. Set the knob pointer to the desired pool or spa temperature. If further adjustment is needed, rotate the knob until the desired temperature is obtained. This knob position corresponding to your desired maximum pool or spa temperature may now be preset (locked) by the knob stopper which prevents the knob from being turned beyond the maximum temperature you set.
Knob Stopper
Figure 4.
Screw A
POWER (THERMOSTAT SELECT) SWITCH
The Pool/Off/Spa switch allows the heater to be turned off when heating is not desired.
1. “Pool” position - Maintains selected pool temperature.
2. “Off” position - Heater will not come on regardless of drop in pool or spa temperature.
3. “Spa” position - This allows separate control of spa water temperature.
26
INDICATOR LIGHT DESCRIPTION
The MiniMax Pool Heater provides nine status indicator lights, six can be seen from the front of the control panel which help you understand the operation of the heater. If something should go wrong, the lights will aid in troubleshooting the problem. Three additional lights can be seen after opening the control panel. These three lights give the service technician
advanced troubleshooting capability. All the LED lights are green with the exception of the red service LED.
POWER LIGHT (POWER)
The light is on at all times, in any switch position, indicating 24 VAC power is being supplied to the control circuit. If it fails to light, no other light will be on. Possible causes are: a) external power to the heater is disconnected, check service panel circuit breaker or fuses; b) local circuit breaker inside the transformer has tripped -- investigate cause before resetting; c) transformer has failed.
THERMOSTAT (TSTAT)
This light is on when the thermostat contacts close, signaled by the water temperature falling below the setpoint, calling for the heater to fire to maintain the desired water temperature.
P/N 472128 Rev. B 1-17-03
AUXILIARY (AUX)
This light is on when it indicates the remote switch contacts are closed. This allows you to observe if your remote switch is properly closing the heater control circuit. When shipped from the factory a jumper is installed to maintain closed circuit in the absence of a remote switch.
PRESSURE (PRESS)
This light is on when Spa/Pool Selector switch is on, indicates the circulation pump is running properly. If pressure light fails to light, the pump may have lost its prime or water flow may be restricted by an inadvertently closed valve or clogged filter or pump basket. If you have determined that there is no water flow restriction to the heater, you should call a qualified serviceman.
A-4
Operation (contd.)
27
HEAT (HEAT)
The heat light is on any time the thermostat has signaled a call for heat which initializes the ignition safety firing circuit -- the light comes on to indicate successful firing of the main burners.
TROUBLESHOOTING (CONTROLS)
Example of troubleshooting with the assistance of the indicator lights.
SYMBOL TABLE
SWITCH OR DEVICE
LED LIT
LED OFF
OPEN CIRCUIT (BLOCK CURRENT)
SERVICE (SERVICE)
The service light is off during normal operation of heater. The light only comes on if a problem with a control has occurred or when the heater is first firing. The problem must be investigated by the serviceman prior to attempts to fire the heater again.
The diagrams that follow give examples of troubleshooting a malfunctioning heater using the assistance of the indicator lights.
SWITCH OR DEVICE CLOSED CIRCUIT (PASS CURRENT)
IGNITION MODULE
THERM
AUX
PRESS
HEAT
THERM
AUX
INCOMING
LINE VOLTAGE
INCOMING
LINE VOLTAGE
TRANSFORMER
FRONT PANEL LEDS
TRANSFORMER
POWER
SERVICE
POWER
SERVICE
CIRCUIT
THERMOSTAT
PWR TSTAT RMT PRESS
REMOTE PRESS TFUSE
RELAY
SRVE
LIMIT SWITCHESBREAKER
HI TEMP
HI TEMP TFUSE
CLOSE IF NO MV
IND GND VAL
MV HEAT
THERMOSTAT CIRCUIT BOARD
WATER AT SELECTED TEMPERATURE.... NORMAL OPERATION
OR POOL/OFF/SPA THERMOSTAT SELECT SWITCH OFF.... NORMAL OPERATION
IGNITION MODULE
GND VAL
CIRCUIT BREAKER
PWR
THERMOSTAT
RELAY
TSTAT RMT
REMOTE
PRESS
PRESS
LIMIT SWITCHES
SRVE
HI TEMP
HI TEMP
CLOSE IF NO MV
TFUSE
IND
HEAT
MVTFUSE
GAS VALVE
MV
MV
GAS VALVE
MV
MV
PRESS
HEAT
FRONT PANEL LEDS
THERMOSTAT CALLING FOR HEAT - PUMP OFF(NO PRESSURE) BLOCKS FIRING NORMAL OPERATION
Rev. B 1-17-03 P/N 472128
THERMOSTAT CIRCUIT BOARD
A-5
Operation (contd.)
