Pentair Hydromatic S4B, Hydromatic S6AX, Hydromatic S4LRC, Hydromatic S4LVX, Hydromatic S6A Installation And Service Manual

...
Page 1
MODELS S4L(X*), S4LRC/S4LVX*, S4B(X*), S4K(X*), H4Q(X*), S6L(X*), S6A(X*) and S8F(X*)
*
Used in Hazardous Locations Class I, Division 1
SUBMERSIBLE SOLIDS HANDLING PUMPS
INSTALLATION AND SERVICE MANUAL
For use with product built with USEM motor.
NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system.
Item # E-03-491 | Part # 5625-491-1 | © 2014 Pentair Ltd. | 08/25/14
(*Hazardous Location
Motor End)
Page 2
General Information
This manual contains important information for the safe use of this product. Read this manual completely before using this product and refer to it often for con tin ued safe product use. DO NOT THROW AWAY OR LOSE THIS MAN U AL.
When un pack ing unit, check for con cealed damage. Claims for damage must be made at the receiving end through the delivery carrier. Dam age cannot be processed from the factory.
WARNING: Before handling these pumps and controls, always disconnect the power first. Do not smoke or use sparkable electrical devices or flames in a septic (gaseous) or possible septic sump.
CALIFORNIA PROPOSITION 65 WARNING:
This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
Pumps Not Operating or in Storage:
Pumps with carbon ceramic seals must have impellers manually rotated (6 revolutions) after setting non-operational for 3 months or longer and prior to electrical start-up.
Pumps with tungsten carbide seals must have impellers manually rotated (6 revolutions) after setting non-operational for 3 weeks or longer and prior to electrical start-up.
Seal Failure:
An electrode probe is installed in the seal chamber so if any water enters the chamber through the first seal, the electrode will be energized and a signal will be transmitted to
the sensing unit at ground surface causing a red light to flash. The electrode probe is installed in all units, but the sensing unit is supplied at extra cost and must be ordered.
In operation the seal failure unit in di cates only that there is some water in the seal chamber. The pump will con tin ue to operate without damage, but the seal should be checked immediately after failure is indicated.
CAUTION: Failure to correct leaking seal could result in water entering motor chamber causing shorting out of motor.
The sensing unit is recommended on all installations as good insurance against motor failure.
Seal Failure Probes:
All our hazardous location submersible pumps have two factory installed mois ture detectors (seal failure probes). They are in a normally open series cir cuit, in the seal chamber. Un der normal operating conditions, the circuit remains open. If the lower seal leaks and moisture enters this cham ber, the moisture would settle to the bottom of the chamber and will com plete the circuit between the mois ture detectors.
This circuit must be connected to a sensing unit and signaling device. This is supplied in a Hydromatic® built control panel.
NOTE: Failure to install such a device negates all war ran ties by Hydromatic.
Pump:
Power cable is supplied with sepa rate wire for ground. Be sure green wire is con nect ed to a good ground such as water pipe or ground stake.
Heat Sensors:
All motors have heat sensor units embedded in the motor winding to detect excessive heat. The
sensors automatically reset when motor cools to safe temperature.
The sensors are connected in series with the motor starter coil so that the starter is tripped if heat sensor opens. The motor starter is equipped with overload heaters so all normal overloads are protected by the starter.
IMPORTANT: If Hydromatic electrical starting equip ment is not supplied, the heat sensor circuit must be connected in series with the starter coil or warranty is void.
Once sensor re sets, the starter is to be automatically reset for FM for continued operation of the pump. This circuitry is supplied in a Hydromatic control panel.
Power Cords:
The power cord and heat sensor seal failure cord are potted into the con nec tion box cap. The cords must not be spliced.
NOTE: Each cable has a green lead. This is the ground wire and must be grounded properly per NEC and/or local codes. Cords should be in spected for abnormal wear and replaced ac cord ing ly.
Sump Level Control:
Sump level is controlled by Hydromatic float switch controls. The float is held in position in the sump by a weight attached to the power cord above the float. The cord supports the float and is adjusted for height from the surface.
Typical duplex systems use three con trols: one set at turn-off, one set at turn-on for one pump, and one set for turn-on for two pumps. Pumps alternate op er a tion on each successive cycle.
Two pumps operate together only if sump level rises to the third or override control. The override control also brings on the second pump in case of failure of the first
2
Page 3
pump. Extra floats with ap pro pri-
33131
53131
56162
76162
WIRE SIZE AND MAXIMUM LENGTH (FEET) FOR REMOTE LOCATION OF CONTROL PANEL
BASED ON A 2% VOLTAGE DROP (230 VOLTS 3 PHASE)
Copper Wire Amperes @ 230 Volts*
No. D.C. Res.
AWG/M Ft. 51015202530405060708090 100 120 140 160 180 200
12 1.620 325 165 110 80 65 55 10 1.018 520 260 175 130 105 85 65
8 0.6404 830 415 275 205 165 140 105 80 6 0.410 1295 645 430 320 260 215 160 130 105 90 80 4 0.259 1025 680 510 410 340 255 205 170 145 130 115 100 85
M 3 0.205 1295 865 650 520 430 325 260 215 185 160 145 130 110 90
2 0.162 1090 820 655 545 410 340 295 255 230 205 180 160 135 110 100 1 0.129 1030 825 685 515 410 340 295 255 230 205 170 145 130 115 0 0.102 1040 865 650 520 435 370 325 290 260 215 185 160 145 130
00 0.0811 1090 820 655 545 470 410 365 325 270 235 205 180 165
000 0.0642 1035 825 690 590 515 460 415 345 295 260 230 205
NOTE: For 460 volts obtain distance by multiplying by 2.0 ‡60˚C
For 570 volts obtain distance by multiplying by 2.5 ‡Rating 90˚C
* 230 volt system not recommended for above 30 to 40 horsepower. Insulation @ 30˚C Amb. Based on 3 power conductors in cable or conduit; for 4 to 6 reduce ampacity to 80% & for 7 to 24 reduce to 70%.
M Special junction box required for wire sizes larger than #4.
ate controls can be supplied for alarm functions. Triplex systems use four controls: one set at turn-off, one set at turn-on for one pump, one set at turn-on for two pumps, and one set at turn-on for three pumps. Pumps alternate each successive cycle.
Three pumps operate together only if sump level rises to the fourth control (second override). This control also brings on the third pump in case of failure of either or both of the first two pumps.
Alarm Controls:
The alarm level is usually set above the override level so the alarm will signal only if the override level is exceeded. However, some engineers prefer to have the alarm level set below the override level as it is possible for one pump to fail and the other pump to operate on the override level with the sump level never reach ing the alarm level. This is par tic u lar ly true in cases of low inflow ca pac i ty.
Electrical Control Panel:
It is recommended that the Hydromatic® control panel be used with all pumps as proper starter heaters and connections for heat sensor wires are furnished.
The electrical equipment includes a main circuit breaker for each pump, a magnetic starter with overload protec tion for each pump, an H-O-A switch and run light for each pump, an elec tric alternator and a trans former to provide appropriate con trol circuit and alarms.
Overload Heaters:
If the Hydromatic electrical panel is not used, starters with 3 leg overload protection must be supplied. The heaters must be sized in ac cor dance with the nameplate amps on the motor housing. The amp draw on these submersible motors is slightly higher than a corresponding horsepower surface motor, so heaters must be sized by the nameplate rating.
IMPORTANT: Be sure the heat sensor wires are connected in series with the starter coil circuit.
Pump Installation
Installing Pump in Sump:
Before installing pump in sump, lay it on side and turn impeller manually. Impeller may be slightly stuck due to factory test water, so it must be broken loose with small bar or screwdriver in edge of vanes. The impeller should turn freely.
Clean all trash and sticks from sump and connect pump to piping.
A check valve must be installed on each pump. A gate or plug valve in each pump discharge line is also recommended. This valve should be installed on the discharge side of the check valve so if necessary to service the check valve, the line pressure can be cut off. Single pump systems are sometimes installed without a check valve where it is desirable to self-drain the discharge line to
prevent freezing. This can be done only with short discharge lines, otherwise water will return to the sump and cause short cycling of the pump.
Installing Sump Level Control Float Controls:
In either simplex, duplex or triplex systems the lower or turn-off control is to be set to maintain a minimum level in the sump. This level shall be no more than 3-1/4" from the top of the motor housing down to the surface of the sewage.
The second or turn-on control is set above the lower turn-off control. The exact distance between the two floats must be a compromise between a fre quent pumping cycle (10 starts per hour max.) to control septicity, solids and a slower cycle for energy econ o my. This distance should be de ter mined by the engineer or con sult ing engineer de pend ing on the con di tions of the application.
For installation of Hydromatic sup plied level con trols, refer to your sys tems installation and service manual.
NEMA 4 Junction Box (Optional):
If electrical control panel is to be set remote from the pump sump a NEMA 4 junction box should be used to make power and control connections. The Hydromatic NEMA 4 junction box is provided with compression con nec tors for sealing all wires. No sealing compound is needed to make con nec tions waterproof.
Wiring diagrams are provided with panel for making connections.
NUMBER OF CONDUCTORS REQUIRED BETWEEN CONTROL PANEL AND NEMA 4 JUNCTION BOX
System Number of Number of Number of
Type Control Wires Power Lines Ground Wires #8 Number of Number of
Simplex
Simplex with Alarm
Duplex
Duplex with Alarm
Power lines and control wires can be carried in conduit or can be underground buried cable.
HEAT SENSOR & SEAL FAILURE
Sensor Wires Ground Wires
3
Page 4
The size wire to use from panel to
NON-HAZARDOUS LOCATION ONLY
HAZARDOUS LOCATION ONLY
sump depends on motor size and distance in feet.
Be sure each wire is checked out so that a wrong connection will not be made. An ohmmeter or Megger can be used to check wire continuity.
Installing Float Switch Controls:
The controls are supported by a mounting bracket that is attached to sump wall or cover or to the NEMA 4 junction box.
Cord snubbers are used to hold the cord in place. Control lever can be changed at any time by loosening the snubber and readjusting cord length.
In either simplex or duplex system the lower or turn-off control is set just above the top of volute so that the volute will always be submerged during the pumping cycle. The second or turn-on control is set about 24 inches above the lower turn-off control.
More distance between turn-on and turn-off controls can be used, but sewage may become septic and excessive solids may collect for the pump to handle. A frequent pumping cycle is recommended for best operation.
If an alarm system is used, this control is usually set about 6 inches above the override control.
Making Electrical Connections:
All electrical wiring must be in accordance with the local code, and only competent electricians should make the installations. Complete wiring diagrams are on the inside cover of the panel. All wires should be checked for ground with an ohmmeter or Megger after the connections are made. This is important, as
one grounded wire can cause considerable trouble.
IMPORTANT: If equipment is not properly wired and protected as recommended, the warranty is void.
Heat Sensors and Seal Failure Connections:
Be sure that heat sensor wires are connected in series with the starter coil. Connections are provided on the terminal strip.
DUAL VOLTAGE
3 PHASE MOTOR WIRING
230V 3N 460V 3N
WHITEBLACK
WHITEBLACK
45 6
78 9
12 3
W
BL
(L2)
(L1)
ELECTRODE
REDORANGE DARK
ELECTRODE
RED DARK
(L3)
R
GREEN
GREEN
45 6
78 9
12 3
W
BL
(L2)
(L1)
HEAT SENSORS AND SEAL FAILURE CONNECTIONS
HEAT SENSORS
HEAT SENSORS SEAL FAILURE
HEAT SENSORS AND SEAL FAILURE CONNECTIONS
HEAT SENSORS
HEAT SENSORS SEAL FAILURE
GREEN GREEN
R
(L3)
FOR ANY VOLTAGE MOTOR
IN MOTOR WINDINGS
FOR ANY VOLTAGE MOTOR
IN MOTOR WINDINGS
Pump Operations
Starting System:
1. Turn H-O-A switch to Off position, then turn on main circuit breakers.
2. Open all discharge valves and allow water to rise in sump pump.
3. Turn H-O-A switch to Hand position on one pump and notice operation. If pump is noisy and vibrates, rotation is wrong. To change rotation interchange any two line leads to motor on 3ø only. DO NOT INTERCHANGE MAIN INCOMING LINES. If duplex system, check second pump in the same manner.
