Pentair H3H, H4H, S4M, S4P, S4HRC Installation And Service Manual

...
Page 1
S4M Shown
H3H Shown
S4HRC Shown
MODELS H3H, H4H, S4M, S4P, S4HRC and S4MRC
SUBMERSIBLE SOLIDS HANDLING PUMPS
INSTALLATION AND SERVICE MANUAL
NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system.
Item # E-03-486 | Part # 5625-486-1 | © 2017 Pentair Ltd. | 09/29/17
Page 2
General Information
Attention:
This manual contains important information for the safe use of this product. Read this manual completely before using this product and refer to it often for con tin ued safe product use. DO NOT THROW AWAY OR LOSE THIS MAN U AL. Keep it in a safe place so that you may refer to it often. Reasonable care and safe meth ods should be practiced. Check local codes and requirements before installation.
Unpacking Pump:
Remove pump from carton. When un pack ing unit, check for concealed damage. Claims for damage must be made at the receiving end through the delivery carrier. Dam age cannot be processed from the factory.
WARNING: Before handling these pumps and controls, always disconnect the power first. Do not smoke or use sparkable electrical devices or flames in a septic (gaseous) or possible septic sump.
CALIFORNIA PROPOSITION 65 WARNING:
This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
Pumps Not Operating or in Storage:
Pumps with carbon ceramic seals must have impellers manually rotated (6 revolutions) after setting non-operational for 3 months or longer and prior to electrical start-up.
2
Pumps with tungsten carbide seals must have impellers manually rotated (6 revolutions) after setting non-operational for 3 weeks or longer and prior to electrical start-up.
Seal Failure:
An electrode is installed in the seal chamber so if any water enters the chamber through the first seal the electrode will be energized and a signal will be trans mit ted to the sen sing unit at ground surface causing a red light to turn on. The elec trode probe is installed in all units, but the sensing unit is supplied at extra cost and must be ordered.
In operation the seal failure unit in di cates only that there is some water in the seal chamber. The pump will con tin ue to operate, but the seal should be checked im medi ate ly after failure is indicated.
The sensing unit is recommended on all installations as good insurance against motor failure.
Pump:
The submersible pumps in this manual are supplied for 1 and 3 phase and for 200, 230, 460 or 575 volts. Power cable is supplied with the green wire for ground. Be sure green wire is connected to a good ground such as water pipe or ground stake.
Heat Sensors:
All motors have heat sensor units em bed ded in the motor winding to detect ex ces sive heat. The heat sen sors are set to trip at 130°C. The sensors au tomatically reset when motor cools to safe temperature.
The sensors are connected in series with the motor starter coil
so that the starter is tripped if heat sensor opens. The motor starter is equipped with overload heaters so all normal over loads are protected by the starter.
IMPORTANT: If Hydromatic® electrical starting equip ment is not supplied, the heat sensor circuit must be connected in series with the starter coil or warranty is void.
Sump Level Control:
Sump level is controlled by Hydromatic switch controls. The float is held in position in the sump by a weight attached to the power cord above the float. The cord supports the float and is adjusted for height from the surface.
Duplex systems use three controls: one set at turn-off, one set at turn-on for one pump, and one set for turn-on for two pumps. Pumps alternate op er a tion on each successive cycle.
Two pumps operate together only if sump level rises to the third or over ride control. The override control also brings on the second pump in case of failure of the first pump. Extra floats with ap propriate controls can be supplied for alarm functions. Triplex systems use four controls: one set at turn-off, one set at turn­on for one pump, one set at turn­on for two pumps, and one set at turn-on for three pumps. Pumps alternate each successive cycle.
Three pumps operate together only if sump level rises to the fourth control (second override). This control also brings on the third pump in case of failure of either or both of the first two pumps.
Page 3
Alarm Controls:
System
Si
WIRE SIZE TABLE
FOR REMOTE LOCAT ION OF CONTROL PANEL
LENGTHS ARE BASED ON A VOLTAGE DROP OF TWO PERCENT
Maximum length in feet from NEMA 4 Junction Box to control panel. All control wires can be = 14–16 or 18 gauge wire. If power lines are greater than 300 volts, and the control wires are used in the same conduit, then the insulation of the control wires must be for 600 volts.
