WinterGard, WinterGard Plus, WinterGard Wet
Selection Guide (for PiPe freeze Protection APPlicAtionS)
Raychem WinterGard self-regulating heating cables provide
convenient, reliable freeze protection for a wide variety of professionally installed residential and commercial water-pipe and
roof-and-gutter de-icing applications in nonhazardous areas.
This data sheet is designed to assist in cable and accessory
selection and basic circuit design of pipe-freeze-prevention
applications.
Self-Regulating Heating Products Application and Design Guide
(H53585), the H900 Power Connection Kit, the H908 Plug-in
Power Connection Kit, and the H921 120-V ground-fault protected junction box.
For detailed information on roof and gutter de-icing applications, please refer to the WinterGard Wet Design, Installation
and Maintenance Guide (H56804).
Complete design guidelines, installation instructions, and safety
information are provided in the Commercial and Residential
Construction
Water-proof
outer jacket
(black)
H612, H622 only
Pipe Applications
16 AWG
bus wires
Conductive
core (black)
Inner jacket
(blue or red)
Tinned
copper braid
Water pipes in dry areas: H311/H611/H621
Water pipes in wet areas and refrigeration
H612/H622
condensate drains:
Product Specifications and Data
WinterGard Wet
H612050
H612100
H612250
H612500
H6121000
WinterGard
H311100
H311250
WinterGard Plus
H611050
H611100
H611250
WinterGard Plus
H621050
H621100
H621250
Service voltage 120 V 120 V 240 V 120 V 240 V
Power output at 40°F (W/ft) 3 6 6 6 6
Power output in refrigeration condensate
drains at 32°F (W/ft)
n/a n/a n/a 8 8
Weight per 100 ft (lb) 6 6 6 7 7
Nom. cable width (in) 0.380 0.380 0.380 0.415 0.415
Nom. cable thickness (in) 0.180 0.180 0.180 0.215 0.215
Bus wire gauge (AWG) 16 16 16 16 16
Braid wire gauge equivalent (AWG) 14 14 14 14 14
Insulating jacket type Modified polyolefin
Outer jacket type n/a n/a n/a Modified polyolefin
Maximum exposure temp. (°F) 150 150 150 150 150
Environment Use only in ordinary (nonhazardous) areas. Do not expose to any chemicals.
Agency approvals
*
1 = UL System Listed 718K Pipe Heating Cable; 2 = UL System Listed 877Z De-Icing and Snow Melting Equipment; 3 = CSA Certified LR21133
WARNING:
WinterGard systems must be installed correctly to
ensure proper operation and to prevent shock or
fire. Carefully read and follow the Commercial and
Residential Self-Regulating Heating Products
Application and Design Guide and the H900 series
connection kit installation instructions.
• Use only in ordinary (nonhazardous) areas. Do not
expose to any chemicals, oil or grease.
*
1, 3 1, 3 1, 3 1, 2, 3 1, 2, 3
• In wet areas, use only WinterGard Wet.
• To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or
improperly installed, and to comply with the
requirements of Pentair Thermal Management,
agency approvals, and national electrical codes,
ground-fault equipment protection must be used
on each heating cable branch circuit. Arcing may
not be stopped by conventional circuit protection.
• This selection guide does not take the place of the
installation instructions included in the
Commercial and Residential Self-Regulating
Heating Products Application and Design Guide and
in the H900 series accessory kits.
• System approvals and performance are based on
the use of only H900 series accessories with
WinterGard heating cables. These accessories
must be used. Do not substitute parts.
WinterGard Wet
H622050
H622100
H622250
H622500
H6221000

2
0 20
40
0
2
4
6
8
10
60 80 100
Pipe temperature (F)
Power output (W/ft)
H6XX
H3XX
WinterGard Selection Guide
Circuit Sizing Guide
WinterGard Power Temperature Curves
Maximum heater length (ft)
Circuit breaker
Heating cable type 0°F 32°F 40°F
WinterGard 120 V
H311 on pipe
rating (A)
15 150 250
20 200 250
per circuit at start-up temperature
30 250 250
WinterGard Plus 120 V
H611 on pipe
15 125 150
20 140 195
30 200 200
WinterGard Plus 240 V
H621 on pipe
15 200 255
20 250 340
30 375 400
WinterGard Wet 120 V
H612 on pipe
15 125 150
20 140 195
30 200 200
WinterGard Wet 120 V
H612 in refrigeration
condensate drains
WinterGard Wet 240 V
H622 on pipe
15 100 125
20 125 165
30 150 200
15 200 255
20 250 340
30 375 400
WinterGard Wet 240 V
H622 in refrigeration
condensate drains
Note: Maximum circuit lengths are based on start-up load. Steady-state amps per foot is dependent
upon heating cable temperature.
15 200 250
20 250 320
30 305 400
Catalog References
Catalog Numbers
H X X X XXX
Reel length (ft):
50
100
250
500
1000
Cable construction:
1 = Braided metal
shield only
2 = Waterproof polyolefin
outer jacket over
metal shield
Nominal voltage:
1 = 120 Vac
2 = 240 Vac
Nominal wattage
(watts/ft):
3
6
Cable type
Catalog
number
Cable
construction*
Watts/ft
(on 40°F
metal pipe)
Nominal
voltage
WinterGard H311 H311100 1 3 120
H311250 1 3 120
WinterGard Plus
H611
H611050 1 6 120
H611100 1 6 120
H611250 1 6 120
WinterGard Plus
H621
H621050 1 6 240
H621100 1 6 240
H621250 1 6 240
WinterGard Wet H612 H612050 2 6 120
H612100 2 6 120
H612250 2 6 120
H612500 2 6 120
H6121000 2 6 120
WinterGard Wet H622 H622050 2 6 240
H622100 2 6 240
H622250 2 6 240
H622500 2 6 240
H6221000 2 6 240
*
Construction: 1 = braided metal shield only; 2 = waterproof polyolefin outer jacket over braid.
**
TruckPak consists of 100-foot cable reel, 2 power connections, 1 splice/tee kit, 1 roll application tape, 10 "Electric
Traced" labels.
EN-RaychemWinterGardSelection-AR-H5523509/13
Package
type**
®
TruckPak
box
250-ft reel
50-ft box
TruckPak box
250-ft reel
50-ft box
TruckPak box
250-ft reel
50-ft box
TruckPak box
250-ft reel
500-ft reel
1000-ft reel
50-ft box
TruckPak box
250-ft reel
500-ft reel
1000-ft reel
2 / 4THERMAL MANAGEMENT SOLUTIONS