4. Now set both H-O-A switches to Auto position and allow water to rise in sump until one
pump starts. Allow pump to operate until the level drops to turn-off point.
5. Allow sump level to rise to start other pump. Notice run lights on panel; pumps should alternate on each successive cycle of operation.
6. Turn both H-O-A switches to Off position and allow sump to fill to the override control level.
7. Turn both switches to Auto position and both pumps should start and operate together until level drops to turn-off point.
8. Repeat this operation cycle several times before leaving the job.
9. Check voltage when pumps are operating and check the amp draw of each pump. Check amps on each wire as sometimes a high leg will exist. One leg can be somewhat higher, 5 to 10%, without causing trouble. For excessive amp draw on one leg, the power company should be consulted.
Phase Converters:
Phase converters are generally not recommended, but in cases where only single phase current is available phase converter can be used. Be sure to size the phase converter large enough for the amp draw specified on the motor nameplate, not necessarily by motor horsepower. The warranty on all three phase submersible motors is void if operated with single phase power through a phase converter and 3 leg ambient compensated extra-quick trip overload protectors are not used.
4
Page 5
Pump Maintenance
NOTE: Any unauthorized field repair voids the warranty, the hazardous location rating, and Factory Mutual approval.
If the heat sensor and seal failure are hooked up properly, no attention is necessary as long as the seal failure indicator light doesn’t come on. To ensure continuity of the seal sensor leads, a test light is provided on in trin si cal ly safe Hydromatic® panels as standard equipment.
Pump should be checked every quar ter for cor ro sion and wear.
Maintenance:
As the motors are oil filled, no lu bri ca tion or other maintenance is required.
If the pump is used on a rail system, it should be lifted once every six months and checked for corrosion and wear.
Generally these pumps give very reliable service and can be expected to operate for years on normal sewage pumping without failure.
Lightning:
In some areas where considerable lightning occurs, it is recommended that a lightning arrestor be installed at the control panel to aid against damage to the motor.
Field Service on Hydromatic Hazardous Location Pumps:
If a Hydromatic hazardous location pump is used in a hazardous location, or if the pump is still in war ran ty, the pump must be returned to the factory for service or repaired at an authorized Factory Mutual Hydromatic service center. Charges will not be allowed if in war ran ty pump is not taken to an authorized Factory Mutual Hydromatic service center. This will ensure the integrity of
the hazardous location rating of the pump and com ply with our warranty re quire ments.
Field Service on Motor:
All submersible motors out of warranty can be serviced in the field by any reliable motor service shop. Any pump, in warranty, must be returned to the factory for service or re paired at an authorized Hydromatic service center. Charg es will not be allowed if in warranty pump is not taken to an authorized Hydromatic service center.
When field service is performed on a pump, these instructions should be carefully followed.
COIL
WARNING
COIL
THERMOSTATS
IN SERIES
BLACK
BLACK
THERMOSTATS
IN SERIES
OL OLSTART
L2
WHITE
L2
WHITE
WARRANTY IS VOID IF HEAT SENSORS ARE NOT
CONNECTED AS SHOWN (IN SERIES WITH CONTACTOR OIL)
TWO WIRE CONTROL OFFERING AUTOMATIC RESET
L1
ON-OFF
SWITCH
THREE WIRE CONTROL OFFERING AUTOMATIC RESET
L1
IN CERTAIN APPLICATIONS THE NEC MAY REQUIRE THREE OVERLOAD RELAYS
Replacing Stator:
1. If stator only is damaged, it may not be necessary to completely dismantle pump as stator and housing can be lifted from pump without disturbing seals or bear ings.
2. Drain all oil from upper housing, remove drain plug in bottom of stator housing and remove plug in top of housing to allow air to enter.
3. After chamber is drained, remove hold-down bolts and lift off. Use care in lifting as the seal failure connecting wire must be dis con nect ed before housing is com pletely removed.
4. Set assembly on bench and re move connection box. When box is lifted off, connection wires to motor will be exposed. These wires will probably be burned, but each wire is tagged with a metal marker giving wire number. Cut the wires.
If the leads to the connection
box are burned, a complete new con nec tion box with new wire must be used. The wires are potted in with sealing compound and a new unit must be obtained from the factory.
5. The stator is held in the housing with a bolted-in end ring and an outside locking screw to prevent stator from turning.
6. After ring is removed, turn hous ing upright and bump on hard wood blocks. This should jar the stator loose and allow it to drop out.
7. Thoroughly clean housing before replacing new stator. Replace stator and make all wire con nec tions to connection box before replacing housing on pump. This is important as leads must be tucked behind the windings by using hands up through rotor core.
IMPORTANT: Use only com pres sion type insulated connectors on the wires.
DO NOT TAPE LEADS AS OIL WILL DETERIORATE THE TAPE AND CAUSE DAMAGE TO STATOR AND BEARINGS.
8. Drain oil from seal chamber. Check top bearing. If clean and does not turn rough, bearings can be reused and it is not necessary to completely dismantle pump to change bearings. If bearings are damaged with dirt or heat, they must be replaced. Remember to reinstall the upper bearing load spring.
9. Before replacing stator housing be sure outside lock screw is in place and that O-ring is used under head of bolt. A leak here can cause a motor failure.
5
Page 6
10. Replace stator housing onto seal chamber and bolt in place. Be sure seal failure
wire is connected before hous ing is assembled.
Be sure back-off screws have
been loosened so that parts can come metal to metal. Be sure O-ring seal has been replaced. If O-ring is nicked or cut, replace with new rings. This applies to all O-rings used in assembly.
11. After all leads are reconnected in the connection box, make a high voltage ground test on each wire. The only wire that should show ground is the green power lead and the ground lead in the aux il ia ry control cable.
12. For safety, complete pump should be air checked under water for leaks. Lay pump on side for this oil filling with oil fill hole upright. Do not completely fill; leave oil about 1 inch below plug hole. Use only Hydromatic® submersible oil in this chamber. Replace plug; use Permatex on threads. Install air valve in top plug opening of motor housing and charge housing with about 10 psi of air. Be sure air is dry. Do not use air line where water may be trapped in the line. Submerge complete unit under water and check for leaks.
13. Refill motor chamber with Hydromatic submersible oil. Fill chamber until oil covers top of the windings. Leave air space in the top for expansion. Use Permatex on plug threads.
Replacing Seals and Bearings:
1. Drain all oil from motor chamber and seal chamber as described.
2. Remove the motor housing as de scribed.
3. Remove bolts that hold seal cham ber to pump housing. Use back-off screws to break loose. With hardwood block, tap end of impeller to loosen from shaft. When free, remove impeller from shaft.
4. Lift rotating assembly (rotor, shaft and impeller) from pump case and place horizontally on bench.
5. Remove screw and washer from end of shaft and then screw socket head bolt back into shaft. Using a screwdriver on opposite sides behind impeller apply force, then tap on end of socket bolt to break impeller loose from taper shaft.
6. Remove key and then slide seal off the shaft.
7. To remove seal plate, take out socket head flat screws and using screws in back off holes, pry plate loose. This will also force seal off if not already removed.
8. Remove snap ring that holds upper seal. Pull seal if it is free. If not free, it can be forced off when shaft is removed.
9. Set assembly in upright position and bump end of shaft on hardwood block. This will push the bearing from the housing and will force upper seal from shaft.
10. Use bearing puller to remove bearings. Replace with new bear ings. Press only on inner face of bearing when replacing. Pressing on outer face can damage the bearing.
IMPORTANT: Do not use
any of the old seal parts. Replace with all new seals.
11. Thoroughly clean all castings before replacing seals. One grain of dirt between the seal faces can cause failure.
12. Examine all O-rings for nicks before using.
13. Use Locktite® on socket head locking screw in end of shaft.
14. Before refilling chamber with oil, air test as described above and refill both chambers with oil.
15. Always check all leads with high voltage or with Megger for grounds before operating the pump.
Replacing Cords:
The power cord and heat sensor ­seal failure cord is potted into the con nec tion box cap, forming the cord and cap assembly.
If cords require replacement due to damage or cords being too short, cord and cap assembly must be replaced as a complete assembly avail able from factory.
Check pump for proper rotation before re turn ing to normal service.
Disconnecting Pump Cords:
If a Hydromatic hazardous location pump is to be removed from its loca tion, the pump cords may be disconnected at control panel (on sump mounted con trol panels) and cord as sem bly taken with pump.
CAUTION: If cord openings from sump to con trol panel are open, gas es from sump could enter panel and an explosive condition could ex ist.
Replacing Lower Seal, Impeller or Volute:
The wet end components may be repaired or replaced by an authorized Hydromatic service facility without compromising the hazardous location rating to the pump.
NOTE: Any time the seal is disturbed, it must be replaced.
6
Page 7
Pump Troubleshooting
The following is a list of common problems and their probable causes.
Pump will not start.
1. No power to the motor. Check for blown fuse or open circuit breaker.
2. Selector switch may be in the Off position.
3. Control circuit transformer fuse may be blown.
4. Overload heater on starter may be tripped. Push to reset.
Pump will not start and overload heaters trip.
1. Turn off power and check motor leads with Megger or ohmmeter for possible ground.
2. Check resistance of motor windings. All 3 phases should show the same reading.
3. If no grounds exist and the motor windings check OK, remove pump from sump and check for clogged or blocked impeller.
Pump operates with selector switch in Hand position but will not operate in Auto position.
Pump does not deliver proper capacity.
1. Discharge gate valve may be partially closed or partially clogged.
2. Check valve may be partially clogged. Raise level up and down to clear.
3. Pump may be running in wrong direction. Low speed pumps can operate in reverse direction without much noise or vibration.
4. Discharge head may be too high. Check total head with gauge when pump is operating. Total head is discharge gauge pressure converted to feet plus vertical height from water level in sump to center line of pressure gauge in discharge line. Gauge should be installed on pump side of all valves. Multiply gauge pressure in pounds by 2.31 to get head in feet.
5. If pump has been in service for some time and capacity falls off, remove pump and check for wear or clogged impeller.
Motor stops and then restarts after short period but overload heaters in starter do not trip.
1. This indicates trouble in the float level control or the alternator relay.
2. Check control panel for trouble.
Pump runs but will not shut off.
1. Pump may be air locked. Turn pump off and let set for several minutes, then restart.
2. Lower float control may be hung-up in the closed position. Check in sump to be sure control is free.
3. Selector switch may be in the Hand position.
1. This indicates heat sensors in the motor are tripping due to excessive heat. Impeller may be partially clogged giving a sustained overload but not high enough to trip overload heater switch.
2. Motor may be operating out of liquid due to a failed level control.
3. Pump may be operating on a short cycle due to sump being too small or from water returning to sump due to a leaking check valve.
7
Page 8
D3D4
D2 D1 D6 D5
D3D4
D5D2D1
Wet End Components
D4 D3
S4L(X)
D3
D1 D2
S4LRC
D3D4
D4 D3
S4LVX
D4
D1D2
D5D6D1D2
S4B(X)
D3D4
D5D2D1
D4 D3
S6L(X) S8F(X)
S4K(X)
D5D6D1D2
S6A(X)
H4Q(X)
D1 D2 D5
D5D1 D2D6
D3D4
8
Page 9
Wet End Parts List For use with product built with USEM motor.
Item
Description S4B(X) S4L(X)
#
D1 SCREW – HHC 5/8-11 UNF x 1-1/4 D2 WASHER – IMPELLER D3 KEY – 1/3" SQUARE D4 VOLUTE D5 RING – WEAR D6 SCREW MACH.