1 Phase 3 Phase
HP HP
Wire Size Volts 1
1
2 2 3 5 Volts 112 2 3 5 712 10 15
200V - - - - 200 217 190 101 - - - -
230 105 95 - - 230 291 250 134 - - - -
12 460 1165 1019 540 412 333 233 -
575 1820 1450 820 624 515 364 - 200 121 111 103 - 200 340 297 158 119 - - - 230 163 148 139 - 230 456 390 210 161 - - -
10
460 1822 1594 846 645 522 364 -
575 2847 2270 1360 976 806 569 - 200 190 175 162 - 200 533 466 249 187 155 - - 230 257 232 219 - 230 715 613 330 252 204 - -
8 460 2860 2500 1328 1013 819 572 390
575 4468 3570 2145 1532 1266 894 - 200 296 272 252 - 200 830 726 387 291 242 170 - 230 400 362 340 181 230 1114 955 514 393
318 223 -
6 460 4455 3898 2068 1577 1275 891 607
575 - - 3341 2386 1972 1392 - 200 452 416 384 - 200 1268 1110 592 444 370 260 - 230 610 553 520 276 230 1701 1458 785 601 486 340 232
4 460 - - 3160 2410 1449 1361 928
575 - - - 3646 2513 2127 - 200 689 633 586 - 200 1932 1690 902 676 563 395 - 230 930 842 792 421 230 2592 2222 1196 915 741 578 353
*2* 460 - - - 3672 2969 2074 1414
575 - - - - 4590 3240 -
*Special junction box required for wire sizes larg er than #4.
The alarm level is usually set above the override level so the alarm will signal only if the override level is exceeded.
amp draw on these submersible motors is slightly higher than a corresponding horsepower surface motor, so heaters must be sized by the nameplate rating.
However, some engineers prefer to have the alarm level set below the override level as it is pos si ble for one pump to fail and the other pump to operate on the override level with the sump level never
IMPORTANT: Make certain the heat sensor wires are connected in series with the starter coil circuit if other than Hydromatic starters are used.
reach ing the alarm level. This is par tic u lar ly true in cases of low inflow capacity.
Installation Instructions
Electrical Control Panel:
It is recommended that the Hydromatic control panel be used with all pumps as proper starter heat ers and connections for heat sensor wires are fur nished.
Hydromatic® electrical equipment
NEMA 3R enclosure. The electrical equipment includes a main circuit breaker for each pump, a magnetic starter with overload protection for each pump, an H-O-A switch and run light for each pump, and an electric alternator and a transformer to provide appropri ate control for control circuit and alarms.
Overload Heater:
Starters with 3 leg overload protection must be supplied if the Hydromatic electrical panel is not used. The heaters must be sized in accordance with the nameplate amps on the motor. The
NUMBER OF CONDUCTORS REQUIRED BETWEEN CONTROL PANEL AND NEMA 4 JUNCTION BOX
POWER LINES AND CONTROL WIRES CAN BE CARRIED IN CONDUIT OR CAN BE UNDERGROUND BURIED CABLE
Type Control Wires Power Lines Ground Wires #8 Number of Number of
Simplex with Alarm 6 3 1 3 1
Duplex 6 6 2 6 2
Duplex with Alarm 8 6 2 6 2
Number of Number of Number of
mplex 4 3 1 3 1
is installed in a weatherproof
Installing Pump in Sump:
Before installing pump in sump, lay it on side and turn impeller manually. Im pel ler may be slightly stuck due to factory test water, so it must be bro ken loose with small bar or screwdriver in edge of vanes. The impeller should turn freely.
Clean all trash and sticks from sump and connect pump to piping.
A check valve must be installed on each pump. A gate or plug valve in each pump discharge line is also recommended. This valve should be installed on the discharge side of the check valve so the line pressure can be cut off if necessary to service the check valve. Single pump systems are sometimes installed without a check valve where it is desirable to self-drain the dis charge line to prevent freezing. This can be done
Sensor Wires Ground Wires
only with short discharge lines. Otherwise water will return to the sump and cause short cycling of the pump.
