Pentair Hydromatic S4F Installation And Service Manual

MODEL S4F
SUBMERSIBLE SOLIDS HANDLING PUMP
INSTALLATION AND SERVICE MANUAL
NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system.
Item # E-03-306 | Part # 5625-306-1 | © 2012 Pentair Pump Group, Inc. | 10/25/12
General Information
Before Operation:
Read the following in structions care ful ly. Reasonable care and safe meth ods should be practiced. Check local codes and requirements before installation.
Attention:
This manual contains important information for the safe use of this product. Read this manual completely before using this product and refer to it often for con tin ued safe product use. DO NOT THROW AWAY OR LOSE THIS MAN U AL. Keep it in a safe place so that you may refer to it often.
Unpacking Pump:
Remove pump from carton. When un pack ing unit, check for con cealed damage. Claims for damage must be made at the receiving end through the delivery carrier. Dam age cannot be processed from the factory.
WARNING: Before handling these pumps and controls, always disconnect the power first. Do not smoke or use sparkable electrical devices or flames in a septic (gaseous) or possible septic sump.
CALIFORNIA PROPOSITION 65 WARNING:
This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
The Pump
Shipping:
When unpacking unit check for concealed damage. Claim for damage must be made at the receiving end through the delivering carrier. Damage cannot be processed from the factory.
Pumps in Storage or Not Operating:
Pumps with carbon ceramic seals must have impellers manually rotated (6 revolutions) after setting non-operational for 3 months or longer and prior to electrical start-up.
Pumps with tungsten carbide seals must have impellers manually rotated (6 revolutions) after setting non-operational for 3 weeks or longer and prior to electrical start-up.
Seal Failure:
An electrode is installed in the seal chamber so if any water enters the chamber through the first seal the electrode will be energized and a signal will be transmitted to the sensing unit at ground surface causing an alarm function to energize.
In operation the seal failure unit indicates only that there is some water in the seal chamber. The pump will continue to operate
without damage but the seal should be checked immediately after failure is indicated.
N OTE: Failure to install such a device negates all warranties by Hydromatic.
Pump:
The S4F submersible pump is supplied for 1 and 3 phase and for 200, 230, 460 or 575 volts. Power cable is supplied with the green wire for ground. Be sure green wire is connected to a good ground such as water pipe or ground stake.
Heat Sensors:
All motors have heat sensor units embedded in the motor winding to detect excessive heat. The heat sensors are set to trip at 105°C so will not operate if dangerous heat occurs. The sensors automatically reset when motor cools to safe temperature.
The sensors are connected in series with the motor starter coil so that the starter is tripped if heat sensor opens. The motor starter is equipped with overload heaters so all normal overloads are protected by the starter.
NOTE: Failure to install such a device negates all warranties by Hydromatic pumps.
IMPORTANT: If Hydromatic electrical starting equipment is not supplied, the heat sensor circuit must be connected in series with the starter coil or warranty is void. Connection diagram is included in this manual.
2
Sump Level Control:
Sump level is controlled by Hydromatic float switch controls. The float is held in position in the sump by a weight attached to the power cord above the float. The cord supports the float and is adjusted for height from the surface.
Typical duplex systems use three controls: one set at turn-off, one set at turn-on for one pump, and one set for turn-on for two pumps. Pumps alternate operation on each successive cycle.
Two pumps operate together only if sump level rises to the third or override control. The override control also brings on the second pump in case of failure of the first pump. Extra floats with appropriate controls can be supplied for alarm functions.
Triplex systems use four controls: one set at turn-off, one set at turn­on for one pump, one set at turn­on for two pumps, and one set at turn-on for three pumps. Pumps alternate each successive cycle.
Three pumps operate together only if sump level rises to the fourth control (second override). This control also brings on the third pump in case of failure of either or both of the first two pumps.
Alarm Controls:
The alarm level is usually set above the override level so the alarm will signal only if the override level is exceeded. However, some engineers prefer to have the alarm level set below the override level as it is possible for one pump to fail and the other pump to operate on the override
level with the sump level never reaching the alarm level. This is particularly true in cases of low inflow capacity.
Electrical Control Panel:
It is recommended that the Hydromatic control panel be used with all pumps as proper starter heaters and connections for heat sensor wires are furnished.
IMPORTANT: If Hydromatic electrical controls are not used and the motor fails because of improper components or if the heat sensors are not properly connected, the warranty is void.