IMPELLER
005700181 005700181 005700181 005700181 005700181 005700181 005700181 005700181 005700181 019450001 019450001 019450001 019450001 019450001 019450001 019450001 019450001 019450001 028550081 028550081 028550031 028550081 028550081 028550081 028550081 028550081 028550081 136910002 089190015 107830002 107830002 136930012 089180015 089260025 137190002 151520015 136900003 042890023 048200101
(3)
7.38"
7.88"
8.38"
8.63"
8.81" 9"
9.25"
9.5"
9.63"
9.81"
10"
10.18"
10.25"
10.31"
10.38"
10.5"
10.85" 11"
11.25"
11.38"
11.5"
11.63"
11.88"
12"
110430162 — — 110430152 — — 025940242 025940242 025940242 — — 025940292 110430132 025940292 137200242
025940232 137200362 — 136920132 025940022 136940132 025940022 025940022 137200132 151510062 136920122 025940032 110430122 136940122 025940032 025940032 137200122 151510122 136920112 025940042 136940112 025940042 025940042 137200112 151510052
025940302 136940232 025940302 025940302 137200282 — 136920382 025940192 025940192 — 136920092 025940062 110430042 136940092 137200092 151510042
025940212 025940212 151510102 136920082 025940072 025940072 025940072 137200082
110430112 137200342 — 136920152 025940162 136940182 025940162 025940162 137200212 — 136920072 025940082 136940072 025940082 025940082 137200072 151510032
025940492 025940492 025940492 — 136920052 025940102 136940052 025940102 137200052 151510022 136920042 025940422 110430082 136940042 025940112 025940112 137200042 151510092 136920182 025940202 136940292 025940202 025940202 137200322 151510162 136920032 025940122 110430012 136940032 025940122 025940122 137200032 151510012 136920202 025940182 136940332 025940122 025940122 137200172 151510182 136920232 025940002 025940002 025940002 137200302 — 136920012 025940352 110430002 136940012 025940352 025940352 137200012 151510002
S4LRC
3450 RPM
048200111
REFER
TO
FACTORY
S4LRC/
S4LVX
136950003 042890023 042890023 136900003 136900033
S6A(X) S6L(X) S8F(X) S4K(X) H4Q(X)
(4)
048200101
(3)
000110021
(2)
9
Page 10
Standard Location S4L, S4LRC, S4B, S4K, H4Q, S6L, S6A and S8F Motor End Components
2
27
A1
4
5
24
26
1
30
31
3
6
A3
10
11
12
19
14
A2
7
8
9
22
21
25 20
28
23
15
18
10
16 13 29 17
Page 11
Standard Location S4L, S4LRC, S4B, S4K, H4Q, S6L, S6A and S8F Motor End Parts List
For use with product built with USEM motor.
Ref.
Part
No.
1 05454A027 WASHER – LOCK 5/8 SST 2 2 001500121 O-RING – 1/8 x 3.374 I.D. SC 1 3 05454A030 WASHER – LOCK 3/4 SST 4 4 001500071 O-RING – 1/8 x 7.234 I.D. SC 1 5 12672A001 CONNECTOR – WIRE 3 6 08565A027 BEARING – BALL – UPPER 1 7 060000211 WIRE W/TERMINAL 1
8 012720001 TUBING – INSULATING 1
9 048320032 HOUSING – MOTOR 1 10 000650321 BEARING – BALL – LOWER 1 11 005680061 SCREW – HHC 1/2-13 x 1-1/2 8 12 001500251 O-RING – 1/8 x 11.484 I.D. SC 1 13 084720035 SEAL FAILURE ASSY. 1 14 19105A033 SCREW – HHC 5/8-11 x 1-1/2 8 15 001500261 O-RING – 1/8 x 11.984 I.D. SC 1
Part
No.
Description Qty.
Ref.
Part
No.
16 029210011 SCREW – HHC 1/2-13 x 1-1/4 4
17 025960032 PLATE – SEAL 1
18 001500401 O-RING – 1/8 x 9.734 I.D. SC 1 19 025950042 HOUSING – BEARING/SEAL 1 20 009750251 RING – RETAINING 1 21 026030003 RING – STATOR RETAINING 1 22 065790031 KEY SQ – 1/4" x 1.19 1 23 009750061 RING – RETAINING 1 24 000640061 SPRING – BEARING ADJ. 2 25 001780051 SCREW – HEX SOC. 5/16 x 1-1/2 8 26 151751001 LIFTING BAIL 1 27 152770305 35' CORD ASSEMBLY – 10-4 1
152770315 35' CORD ASSEMBLY – 8-4 SOOW 1
152770325 35' CORD ASSEMBLY – 8-4 1
152770335 35' CORD ASSEMBLY – 6-4 1
Part
No.
Description Qty.
Notes: S — Parts in Seal Kit C — Parts in Carbide Seal Kit — Fill oil to above the motor windings.
Ref.
Part
No.
152770345 35' CORD ASSEMBLY – 4-4 1
152770355 35' CORD ASSEMBLY – 2-4 1 28 019570001 29 019570001
019570021 CARBIDE (OPT) – LOWER C 1 30 19109A080 NUT – HEX 3/4 SST 4 31 151740001 BRACKET – MOUNTING 2
Part
No.
Description Qty.
CARBON CERAMIC/BUNA-N – UPPER CARBON CERAMIC (STD)/BUNA-
N – LOWER
S 1 S 1
Motor Parts List
For use with product built with USEM motor.
hp
VOLTAGE/
ph/RPM
A1
BOX
CONNECTION
3–5 200/3/870 062370015 143990115 143992031 076650011 3–5 230-460/3/870 062370005 143990115 143990031 076650011 3–5 575/3/870 062370015 143990115 143996031 076650011 3–5 200/3/1150 062370015 144000115 144002031 076650121 3–5 230-460/3/1150 062370005 144000115 144000031 076650121 3–5 575/3/1150 062370015 144000115 144006031 076650121
7.5–10 200/3/1150 062370015 141500115 141502031 076650101
7.5–10 230-460/3/1150 062370005 141500115 141500031 076650101
7.5–10 575/3/1150 062370015 141500115 141506031 076650101 15 200/3/1150 062370035 141510115 151512031 076650051 15 230/3/1150 062370055 141510115 141510031 076650051 15 460/3/1150 062370005 141510115 141510031 076650051 15 575/3/1150 062370015 141510115 141516031 076650051 20 200/3/1750 062370035 141520115 141522031 076650041 20 230-460/3/1750 062370005 141520115 141520031 076650041 20 575/3/1750 062370015 141520115 141526031 076650041
25–30 200/3/1750 062370075 141530115 141532031 – 25–30 230/3/1750 062370055 141530115 141530031 – 25–30 460/3/1750 062370005 141530115 141530031 – 25–30 575/3/1750 062370015 141530115 141536031
40 230/3/1750 062370075 141530115 141540031 – 40 460/3/1750 062370005 141530115 141540031 – 40 575/3/1750 062370015 141530115 141546031 – 50 460/3/1750 062370055 141530115 141550031 – 50 575/3/1750 062370035 141530115 141556031 – 60 460/3/3450 062370075 143030115 143030031 076650011 60 575/3/3450 062370035 143030115 143036031 076650011
A2
ROTOR/
SHAFT
A3
STATOR
R
RING SPACER
Fill oil to above the motor windings.
11
Page 12
Hazardous Location
19
A5
18
17
11
14
A3
16
15
22
13
1221109537
A2
A6
20
A4
A1
1
2
4
3
8
6
S4LX, S4LVX, S4BX, S4KX, H4QX, S6LX, S6AX and S8FX Motor End Components
12
Page 13
Hazardous Location S4LX, S4LVX, S4BX, S4KX, H4QX, S6LX, S6AX and S8FX Motor End Parts List
For use with product built with USEM motor.
Ref.
Part
No.
1 001500191 0-RING 1/8 x 6.734 I.D. 1 2 152790305 35' CORD ASSEMBLY – 10-4 1
152790315 35' CORD ASSEMBLY – 8-4 SOOW 1 152790325 35' CORD ASSEMBLY – 8-4 W 1 152790335 35' CORD ASSEMBLY – 6-4 1 152790345 35' CORD ASSEMBLY – 4-4 1
152790355 35' CORD ASSEMBLY – 2-4 1 3 001500361 0-RING – 1/8 x 5.234 I.D. 2 4 108980001 CONNECTOR – ELECTRIC 4 5 019570001 LOWER SEAL – CARBON CERAMIC 1
019570021 6 109000035 SEAL FAILURE ASSY. 1 7 080730001 UPPER SEAL – CARBON CERAMIC 1
Part
No.
Description Qty.
LOWER SEAL – TUNGSTEN CARBIDE
6-Pole 1150 RPM
Ref.
Part
No.
8 109010001 TERMINAL – HERMETIC 2
9 009750251 RING – RETAINING (LOWER BRG.) 1 10 107550012 PLATE – SEAL 1 11 000640051 SPRING – BEARING ADJ. 2 12 001500261 O-RING – 1/8 x 11.984 I.D. 2 13 107820033 RING – LABYRINTH 1 14 08565A027 BEARING – BALL 1
15 026030003 RING – STATOR 1
16 065790031 KEY – 1/4 SQUARE 1
1
17 011240021 NUT – HEX 5/8-11 0 18 19103A043 SCREW – HHC 1/2-13 UNC 1-1/4 4 19 19101A017 SCREW – HHC 3/8-16 UNC 1-1/4 6 20 107810052 HOUSING – MOTOR 1
Part
No.
Description Qty.
Ref.
Part
No.
21 107450012 HOUSING – BEARING 1 22 000650321 BEARING – BALL 1
517000787 CARBON CERAMIC SEAL KIT 517003777 TUNGSTEN CARBIDE SEAL KIT
Part
No.
Description Qty.
6Pole 1150RPM Description
Item
A1 Connection Box 114080005 114080015 114080005 114080005 114080015 114080005 114080025 114080035 114080015 114080005 A2 Rotor/Shaft Assy 143990125 143990125 143990125 143990125 143990125 143990125 141510125 141510125 141510125 141510125 A3 Stator 144002031 144000031 144006031 141502031 141500031 141506031 141512031 141510031 141510031 141516031
Connector
A4
(stator to conn. box)
Connector
A5
(box to cord cap)
A6 Spacer 076650121 076650121 076650121 076650101 076650101 076650101 076650051 076650051 076650051 076650051
InsulatorSplit Bolt 086750011(3)
3 – 5 hp
200/3/1150
116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116910001(3) 116910001(9) 116910001(3) 116910001(3) 116910001(9) 116910001(3) 116910001(3) 116910001(9) 116910001(9) 116910001(3) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2)
024930001(3) 024930001(3) 024930001(3) 024940001(3) 024940001(3) 024930001(3) 024980071(3) 024940001(3) 024930001(3) 024930001(3)
3 – 5 hp
230-460/3/1150
3 – 5 hp
575/3/1150
7.5 – 10 hp
200/3/1150
7.5 – 10 hp
230-460/3/1150
7.5 – 10 hp
575/3/1150
15 hp
200/3/1150
15 hp
230/3/1150
15 hp
460/3/1150
15 hp
575/3/1150
8-Pole 870 RPM
8Pole 870 RPM Description
Item
A1 Connection Box 114080005 114080015 114080005 114080005 114080015 114080005 A2 Rotor/Shaft Assy 143990125 143990125 143990125 143990125 143990125 143990125 A3 Stator 143992031 143990031 143996031 144022031 144020031 144026031
Connector
A4
(stator to conn. box)
Connector
A5
(box to cord cap)
A6 Spacer 076650011 076650011 076650111 076650101 076650101 076650101
3 – 5 hp
200/3/870
116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116910001(3) 116910001(9) 116910001(3) 116910001(3) 116910001(3) 116910001(3) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2)
024930001(3) 024930001(3) 024930001(3) 024940001(3) 024940001(3) 024930001(3)
3 – 5 hp
230-460/3/870
3 – 5 hp
575/3/870
7 hp
200/3/870
7 hp
230-460/3/870
7 hp
575/3/870
13
Page 14
Hazardous Location S4LX, S4LVX, S4BX, S4KX, H4QX, S6LX, S6AX and S8FX Motor End Parts List (Continued)
For use with product built with USEM motor.
