Pentair Hydromatic S4B, Hydromatic S6AX, Hydromatic S4LRC, Hydromatic S4LVX, Hydromatic S6A Installation And Service Manual

...
MODELS S4L(X*), S4LRC/S4LVX*, S4B(X*), S4K(X*), H4Q(X*), S6L(X*), S6A(X*) and S8F(X*)
*
Used in Hazardous Locations Class I, Division 1
SUBMERSIBLE SOLIDS HANDLING PUMPS
INSTALLATION AND SERVICE MANUAL
For use with product built with USEM motor.
NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system.
Item # E-03-491 | Part # 5625-491-1 | © 2014 Pentair Ltd. | 08/25/14
(*Hazardous Location
Motor End)
General Information
This manual contains important information for the safe use of this product. Read this manual completely before using this product and refer to it often for con tin ued safe product use. DO NOT THROW AWAY OR LOSE THIS MAN U AL.
When un pack ing unit, check for con cealed damage. Claims for damage must be made at the receiving end through the delivery carrier. Dam age cannot be processed from the factory.
WARNING: Before handling these pumps and controls, always disconnect the power first. Do not smoke or use sparkable electrical devices or flames in a septic (gaseous) or possible septic sump.
CALIFORNIA PROPOSITION 65 WARNING:
This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
Pumps Not Operating or in Storage:
Pumps with carbon ceramic seals must have impellers manually rotated (6 revolutions) after setting non-operational for 3 months or longer and prior to electrical start-up.
Pumps with tungsten carbide seals must have impellers manually rotated (6 revolutions) after setting non-operational for 3 weeks or longer and prior to electrical start-up.
Seal Failure:
An electrode probe is installed in the seal chamber so if any water enters the chamber through the first seal, the electrode will be energized and a signal will be transmitted to
the sensing unit at ground surface causing a red light to flash. The electrode probe is installed in all units, but the sensing unit is supplied at extra cost and must be ordered.
In operation the seal failure unit in di cates only that there is some water in the seal chamber. The pump will con tin ue to operate without damage, but the seal should be checked immediately after failure is indicated.
CAUTION: Failure to correct leaking seal could result in water entering motor chamber causing shorting out of motor.
The sensing unit is recommended on all installations as good insurance against motor failure.
Seal Failure Probes:
All our hazardous location submersible pumps have two factory installed mois ture detectors (seal failure probes). They are in a normally open series cir cuit, in the seal chamber. Un der normal operating conditions, the circuit remains open. If the lower seal leaks and moisture enters this cham ber, the moisture would settle to the bottom of the chamber and will com plete the circuit between the mois ture detectors.
This circuit must be connected to a sensing unit and signaling device. This is supplied in a Hydromatic® built control panel.
NOTE: Failure to install such a device negates all war ran ties by Hydromatic.
Pump:
Power cable is supplied with sepa rate wire for ground. Be sure green wire is con nect ed to a good ground such as water pipe or ground stake.
Heat Sensors:
All motors have heat sensor units embedded in the motor winding to detect excessive heat. The
sensors automatically reset when motor cools to safe temperature.
The sensors are connected in series with the motor starter coil so that the starter is tripped if heat sensor opens. The motor starter is equipped with overload heaters so all normal overloads are protected by the starter.
IMPORTANT: If Hydromatic electrical starting equip ment is not supplied, the heat sensor circuit must be connected in series with the starter coil or warranty is void.
Once sensor re sets, the starter is to be automatically reset for FM for continued operation of the pump. This circuitry is supplied in a Hydromatic control panel.
Power Cords:
The power cord and heat sensor seal failure cord are potted into the con nec tion box cap. The cords must not be spliced.
NOTE: Each cable has a green lead. This is the ground wire and must be grounded properly per NEC and/or local codes. Cords should be in spected for abnormal wear and replaced ac cord ing ly.
Sump Level Control:
Sump level is controlled by Hydromatic float switch controls. The float is held in position in the sump by a weight attached to the power cord above the float. The cord supports the float and is adjusted for height from the surface.
Typical duplex systems use three con trols: one set at turn-off, one set at turn-on for one pump, and one set for turn-on for two pumps. Pumps alternate op er a tion on each successive cycle.
Two pumps operate together only if sump level rises to the third or override control. The override control also brings on the second pump in case of failure of the first
2
pump. Extra floats with ap pro pri-
33131
53131
56162
76162
WIRE SIZE AND MAXIMUM LENGTH (FEET) FOR REMOTE LOCATION OF CONTROL PANEL
BASED ON A 2% VOLTAGE DROP (230 VOLTS 3 PHASE)
Copper Wire Amperes @ 230 Volts*
No. D.C. Res.
