Pentair Hydromatic S4S, Hydromatic SB4S Installation And Service Manual

Pump Installation and Service Manual
S4S/SB4S
Submersible Sewage Pump
S4S Shown
NOTE! To the installer: Please make sure you provide this manual to the owner of the pumping equipment or to the responsible party who maintains the system.
Item # E-03-321 04/09
General Information
Thank you for purchasing your Hydromatic ensure years of trouble-free operation, please read the following manual carefully.
Before Operation:
Read the following instructions carefully. Reasonable care and safe methods should be practiced. Check local codes and requirements before installation.
Attention:
This manual contains important information for the safe use of this product. Read this manual completely before using this product and refer to it often for continued safe product use. DO NOT THROW AWAY OR LOSE THIS MANUAL. Keep it in a safe place so that you may refer to it often.
Unpacking Pump:
Remove pump from carton. When unpacking unit, check for concealed damage. Claims for damage must be made at the receiving end through the delivery carrier. Damage cannot be processed from the factory.
WARNING: Before handling these pumps and controls, always disconnect the power first. Do not smoke or use sparkable electrical devices or flames in a septic (gaseous) or possible septic sump.
®
pump. To help
Pumps Not Operating or in Storage:
Pumps with carbon ceramic seals must have impellers manually rotated (6 revolutions) after setting non-operational for 3 months or longer and prior to electrical start-up.
Pump:
The S4S/SB4S submersible pumps are supplied for 1 and 3 phase and for 200, 230, 460 or 575 volts. Pump is supplied with 15 feet of power cord. Longer cable lengths can be furnished but must be specified at time of order. Power cable is 4 wire with the green wire for ground. Be sure green wire is connected to a ground lug in the control panel and the control panel must be connected to a ground rod or ground wire from supply service.
NOTE: All single phase pumps require properly sized start capacitor, start relay and run capacitor in the panel.
Sump Level Control:
Sump level is controlled by Hydromatic 3900 mercury switch level controls. The 3900 level controls is a metal case mercury switch sealed in a solid polyurethane float. The float is held in position by a weight attached to the power cord above the float. The cord supports the float and is adjusted for height from the surface.
Typical duplex systems use three floats: the lowest float turns the pumps off, the next higher float starts the lead pump, the next higher float (override) starts the lag pump. The pumps alternate on successive cycles.
Two pumps operate together only if sump level rises to the third or override float. The override float also brings on the second pump in case of failure of the first pump. Extra floats with appropriate controls can be supplied for alarm functions. Triplex systems use four floats. The fourth highest float brings on the second lag pump. Three pumps operate together only if sump level rises to the fourth float (second override). This float also brings on the third pump in case of failure of either or both of the first two pumps.
Alarm Controls:
The alarm float is usually set above the override level so the alarm will signal only if the override level is exceeded. However, some engineers prefer to have the alarm float set below the override level as it is possible for one pump to fail and the other pump to operate on the override level with the sump level never reaching the alarm level. This is particularly true in cases of low inflow capacity.
Electrical Control Panel:
It is recommended that the Hydromatic control panel be used with all pumps as proper start components and pump protection are furnished.
NOTE: All single phase pumps require properly sized start capacitor, start relay, and run capacitor in the control panel.
IMPORTANT: If Hydromatic control panel is not used and the motor fails because of improper components, the motor guarantee is void.
2
Hydromatic electrical equipment is installed in a weatherproof enclosure. The electrical equipment includes a main circuit breaker for each pump, a magnetic starter with overload protection for each pump, an H-O-A switch and run light for each pump, an electric alternator and a transformer to provide appropriate control for control circuit and alarms.
Overload Heaters:
If a Hydromatic control panel is not used, on three phase pumps all three phases must have overload protection. The overload should be ambient compensated class 10. The heater's full load amps on the pump must be sized in accordance with the nameplate amps on the motor housing. The amp draw on these submersible motors is slightly higher than a corresponding horsepower surface motor, so heaters must be sized by the nameplate full load amp rating.
Installing:
Before installing pump in sump, lay it on side and turn impeller with fingers. Impeller may be slightly stuck due to factory test water, so it must be broken loose with small bar or screwdriver in edge of vanes. The impeller should turn freely.