TROUBLESHOOTING (CONTROLS) - Continued
SYMBOL TABLE
THERM
AUX
PRESS
HEAT
INCOMING
LINE VOLTAGE
TRANSFORMER
FRONT PANEL LEDS
POWER
SERVICE
SWITCH OR DEVICE
RMT
OPEN CIRCUIT (BLOCK CURRENT)
PRESS
PRESS
CIRCUIT BREAKER
PWR
LED LIT
THERMOSTAT
RELAY
TSTAT
LED OFF
REMOTE
THERMOSTAT CIRCUIT BOARD
HEATER FIRING - NORMAL OPERATION
LIMIT SWITCHES
SRVE
HI TEMP
HI TEMP
CLOSE IF NO MV
SWITCH OR DEVICE CLOSED CIRCUIT (PASS CURRENT)
IND
TFUSE
TFUSE MV
IGNITION MODULE
GND
HEAT
28
VAL
GAS VALVE
MV
MV
THERM
AUX
PRESS
HEAT
INCOMING
LINE VOLTAGE
TRANSFORMER
POWER
SERVICE
FRONT PANEL LEDS
IGNITION MODULE
GND
CIRCUIT BREAKER
PWR
THERMOSTAT
RELAY
TSTAT
REMOTE
RMT
PRESS
PRESS
THERMOSTAT CIRCUIT BOARD
LIMIT SWITCHES
SRVE
HI TEMP
HI TEMP
CLOSE IF NO MV
IND
TFUSE
TFUSE MV
VAL
HEAT
THERMOSTAT CALLING FOR HEAT - BLOWN THERMAL FUSE BLOCKS FIRING NOTE: SERVICE LED LIT FLAGS PROBLEM, TFUSE LED OFF SHOWS PROBLEM
IS IN THERMAL FUSE CIRCUIT
GAS VALVE
MV
MV
P/N 472128 Rev. B 1-17-03
A-6
HONEYWELL
PILOT
1/2 P.S.I.
PILOT ADJ.
REGULATOR
ADJUSTMENT CAP
PRESS TAP
Installation
REGULATED MANIFOLD PRESSURE TEST
1. Attach the manometer to the heater jacket.
2. Shut off the main gas valve.
3. Remove 1/8 in. NPT plug on the outlet side of the valve and screw in the fitting from the manometer kit.
4. Connect the manometer hose to the fitting.
5. Fire the heater.
6. The manometer must read 4 in. WC for natural gas, 11 in. WC for propane gas, while the heater is operating.
7. For adjustment, remove the Regulator Adjustment Cap and using a screwdriver turn the screw clockwise to increase ­counterclockwise to decrease gas pressure.
1/8" NPT Plug (Inlet Press)
Regulator Adjustment Cap
1/8" NPT Plug (Manifold Press)
29
ON
OFF
ELECTRICAL, IID ELECTRONIC UNITS
Electrical Rating
60 Hz 115 V.A.C. or 230 V.A.C. 50/60 Hz 208 V.A.C. or 240 V.A.C.
NOTE
If any of the original wiring supplied with this heater must be replaced, installer must supply (No. 18 AWG 105° C. U.L. approved AWM low energy stranded) copper wire or it's equivalent.
In Canada: wires must be CSA approved.
WARNING
The heater must be electrically grounded and bonded in accordance with local codes or, in the absence of local codes, with the latest national electrical codes ANSI/NFPA No. 70.
In Canada: CSA standard C22.1 Canada Electrical Code Part 1 and/or local codes.
Transformer Wiring Instruction
Always use crimp type connectors when connecting two wires.
This heater is equipped with a reversible junction box to allow line voltage to be wired from either side.
Rev. B 1-17-03 P/N 472128
Figure 5.
A-7
Figure 6.
Installation (contd.)
MiniMax CH (150 IID Model) Electronic Ignition Wiring Diagram
MV/PV
PV/MV
MV
GAS VALVE
PLUG
PV
MV
IGNITION MODULE
PLUG
PV
GND
(BURNER)
GND
24 V
TH-W
( OPT )
SPARK
30
SPARK IGNITER
MV
PV
GRN
PV/MV
MV/PV
MV
PV
F2
BLU
RED
WHT
IGNITION RETURN
GRN
THERMAL FUSE
F1
ORG
RED
BLU
WHT
MiniMax Plus WIRING DIAGRAM
MiniMax CH 150 IID Wiring Diagram
RED
L1-2
L1-1
RED
WHT
L2-2
L2-1
WHT
W2
SWITCH
WATER PRESSURE
W1
WHT
ORG
INTERCONNECTING WIRING TO APPLIANCE MUST CONFORM TO THE NATIONAL ELECTRICAL
CODE OR SUPERCEDING LOCAL (WIRING) CODES.