AWG/M Ft. 51015202530405060708090 100 120 140 160 180 200
12 1.620 325 165 110 80 65 55 10 1.018 520 260 175 130 105 85 65
8 0.6404 830 415 275 205 165 140 105 80 6 0.410 1295 645 430 320 260 215 160 130 105 90 80 4 0.259 1025 680 510 410 340 255 205 170 145 130 115 100 85
M 3 0.205 1295 865 650 520 430 325 260 215 185 160 145 130 110 90
2 0.162 1090 820 655 545 410 340 295 255 230 205 180 160 135 110 100 1 0.129 1030 825 685 515 410 340 295 255 230 205 170 145 130 115 0 0.102 1040 865 650 520 435 370 325 290 260 215 185 160 145 130
00 0.0811 1090 820 655 545 470 410 365 325 270 235 205 180 165
000 0.0642 1035 825 690 590 515 460 415 345 295 260 230 205
NOTE: For 460 volts obtain distance by multiplying by 2.0 ‡60˚C
For 570 volts obtain distance by multiplying by 2.5 ‡Rating 90˚C
* 230 volt system not recommended for above 30 to 40 horsepower. Insulation @ 30˚C Amb. Based on 3 power conductors in cable or conduit; for 4 to 6 reduce ampacity to 80% & for 7 to 24 reduce to 70%.
M Special junction box required for wire sizes larger than #4.
ate controls can be supplied for alarm functions. Triplex systems use four controls: one set at turn-off, one set at turn-on for one pump, one set at turn-on for two pumps, and one set at turn-on for three pumps. Pumps alternate each successive cycle.
Three pumps operate together only if sump level rises to the fourth control (second override). This control also brings on the third pump in case of failure of either or both of the first two pumps.
Alarm Controls:
The alarm level is usually set above the override level so the alarm will signal only if the override level is exceeded. However, some engineers prefer to have the alarm level set below the override level as it is possible for one pump to fail and the other pump to operate on the override level with the sump level never reach ing the alarm level. This is par tic u lar ly true in cases of low inflow ca pac i ty.
Electrical Control Panel:
It is recommended that the Hydromatic® control panel be used with all pumps as proper starter heaters and connections for heat sensor wires are furnished.
The electrical equipment includes a main circuit breaker for each pump, a magnetic starter with overload protec tion for each pump, an H-O-A switch and run light for each pump, an elec tric alternator and a trans former to provide appropriate con trol circuit and alarms.
Overload Heaters:
If the Hydromatic electrical panel is not used, starters with 3 leg overload protection must be supplied. The heaters must be sized in ac cor dance with the nameplate amps on the motor housing. The amp draw on these submersible motors is slightly higher than a corresponding horsepower surface motor, so heaters must be sized by the nameplate rating.
IMPORTANT: Be sure the heat sensor wires are connected in series with the starter coil circuit.
Pump Installation
Installing Pump in Sump:
Before installing pump in sump, lay it on side and turn impeller manually. Impeller may be slightly stuck due to factory test water, so it must be broken loose with small bar or screwdriver in edge of vanes. The impeller should turn freely.
Clean all trash and sticks from sump and connect pump to piping.
A check valve must be installed on each pump. A gate or plug valve in each pump discharge line is also recommended. This valve should be installed on the discharge side of the check valve so if necessary to service the check valve, the line pressure can be cut off. Single pump systems are sometimes installed without a check valve where it is desirable to self-drain the discharge line to
prevent freezing. This can be done only with short discharge lines, otherwise water will return to the sump and cause short cycling of the pump.
Installing Sump Level Control Float Controls:
In either simplex, duplex or triplex systems the lower or turn-off control is to be set to maintain a minimum level in the sump. This level shall be no more than 3-1/4" from the top of the motor housing down to the surface of the sewage.
The second or turn-on control is set above the lower turn-off control. The exact distance between the two floats must be a compromise between a fre quent pumping cycle (10 starts per hour max.) to control septicity, solids and a slower cycle for energy econ o my. This distance should be de ter mined by the engineer or con sult ing engineer de pend ing on the con di tions of the application.
For installation of Hydromatic sup plied level con trols, refer to your sys tems installation and service manual.