4-Pole 1750 RPM
4Pole 1750 RPM
Item
Description
A1 Connection Box 114080005 114080015 114080005 114080025 114080035 114080015 A2 Rotor/Shaft Assy 141510125 141510125 141510125 141520125 141520125 141520125 A3 Stator 141522031 141520031 141526031 141522031 141520031 141520031
Connector
A4
(stator to conn. box)
Connector
A5
(box to cord cap)
A6 Spacer 076650041 076650041 076650041 076650041 076650041 076650041
InsulatorSplit Bolt 086750021(3) 086750021(3)
4-Pole 1750 RPM
4Pole 1750 RPM
Item
Description
A1 Connection Box 114080005 114080025 114080035 114080035 114080005 114080045 114080055 A2 Rotor/Shaft Assy 141520125 141520125 141520125 141520125 141520125 141530125 141530125 A3 Stator 141526031 141522031 141520031 141520031 141526031 141532031 141530031
Connector
A4
(stator to conn. box)
Connector
A5
(box to cord cap)
A6 Spacer 076650041 0766500418 0766500418 0766500418 0766500418
InsulatorSplit Bolt
4-Pole 1750 RPM
4Pole 1750 RPM
Item
Description
A1 Connection Box 114080015 114080005 114080045 114080055 114080035 114080005 114080065 A2 Rotor/Shaft Assy 141530125 141530125 141530125 141530125 141530125 141530125 141530125 A3 Stator 141530031 141532031 141532031 141530031 141530031 141536031 141542031
Connector
A4
(stator to conn. box)
Connector
A5
(box to cord cap)
A6 Spacer
InsulatorSplit Bolt
4-Pole 1750 RPM
4Pole 1750 RPM
Item
Description
A1 Connection Box 114080055 114080035 114080025 114080065 114080055 114080025 A2 Rotor/Shaft Assy 141530125 141530125 141530125 141530125 141530125 141530125 A3 Stator 141540031 141540031 141546031 141550031 141550031 141556031
Connector
A4
(stator to conn. box)
Connector
A5
(box to cord cap)
A6 Spacer
InsulatorSplit Bolt
10 hp
200/3/1750
116750001(2) 116750001(2) 116750001(4) 116750001(2) 116750001(2) 116750001(2) 23394A001(3) 116910001(9) 116910001(3) 23394A001(3) 116910001(9) 116910001(9) 151550011(2) 151550011(2) 151550011(4) 151550011(2) 151550011(2) 151550011(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 024940001(3) 024940001(4) 024930001(3) 024980051(3) 024940001(1) 024940001(6)
024980041(3) — —
15 hp
575/3/1750
116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116910001(3) 23394A001(3) 116910001(9) 116910001(9) 116910001(3) 23394A001(3) 116910001(9) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 024930001(3) 024980071(3) 024940001(1) 024940001(6) 024930001(3) 024980071(3) 024980071(3)
024980051(3) 024980041(1) —
06750011(3) 086750021(3) 086750011(3) 086750011(3) — 086750021(1)
25 hp
460/3/1750
116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116670001(2) 116910001(9) 116910001(3) 23394A001(3) 23394A001(9) 116910001(9) 116910001(3) 116910001(9) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2)
151550031(3)
— 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 024940001(6) 024940001(3) 024980071(3) 024980071(3) 024940001(6) 024940001(3) 024980071(3)
024980041(1)
086750011(3) 086750011(3) 086750011(3)
40 hp
230/3/1750
116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 116750001(2) 23394A001(9) 23394A001(9) 116910001(3) 116670001(3) 23394A001(9) 23394A001(3) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2) 151550011(2)
151550031(3)
116680001(1) — 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 108980001(2) 024980071(3) 024940001(3) 024940001(3) 024980071(3) 024940001(3) 024940001(3) 024980041(1) 024980071(3)
086750011(3) 086750011(3) 086750011(3) — 086750021(1)
10 hp
230-460/3/1750
20 hp
200/3/1750
25 hp
575/3/1750
086750021(1)
40 hp
460/3/1750
10 hp
575/3/1750
20 hp
230/3/1750
30 hp
200/3/1750
40 hp
575/3/1750
15 hp
200/3/1750
20 hp
460/3/1750
30 hp
230/3/1750
50 hp
230/3/1750
15 hp
230/3/1750
20 hp
575/3/1750
30 hp
460/3/1750
50 hp
460/3/1750
15 hp
460/3/1750
25 hp
200/3/1750
30 hp
575/3/1750
50 hp
575/3/1750
25 hp
230/3/1750
40 hp
200/3/1750
14
Page 15
Wiring Diagrams
PROBE TEST RESISTOR ON HAZARDOUS LOCATION ONLY
PROBE TEST RESISTOR ON HAZARDOUS LOCATION ONLY
PROBE TEST RESISTOR ON HAZARDOUS LOCATION ONLY
15
Page 16
STANDARD LIMITED WARRANTY
Pentair Hydromatic® warrants its products against defects in material and workmanship for a period of 12 months from the date of shipment from Pentair Hydromatic or 18 months from the manufacturing date, whichever occurs first – provided that such products are used in compliance with the requirements of the Pentair Hydromatic catalog and technical manuals for use in pumping raw sewage, municipal wastewater or similar, abrasive-free, noncorrosive liquids.
During the warranty period and subject to the conditions set forth, Pentair Hydromatic, at its discretion, will repair or replace to the original user, the parts that prove defective in materials and workmanship. Pentair Hydromatic reserves the right to change or improve its products or any portions thereof without being obligated to provide such a change or improvement for prior sold and/or shipped units.
Start-up reports and electrical schematics may be required to support warranty claims. Submit at the time of start up through the Pentair Hydromatic website: http://forms.pentairliterature.com/startupform/startupform.asp?type=h. Warranty is effective only if Pentair Hydromatic authorized control panels are used. All seal fail and heat sensing devices must be hooked up, functional and monitored or this warranty will be void. Pentair Hydromatic will cover only the lower seal and labor thereof for all dual seal pumps. Under no circumstance will Pentair Hydromatic be responsible for the cost of field labor, travel expenses, rented equipment, removal/reinstallation costs or freight expenses to and from the factory or an authorized Pentair Hydromatic service facility.
This limited warranty will not apply: (a) to defects or malfunctions resulting from failure to properly install, operate or maintain the unit in accordance with the printed instructions provided; (b) to failures resulting from abuse, accident or negligence; (c) to normal maintenance services and parts used in connection with such service; (d) to units that are not installed in accordance with applicable local codes, ordinances and good trade practices; (e) if the unit is moved from its original installation location; (f) if unit is used for purposes other than for what it is designed and manufactured; (g) to any unit that has been repaired or altered by anyone other than Pentair Hydromatic or an authorized Pentair Hydromatic service provider; (h) to any unit that has been repaired using non factory specified/ OEM parts.
Warranty Exclusions: PENTAIR HYDROMATIC MAKES NO EXPRESS OR IMPLIED WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. PENTAIR HYDROMATIC SPECIFICALLY DISCLAIMS THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR ANY PARTICULAR PURPOSE.
Liability Limitation: IN NO EVENT SHALL PENTAIR HYDROMATIC BE LIABLE OR RESPONSIBLE FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES RESULTING FROM OR RELATED IN ANY MANNER TO ANY PENTAIR HYDROMATIC PRODUCT OR PARTS THEREOF. PERSONAL INJURY AND/OR PROPERTY DAMAGE MAY RESULT FROM IMPROPER INSTALLATION. PENTAIR HYDROMATIC DISCLAIMS ALL LIABILITY, INCLUDING LIABILITY UNDER THIS WARRANTY, FOR IMPROPER INSTALLATION. PENTAIR HYDROMATIC RECOMMENDS INSTALLATION BY PROFESSIONALS.
Some states do not permit some or all of the above warranty limitations or the exclusion or limitation of incidental or consequential damages and therefore such limitations may not apply to you. No warranties or representations at any time made by any representatives of Pentair Hydromatic shall vary or expand the provision hereof.
740 EAST 9TH STREET 490 PINEBUSH ROAD, UNIT #4 ASHLAND, OHIO, USA 44805 CAMBRIDGE, ONTA RIO, CANADA N1T 0A5 419-289-1144 800-363-PUMP
WWW.HYDROMATIC.COM
Warranty Rev. 12/13
Page 17
S6A
S4L
MODELS S4L, S4B, S4K, S4Q, H4Q, S4LRC, S6A, S6L and S8F
SUBMERSIBLE
S8F
SOLIDS HANDLING PUMP
INSTALLATION AND SERVICE MANUAL
For use with product built with GE® motor.
NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system.
Item # E-03-314 | Part # 5625-314-1 | © 2013 Pentair Ltd. | 11/26/13
Page 18
General Information
Attention:
This manual contains important information for the safe use of this product. Read this manual completely before using this product and refer to it often for con tin ued safe product use. DO NOT THROW AWAY OR LOSE THIS MAN U AL. Keep it in a safe place so that you may refer to it often. Reasonable care and safe meth ods should be practiced. Check local codes and requirements before installation.
Unpacking Pump:
Remove pump from carton. When un packing unit, check for con cealed damage. Claims for damage must be made at the receiving end through the delivery carrier. Dam age cannot be processed from the factory.
WARNING: Before handling these pumps and controls, always disconnect the power first. Do not smoke or use sparkable electrical devices or flames in a septic (gaseous) or possible septic sump.
CALIFORNIA PROPOSITION 65 WARNING:
This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
Pumps Not Operating or in Storage:
Pumps with carbon ceramic seals must have impellers manually rotated (6 revolutions) after setting non-operational for 3 months or longer and prior to electrical start-up.
Pumps with tungsten carbide seals must have impellers manually rotated (6 revolutions) after setting non-operational for 3 weeks or longer and prior to electrical start-up.
Seal Failure:
An electrode probe is installed in the seal chamber so if any water enters the chamber through the first seal, the electrode will be energized and a signal will be transmitted to the sensing unit at ground surface causing a red light to flash. The electrode probe is installed in all units, but the sensing unit is supplied at extra cost and must be ordered.
In operation the seal failure unit indicates only that there is some water in the seal chamber. The pump will con tin ue to
2
operate without damage, but the seal should be checked immediately after failure is indicated.
The sensing unit is recommended on all installations as good insurance against motor failure.
Pump:
The submersible pumps are supplied for 3 phase and for 200, 230, 460 or 575 volts. Power cable is supplied with separate wire for ground. Be sure green wire is connect ed to a good ground such as water pipe or ground stake.
Heat Sensors:
All motors have heat sensor units embedded in the motor winding to detect excessive heat. The heat sen sors are set to trip at 105°C, so will not operate if dangerous heat occurs. The sensors automatically reset when motor cools to safe temperature.
The sensors are connected in series with the motor starter coil so that the starter is tripped if heat sensor opens. The motor starter is equipped with overload heaters so all normal overloads are protected by the starter.
IMPORTANT: If Hydromatic® electrical starting equip ment is not supplied, the heat sensor circuit must be connected in series with the starter coil or warranty is void.
Sump Level Control:
Sump level is controlled by Hydromatic float switch controls. The float is held in position in the sump by a weight attached to the power cord above the float. The cord supports the float and is adjusted for height from the surface.
Typical duplex systems use three con trols: one set at turn-off, one set at turn-on for one pump, and one set for turn-on for two pumps. Pumps alternate op er a tion on each successive cycle.
Two pumps operate together only if sump level rises to the third or override control. The override control also brings on the second pump in case of failure of the first pump. Extra floats with ap propriate controls can be supplied for alarm functions. Triplex systems use four controls: one set at turn-off, one set at turn-on for one pump, one set at turn­on for two pumps, and one set at turn-on for three pumps. Pumps alternate each successive cycle.
Three pumps operate together only if sump level rises to the fourth control (second override). This control also brings on the third pump in case of failure of either or both of the first two pumps.
Alarm Controls:
The alarm level is usually set above the override level so the alarm will signal only if the override level is exceeded. However, some engineers prefer to have the alarm level set below the override level as it is possible for one pump to fail and the other pump to operate on the override level with the sump level never reach ing the alarm level. This is par ticular ly true in cases of low inflow ca pac i ty.
Electrical Control Panel:
It is recommended that the Hydromatic control panel be used with all pumps as proper starter heaters and connections for heat sensor wires are furnished.
The electrical equipment includes a main circuit breaker for each pump, a magnetic starter with overload protec tion for each pump, an H-O-A switch and run light for each pump, an electric alternator and a trans former to provide appropriate con trol circuit and alarms.
Overload Heaters:
Starters with 3 leg overload protection must be supplied. The heaters must be sized in accordance with the nameplate amps on the motor housing. The amp draw on these submersible motors is slightly higher than a corresponding horsepower surface motor so heaters must be sized by the nameplate rating.
IMPORTANT: Be sure the heat sensor wires are connected in series with the starter coil circuit.
Pump Installation
Installing Pump in Sump:
Before installing pump in sump lay it on side and turn impeller manually. Impeller may be slightly stuck due to factory test water so it must be broken loose with small bar or screwdriver in edge of vanes. The impeller should turn freely.