NEMA 4 Junction Box (Optional):
A NEMA 4 junction box should be used to make power and control con nec tions if electrical control panel is to be set remote from the pump sump. The Hydromatic NEMA 4 junction box is provided with com pres sion con nec tors for sealing all wires. No sealing compound is need ed to make connec tions wa ter proof.
Wiring diagrams are provided with the panel for making connections. The size wire to use from the panel to sump de pends on motor size and distance in feet.
Be sure each wire is checked out so that a wrong connection will not be made. An ohm me ter or Megger can be used to check wire continuity.
Installing Switch Controls:
The controls are supported by a mount ing bracket that is attached to sump wall, cover, or to the NEMA 4 junction box.
Cord snubbers are used to hold the cord in place. Control level can be changed at any time by loosening the snubber and readjusting cord length.
HEAT SENSOR & SEAL FAILURE
3
Page 4
In either a simplex or duplex system, the lower or turn-off control is set just above the top of volute, so that the volute will always be submerged during the pumping cycle. The sec ond, or turn-on control, is set about 24 inches above the lower turn-off con trol.
More distance between turn-on and turn-off controls can be used, but sew age may become septic, and excessive solids may collect for the pump to handle. A frequent pumping cycle is recommended for best op er a tion.
If an alarm system is used, this con trol is usually set about 6 inches above the override control.
Making Electrical Connections:
All electrical wiring must be in ac cor dance with local codes, and only competent electricians should make the installations. Complete wiring diagrams are glued to the inside cover of the panel. All wires should be checked for grounds with an ohm me ter or Megger after the connections are made. THIS IS IMPORTANT, AS ONE GROUNDED WIRE CAN CAUSE CON SID ER ABLE TROU BLE.
IMPORTANT: If equipment is not properly wired and protect ed as recommended, the warranty is void.
Heat Sensors and Seal Failure Connections:
Be sure heat sensor wires are connect ed in series with the starter coil. Connections are provided on the terminal strip.
Pump Operations
Starting System:
1. Turn H-O-A switch to Off position and then turn on main circuit breakers.
2. Open all discharge valves and allow water to rise in sump.
3. Turn H-O-A switch to Hand position on one pump and notice operation. If pump is noisy and vibrates, rotation is wrong. To change rotation, interchange any two line leads to motor 3ø only. Do not interchange main incoming lines. If duplex system, check second pump in the same manner.
4. Now set both H-O-A switches to Auto position and allow water to rise in sump until one pump starts. Allow pump to op er ate until the level drops to turn-off point.
5. Allow sump level to rise to start other pump. Notice run lights on panel. Pumps should alternate on each successive cycle of op er a tion.
6. Turn both H-O-A switches to Off position and allow sump to fill to the override control level.
7. Turn both switches to Auto po si tion and both pumps should start and operate together until level drops to turn-off point.
8. Repeat this operation cycle sev er al times before leaving the job.
9. Check voltage when pumps are operating and check the amp draw of each pump. Check amps on each wire, as sometimes a high leg will exist. One leg can be somewhat higher (5 to 10%) without causing trouble. For excessive amp draw on one leg, the power company should be con sult ed.
Phase Converters:
Phase converters are generally not recommended, but in cases where only single phase current is available, phase converters can be used. Be sure to size the phase converter large enough for the amp draw specified on the motor nameplate, not necessarily by motor horsepower. The warranty on all three phase submersible motors is void if operated with single phase power through a phase converter, and 3 leg ambient compensated extra-quick trip overload protectors are not used.
DUAL VOLTAGE
3 PHASE MOTOR WIRING
230V 3ø 460V 3ø
45 6
78 9
12 3
BL
(L1)
4
W
(L2)
GREEN GREEN
R
(L3)
45 6
78 9
12 3
BL
(L1)
W
(L2)
R
(L3)
HEAT SENSORS AND SEAL FAILURE CONNECTIONS
FOR ANY VOLTAGE MOTOR
ELECTRODE
HEAT SENSORS
IN MOTOR WINDINGS
WHITEBLACK
HEAT SENSORS SEAL FAILURE
RED DARK
GREEN
Page 5
When field service is performed
Pump Maintenance
on a pump, these instructions should be carefully followed.