NEMA 4 Junction Box (Optional):
If electrical control panel is to be set remote from the pump sump a NEMA 4 junction box should be used to make power and control connections. The Hydromatic NEMA 4 junction box is provided with compression con nec tors for sealing all wires. No sealing compound is needed to make con nec tions waterproof.
Wiring diagrams are provided with panel for making connections.
NUMBER OF CONDUCTORS REQUIRED BETWEEN CONTROL PANEL AND NEMA 4 JUNCTION BOX
System Number of Number of Number of
Type Control Wires Power Lines Ground Wires #8 Number of Number of
Simplex
Simplex with Alarm
Duplex
Duplex with Alarm
Power lines and control wires can be carried in conduit or can be underground buried cable.
HEAT SENSOR & SEAL FAILURE
Sensor Wires Ground Wires
3
The size wire to use from panel to
NON-HAZARDOUS LOCATION ONLY
HAZARDOUS LOCATION ONLY
sump depends on motor size and distance in feet.
Be sure each wire is checked out so that a wrong connection will not be made. An ohmmeter or Megger can be used to check wire continuity.
Installing Float Switch Controls:
The controls are supported by a mounting bracket that is attached to sump wall or cover or to the NEMA 4 junction box.
Cord snubbers are used to hold the cord in place. Control lever can be changed at any time by loosening the snubber and readjusting cord length.
In either simplex or duplex system the lower or turn-off control is set just above the top of volute so that the volute will always be submerged during the pumping cycle. The second or turn-on control is set about 24 inches above the lower turn-off control.
More distance between turn-on and turn-off controls can be used, but sewage may become septic and excessive solids may collect for the pump to handle. A frequent pumping cycle is recommended for best operation.
If an alarm system is used, this control is usually set about 6 inches above the override control.
Making Electrical Connections:
All electrical wiring must be in accordance with the local code, and only competent electricians should make the installations. Complete wiring diagrams are on the inside cover of the panel. All wires should be checked for ground with an ohmmeter or Megger after the connections are made. This is important, as
one grounded wire can cause considerable trouble.
IMPORTANT: If equipment is not properly wired and protected as recommended, the warranty is void.
Heat Sensors and Seal Failure Connections:
Be sure that heat sensor wires are connected in series with the starter coil. Connections are provided on the terminal strip.
DUAL VOLTAGE
3 PHASE MOTOR WIRING
230V 3N 460V 3N
WHITEBLACK
WHITEBLACK
45 6
78 9
12 3
W
BL
(L2)
(L1)
ELECTRODE
REDORANGE DARK
ELECTRODE
RED DARK
(L3)
R
GREEN
GREEN
45 6
78 9
12 3
W
BL
(L2)
(L1)
HEAT SENSORS AND SEAL FAILURE CONNECTIONS
HEAT SENSORS
HEAT SENSORS SEAL FAILURE
HEAT SENSORS AND SEAL FAILURE CONNECTIONS
HEAT SENSORS
HEAT SENSORS SEAL FAILURE
GREEN GREEN
R
(L3)
FOR ANY VOLTAGE MOTOR
IN MOTOR WINDINGS
FOR ANY VOLTAGE MOTOR
IN MOTOR WINDINGS
Pump Operations
Starting System:
1. Turn H-O-A switch to Off position, then turn on main circuit breakers.
2. Open all discharge valves and allow water to rise in sump pump.
3. Turn H-O-A switch to Hand position on one pump and notice operation. If pump is noisy and vibrates, rotation is wrong. To change rotation interchange any two line leads to motor on 3ø only. DO NOT INTERCHANGE MAIN INCOMING LINES. If duplex system, check second pump in the same manner.
4. Now set both H-O-A switches to Auto position and allow water to rise in sump until one
pump starts. Allow pump to operate until the level drops to turn-off point.
5. Allow sump level to rise to start other pump. Notice run lights on panel; pumps should alternate on each successive cycle of operation.
6. Turn both H-O-A switches to Off position and allow sump to fill to the override control level.
7. Turn both switches to Auto position and both pumps should start and operate together until level drops to turn-off point.
8. Repeat this operation cycle several times before leaving the job.
9. Check voltage when pumps are operating and check the amp draw of each pump. Check amps on each wire as sometimes a high leg will exist. One leg can be somewhat higher, 5 to 10%, without causing trouble. For excessive amp draw on one leg, the power company should be consulted.
