Pentair Hydromatic S4MN Installation And Service Manual

MODEL S4MN
SUBMERSIBLE SOLIDS HANDLING PUMP
INSTALLATION AND SERVICE MANUAL
NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system.
Item # E-03-311 | Part # 5625-311-1 | © 2013 Pentair Pump Group, Inc. | 11/11/13
Attention:
This manual contains important information for the safe use of this product. Read this manual completely before using this product and refer to it often for con tin ued safe product use. DO NOT THROW AWAY OR LOSE THIS MAN U AL. Keep it in a safe place so that you may refer to it often. Reasonable care and safe meth ods should be practiced. Check local codes and requirements before installation.
Unpacking Pump:
Remove pump from carton. When un pack ing unit, check for con cealed damage. Claims for damage must be made at the receiving end through the delivery carrier. Dam age cannot be processed from the factory.
WARNING: Before handling these pumps and controls, always disconnect the power first. Do not smoke or use sparkable electrical devices or flames in a septic (gaseous) or possible septic sump.
CALIFORNIA PROPOSITION 65 WARNING:
This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
Pumps Not Operating or in Storage:
Pumps with carbon ceramic seals must have impellers manually rotated (6 revolutions) after setting non­operational for 3 months or longer and prior to electrical start-up.
Pumps with tungsten carbide seals must have impellers manually rotated (6 revolutions) after setting non­operational for 3 weeks or longer and prior to electrical start-up.
Seal Failure:
An electrode is installed in the seal chamber so if any water enters the chamber through the first seal the electrode will be energized and a signal will be trans mitted to the sen sing unit at ground surface causing a red light to turn on. The electrode probe is installed in all units, but the sensing unit is sup plied at extra cost and must be ordered.
In operation the seal failure unit in dicates only that there is some water in the seal chamber. The pump will con tin ue to operate but the seal should be checked immedi ate ly after failure is indicated.
The sensing unit is recommended on all installations as good insurance against motor failure.
Pump:
The S4MN submersible pump is supplied for 1 and 3 phase and for 200, 230, 460 or 575 volts. Power cable is supplied with the green wire for ground. Be sure green wire is connected to a good ground such as water pipe or ground stake.
Heat Sensors:
All motors have heat sensor units em bedded in the motor winding to detect ex ces sive heat. The heat sen sors are set to trip at 120°C on the S4MN. The sensors au to mat i cal ly reset when motor cools to safe tem per a ture.
The sensors are connected in series with the motor starter coil so that the starter is tripped if heat sensor opens. The motor starter is equipped with overload heaters so all normal over loads are protected by the starter.
IMPORTANT: If Hydromatic electrical starting equip ment is not supplied, the heat sensor circuit must be connected in series with the starter coil or warranty is void.
Sump Level Control:
Sump level is controlled by Hydromatic switch controls. The float is held in position in the sump by a weight attached to the power cord above the float. The cord supports the float and is adjusted for height from the surface.
Duplex systems use three controls: one set at turn-off, one set at turn-on for one pump, and one set for turn-on for two pumps. Pumps alternate op er a tion on each successive cycle.
Two pumps operate together only if sump level rises to the third or over ride control. The override control also brings on the second pump in case of failure of the first pump. Extra floats with ap pro pri ate controls can be supplied for alarm functions. Triplex systems use four controls: one set at turn-off, one set at turn-on for one pump, one set at turn-on
®
for two pumps, and one set at turn-on for three pumps. Pumps alternate each successive cycle.
Three pumps operate together only if sump level rises to the fourth control (second override). This control also brings on the third pump in case of failure of either or both of the first two pumps.
Alarm Controls:
The alarm level is usually set above the override level so the alarm will signal only if the override level is exceeded. However, some engineers prefer to have the alarm level set below the override level as it is pos si ble for one pump to fail and the other pump to operate on the override level with the sump level never reach ing the alarm level. This is par tic u lar ly true in cases of low inflow capacity.
Electrical Control Panel:
It is recommended that the Hydromatic control panel be used with all pumps as proper starter heat ers and connections for heat sensor wires are fur nished.
Hydromatic electrical equipment is installed in a weatherproof NEMA 3R enclosure. The electrical equip ment includes a main circuit breaker for each pump, a magnetic starter with overload protection for each pump, an H-O-A switch and run light for each pump, and an electric alternator and a transformer to provide appropriate control for control circuit and alarms.
Overload Heaters:
Starters with 3 leg overload protection must be supplied if the Hydromatic electrical panel is not used. The heaters must be sized in accordance with the nameplate amps on the motor. The amp draw on these submersible motors is slightly higher than a corresponding horsepower surface motor, so heaters must be sized by the nameplate rating.
2
Installation
WIRE SIZE TABLE
FOR REMOTE LOCATION OF CONTROL PANEL
LENGTHS ARE BASED ON A VOLTAGE DROP OF TWO PERCENT
Maximum length in feet from NEMA 4 Junction Box to control panel. All control wires can be = 14-16 or 18 gauge wire. If power lines are greater the 300 volts, and the control wires are used in the same conduit, then the insulation of the control wires must be for 600 volts.