Hydromatic electrical equipment is installed in a weather-proof NEMA 3R enclosure. The electrical equipment includes
FOR REMOTE LOCATION OF CONTROL PANEL LENGTHS ARE BASED ON A VOLTAGE DROP OF TWO PERCENT
Maximum length in feet from NEMA 4 junction box to control panel. For 3 phase only and for power lines only. All control wires can be = 14–16 or 18 gauge wire. If power lines are for 460 or 575 volts insulation of control wires must be for this voltage if used in conduit with power lines.
Volts 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575 230 460 575
Wire Motor
Size HP 33355571⁄271⁄271⁄210 10 10 15 15 15 20 20 20 25 25 25 30 30 30 35 35 35
12 110 450 700 90 370 580
10 180 720 1120 140 550 370 90 360 560 50 220 340
8 270 1100 1650 220 900 1400 175 700 1100 105 420 650 320 500 230 360 180 280
6 400 1600 2500 350 1400 2200 220 900 1400 150 600 930 105 420 650 90 370 570 360 560 320 500 230 360
4 370 1500 2300 230 950 1450 175 700 1100 140 550 850 125 500 800 100 400 620 90 360 560
2 370 1500 230 270 1100 1700 220 900 1400 210 820 1250 200 800 1250 150 600 930
*Special Junction Box required for wire sizes larger than #4.
NUMBER OF CONDUCTORS REQUIRED BETWEEN CONTROL PANEL AND NEMA 4 JUNCTION BOX
System Number of Number of Number of
Type Control Wires Power Lines Ground Wires #8 Number of Number of
Simplex 33131
Simplex with Alarm 53131
Duplex 56162
Duplex with Alarm 76162
WIRE SIZE TABLE
HEAT SENSOR & SEAL FAILURE
Sensor WiresGround Wires
3
The Pump
Installation Instructions
otherwise water will return to the sump and cause short cycling of the pump.
a main circuit breaker for each pump, a magnetic starter with overload protection for each pump, an H-O-A switch and run light for each pump, an electric alternator and a transformer to provide appropriate control for control circuit and alarms.
Overload Heaters:
If the Hydromatic electrical panel is not used, starters with 3 leg overload protection must be supplied. On 3 phase pumps the heaters must be sized in accordance with the nameplate amps on the motor housing. The amp draw on these submersible motors is slightly higher than a corresponding horsepower surface motor, so heaters must be sized by the nameplate rating.
Single phase pumps with capacitor start have a run and a start winding, each drawing a different current. To adequately protect these windings with the appropriate heaters, consult the factory.
Installing Pump in Sump:
Before installing pump in sump lay it on side and turn impeller manually. Impeller may be slightly stuck due to factory test water, so it must be broken loose with small bar or screwdriver in edge of vanes. The impeller should turn freely.
Clean all trash and sticks from sump and connect pump to piping.
A check valve must be installed on each pump. A gate or plug valve in each pump discharge line is also recommended. This valve should be installed on the discharge side of the check valve so if necessary to service the check valve the line pressure can be cut off. Single pump systems are sometimes installed without a check valve where it is desirable to self-drain the discharge line to prevent freezing. This can be done only with short discharge lines,
NEMA 4 Junction Box: (Optional)
If electrical control panel is to be set remote from the pump sump, a NEMA 4 junction box should be used to make power and control connections. The Hydromatic NEMA 4 junction box is provided with compression connectors for sealing all wires. No sealing compound is needed to make connections waterproof.
Wiring diagrams are provided with the panel for making connections. An extra set of diagrams is included so that one set can be used in the sump when making connections. The size wire to use from panel to sump depends on motor size and distance in feet.
Be sure each wire is checked out so that wrong connection will not be made. An ohmmeter or Megger can be used to check wire continuity.
IMPORTANT: If other than Hydromatic starters are used, be sure the heat sensor wires are connected in series with the starter coil circuit. Typical wiring diagrams are included.
HYDR-O-RAIL:
If the pump or pumps are to be used with Hydr-O-Rail system, the pumps will be equipped with guide brackets and hydraulic sealing flange.
4
CONNECTION DIAGRAM FOR LEADS IN
MOTOR AND CONNECTION BOX
(Y) WYE MOTOR CONNECTIONS
65 4
98 7
32 1
HEAT SENSORS AND SEAL FAILURE CONNECTIONS
230 VOLTS 460 VOLTS
65 4
98 7
GREEN GREEN
FOR ANY VOLTAGE MOTOR
HEAT SENSORS
IN MOTOR WINDINGS
HEAT SENSORS SEAL FAILURE
32 1
WHITEBLACK
L3L2L1L3L2L1
ELECTRODE
RED DARK
GREEN
Loading...
+ 8 hidden pages