Phase Converters:
Phase converters are generally not recommended, but in cases where only single phase current is available phase converter can be used. Be sure to size the phase converter large enough for the amp draw specified on the motor nameplate, not necessarily by motor horsepower. The warranty on all three phase submersible motors is void if operated with single phase power through a phase converter and 3 leg ambient compensated extra-quick trip overload protectors are not used.
4
Pump Maintenance
NOTE: Any unauthorized field repair voids the warranty, the hazardous location rating, and Factory Mutual approval.
If the heat sensor and seal failure are hooked up properly, no attention is necessary as long as the seal failure indicator light doesn’t come on. To ensure continuity of the seal sensor leads, a test light is provided on in trin si cal ly safe Hydromatic® panels as standard equipment.
Pump should be checked every quar ter for cor ro sion and wear.
Maintenance:
As the motors are oil filled, no lu bri ca tion or other maintenance is required.
If the pump is used on a rail system, it should be lifted once every six months and checked for corrosion and wear.
Generally these pumps give very reliable service and can be expected to operate for years on normal sewage pumping without failure.
Lightning:
In some areas where considerable lightning occurs, it is recommended that a lightning arrestor be installed at the control panel to aid against damage to the motor.
Field Service on Hydromatic Hazardous Location Pumps:
If a Hydromatic hazardous location pump is used in a hazardous location, or if the pump is still in war ran ty, the pump must be returned to the factory for service or repaired at an authorized Factory Mutual Hydromatic service center. Charges will not be allowed if in war ran ty pump is not taken to an authorized Factory Mutual Hydromatic service center. This will ensure the integrity of
the hazardous location rating of the pump and com ply with our warranty re quire ments.
Field Service on Motor:
All submersible motors out of warranty can be serviced in the field by any reliable motor service shop. Any pump, in warranty, must be returned to the factory for service or re paired at an authorized Hydromatic service center. Charg es will not be allowed if in warranty pump is not taken to an authorized Hydromatic service center.
When field service is performed on a pump, these instructions should be carefully followed.
COIL
WARNING
COIL
THERMOSTATS
IN SERIES
BLACK
BLACK
THERMOSTATS
IN SERIES
OL OLSTART
L2
WHITE
L2
WHITE
WARRANTY IS VOID IF HEAT SENSORS ARE NOT
CONNECTED AS SHOWN (IN SERIES WITH CONTACTOR OIL)
TWO WIRE CONTROL OFFERING AUTOMATIC RESET
L1
ON-OFF
SWITCH
THREE WIRE CONTROL OFFERING AUTOMATIC RESET
L1
IN CERTAIN APPLICATIONS THE NEC MAY REQUIRE THREE OVERLOAD RELAYS
Replacing Stator:
1. If stator only is damaged, it may not be necessary to completely dismantle pump as stator and housing can be lifted from pump without disturbing seals or bear ings.
2. Drain all oil from upper housing, remove drain plug in bottom of stator housing and remove plug in top of housing to allow air to enter.
3. After chamber is drained, remove hold-down bolts and lift off. Use care in lifting as the seal failure connecting wire must be dis con nect ed before housing is com pletely removed.
4. Set assembly on bench and re move connection box. When box is lifted off, connection wires to motor will be exposed. These wires will probably be burned, but each wire is tagged with a metal marker giving wire number. Cut the wires.
If the leads to the connection
box are burned, a complete new con nec tion box with new wire must be used. The wires are potted in with sealing compound and a new unit must be obtained from the factory.
5. The stator is held in the housing with a bolted-in end ring and an outside locking screw to prevent stator from turning.
6. After ring is removed, turn hous ing upright and bump on hard wood blocks. This should jar the stator loose and allow it to drop out.
7. Thoroughly clean housing before replacing new stator. Replace stator and make all wire con nec tions to connection box before replacing housing on pump. This is important as leads must be tucked behind the windings by using hands up through rotor core.
IMPORTANT: Use only com pres sion type insulated connectors on the wires.
DO NOT TAPE LEADS AS OIL WILL DETERIORATE THE TAPE AND CAUSE DAMAGE TO STATOR AND BEARINGS.
8. Drain oil from seal chamber. Check top bearing. If clean and does not turn rough, bearings can be reused and it is not necessary to completely dismantle pump to change bearings. If bearings are damaged with dirt or heat, they must be replaced. Remember to reinstall the upper bearing load spring.
9. Before replacing stator housing be sure outside lock screw is in place and that O-ring is used under head of bolt. A leak here can cause a motor failure.
5
10. Replace stator housing onto seal chamber and bolt in place. Be sure seal failure
wire is connected before hous ing is assembled.