THERMAL FUSE WIRING MUST BE REPLACED WITH UL OR CSA (IF CANADA) APPROVED
IF ORIGINAL FACTORY WIRING MUST BE REPLACED, INSTALLER MUST SUPPLY
WIRE, 18 GAUGE, 600V, 125 C TEMPERATURE RATING..
UL OR CSA (IF CANADA) APPROVED WIRE, 18 GAUGE, 600V, 105 C TEMPERATURE RATING.
CHASSIS
THERMAL SWITCHES
SHEET METAL
HIGH LIMIT
4 3 2
P11
1
3 2
PI0
1 6
5 4
P7
3 2 1 2 1
P4
IGNITION WIRE
J11
IGN MODULE
1
JI0
1
TFUSE HLMT
J7
PRESS
1
J4
1
24V VLV
J3
J2
AUX.
CONTACTS
THERMOSTAT
CIRCUIT BOARD
J9
TPROBE
J5
POOL
J8
COM
J6
SPA
FOR HEAT
CONTROL RELAY
CLOSE ON CALL
PROBE
TEMPERATURE
BLK
BLK
P9
P5
P8
P6
POOL OFF SPA
THERMOSTAT SELECT SWITCH
GRN
T1
CHASSIS
SHEET METAL
TERMINATE SUPPLY SAFETY GROUND WIRE (GREEN) HERE
GROUND SCREW WITH PAINT CUTTING WASHER
EXTERNAL
BOND LUG
RED
WHT/RED
P/N 472128 Rev. B 1-17-03
WHT/BLK
T2
BLK
25D K .032 D.C TAB
JUMPER REQUIRED IF NO REMOTE SWITCH
SPST. EXTERNAL ON/OFF SWITCH
A-8
Installation (contd.)
31
REMOTE SWITCH DUAL THERM IID ONLY
3 Wire Remote
REMOTE POOL/OFF/SPA
THERMOSTAT SELECT SWITCH
JUMPER REQUIRED IF NO 2 WIRE REMOTE SWITCH
OUT RETURN
EXT SWITCH
24 VAC
PRESS
HILMT
TFUSE VALVE
THERMOSTAT CIRCUIT BOARD
SPA COM POOL TPROBE
IGNITION MOD
FRONT PANEL POOL/
OFF/SPA THERMOSTAT SELECT SWITCH
Figure 7.
2 Wire Remote
JUMPER REQUIRED IF NO 2 WIRE REMOTE SWITCH
OUT RETURN
EXT SWITCH
24 VAC
PRESS
HILMT
TFUSE VALVE
THERMOSTAT CIRCUIT BOARD
SPA COM POOL TPROBE
FRONT PANEL POOL/OFF/SPA THERMOSTAT SELECT SWITCH
IGNITION MOD
Figure 8.
NOTE: When connecting a remote control to the MiniMax CH, you must install the low voltage
thermostat wires in separate conduit from ANY line voltage wires. Failure to follow these instructions will cause the thermostat relay to react erratically..