Replacing Stator:
Lubrication or other maintenance is not required, as the motors are oil filled.
1. If stator only is damaged, it may not be necessary to completely dismantle pump
Generally, these pumps give very reliable service, and can be expected to operate for many years without failure under normal operating con di tions.
as stator and housing can be lifted from pump without disturbing seals or bear ings.
2. To drain all oil from upper hous ing, remove drain plug in bot tom of stator housing and
Lightning:
In some areas where considerable lightning occurs, it is recommended that a lightning arrestor be installed at the control panel. Lightning arrestors are good insurance against damage to an expensive motor.
remove plug in top of housing to allow air to enter.
3. After chamber is drained, remove hold-down bolts and lift off. Use care in lifting as the seal failure con necting wire must be dis con nected before housing is com pletely removed.
Field Service on Motor:
All submersible motors out of warranty can be serviced in the field by any reliable motor service shop. Any pump in warranty must be returned to the factory for service or re paired at an authorized Hydromatic® service center. Charges will not be allowed if in warranty pump is not taken to an authorized Hydromatic service center.
4. Set assembly on bench and remove connection box. When box is lifted off, connection wires to motor will be exposed. These wires will probably be burned, but each wire is tagged with a metal marker giving wire number. Cut the wires.
If the leads to the connection
box are burned, a complete new con nec tion box with new
WARNING
WARRANTY IS VOID IF HEAT SENSORS ARE NOT
CONNECTED AS SHOWN (IN SERIES WITH CONTACTOR OIL)
TWO WIRE CONTROL OFFERING AUTOMATIC RESET
L1
ON-OFF SWITCH
THREE WIRE CONTROL OFFERING AUTOMATIC RESET
L1
IN CERTAIN APPLICATIONS THE NEC MAY REQUIRE THREE OVERLOAD RELAYS
COIL
COIL
BLACK
OL OLSTART
BLACK
THERMOSTATS
IN SERIES
WHITE
THERMOSTATS
IN SERIES
WHITE
L2
L2
wire must be used. The wires are potted in with sealing compound and a new unit must be obtained from the factory.
5. The stator is held in the housing with a bolted-in clamp ring.
6. After ring is removed, turn hous ing upright and bump on hard wood blocks. This should jar the stator loose and allow it to drop out.
7. Thoroughly clean housing before replacing new stator. Replace stator and make all wire con nec tions to connection box before replacing housing on pump. This is important as leads must be tucked behind the windings by using hands up through rotor core.
IMPORTANT: Use only
compression type insulated connectors on the wires.
Do not tape leads as oil will
de te ri o rate the tape and cause damage to stator and bear ings.
8. Check top bearing. If clean and does not turn rough, bearings can be reused and it is not necessary to completely dismantle pump to change bearings. If bearings are damaged with dirt or heat, they must be replaced. Remember to reinstall the upper bearing load spring.
9. Replace stator housing onto seal chamber and bolt in place. BE SURE SEAL FAILURE WIRE IS CONNECTED BEFORE HOUS ING IS ASSEMBLED.
Be sure O-ring seal has been
replaced. If O-ring is nicked or cut, replace with new one. This ap plies to all O-rings used in as sem bly.
5
Page 6
10. After all leads are reconnected in the connection box, make a high voltage ground test on each wire. The only wire that should show ground is the green power lead and the ground lead in the aux il ia ry control cable.
11. For safety, complete pump should be air checked under water for leaks. Lay pump on side for this oil filling with oil fill hole upright. Do not completely fill; leave oil about 1 inch below the plug hole. Use only Hydromatic® submers ible oil in this chamber or high grade trans form er oil. Re place the plug; use Permatex on threads. Install air valve in top plug open ing of motor housing and charge housing with about 10 psi of air. Be sure air is dry. Do not use air line where water may be trapped in the line. Submerge complete unit under water and check for leaks.
12. Refill motor chamber with oil. Use high grade transformer oil or Hydromatic special submers ible oil. Fill chamber until oil covers top of the windings. Leave air space in top for expansion. Use Permatex on plug threads.