Clean all trash and sticks from sump and connect pump to piping.
Page 19
A check valve must be installed on each pump. A gate or plug valve in each pump discharge line is also recommended. This valve should be installed on the discharge side of the check valve so if necessary to service the check valve, the line pressure can be cut off. Single pump systems are sometimes installed without a check valve where it is desirable to self-drain the discharge line to prevent freezing. This can be done only with short discharge lines; otherwise water will return to the sump and cause short cycling of the pump.
NEMA 4 Junction Box (Optional):
A NEMA 4 junction box should be used to make power and control connections. The Hydromatic® NEMA 4 junction box is provided with compression connectors for sealing all wires. No sealing compound is needed to make connec tions waterproof.
Wiring diagrams are provided with panel for making connections. The size wire to use from panel to sump depends on
Installing Float Switch Controls:
The controls are supported by a mounting bracket that is attached to sump wall or cover or to the NEMA 4 junction box.
Cord snubbers are used to hold the cord in place. Control lever can be changed at any time by loosening the snubber and readjusting cord length.
In either simplex or duplex system the lower or turn-off control is set just above the top of volute so that the volute will always be submerged during the pumping cycle. The second or turn-on control is set about 24 inches above the lower turn-off control.
More distance between turn-on and turn­off controls can be used, but sewage may become septic and excessive solids may collect for the pump to handle. A frequent pumping cycle is recommended for best operation.
If an alarm system is used, this control is usually set about 6 inches above the override control.
motor size and distance in feet.
Be sure each wire is checked out so that wrong connections will not be made.
WARNING
WARRANTY IS VOID IF HEAT SENSORS ARE NOT
CONNECTED AS SHOWN (IN SERIES WITH CONTACTOR OIL)
TWO WIRE CONTROL OFFERING AUTOMATIC RESET
BLACK
BLACK
THERMOSTATS
IN SERIES
THERMOSTATS
IN SERIES
L1
ON-OFF SWITCH
THREE WIRE CONTROL OFFERING AUTOMATIC RESET
L1
IN CERTAIN APPLICATIONS THE NEC MAY REQUIRE THREE OVERLOAD RELAYS
COIL
COIL
OL OLSTART
WHITE
WHITE
Making Electrical Connections:
All electrical wiring must be in accordance with the local codes, and only competent electricians should make the installations. Complete wiring diagrams are glued to the inside cover of the panel. All wires should be checked for grounds with an ohmmeter or Megger after the connections are made. This is
important, as one grounded wire can cause considerable trouble.
IMPORTANT: If equipment is not properly wired and protected as recommended, the warranty is void.
Heat Sensors and Seal Failure Connections:
Be sure that heat sensor wires are connected in series with the starter coil. Connections are provided on the terminal strip.
Pump Operations
Starting System:
1. Turn H-O-A switch to Off position, then turn on main circuit breakers.
2. Open all discharge valves and allow water to rise in sump pump.
3. Turn H-O-A switch to Hand position on one pump and notice operation. If pump is noisy and vibrates, rotation is wrong. To change rotation interchange any two line leads to motor on 3ø only. Do not interchange main incoming lines. If duplex system, check
L2
L2
second pump in the same manner.
4. Now set both H-O-A switches to Auto position and allow water to rise in sump until one pump starts. Allow pump to operate until level drops to turn-off point.
5. Allow sump level to rise to start other pump. Notice run lights on panel; pumps should alternate on each successive cycle of operation.
NUMBER OF CONDUCTORS REQUIRED BETWEEN CONTROL PANEL AND NEMA 4 JUNCTION BOX
System Number of Number of Number of Type Control Wires Power Lines Ground Wires #8 Number of Number of Sensor Wires Ground Wires
Simplex 3 3 1 3 1
Simplex with Alarm 5 3 1 3 1
Duplex 5 6 1 6 2
Duplex with Alarm 7 6 1 6 2
Power lines and control wires can be carried in conduit or can be underground buried cable.
HEAT SENSOR & SEAL FAILURE
3
Page 20
6. Turn both H-O-A switches to Auto position and allow sump to fill to the override control level.
7. Turn both switches to Auto position and both pumps should start and operate together until level drops to turn-off point.
8. Repeat this operation cycle several times before leaving the job.
9. Check voltage when pumps are operating and check the amp draw of each pump. Check amps on each wire as sometimes a high leg will exist. One leg can be somewhat higher, 5 to 10%, without causing trouble. For excessive amp draw on one leg, the power company should be consulted.
Phase Converters:
Phase converters are generally not recommended, but in cases where only single phase current is available phase converter can be used. Be sure to size the phase converter large enough for the amp draw specified on the motor nameplate, not necessarily by motor horsepower. The warranty on all three phase submersible motors is void if operated with single phase power through a phase converter and 3 leg ambient compensated extra-quick trip overload protectors are not used.
Pump Maintenance
As the motors are oil filled no lu bri ca tion or other maintenance is required.
Generally these pumps give very reliable service and can be expected to operate for years on normal sewage pumping without failure.
Lightning:
In some areas where considerable lightning occurs, it is recommended that a lightning arrestor be installed at the control panel.
Lightning arrestors are good insurance against damage to an expensive motor.
Field Service on Motor:
All submersible motors out of warranty can be serviced in the field by any reliable motor service shop. Any pump in warranty must be returned to the factory for service or re paired at an authorized Hydromatic® service center. Charg es will not be allowed if in warranty pump
is not taken to an authorized Hydromatic service center.
When field service is performed on a pump, these instructions should be carefully followed.
Replacing Stator:
1. If stator only is damaged, it may not be necessary to completely dismantle pump as stator and housing can be lifted from pump without disturbing seals or bear ings.
2. Drain all oil from upper housing, remove drain plug in bottom of stator housing and remove plug in top of housing to allow air to enter.
3. After chamber is drained, remove hold-down bolts and lift off. Use care in lifting as the seal failure connecting wire must be disconnect ed before housing is com plete ly removed.
4. Set assembly on bench and re move connection box. When box is lifted off, connection wires to motor will be exposed. These wires will probably be burned, but each wire is tagged with a metal marker giving wire number. Cut the wires.
If the leads to the connection box are
burned, a complete new con nec tion box with new wire must be used. The wires are potted in with sealing compound and a new unit must be obtained from the factory.
5. The stator is held in the housing with a bolted-in end ring and an outside locking screw.
6. After the ring is removed, turn housing upright and bump on hardwood blocks. This should jar the stator loose and allow it to drop out.
7. Thoroughly clean housing before replacing new stator. Replace stator and make all wire con nec tions to connection box before replacing housing on pump. This is important as leads must be tucked behind the windings by using hands up through rotor core.
IMPORTANT: Use only com pres sion type insulated connectors on the wires.
Do not tape leads as oil will deteriorate the tape and cause damage to stator and bearings.
8. Check top bearing. If clean and does not turn rough, bearings can be reused and it is not necessary to completely dismantle pump to change bearings. If bearings are damaged with dirt or heat, they must be replaced. Remember to reinstall the upper bearing load spring.
9. Before replacing stator housing, be sure outside lock screw is in place and that O-ring is used under head of bolt. A leak here can cause a motor failure.
10. Replace stator housing onto the seal chamber and bolt in place. Be sure the seal failure wire is connected before the hous ing is assembled.
Be sure back-off screws have been
loosened so that parts can come metal to metal. Be sure O-ring seal has been replaced. If O-ring is nicked or cut, replace with new rings. This applies to all O-rings used in assembly.
11. After all leads are reconnected in the connection box, make a high voltage ground test on each wire. The only wire that should show ground is the green power lead and the ground lead in the auxil ia ry control cable.
12. For safety, complete pump should be air checked under water for leaks. Lay pump on side for this oil filling with oil fill hole upright. Do not completely fill; leave oil about 1 inch below plug hole. Use only Hydro matic submersible oil in this chamber. Replace plug; use Permatex on threads. Install air valve in top plug opening of motor housing and charge housing with about 10 psi of air. Be sure air is dry. Do not use air line where water may be trapped in the line. Submerge complete unit under water and check for leaks.
13. Refill motor chamber with oil. Use Hydromatic special submers ible oil. Fill chamber until oil cov ers top of windings. Leave air space in top for expansion. Use Permatex on plug threads.
4
Page 21
Replacing Seals and Bearings:
1. Drain all oil from motor chamber and seal chamber as described.
2.
Remove motor housing as de scribed.
3. Remove bolts that hold seal chamber to pump housing. Use back-off screws to break loose. With hardwood block, tape end of impeller to loosen from shaft. When free, remove impeller from shaft.
4. Lift rotating assembly (rotor, shaft and impeller) from pump case and place horizontally on bench.
5. Remove screw and washer from end of shaft and then screw socket head bolt back into shaft. Using a screwdriver on opposite sides behind impeller, apply force then tap on end of socket bolt to break impeller loose from taper shaft.
6. Remove key and pry on each side of shoulder of shaft sleeve to remove. Seal should come off with sleeve. If sleeve is not free, leave in place and push off when seal plate is removed.
7. To remove seal plate, take out socket head flat screws and using screws in back-off holes, pry plate loose. This will also force seal off if not already removed.
8. Remove snap ring that holds upper seal. Pull seal if it is free. If not free, it can be forced off when shaft is removed.
9. Remove bolts that hold bearing housing in place. Set assembly in upright position and bump end of shaft on hardwood block. This will push the bearing from the housing and will force upper seal from shaft.
10. Use bearing puller to remove bearings. Replace with new bear ings. Press only on inner face of bearing when replacing. Pressing on outer face can damage the bearing.
IMPORTANT: Do not use any of
the old seal parts. Replace with all new seals.
11. Thoroughly clean all castings before replacing seals. One grain of dirt between the seal faces can cause failure.
12. Examine all O-rings for nicks before using.
13. Be sure key is in place in notch of shaft sleeve to prevent sleeve from turning.
14. Use Locktite® on socket head locking screw in end of shaft.
15. Before refilling chamber with oil, air test as described above and then refill both chambers with oil.
16. Always check all leads with high voltage or with Megger for grounds before operating the pump.
Pump Troubleshooting
Below is a list of common problems and the probable causes:
Pump will not start.
1. No power to the motor. Check for blown fuse or open circuit breaker.
2. Selector switch may be in the Off position.
3. Control circuit transformer fuse may be blown.
4. Overload heater on starter may be tripped. Push to reset.
Pump will not start and overload heaters trip.
1. Turn off power and check motor leads with Megger or ohmmeter for possible ground.
2. Check resistance of motor windings. All 3 phases should show the same reading.
3. If no grounds exist and the motor windings check OK, remove pump from sump and check for clogged or blocked impeller.
Pump operates with selector switch in Hand position but will not operate in Auto position.
1. This indicates trouble in the float level control or the alternator relay.
2. Check control panel for trouble.
Pump runs but will not shut off.
1. Pump may be air locked. Turn pump off and let set for several minutes, then restart.
2. Lower float control may be hung-up in the closed position. Check in sump to be sure control is free.
3. Selector switch may be in the Hand position.
Pump does not deliver proper capacity.
1. Discharge gate valve may be partially closed or partially clogged.
2. Check valve may be partially clogged. Raise level up and down to clear.
3. Pump may be running in wrong direction. Low speed pumps can operate in reverse direction without much noise or vibration.
4. Discharge head may be too high. Check total head with gauge when pump is operating. Total head is discharge gauge pressure converted to feet plus vertical height from water level in sump to center line of pressure gauge in discharge line. Gauge should be installed on pump side of all valves. Multiply gauge pressure in pounds by 2.31 to get head in feet.
5. If pump has been in service for some time and capacity falls off, remove pump and check for wear or clogged impeller.
Motor stops and then restarts after short period but overload heaters in starter do not trip.
1. This indicates heat sensors in the motor are tripping due to excessive heat. Impeller may be partially clogged giving a sustained overload but not high enough to trip overload heater switch.
2. Motor may be operating out of liquid due to a failed level control.
3. Pump may be operating on a short cycle due to sump being too small or from water returning to sump due to a leaking check valve.
5
Page 22
21
23
17
7
39
12
32
1
3
5
6
38
14
40
35
36
31
33
30
373428272625
2
8
4
9
11
13
15 16
18
19
24
22
29
20
10
S4L Parts List For use with product built with GE
Ref.
Part
No.