1 Phase 3 Phase HP HP Wire Size Volts 11/2 2 3 5 Volts 11/2 2 3 5 71/2 10 15 200V - - - - 200 217 190 101 - - - - 230 105 95 - - 230 291 250 134 - - - -
12 460 1165 1019 540 412 333 233 -
575 1820 1450 820 624 515 364 - 200 121 111 103 - 200 340 297 158 119 - - - 230 163 148 139 - 230 456 390 210 161 - - -
10 460 1822 1594 846 645 522 364 -
575 2847 2270 1360 976 806 569 - 200 190 175 162 - 200 533 466 249 187 155 - - 230 257 232 219 - 230 715 613 330 252 204 - -
8 460 2860 2500 1328 1013 819 572 390
575 4468 3570 2145 1532 1266 894 - 200 296 272 252 - 200 830 726 387 291 242 170 - 230 400 362 340 181 230 111 4 955 514 393 318 223 -
6 460 4455 3898 2068 1577 1275 891 607
575 - - 3341 2386 1972 1392 - 200 452 416 384 - 200 1268 1110 592 444 370 260 - 230 610 553 520 276 230 1701 1458 785 601 486 340 232
4 460 - - 3160 2410 1449 1361 928
575 - - - 3646 2513 2127 - 200 689 633 586 - 200 1932 1690 902 676 563 395 - 230 930 842 792 421 230 2592 2222 1196 915 741 578 353
*2 460 - - - 3672 2969 2074 1414
575 - - - - 4590 3240 -
*Special Junction Box required for wire sizes larger than #4.
NUMBER OF CONDUCTORS REQUIRED BETWEEN CONTROL PANEL AND NEMA JUNCTION BOX
POWER LINES AND CONTROL WIRES CAN BE CARRIED IN CONDUIT OR CAN BE UNDERGROUND BURIED CABLE
HEAT SENSOR & SEAL FAILURE
System Number of Number of Number of Number of Number of Type Control Power Lines Ground Wires #8 Sensor Wires Ground Wires
Simplex 4 3 1 3 1
Simplex with Alarm 6 3 1 3 1
Duplex 6 6 2 6 2
Duplex with Alarm 8 6 2 6 2
Installing Switch Controls:
Pump Operations
The controls are supported by a mounting
Instructions
Installing Pump in Sump:
Before installing the pump in the sump, lay it on side and turn impeller manually. Im pel ler may be slightly stuck due to factory test water, so it must be bro ken loose with small bar or screwdriver in edge of vanes. The impeller should turn freely.
Clean all trash and sticks from sump and connect pump to piping.
A check valve must be installed on each pump. A gate or plug valve in each pump discharge line is also recommended. This valve should be installed on the discharge side of the check valve so the line pressure can be cut off if necessary to service the check valve. Single pump systems are sometimes installed without a check valve where it is desirable to self-drain the dis charge line to prevent freezing. This can be done only with short discharge lines. Otherwise water will return to the sump and cause short cycling of the pump.
bracket that is attached to sump wall, cover, or to the NEMA 4 junction box.
Control level can be changed at any time by loosening the snubber and readjusting cord length.
In either a simplex or duplex system, the lower or turn-off control is set just above the top of volute, so that the volute will always be submerged during the pumping cycle. The second, or turn-on control, is set about 24 inches above the lower turn-off con trol.
More distance between turn-on and turn­off controls can be used, but sew age may become septic, and excessive solids may collect for the pump to handle. A frequent pumping cycle is recommended for best op er a tion.
If an alarm system is used, this con trol is usually set about 6 inches above the override control.
Making Electrical Connections:
All electrical wiring must be in ac cordance with local codes, and only competent electricians should make the
NEMA 4 Junction Box: (Optional)
A NEMA 4 junction box should be used to make power and control con nec tions if electrical control panel is to be set remote from the pump sump. The Hydromatic® NEMA 4 junction box is provided with com pres sion con nec tors for sealing all wires. No sealing compound is need ed to make con nec tions wa ter proof.
Wiring diagrams are provided with panel for making connections. The size wire to use from panel to sump de pends on motor size and distance in feet.
Be sure each wire is checked out so that a wrong connection will not be made. An ohm me ter or Megger can be used to check wire continuity.
installations. All wires should be checked for grounds with an ohm meter or Megger after the connections are made. THIS IS IMPORTANT, AS ONE GROUNDED WIRE CAN CAUSE CON SID ER ABLE TROU BLE.
IMPORTANT: If equipment is not properly wired and pro tect ed as recommended, the warranty is void.
Heat Sensors and Seal Failure Connections:
Be sure heat sensor wires are con nect ed in series with the starter coil. Connections are provided on the terminal strip.
Starting Systems:
1. Turn the H-O-A switch to Off position and then turn on main circuit breakers.
2. Open all discharge valves and allow water to rise in sump.
3. Turn H-O-A switch to Hand position on one pump and notice operation. If pump is noisy and vibrates, rotation is wrong. To change rotation, interchange any two line leads to motor 3ø only. Do not interchange main incoming lines. If duplex system, check second pump in the same manner.
4. Now set both H-O-A switches to Auto position and allow water to rise in sump until one pump starts. Allow pump to operate until level drops to turn-off point.
5. Allow sump level to rise to start other pump. Notice run lights on panel. Pumps should alternate on each successive cycle of operation.
6. Turn both H-O-A switches to Off position and allow sump to fill to the override control level.
7. Turn both switches to Auto position and both pumps should start and operate together until level drops to turn-off point.
8. Repeat this operation cycle several times before leaving the job.
9. Check voltage when pumps are operating and check the amp draw of each pump. Check amps on each wire, as sometimes a high leg will exist. One leg can be somewhat higher (5 to 10%) without causing trouble. For excessive amp draw on one leg, the power company should be consulted.
3
Loading...
+ 5 hidden pages