Rev. B 1-17-03 P/N 472128
A-9
MINIMAX CH HEATER - 150 IID MODEL
32
H
O
T
31
30
32
POTRENNI
.oNledoM.oNtraP
051420074
1a
18
36
25
28
29
37
20
15
27 23 24
22
21
5
19
2
3
4
1
16
6
7
34
9
8
35
37
26
33
14
10
11
12
P/N 472128 Rev. B 1-17-03
13
A-10
17
38
MiniMax CH Parts List - 150 IID Model
METI NOITPIRCSED YTQ 051
1)roodni(.yssatiktneV1722064
a1)roodtuo(.yssatiktneV1732064
2redaehnruteR1499070
3regnahcxetaeh,tloB61199174
4DO"1DI"8/3rehsaW61481270
5teksaglaesebuT81159070
6ledoMDII-draobtiucrictatsomrehTcinortcelE1971074
7)worhtelbuod&elopelgnis(rekcorhctiwS1681074
33
8
larutaNDII-)etelpmoc(.yssalenaplortnoC1151274
enaporPDII-)etelpmoc(.yssalenaplortnoC1191274
9DIIrotlovilliM-rooD1864570
01renrubdlofinaM1652070
DII-larutaNevlavsaG1899370
11
DII-enaporPevlavsaG1999370
21DII-ebuttoliP 191570
DII-)etelpmoc(larutaN.yssayartrenruB1257370
31
DII-)etelpmoc(enaporP.yssayartrenruB1609370
41renruB 032070
a41tekcarbtoliphtiwrenruB)nwohston(1055074
51hctiwserusserP1276174
61)etelpmoc(.yssarebmahcnoitsubmoC1858370
71egatlovlaud-rekaerbtiucric/w-remrofsnarT1063174
81bonktatsomrehT2481074
91.yssaevlavwolF1057174
.AE2
0511tatsomrehttimiL-iH1785174
12.ni2,daehklub-rotpadA2144174
22gnirdaehklub-rotpadA2044472
32.yssadlofinamniaM1399174
42.yssaredaehniaM1299174
52mottobdlofinamniaM1914174
62mottobdlofinamniam,paC1024174
7051tatsomrehttimiL-iH1496174
82
92
elffaB
03004noselffab)2(nwoddlohelffaB1018370
Rev. B 1-17-03 P/N 472128
)sdaehtuohtiw(regnahcxetaeH1131274
)sdaehhtiw(regnahcxetaeH1961274
.ae8
772070
A-11
MiniMax CH Parts List - 150 IID Model, contd.
METI NOITPIRCSED YTQ 051
13rotcelloceulF1468370
23.yssapotroodtuO1174074
33)ylnostinusaGenaporP(dleihskcabthgiL1387570
34
43
53)nruter(lenaP1987370
63)tuo/ni(lenaP1721274
73DII-etelpmoc)eborp(rotsimrehT1665174
83xoBnoitcnuJ1221074
nwohStoN*
*
*
*
*
*
*
*
*
*
*
*
* *
*
*
*
*
*
*
*
*
*
*
*
"2/1gnihsuB 155070
stekcarb"L"3045470
repmuJ 352270
hctalrooD 042170
saGlarutaNeludoM1485370
saGenaporPeludoM1585370
tekcarbgnitnuomcitsalP 517070
ssenraheriwrofspilC 772174
tlovilliM-tiKeriW 115570
HH"4/1x8wercS 307170
HH"2/1x8wercS 896170
"4/1x6wercS 617170
"4/1x23-01wercS 956170
61/3x23-01wercS 296570
reppotsbonkmrehT2414074
'4/3x81-"61/5tloB2527370
larutanrenrubniamecifirO 727370
enaporprenrubniamecifirO 827370
tlovilliM-larutan-toliP1292174
tlovilliM-enaporp-toliP1192174
rotareneg-toliP1515170
knilelbisuf-ffotuclamrehT1371570
)evlav-wolf(tnemelerewoP1871074
dleihsniartoliP1392174
)ylno(edortceletoliP1823174
VM,tolip973QretpadatekcarB 172174
.ae3
ProN
P/N 472128 Rev. B 1-17-03
A-12
NOTES
35
Rev. B 1-17-03 P/N 472128
A-13
MiniMax® CH Heaters
Limited Warranty
Your MiniMax CH pool heater is another quality product from Pentair Pool Products, Inc. and is backed by the following warranty.
1. The following parts are warranted for 5 years from date of purchase:
The MiniMax CH cabinet and combustion chamber, the main burners and burner manifold, the inlet/outlet header and the return header. This warranty does not cover rusting or corrosion on cabinets or burners that does not affect the heater's operation.
40
36
2. The following parts are covered for 2 years from date of purchase:
The automatic flow control valve, all controls, heat exchanger, pilot generator and the pilot assembly.
This warranty only applies to the original purchaser.
3. This warranty shall not apply to any units or parts which have been subject to accident, negligence, alteration, abuse, misapplication or misuse.
The above warranty applies only if the heater is installed and operated in complete compliance with the installation and operation manual provided with each unit. Copies of this manual are available by writing to Pentair Pool Products, Inc., at the address below.
Pentair Pool Products, Inc. assumes no liability except for the repair or replacements of parts as specified above. Ship defective parts or equipment along with serial number and purchase date, transportation prepaid to the address below. Purchaser shall be responsible for freight charges for return of merchandise to purchaser. Some states do not allow exclusion or limitation of incidental or consequential damages so the above may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
HEATER SERIAL NUMBER
(Please Fill In)
Pentair Pool Products, Inc.
1620 Hawkins Ave., Sanford, NC 27330 (919) 774-4151
10951 W. Los Angeles Ave., Moorpark, CA 93021
P/N 472128 Rev. B 1-17-03
(805) 523-2400
Loading...