1 060000035 Wire & Terminal Assy. – (Prior to 5/1/78) 1
060000211 Wire & Terminal Assy. – (Present) 1 2 005570001 Wire Connector 3 3 RTF Rotor & Shaft 1 4 000640051 Bearing Spring 2 5 RTF Stator 1 6 025970022 Motor Housing for Use with 20 hp & Below 1
048320012 Motor Housing for Use with 25 hp & Up 1 7 001500071 O-Ring SC 1 8 011240021 Jam Nut 2 9 009750051 Retaining Ring 1
10 076650011 Spacer for Stator – 3 to 15 hp, 1150 RPM 1 11 008340021 O-Ring SC 2 12 12672A001 Wire Connector 3 13 026030003 Stator Ring 1 14 005680061 Bolt 8 15 009750081 Retaining Ring 1 16 025950032 Housing Seal (Present) 1 17 008530001 Wire Conn. – 200V, 10/4 Cord 3
024940001 Wire Conn. – 200V, 8/4 Cord 3
024940001 Wire Conn. – 230V 4
008530001 Wire Conn. – 460V, 10/4 Cord 6
024940001 Wire Conn. – 460V, 8/4 Cord 3
008530001 Wire Conn. – 460V, 8/4 Cord 3
008530001 Wire Conn. – 575V, 10/4 Cord 3
024940001 Wire Conn. – 575V, 8/4 Cord 3
18 001500401 O-Ring SC 1 19 025960002 Seal Plate – (Prior to 3/1/74) 1
025960032 Seal Plate – (Present) 1
20 019570001 Shaft Seal – Ceramic SC 1 or 2
019570021 Shaft Seal – Opt. Carbide
21 RTF Cord Cap Assy. 1 22 001500121 O-Ring SC 1 23 062370005 Conn. Box Assy. – 230/460V 1
062370015 Conn. Box Assy. – 200/575V 1
24 000130041 Set Screw 2 25 042890023 Wear Ring Brz. 1 26 028550011 Key 1 27 019450001
001560111
28 005700181 Capscrew (Up to 25 hp) 1
048340001 Imp. Nut (25–35 hp) 1
29 029210011 Flat Hd. Screw 4 30 025940242 Impeller – 8.38" Diameter 1
025940232 Impeller – 8.81" Diameter 1
025940022 Impeller – 9" Diameter 1
025940032 Impeller – 9.25" Diameter 1
025940042 Impeller – 9.5" Diameter 1
025940192 Impeller – 9.81" Diameter 1
025940062 Impeller – 10" Diameter 1
025940162 Impeller – 10.38" Diameter 1
025940082 Impeller – 10.5" Diameter 1
025940102 Impeller – 11" Diameter 1
025940202 Impeller – 11.38" Diameter 1
025940182 Impeller – 11.63" Diameter 1
025940002 Impeller – 11.88" Diameter 1
31 001500261 O-Ring SC 1 32 08565A026 Upper Bearing 1 33 089190015 Volute 1 34 05876A007 O-Ring SC 1 35 084720035 Sensor Assy. (Present) 1 36 026020003 Sleeve SC 1
Notes: S — Parts in Seal Kit C — Parts in Carbide Seal Kit RTF — Refer To Factory — Fill oil to above motor windings
Part
No.
Description Qty.
(Bottom Seal Only)
Shaft Holding Washer – (Up to 25 hp) Shaft Holding Washer – (25–35 hp)
C 1
1 1
Ref.
Part
No.
37 009750061 Snap Ring 1 38 000650261 Lower Bearing (Present) 1 39 010060011 Wire Conn. 230/460V 9
010060011 Wire Conn. 200/575V 3
40 001500251 O-Ring SC 1
076650001 Spacer for Stator – 10 to 20 hp, 1750 RPM 1 – 517000197 Seal Kit – 517003197 Carbide Seal Kit
Part
No.
Description Qty.
®
motor.
6
Page 23
5
1
6
7
2
11
13
32
37
3
8
36
29
15
18
30
16
17
28
23
27
4
35
9
36
38
10
12
33
34
14
31
26
24
21
25
22
19 20
®
motor.
S4B Parts List For use with product built with GE
Ref.
Part
No.
1 001500121 O-Ring SC 1 2 005570001 Con nec tor 3 3 060000211 Wire & Terminal Assy. 1 4 000640051 Bearing Spring 2 5 RTF Cord Cap Assy. – 35' 1
6 062370005 Conn Box Assy. – 230/460 1
062370015 Conn Box Assy. – 200/575 1
7 024980041 Wire Connector – 200, 4-3 cord 4
024940001 Wire Connector – 230/460, 6-3 cord 4 008530001 Wire Connector – 575, 8-4 cord 3 024980051 Wire Connector – 230, 4-3 cord 4 008530001 Wire Connector – 460, 8-4 cord 3 024940001 Wire Connector – 460, 8-4 cord 3 024940001 Wire Connector – 460/575, 6-3 cord 3 008530001 Wire Connector – 460/575, 6-3 cord 3
008530001 Wire Connector – 200, 10-4 cord 3 8 RTF Rotor and Shaft 1 9 009750051 Re tain ing Ring 1
10 008340021 O-Ring SC 2 11 001500071 O-Ring SC 1 12 026030003 Sta tor Ring 1 13 002820011 Wire Connector 3 14 009750081 Re tain ing Ring 1 15 025950032 Seal Housing 1 16 001500401 O-Ring SC 1 17 025960032 Seal Plate 1 18 019570001 Seal – Ceramic (Std.) SC 1 or 2
019570021 Seal – Carbide (Opt.) C 1
19 008290061 Mach Screw 3 20 136900003 Wear Ring, Bronze 1 21 028550011 Key 1 22 001560111 Shaft Holding Washer – 25 hp & Up 1
019450001 Shaft Holding Washer – 20 hp and Below 1
23 005700181 Impeller Nut – Up to 25 hp 1
048340001 Impeller Nut – 25 hp & Up 1
24 029210011 Flat Hd Screw 4 25 136920012 Impeller – 12" Diameter 1
136920052 Impeller – 11" Diameter 1
136920092 Impeller – 10" Diameter 1
136920102 Impeller – 9.5" Diameter 1
136920132 Impeller – 9" Diameter 1
26 001500261 O-Ring SC 1 27 136910002 Volute 1 28 001500031 O-Ring SC 1 29 084720035 Sensor Assy. 1 30 026020003 Sleeve SC 1 31 009750061 Snap Ring 1 32 010060011 Wire Connector – 230/460 9
010060011 Wire Connector – 200/575 3
33 001500251 O-Ring SC 1 34 000650261 Lower Bearing 1 35 000650061 Upper Bearing 1 36 076650011 Spacer – 3–15 hp, 1150 RPM 1
076650001 Spacer – 10–20 hp, 1750 RPM 1
076650061 Spacer – 3–5 hp, 870 RPM 1
37 048320012 Motor Housing – 10274 Series 1
025970022 Motor Housing – 10272 & 10273 Series 1
38 RTF Stator 1
517000197 Seal Kit – 517003197 Carbide Seal Kit
Notes: S — Parts in Seal Kit C — Parts in Carbide Seal Kit RTF — Refer To Factory — Fill oil to above motor windings
Part
No.
Description Qty.
7
Page 24
S4K Parts List For use with product built with GE
Ref.
Part
No.
1 001500121 O-Ring SC 1 2 005570001 Con nec tor 3 3 RTF Cord Cap Assy. – 35' 1 4 025970022 Motor Housing – 20 hp 1
048320012 Motor Housing – 25–40 hp 1
5 062370005 Conn Box Assy. – 230/460 1
062370015 Conn Box Assy. – 200/575 1
6 008530001 Wire Conn. – 25–40 hp, 460/3/60 3
008530001 Wire Conn. – 20 hp, 575/3/60 3 024940001 Wire Conn. – 20 hp, 230/460 4 024940001 Wire Conn. – 25–40 hp, 460/3/60 3
024940001 Wire Conn. – 25–30 hp, 575/3/60 3 7 001500071 O-Ring SC 1 8 RTF Rotor & Shaft 1 9 009750051 Re tain ing Ring 1
10 008340021 O-Ring SC 2 11 002820011 Wire Connector 3 12 026030003 Stator Ring 1 13 010060011 Wire Conn. – 200/230/460, 25 & 40 hp 9
010060011 Wire Conn. – 200, 20 hp 3
010060011 Wire Conn. – 575, 20–30 hp 3
14 009750081 Retaining Ring – (15–20 hp) 1
009750251 Retaining Ring – (25–40 hp) 1
15 025950032 Housing Seal – (15–20 hp) 1
025950042 Housing Seal – (25–40 hp) 1
16 001500401 O-Ring SC 1 17 025960032 Seal Plate 1 18 019570001 Upper Seal – Ceramic SC 1 19 019570001 Lower Seal – (Ceramic) Std. S 1
019570021 Lower Seal – (Carbide) Opt. C 1
20 008290061 Flat H. Screw 3 21 136900003 Wear Ring (Bronze) 1 22 028550081 Key 1 23 019450001 Imp Washer 1 24 005700181 Impeller Bolt 1 25 029210011 Flat Hd. Screw 4 26 137200122 Impeller – 9.25" Diameter 1
137200072 Impeller – 10.5" Diameter 1
137200052 Impeller – 11" Diameter 1
137200012 Impeller – 12" Diameter 1
27 001500261 O-Ring SC 1 28 137190002 Volute 1 29 084720035 Sensor Assy. 1 30 009750061 Retaining Ring 1 31 000650061 Upper Bearing 1 32 001500251 O-Ring SC 1 33 00065026l Lower Bearing – (15–20 hp) 1 33 000650321 Lower Bearing – (25–40 hp) 1 34 060000211 Wire & Terminal Assy. 1 35 000640051 Bearing Spring 2 36 RTF Stator 1
517000657 Seal Kit S 1 – 517003657 Carbide Seal Kit C 1
Part
No.
Description Qty.
3
1
5
6
2
7
11
13
9
34
8
36
33
29
15
18
17
25
28
22
21
®
motor.
24 23
35 31
4
10
12
14 32
30
19
27
16
26
20
Notes: S — Parts in Seal Kit C — Parts in Carbide Seal Kit RTF — Refer To Factory — Fill oil to above motor windings
8
Page 25
10
1
S4Q Parts List For use with product built with GE
Ref.
Part
No.
1 RTF Cord Cap Assy. – 30' 1 2 005570001 Con nec tor 3 3 RTF Stator 1 4 076650001 Spacer – 10–20 hp, 1750 RPM 1 5 062370005 Conn Box Assy. – 230/460 1
062370015 Conn Box Assy. – 200/575 1
6 024980041 Wire Connector – 200 4-3, cord 4
024940001 Wire Connector – 230/460, 6-3 cord 4 008530001 Wire Connector – 575, 8-4 cord 3 024980051 Wire Connector – 230, 4-3 cord 4 008530001 Wire Connector – 460, 8-4 cord 3 024940001 Wire Conector – 460, 8-4 cord 3 024940001 Wire Connector – 460/575, 6-3 cord 3 008530001 Wire Connector – 460/575, 6-3 cord 3
008530001 Wire Connector – 200, 10-4 cord 3 7 001500071 O-Ring SC 1 8 RTF Rotor and Shaft 1 9 009750051 Re tain ing Ring 1
10 008340021 O-Ring SC 2 11 002820011 Wire Connector 3 12 026030003 Sta tor Ring 1 13 010060011 Wire Connector – 230/460 9
010060011 Wire Connector – 200/575 3
14 009750081 Re tain ing Ring 1 15 025950032 Seal Housing 1 16 001500401 O-Ring SC 1 17 025960032 Seal Plate 1 18 019570001 Seal – Ceramic (Std.) SC 1 or 2
019570021 Seal – Carbide (Opt.) C 1
19 008290061 Mach Screw 6 20 136900013 Wear Ring 1 21 028550011 Key 1 22 001560111 Shaft Holding Washer – 25 hp & Up 1
019450001 Shaft Holding Washer – 20 hp and Below 1
23 005700181 Impeller Nut – Up to 25 hp 1
048340001 Impeller Nut – 25 hp & Up 1
24 029210011 Flat Head Screw 4 25 141250012 Impeller – 12" Diameter 1
141250052 Impeller – 11" Diameter 1
141250092 Impeller – 10" Diameter 1
141250112 Impeller – 9.5" Diameter 1
141250132 Impeller – 9" Diameter 1
26 143310001 Gasket 2 27 136910022 Volute 1 28 000640051 Bearing Spring 2 29 084720035 Sensor Assy. 1 30 001500121 O-Ring SC 1 31 009750061 Snap Ring 1 32 000650061 Upper Bearing 1 33 001500251 O-Ring SC 1 34 000650261 Lower Bearing 1 35 060000215 Wire & Terminal Assy. 1 36 012720013 Insulating Tubing 1 37 048320012 Motor Housing – 10274 Series 1
025970022 Motor Housing – 10272 & 10273 Series 1
141240003 Wear Ring Adapter 1 – 141240013 Adapter Plate 1 – 517000197 Seal Kit – 517003197 Carbide Seal Kit
Part
No.
