Pentair Hydromatic Dry Pit Installation And Service Manual

MODEL DRY PIT
SOLIDS HANDLING DRY PIT PUMPS
INSTALLATION AND SERVICE MANUAL
NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system.
Item # E-03-458 | Part # 5625-458-1 | © 2013 Pentair Ltd. | 11/11/13
Shipping:
When unpacking unit, check for concealed damage. Claim for damage must be made at the receiving end through the delivering carrier. Damage cannot be processed from the factory.
CALIFORNIA PROPOSITION 65 WARNING:
This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
Pumps Not Operating or in Storage:
Pumps with carbon ceramic seals must have impellers manually rotated (6 revolutions) after setting nonoperational for 3 months or longer and prior to electrical start-up.
Pumps with carbide seals must have impellers manually rotated (6 revolutions) after setting nonoperational for 3 weeks or longer and prior to electrical start-up.
Seal Failure:
An electrode is installed in the seal chamber so if water enters the chamber through the first seal, the electrode will be energized and a signal will be transmitted to the sensing unit at ground surface, causing an alarm activation. The electrode probe is installed in all units, but the sensing unit is supplied at an extra cost and must be ordered.
In operation the seal failure unit indicates only that there is some water in the seal chamber. The pump will continue to operate, but the seal should be checked immediately after failure is indicated.
2
The sensing unit is recommended on all installations as good insurance against motor failure.
Pump:
The dry pit submersible pump is supplied for 1 or 3 phase and for 200, 230, 460 or 575 volts. Power cable is supplied with green wire to connect to a good ground such as water pipe or ground stake.
Heat Sensors:
All motors have heat sensor units embedded in the motor winding to detect excessive heat. The heat sensors are set to trip at 120ºC. The sensors automatically reset when the motor cools to safe temperature.
The sensors are connected in series with the motor starter coil so that the starter is tripped if heat sensor opens. The motor starter is equipped with overload heaters so all normal overloads are protected by the starter.
IMPORTANT: If Hydromatic electrical starting equipment is not supplied, the heat sensor circuit must be connected in series with the starter coil or warranty is void.
Wet Well Level Control:
Sump level is controlled by Hydromatic switch controls. The float is held in position in the sump by a weight attached to the power cord above the float. The cord supports the float and is adjusted for height from the surface.
Duplex systems use three controls: one set at turn-off, one set at turn­on for one pump, and one set at turn-on for both pumps. Pumps then alternate lead and lag on each successive cycle. Two pumps operate together only when the sump level rises to the third or override control. The override control also brings on the second pump in case of failure of the first pump. Extra floats with appropriate
®
controls can be supplied for alarm functions. Triplex systems use four controls: One set at turn-off, one set at turn-on for one pump, one set at turn-on for two pumps, and one set at turn-on for three pumps. The pumps alternate with each successive cycle.
Three pumps operate together only if the sump level rises to the fourth control (second override). This control also brings on the third pump in case of failure of either or both of the first two pumps.
Alarm Controls:
The alarm level is usually set above the override level so the alarm will signal only if the override level is exceeded. However, some engineers prefer to have the alarm level set below the override level as it is possible for one pump to fail and the other pump to operate on the override level with the sump level never reaching the alarm level. This is particularly true in cases of low inflow capacity.
Electrical Control Panel:
It is recommended that the Hydromatic control panel be used with all pumps as proper starter heaters and connections for heat sensor wires are furnished.
Hydromatic electrical equipment is installed in a weatherproof NEMA 3R enclosure. The electrical equipment includes a main circuit breaker for each pump, a magnetic starter with overload protection for each pump, an H-O-A switch and a run light for each pump, an electrical alternator and a transformer to provide appropriate control for control circuit and alarms.
Overload Heaters:
Starters with 3 leg overload protection must be supplied if the Hydromatic electrical panel is not used. The heaters must be sized in accordance with the nameplate
amps on the motor. The amp draw on these oil-filled motors is slightly higher than a corresponding horsepower surface motor, so heaters must be sized by the nameplate rating.
Installation Instructions
Installing Pump in Dry Pit:
Before installing pump in the dry pit, lay it on side and turn the impeller manually. The impeller may be slightly stuck due to factory water testing, so it must be broken loose with a small bar or screwdriver in the edge of the vanes. The impeller must turn freely.
Clean all trash and debris from pump installation area and connect pump to plumbing.
A check valve must be installed on each pump. A gate or plug valve in each pump discharge line is also recommended. This valve should be installed on the discharge side of the check valve so the line pressure can be cut off to service the check valve. Single pump systems are sometimes installed without a check valve where it is desirable to self drain the discharge line to prevent freezing. This can be done only with short discharge lines. Otherwise water will return to the sump and cause short cycling of the pump.
Mounting Pump Stand:
The pump will ship from the factory on a dry pit pump stand. The suction and discharge of the pump will be oriented at the factory per the prescribed customer order.
The dry pit pump must be anchored to the pump station floor. This must be done to alleviate stress on the suction and discharge piping while the pump is in service. When securing the pump stand to the contractor supplied anchor bolts, it
may be necessary to shim the stand to ensure the suction and discharge piping properly aligns.
Plumbing (General):
The site contractor must supply the use of necessary pipe hangers or other piping supports. Both the suction and discharge piping must be independently supported and properly aligned to ensure no strain is transmitted to the pump when connections are tightened. The use of expansion joints or vibration pads does not preclude the need to properly support the piping.
NOTE: Do not support the piping by the pump. Do not force piping when making connections.
Suction-Inlet Piping:
The correct sizing and installation of the suction plumbing is particularly important. The suction piping must be selected and installed in such a manner that it minimizes pressure losses and allows for sufficient flow during starting and operation. Most NPSH problems can be traced directly to improper design of suction piping systems.
It is recommended that the piping be as direct as possible and the length should be at least 10 times the diameter of the pipe. When a pipe diameter larger than the suction of the pump is used, an eccentric reducer should be used with the eccentric side down. This will allow for the elimination of a potential air pocket in the suction plumbing.
NOTE: A pipe diameter smaller than the suction of the pump must never be used.
It is also recommended that a valve be installed in the suction piping to isolate the pump during routine maintenance and shutdown. A globe valve should not be used when NPSH is critical.
It is recommended that a compound pressure gauge be installed in the suction piping to assist in troubleshooting potential performance problems.
Discharge-Outlet Piping:
The discharge piping for short runs can be of the same size as the discharge of the pump. It is recommended that longer runs be 1 to 2 sizes larger depending on the length. Any elevated points will retain air pockets, and it is recommended that air vents or bleed lines be installed at these points to evacuate the entrapped air. Installation of a valve near the discharge of the pump is recommended to isolate the pump during maintenance and shutdown.
It is recommended that a pressure gauge be installed near the discharge of the pump to assist in troubleshooting potential performance problems.
NEMA 4 Junction Box (Optional):
A NEMA 4 junction box should be used to make power and control connections if electrical control panel is to be set remote from the pump station. The Hydromatic NEMA 4 junction box is provided with compression connections for sealing all wires. No sealing compound is needed to make connections waterproof.
Wiring diagrams are provided with the panel for making connections. An extra set of diagrams is included so that one set can be used in the station when making connections. The size wire to use from panel to station depends on motor size and distance in feet.
Be sure each wire is checked out so that a wrong connection will not be made. An ohmmeter or Megger can be used to check the continuity.
®
3
Loading...
+ 5 hidden pages