Be sure back-off screws have
been loosened so that parts can come metal to metal. Be sure O-ring seal has been replaced. If O-ring is nicked or cut, replace with new rings. This applies to all O-rings used in assembly.
11. After all leads are reconnected in the connection box, make a high voltage ground test on each wire. The only wire that should show ground is the green power lead and the ground lead in the aux il ia ry control cable.
12. For safety, complete pump should be air checked under water for leaks. Lay pump on side for this oil filling with oil fill hole upright. Do not completely fill; leave oil about 1 inch below plug hole. Use only Hydromatic® submersible oil in this chamber. Replace plug; use Permatex on threads. Install air valve in top plug opening of motor housing and charge housing with about 10 psi of air. Be sure air is dry. Do not use air line where water may be trapped in the line. Submerge complete unit under water and check for leaks.
13. Refill motor chamber with Hydromatic submersible oil. Fill chamber until oil covers top of the windings. Leave air space in the top for expansion. Use Permatex on plug threads.
Replacing Seals and Bearings:
1. Drain all oil from motor chamber and seal chamber as described.
2. Remove the motor housing as de scribed.
3. Remove bolts that hold seal cham ber to pump housing. Use back-off screws to break loose. With hardwood block, tap end of impeller to loosen from shaft. When free, remove impeller from shaft.
4. Lift rotating assembly (rotor, shaft and impeller) from pump case and place horizontally on bench.
5. Remove screw and washer from end of shaft and then screw socket head bolt back into shaft. Using a screwdriver on opposite sides behind impeller apply force, then tap on end of socket bolt to break impeller loose from taper shaft.
6. Remove key and then slide seal off the shaft.
7. To remove seal plate, take out socket head flat screws and using screws in back off holes, pry plate loose. This will also force seal off if not already removed.
8. Remove snap ring that holds upper seal. Pull seal if it is free. If not free, it can be forced off when shaft is removed.
9. Set assembly in upright position and bump end of shaft on hardwood block. This will push the bearing from the housing and will force upper seal from shaft.
10. Use bearing puller to remove bearings. Replace with new bear ings. Press only on inner face of bearing when replacing. Pressing on outer face can damage the bearing.
IMPORTANT: Do not use
any of the old seal parts. Replace with all new seals.
11. Thoroughly clean all castings before replacing seals. One grain of dirt between the seal faces can cause failure.
12. Examine all O-rings for nicks before using.
13. Use Locktite® on socket head locking screw in end of shaft.
14. Before refilling chamber with oil, air test as described above and refill both chambers with oil.
15. Always check all leads with high voltage or with Megger for grounds before operating the pump.
Replacing Cords:
The power cord and heat sensor ­seal failure cord is potted into the con nec tion box cap, forming the cord and cap assembly.
If cords require replacement due to damage or cords being too short, cord and cap assembly must be replaced as a complete assembly avail able from factory.
Check pump for proper rotation before re turn ing to normal service.
Disconnecting Pump Cords:
If a Hydromatic hazardous location pump is to be removed from its loca tion, the pump cords may be disconnected at control panel (on sump mounted con trol panels) and cord as sem bly taken with pump.
CAUTION: If cord openings from sump to con trol panel are open, gas es from sump could enter panel and an explosive condition could ex ist.
Replacing Lower Seal, Impeller or Volute:
The wet end components may be repaired or replaced by an authorized Hydromatic service facility without compromising the hazardous location rating to the pump.
NOTE: Any time the seal is disturbed, it must be replaced.
6
Pump Troubleshooting
The following is a list of common problems and their probable causes.
Pump will not start.
1. No power to the motor. Check for blown fuse or open circuit breaker.
2. Selector switch may be in the Off position.
3. Control circuit transformer fuse may be blown.
4. Overload heater on starter may be tripped. Push to reset.
Pump will not start and overload heaters trip.
1. Turn off power and check motor leads with Megger or ohmmeter for possible ground.
2. Check resistance of motor windings. All 3 phases should show the same reading.
3. If no grounds exist and the motor windings check OK, remove pump from sump and check for clogged or blocked impeller.
Pump operates with selector switch in Hand position but will not operate in Auto position.
Pump does not deliver proper capacity.
1. Discharge gate valve may be partially closed or partially clogged.
2. Check valve may be partially clogged. Raise level up and down to clear.
3. Pump may be running in wrong direction. Low speed pumps can operate in reverse direction without much noise or vibration.