Description Qty.
30
5
6
2
7
11
13
8
37
36
35
15
29
18
16
17
27
®
motor.
21
23
22
20 19
31
28
32
9
4
3
12
34
33
26
24
25
14
Notes: S — Parts in Seal Kit C — Parts in Carbide Seal Kit RTF — Refer To Factory — Fill oil to above motor windings
9
Page 26
1
H4Q Parts List For use with product built with GE
Ref.
Part
No.
1 RTF Cord Cap Assy. – 35' 1 2 005570001 Con nec tor 3 3 062370005 Conn Box Assy. – 230/460 1
062370015 Conn Box Assy. – 200/575 1 4 076650001 Spacer – 10–20 hp, 1750 RPM 1 5 024980041 Wire Connector – 200, 4-3 cord 4
024940001 Wire Connector – 230/460, 6-3 cord 4
008530001 Wire Connector – 575, 8-4 cord 3
024980051 Wire Connector – 230, 4-3 cord 4
008530001 Wire Connector – 460, 8-4 cord 3
024940001 Wire Connector – 460, 8-4 cord 3
024940001 Wire Connector – 460/575, 6-3 cord 3
008530001 Wire Connector – 460/575, 6-3 cord 3
008530001 Wire Connector – 200, 10-4 cord 3 6 001500071 O-Ring SC 1 7 002820011 Wire Connector 3 8 048320012 Motor Housing – 10274 Series 1
025970022 Motor Housing – 10272 & 10273 Series 1 9 009750051 Re tain ing Ring 1
10 008340021 O-Ring SC 2 11 010060011 Wire Connector – 230/460 9
010060011 Wire Connector – 200/575 3
12 026030003 Sta tor Ring 1 13 08565A026 Upper Bearing 1 14 009750081 Re tain ing Ring 1 15 025950032 Seal Housing 1 16 001500401 O-Ring SC 1 17 025960032 Seal Plate 1 18 019570001 Seal – Ceramic (Std.) SC 1 or 2
019570021 Seal – Carbide (Opt.) C 1
19 060000215 Wire & Terminal Assy. 1 20 136900033 Wear Ring 1 21 028550011 Key 1 22 001560111 Shaft Holding Washer – 25 hp & Up 1
019450001 Shaft Holding Washer – 20 hp and Below 1
23 005700181 Impeller Nut – Up to 25 hp 1
048340001 Impeller Nut – 25 hp & Up 1
24 029210011 Flat Head Screw 4 25 151510002 Impeller – 12" Diameter 1
151510022 Impeller – 11" Diameter 1
151510042 Impeller – 10" Diameter 1
151510052 Impeller – 9.5" Diameter 1
151510062 Impeller – 9" Diameter 1
26 001500261 O-Ring 1 27 151520015 Volute 1 28 000640051 Bearing Spring 2 29 084720035 Sensor Assy. 1 30 001500121 O-Ring SC 1 31 009750061 Snap Ring 1 32 RTF Rotor and Shaft 1 33 001500251 O-Ring SC 1 34 000650261 Lower Bearing 1 35 RTF Stator 1 36 012720013 Insulating Tubing 1
517000197 Seal Kit – 517003197 Carbide Seal Kit
Part
No.
Description Qty.
30
3
5
2
6
7
11
32
8
36
19
15
29
18
16
17
27
®
motor.
21
23
22
20
31
28
13
9
4
35
10
12
34
33
26
24
25
14
Notes: S — Parts in Seal Kit C — Parts in Carbide Seal Kit RTF — Refer To Factory Fill oil to above motor windings
10
Page 27
25
26
27
28
32
34
5
36
7
6
1
3
22
14
8
35
12
31
33
30
2423211920
2
4
9
11
13
15
16 17
18
29
10
S4LRC – 1750 RPM Parts List For use with product built with GE
Ref.
Part
No.
1 RTF Stator 1 2 000730011 Wire Connector 3 3 025970022 Motor Housing – 20 hp & below 1
048320012 Motor Housing – 25 hp & above,
4 000640051 Bearing Spring –
5 002820011 Wire Connector 3 6 RTF Rotor & Shaft 1 7 060000035 Wire & Terminal Assy. – (Prior to 5/1/78) 1
060000211 Wire & Terminal Assy. – (Present) 1 8 001500251 O-Ring SC 1 9 009750051 Retaining Ring 1
10 076650011 Spacer for New Style Stator –
076650001 Spacer for New Style Stator –
11 008340021 O-Ring SC 2 12 026020003 Sleeve SC 1 13 026030003 Stator Ring 1 14 005680061 Bolt 8 15 009750081 Retaining Ring 1 16 025950032 Housing Seal (Present) 1 17 001500401 O-Ring SC 1 18 025960002 Seal Plate – (Prior to 3/1/74) 1
025960032 Seal Plate – (Present) 1
19 028550011 Key 1 20 019570001 Shaft Seal – Ceramic SC 1 or 2
019570021 Shaft Seal – Opt. Carbide
21 019450001 Shaft Holding Washer – (Up to 25 hp) 1
001560111 Shaft Holding Washer – (25–35 hp) 1
22 000650261 Lower Bearing (Present) 1 23 001500031 O-Ring SC 1 24 009750061 Snap Ring 1 25 RTF Cord Cap Assy. – 35' 1 26 001500121 O-Ring SC 1 27 062370005 Conn. Box Assy. – 230/460V 1
062370015 Conn. Box Assy. – 200/575V 1
28 008530001 Wire Connector – 200V, 10/4 Cord 3
024940001 Wire Connector – 200V, 8/4 Cord 3
024940001 Wire Connector – 230V 4
008530001 Wire Connector – 460V, 10/4 Cord 6
024940001 Wire Connector – 460V, 8/4 Cord 3
008530001 Wire Connector – 460V, 8/4 Cord 3
008530001 Wire Connector – 575V, 10/4 Cord 3
024940001 Wire Connector – 575V, 8/4 Cord 3
29 029210011 Flat Head Screw 4 30 069580002 Impeller – 12" Diameter 1
069580012 Impeller – 11.5" Diameter 1
069580192 Impeller – 11.25" Diameter 1
069580142 Impeller – 10.31" Diameter 1
069580042 Impeller – 10" Diameter 1
069580132 Impeller – 9.25" Diameter 1
069580122 Impeller – 8.63" Diameter 1
069580112 Impeller – 7.88" Diameter 1
31 001500261 O-Ring SC 1 32 001500071 O-Ring SC 1 33 107830002 Volute 1 34 010060011 Wire Conn. – 230/460V 9
010060011 Wire Conn. – 200/575V 3
35 084720035 Sensor Assy. (Present) 1 36 000650061 Upper Bearing 1
517000197 Seal Kit – 517003197 Carbide Seal Kit
Notes: S — Parts in Seal Kit C — Parts in Carbide Seal Kit RTF — Refer To Factory Fill oil to above motor windings
Part
No.
Description Qty.
15 hp, 1150 RPM
(None Required Prior to 2/14/78)
3 to 15 hp, 1150 RPM
10 to 20 hp, 1750 RPM
(Bottom Seal Only)
1
2
1
1
C 1
®
motor.
11
Page 28
S4LRC – 3450 RPM Parts List For use with product built with GE
Part
Part
No.
19101A010 Screw – HHC 3/8-16 x 1" 8 021500121 O-Ring – 1/8 1 041500071 O-Ring – 1/8 1 002820011 Connector – Wire 3 000650061 Bearing – Ball 1 060000211 Wire w/Terminal 1 012720013 Tubing – Insulating 1 048320012 Housing – Motor 1 000650261 Bearing – Ball 1 19103A043 Screw – HHC 1/2-13 x 1-1/2" 8 001500251 O-Ring – 1/8 1 084720035 Seal Failure Assembly 1 19105A033 Screw – HHC 5/8-11 x 1-1/2" 8 001500261 O-Ring 1 029210011 Screw – HHC 1/2-13 x 1-1/4" 4 107830002 Volute Case 1
Description Qty.
Notes: RTF — Refer To Factory Fill oil to above motor windings
Part
Part
No.
009750061 Ring – Retaining 1 05876A007 O-Ring – 1/16 1 048340001 Nut – Impeller 1 001560111 Washer – Flat 1 028550031 Key – Square 3/8 1 025960032 Plate – Seal 1 001500401 O-Ring – 1/8 1 025950032 Housing – Bearing/Seal 1 009750081 Ring – Retaining 1 026030003 Ring – Stator Retaining 1 008340021 O-Ring – 3/32 1 009750051 Ring – Retaining 1 000640051 Spring – Bearing Adj. 2
011240021 Nut – Hex 5/8-11 2 016640021 Plug – Pipe 3/8 3 000730011 Connector – Wire 3
Description Qty.
Part
Part
No.
Description Qty.
RTF Stator 1
RTF Rotor/Shaft 1 010060011 Connector – Splice, 460V 9 010060011 Connector – Splice, 575V 3 062370005 Box – Connection, 460V 1 062370015 Box – Connection, 575V 1 076650011 Spacer – 50" 1 024930001 Connector – Wire, 460V 3 148630002 Impeller – 8.31" Dia. 1 148630022 Impeller – 7.00" Dia. 1 148630032 Impeller – 6.00" Dia. 1
RTF Cord Cap Assy. 35' 1 024940011 Connector – 40–50 hp, 60 hp, 575V 3 024980051 Connector – 60 hp, 460V 3 019570001 Seal – Type 21 Ceramic 1 019570021 Seal – Type 21 Carbide (Optional) 1 026020003 Sleeve – Shaft 1
®
motor.
12
Page 29
S6A Parts List For use with product built with GE
Ref.
Part
No.
1 001500121 O-Ring SC 1 2 005570001 Con nec tor 3 3 RTF Stator 1 4 076650011 Spacer – 3–15 hp, 1150 RPM 1
076650001 Spacer – 10–20 hp, 1750 RPM 1
076650061 Spacer – 3–5 hp, 870 RPM 1 5 RTF Cord Cap Assy. – 35' 1 6 000650061 Upper Bearing 1 7 062370005 Conn. Box Assy. – 230/460V 1
062370015 Conn. Box Assy. – 200/575V 1 8 RTF Rotor and Shaft 1 9 009750051 Retaining Ring 1
10 008340021 O-Ring SC 2 11 024980041 Wire Connector – 200V, 4/3 cord 4
024940001 Wire Connector – 230/460V, 6/3 cord
008530001 Wire Connector – 575V, 8/4 cord 3
024980051 Wire Connector – 230V, 4/3 cord 4
008530001 Wire Connector – 460V, 8/4 cord 3
024940001 Wire Connector – 460V, 8/4 cord 3
024940001 Wire Connector – 460 & 575V, 6/3 cord
008530001 Wire Connector – 460 & 575V, 6/3 cord
008530001 Wire Connector – 200V, 10/4 cord 3
12 026030003 Stator Ring 1 13 001500071 O-Ring SC 1 14 009750081 Retaining Ring 1 15 025950032 Seal Housing 1 16 001500401 O-Ring SC 1 17 025960032 Seal Plate 1 18 0l9570001
019570021
19 008290091 Machine Screw 4 20 136950003 Wearing Ring, Bronze 1 21 028550011 Key 1 22 001560111 Shaft Holding Washer – (25 hp & Up) 1
019450001 Shaft Holding Washer – (20 hp & Below) 1
23 060000211 Wire & Terminal Assy. 1 24 029210011 Flat Head Screw 4 25 136940052 Impeller – 11" Diameter 1
136940072 Impeller – 10.5" Diameter 1
136940092 Impeller – 10" Diameter 1
136940112 Impeller – 9.5" Diameter 1
136940132 Impeller – 9" Diameter 1
26 001500261 O-Ring SCI 1 27 136930012 Volute 1 28 05876A007 O-Ring SC 1 29 084720035 Sensor Assy. 1 30 026020003 Sleeve SC 1 31 009750061 Snap Ring 1 32 002820011 Wire Connector 3 33 001500251 O-Ring SC 1 34 000650261 Lower Bearing 1 35 010060011 Wire Connector – 230/460 9
010060011 Wire Connector – 200/575 3
36 000640051 Bearing Spring 2 37 048320012 Motor Housing – (10274 Series) 1
025970022 Motor Housing – (10272 & 10273 Series) 1 – 517000197 Seal Kit – 517003197 Carbide Seal Kit
Part
No.