Clean all trash and sticks from sump and connect pump to piping.
A check valve must be installed on each pump. A gate or plug valve in each pump discharge line is also recommended. This valve should be installed on the discharge side of the check valve so if necessary to service the check valve, the line pressure can be cut off. Single pump systems are sometimes installed without a check valve where it is desirable
Pump Installation
to self-drain the discharge line to prevent freezing. This can be done only with short discharge lines. Otherwise water will return to the sump and cause short cycling of the pump.
NEMA 4 Junction Box (Optional):
If electrical control panel is to be set remote from the pump sump, a NEMA 4 junction box should be used to make power and control connections. The Hydromatic NEMA 4 junction box is provided with compression connectors for sealing all wires. No sealing compound is needed to make connections waterproof.
Wiring diagrams are provided with the panel for making connections. An extra set of diagrams is included so that one set can be used during installation when making connections. The size of any additional wiring from the pump cord to the panel is
Single phase pumps with capacitor start circuit must have the overload protection on the black pump lead.
NOTE: On single phase pumps the white, black, and red pump leads must be connected properly for the pump to run.
3
Pump Installation
based on the distance and pump current. Double check that all wiring is properly connected and tight. NOTE: On single phase pumps the white, black and red pump wires must be connected properly to the panel. Only the proper sequence will work.
Installing 3900 Mercury Switch Float:
The float cords are supported by a mounting bracket that is attached to sump wall or cover or to the NEMA 4 junction box.
Cord snubbers are used to hold the cord in place. Float level can be
changed at any time by loosening the snubber and readjusting cord length.
In either simplex or duplex system the lower or turn-off float is set just above the top of volute so that the volute will always be submerged during the pumping cycle. The second or lead/on float higher is set at about 24 inches above the lower turn-off control.
More distance between turn-on and turn-off controls can be used, but sewage may become septic and excessive solids may collect for the pump to handle. A frequent pumping cycle is recommended for best operation.
If an alarm system is used, this control is usually set about 6 inches above the override control.
Some engineers as described previously prefer to have the alarm control set below the override control.
Making Electrical Connections:
All electrical wiring must be in accordance with local code, and only competent electricians should make the installations. A set of prints is included for use in making the installation. All wires should be checked for grounds with an ohmmeter or Megger after the connections are made.
This is important, as one grounded wire can cause considerable trouble.
IMPORTANT: If equipment is not properly wired and protected as recommended, the motor guarantee is void.
WIRE SIZE TABLE
FOR REMOTE LOCATION OF CONTROL PANEL; LENGTHS ARE BASED ON A VOLTAGE DROP OF TWO PERCENT
Maximum length in feet from NEMA 4 junction box to control panel. For 3 phase only and for power lines only. All control wires can be = 14–16 or 18 gauge wire. If power lines are for 460 or 575 volts insulation of control wires must be for this voltage if used in conduit with power lines.
Volts 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575
Wire Motor
Size HP 33355571⁄271⁄271⁄210 10 10 15 15 15 20 20 20 25 25 25 30 30 30 35 35 35
12 110 450 700 90 370 580
10 180 720 1120 140 550 370 90 360 560 50 220 340
8 270 1100 1650 220 900 1400 175 700 1100 105 420 650 320 500 230 360 180 280
6 400 1600 2500 350 1400 2200 220 900 1400 150 600 930 105 420 650 90 370 570 360 560 320 500 230 360
4 370 1500 2300 230 950 1450 175 700 1100 140 550 850 125 500 800 100 400 620 90 360 560
2 370 1500 230 270 1100 1700 220 900 1400 210 820 1250 200 800 1250 150 600 930
*Special Junction Box required for wire sizes larger than #4.
NUMBER OF CONDUCTORS REQUIRED BETWEEN CONTROL PANEL
AND NEMA 4 JUNCTION BOX
System Number of Number of Number of
Type Control Wires Power Lines Ground Wires #8
Simplex 3 3 1
Simplex with Alarm 5 3 1
Duplex 5 6 1
Duplex with Alarm 7 6 1
4
Loading...
+ 8 hidden pages