4. Discharge head may be too high. Check total head with gauge when pump is operating. Total head is discharge gauge pressure converted to feet plus vertical height from water level in sump to center line of pressure gauge in discharge line. Gauge should be installed on pump side of all valves. Multiply gauge pressure in pounds by 2.31 to get head in feet.
5. If pump has been in service for some time and capacity falls off, remove pump and check for wear or clogged impeller.
Motor stops and then restarts after short period but overload heaters in starter do not trip.
1. This indicates trouble in the float level control or the alternator relay.
2. Check control panel for trouble.
Pump runs but will not shut off.
1. Pump may be air locked. Turn pump off and let set for several minutes, then restart.
2. Lower float control may be hung-up in the closed position. Check in sump to be sure control is free.
3. Selector switch may be in the Hand position.
1. This indicates heat sensors in the motor are tripping due to excessive heat. Impeller may be partially clogged giving a sustained overload but not high enough to trip overload heater switch.
2. Motor may be operating out of liquid due to a failed level control.
3. Pump may be operating on a short cycle due to sump being too small or from water returning to sump due to a leaking check valve.
7
D3D4
D2 D1 D6 D5
D3D4
D5D2D1
Wet End Components
D4 D3
S4L(X)
D3
D1 D2
S4LRC
D3D4
D4 D3
S4LVX
D4
D1D2
D5D6D1D2
S4B(X)
D3D4
D5D2D1
D4 D3
S6L(X) S8F(X)
S4K(X)
D5D6D1D2
S6A(X)
H4Q(X)
D1 D2 D5
D5D1 D2D6
D3D4
8
Wet End Parts List For use with product built with USEM motor.
Item
Description S4B(X) S4L(X)
#
D1 SCREW – HHC 5/8-11 UNF x 1-1/4 D2 WASHER – IMPELLER D3 KEY – 1/3" SQUARE D4 VOLUTE D5 RING – WEAR D6 SCREW MACH.
IMPELLER
005700181 005700181 005700181 005700181 005700181 005700181 005700181 005700181 005700181 019450001 019450001 019450001 019450001 019450001 019450001 019450001 019450001 019450001 028550081 028550081 028550031 028550081 028550081 028550081 028550081 028550081 028550081 136910002 089190015 107830002 107830002 136930012 089180015 089260025 137190002 151520015 136900003 042890023 048200101
(3)
7.38"
7.88"
8.38"
8.63"
8.81" 9"
9.25"
9.5"
9.63"
9.81"
10"
10.18"
10.25"
10.31"
10.38"
10.5"
10.85" 11"
11.25"
11.38"
11.5"
11.63"
11.88"
12"
110430162 — — 110430152 — — 025940242 025940242 025940242 — — 025940292 110430132 025940292 137200242
025940232 137200362 — 136920132 025940022 136940132 025940022 025940022 137200132 151510062 136920122 025940032 110430122 136940122 025940032 025940032 137200122 151510122 136920112 025940042 136940112 025940042 025940042 137200112 151510052
025940302 136940232 025940302 025940302 137200282 — 136920382 025940192 025940192 — 136920092 025940062 110430042 136940092 137200092 151510042
025940212 025940212 151510102 136920082 025940072 025940072 025940072 137200082
110430112 137200342 — 136920152 025940162 136940182 025940162 025940162 137200212 — 136920072 025940082 136940072 025940082 025940082 137200072 151510032
025940492 025940492 025940492 — 136920052 025940102 136940052 025940102 137200052 151510022 136920042 025940422 110430082 136940042 025940112 025940112 137200042 151510092 136920182 025940202 136940292 025940202 025940202 137200322 151510162 136920032 025940122 110430012 136940032 025940122 025940122 137200032 151510012 136920202 025940182 136940332 025940122 025940122 137200172 151510182 136920232 025940002 025940002 025940002 137200302 — 136920012 025940352 110430002 136940012 025940352 025940352 137200012 151510002
S4LRC
3450 RPM
048200111
REFER
TO
FACTORY
S4LRC/
S4LVX
136950003 042890023 042890023 136900003 136900033
S6A(X) S6L(X) S8F(X) S4K(X) H4Q(X)
(4)
048200101
(3)
000110021
(2)
9
Standard Location S4L, S4LRC, S4B, S4K, H4Q, S6L, S6A and S8F Motor End Components
2
27
A1
4
5
24
26
1
30
31
3
6
A3
10
11
12
19
14
A2
7
8
9
22
21
25 20
28
23
15
18
10
16 13 29 17
Loading...
+ 22 hidden pages