Description Qty.
Shaft Seal – Ceramic (Std.) Shaft Seal – Carbide (Opt.) (Lower Only)
5
1
7
11
2
13
32
35
37
8
23
36
SC 1 or 2
C 1
15
29
18
30
16
17
27
28
®
motor.
22 20 19
36
10
12
14
33
31
6
9
4
3
34
6
26
24
21
25
Notes: S — Parts in Seal Kit C — Parts in Carbide Seal Kit RTF — Refer To Factory — Fill oil to above motor windings
13
Page 30
32
34
37
14
39
7
3
1
5
6
8
28
38
35
36
31
33
30
22272625
2
4
9
11
12
13
15
16
18
17
19
24
29
20
10
23
21
S6L Parts List For use with product built with GE
Ref.
Part
No.
1 060000035 Wire & Terminal Assy. – (Prior to 5/1/78) 1
060000211 Wire & Terminal Assy. – (Present) 1 2 000730011 Wire Connector 3 3 RTF Rotor & Shaft 1 4 000640051 Bearing Spring 2 5 RTF Stator 1 6 025970022 Motor Housing – 20 hp & Below 1
048320012 Motor Housing – 25 hp & Above,
7 08565A026 Upper Bearing 1 8 000650261 Lower Bearing (Present) 1 9 009750051 Retaining Ring 1
10 076650011 Spacer for Stator – 5 to 15 hp, 1150 RPM 1
076650001 Spacer for Stator – 10 to 20 hp, 1750 RPM 1
11 008340021 O-Ring SC 2 12 005680011 Screw Cap 2 13 026030003 Stator Ring 1 14 010060011 Wire Conn. – 230/460V 9
010060011 Wire Conn. – 200/575V 3
15 009750081 Retaining Ring 1 16 025950032 Housing Seal 1 17 025960032 Seal Plate 1 18 001500401 O-Ring SC 1 19 000130041 Set Screw 2 20 019570001 Shaft Seal – Ceramic SC 1 or 2
019570021 Shaft Seal – Opt. Carbide
21 05876A007 O-Ring SC 1 22 009750061 Snap Ring 1 23 RTF Cord Cap Assy. – 35' 1 24 001500121 O-Ring SC 1 25 042890023 Wear Ring, Bronze 1 26 028550011 Key 1 27 019450001 Shaft Holding Washer – (Up to 25 hp) 1
001560111 Shaft Holding Washer – (25–35 hp) 1
28 005680061 Bolt 8 29 029210011 Flat Head Screw 4 30 025940002 Impeller – 11.88" Diameter (11-7/8) 1
025940122 Impeller – 11.50" Diameter 1
025940102 Impeller – 11.00" Diameter 1
025940082 Impeller – 10.50" Diameter 1
025940162 Impeller – 10.38" Diameter (10-3/8) 1
025940212 Impeller – 10.18" Diameter 1
025940192 Impeller – 9.81" Diameter 1
025940042 Impeller – 9.50" Diameter 1
025940032 Impeller – 9.25" Diameter 1
025940242 Impeller – 8.37" Diameter 1
31 001500261 O-Ring SC 1 32 062370005 Conn. Box Assy. – 230/460V 1
062370015 Conn. Box Assy. – 200/575V 1
33 089180015 Volute 1 34 008530001 Wire Conn. – 200V, 10/4 Cord 3
024940001 Wire Conn. – 200V, 8/4 Cord 3
024940001 Wire Conn. – 230V 4
008530001 Wire Conn. – 460V, 10/4 Cord 6
024940001 Wire Conn. – 460V, 8/4 Cord 3
008530001 Wire Conn. – 460V, 8/4 Cord 3
008530001 Wire Conn. – 575V, 10/4 Cord 3
024940001 Wire Conn. – 575V, 8/4 Cord 3
35 084720035 Sensor Assy. 1 36 026020003 Sleeve SC 1 37 001500071 O-Ring SC 1 38 001500251 O-Ring SC 1 39 12672A001 Wire Connector 3
517000197 Seal Kit – 517003197 Carbide Seal Kit
Part
No.
Description Qty.
15 hp, 1150 RPM
(Bottom Seal Only)
1
C 1
®
motor.
Notes: S — Parts in Seal Kit C — Parts in Carbide Seal Kit RTF — Refer To Factory — Fill oil to above motor windings
14
Page 31
S8F Parts List For use with product built with GE
Ref.
Part
No.
1 060000211 Wire & Terminal Assy. – (Present) 1 2 000730011 Wire Connector 3 3 RTF Rotor & Shaft 1 4 000640051 Bearing Spring 2 5 RTF Stator 1
6 025970022 Motor Housing – (20 hp and Below) 1
048320012 Motor Housing – (25 hp and Above) 1 7 08565A026 Upper Bearing 1 8 000650261 Lower Bearing 1 9 009750051 Retaining Ring 1
10 076650011 Spacer for Stator – 3 to 15 hp, 1150 RPM 1
076650001 Spacer for Stator – 10 to 20 hp, 1750 RPM 1
11 008340021 O-Ring SC 2 12 005680011 Screw Cap 2 13 026030003 Stator Ring 1 14 002390071 Bolt 8 15 009750081 Retaining Ring 1 16 025950032 Housing Seal 1 17 025960032 Seal Plate – (Present) 1 18 001500401 O-Ring SC 1 19 009750061 Snap Ring 1 20 019570001 Shaft Seal – Ceramic SC 1 or 2
019570021 Shaft Seal – Opt. Carbide
21 001500031 O-Ring SC 1 22 RTF Cord Cap Assy. – 35' 1 23 001500121 O-Ring SC 1 24 000130041 Set Screw 2 25 042890023 Wear Ring, Bronze 1 26 028550011 Key 1 27 019450001 Shaft Holding Washer – (Up to 25 hp) 1
001560111 Shaft Holding Washer – (25–35 hp) 1
28 010060011 Wire Conn. – 230/460V 9
010060011 Wire Conn. – 200/575V 3
29 029210011 Flat Head Screw 4 30 025940122 Impeller – 11.50" Diameter 1
025940202 Impeller – 11.38" Diameter 1
025940112 Impeller – 11.25" Diameter 1
025940272 Impeller – 10.85" Diameter 1
025940082 Impeller – 10.50" Diameter 1
025940162 Impeller – 10.38" Diameter 1
025940072 Impeller – 10.25" Diameter 1
025940212 Impeller – 10.18" Diameter 1
025940302 Impeller – 9.63" Diameter 1
025940042 Impeller – 9.50" Diameter 1
025940032 Impeller – 9.25" Diameter 1
025940242 Impeller – 8.38" Diameter 1
31 001500261 O-Ring SC 1 32 062370005 Conn. Box Assy. – 230/460V 1
062370015 Conn. Box Assy. – 200/575V 1
33 089260025 Volute Base w/Wear Ring 1 34 008530001 Wire Conn. – 200V, 10/4 Cord 3
024940001 Wire Conn. – 200V, 8/4 Cord 3
024940001 Wire Conn. – 230V 4
008530001 Wire Conn. – 460V, 10/4 Cord 6
024940001 Wire Conn. – 460V, 8/4 Cord 3
008530001 Wire Conn. – 460V, 8/4 Cord 3
008530001 Wire Conn. – 575V, 10/4 Cord 3
024940001 Wire Conn. – 575V, 8/4 Cord 3
35 084720035 Sensor Assy. 1 36 026020003 Sleeve SC 1 37 001500071 O-Ring SC 1 38 001500251 O-Ring SC 1 39 002820011 Wire Connector 3
517000197 Seal Kit – 517003197 Carbide Seal Kit
Part
No.
Description Qty.
(Bottom Seal Only)
C 1
2
4
9
10
11
12
13
15
16
18
17
20
®
motor.
22
23
32
34
37
28
39
7
1
3
5
6
8
14
38
35
36
29
31
33
30
24
1921272625
Notes: S — Parts in Seal Kit C — Parts in Carbide Seal Kit RTF — Refer To Factory — Fill oil to above motor windings
15
Page 32
STANDARD LIMITED WARRANTY
Pentair Hydromatic® warrants its products against defects in material and workmanship for a period of 12 months from the date of shipment from Pentair Hydromatic or 18 months from the manufacturing date, whichever occurs first – provided that such products are used in compliance with the requirements of the Pentair Hydromatic catalog and technical manuals for use in pumping raw sewage, municipal wastewater or similar, abrasive-free, noncorrosive liquids.
During the warranty period and subject to the conditions set forth, Pentair Hydromatic, at its discretion, will repair or replace to the original user, the parts that prove defective in materials and workmanship. Pentair Hydromatic reserves the right to change or improve its products or any portions thereof without being obligated to provide such a change or improvement for prior sold and/or shipped units.
Start-up reports and electrical schematics may be required to support warranty claims. Submit at the time of start up through the Pentair Hydromatic website: http://forms.pentairliterature.com/startupform/startupform.asp?type=h. Warranty is effective only if Pentair Hydromatic authorized control panels are used. All seal fail and heat sensing devices must be hooked up, functional and monitored or this warranty will be void. Pentair Hydromatic will cover only the lower seal and labor thereof for all dual seal pumps. Under no circumstance will Pentair Hydromatic be responsible for the cost of field labor, travel expenses, rented equipment, removal/reinstallation costs or freight expenses to and from the factory or an authorized Pentair Hydromatic service facility.
This limited warranty will not apply: (a) to defects or malfunctions resulting from failure to properly install, operate or maintain the unit in accordance with the printed instructions provided; (b) to failures resulting from abuse, accident or negligence; (c) to normal maintenance services and parts used in connection with such service; (d) to units that are not installed in accordance with applicable local codes, ordinances and good trade practices; (e) if the unit is moved from its original installation location; (f) if unit is used for purposes other than for what it is designed and manufactured; (g) to any unit that has been repaired or altered by anyone other than Pentair Hydromatic or an authorized Pentair Hydromatic service provider; (h) to any unit that has been repaired using non factory specified/ OEM parts.
Warranty Exclusions: PENTAIR HYDROMATIC MAKES NO EXPRESS OR IMPLIED WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. PENTAIR HYDROMATIC SPECIFICALLY DISCLAIMS THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR ANY PARTICULAR PURPOSE.
Liability Limitation: IN NO EVENT SHALL PENTAIR HYDROMATIC BE LIABLE OR RESPONSIBLE FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES RESULTING FROM OR RELATED IN ANY MANNER TO ANY PENTAIR HYDROMATIC PRODUCT OR PARTS THEREOF. PERSONAL INJURY AND/OR PROPERTY DAMAGE MAY RESULT FROM IMPROPER INSTALLATION. PENTAIR HYDROMATIC DISCLAIMS ALL LIABILITY, INCLUDING LIABILITY UNDER THIS WARRANTY, FOR IMPROPER INSTALLATION. PENTAIR HYDROMATIC RECOMMENDS INSTALLATION BY PROFESSIONALS.
Some states do not permit some or all of the above warranty limitations or the exclusion or limitation of incidental or consequential damages and therefore such limitations may not apply to you. No warranties or representations at any time made by any representatives of Pentair Hydromatic shall vary or expand the provision hereof.
740 EAST 9TH STREET 490 PINEBUSH ROAD, UNIT #4 ASHLAND, OHIO, USA 44805 CAMBRIDGE, ONTARIO, CANADA N1T 0A5 419-289-1144 800-363-PUMP
WWW.HYDROMATIC.COM
Warranty Rev. 12/13
Loading...