Replacing Seals and Bearings:
1. Drain all oil from motor chamber and seal chamber as described.
2. Remove motor housing as described.
3. Remove bolts that hold seal cham ber to pump housing. Use back-off screws to break loose. With hardwood block, tap end of impeller to loosen from shaft. When free, remove impeller from shaft.
4. Lift rotating assembly
(rotor, shaft and impeller) from pump case and place horizontally on bench.
5. Impeller Removal
Hold rotor and remove bolt
and washer from impeller end of shaft, then thread bolt back into shaft. The impeller is keyed to the shaft, so by using a screwdriver on opposite sides behind the impeller, apply force, then tap on the end of the bolt to break impeller loose from taper shaft. Remove impeller.
IMPORTANT: The impeller
is designed to be self­tightening when running, so impeller may be difficult to break loose. If this is the case, use plastic or rubber hammer on im pel ler tip to free. Remove impeller.
6. Remove lower seal spring and pry out seal with screwdriver.
7. To remove seal housing, take out socket head bolts and using bolts in back of holes, pry plates loose. This will force out lower seal if not already removed.
8. Remove snap ring that holds upper seal. Pull seal if it is free. If not free, it can be forced off when shaft is removed.
9. Remove 4 bolts that hold bearing housing in place. Set assembly in upright position and bump end of shaft on hardwood block. This will push the bearing from the housing and will force upper seal from shaft.
10. Use bearing puller to remove bearings. Replace with new bear ings. Press only on inner face of bearing when replacing. Pressing on outer face can damage the bearing.
IMPORTANT: DO NOT
USE ANY OF THE OLD SEAL PARTS. REPLACE WITH ALL NEW SEALS.
11. Thoroughly clean all castings before replacing seals. One grain of dirt between the seal faces can cause failure.
12. Examine all O-rings for nicks before using.
13. Use Locktite® on socket head locking screw in end of shaft.
Pump Troubleshooting
Below is a list of common problems and the probable causes:
Pump will not start.
1. No power to the motor. Check for blown fuse or open circuit break er.
2. Selector switch may be in the Off position.
3. Control circuit transformer fuse may be blown.
4. Overload heater on starter may be tripped. Push to reset.
Pump will not start and overload heaters trip.
1. Turn off power and check motor leads with Megger or ohmmeter for possible ground.
2. Check resistance of motor wind ings. All 3 phases should show the same reading.
3. If no grounds exist and the motor windings check OK, remove pump from sump and check for clogged or blocked impeller.
Pump operates with selector switch in Hand position but will not operate in Auto position.
1. This indicates trouble in the float level control or the alternator relay.
6
Page 7
2. Check control panel for trouble.
Pump runs but will not shut off.
1. Pump may be air locked. Turn pump off and let set for several minutes, then restart.
2. Lower float control may be hung-up in the closed position. Check in sump to be sure control is free.
3. Selector switch may be in the Hand position.
Pump does not deliver proper capacity.
1. Discharge gate valve may be partially closed or partially clogged.
2. Check valve may be partially clogged. Raise level up and down to clear.
1. This indicates heat sensors in the motor are tripping due to ex ces sive heat. Impeller may be par tial ly clogged giving a sustained overload but not high enough to trip overload heat er switch.
2. Motor may be operating out of liquid due to a failed level control.
3. Pump may be operating on a short cycle due to sump being too small or from water re turn ing to sump due to a leaking check valve.
3. Pump may be running in wrong direction. Low speed pumps can operate in reverse di rec tion with out much noise or vibration.
4. Discharge head may be too high. Check total head with gauge when pump is operating. Total head is dis charge gauge pressure converted to feet plus vertical height from water level in sump to center line of pressure gauge in discharge line. Gauge should be installed on pump side of all valves. Multiply gauge pressure in pounds by 2.31 to get head in feet.
5. If pump has been in service for some time and capacity falls off, remove pump and check for wear or clogged impeller.
Motor stops and then restarts after short period but overload heaters in starter do not trip.
7
Page 8
Common Parts List
Ref. No.
Part
No.
1 19101A010 SCREW – HHC, 3/8-16UNC x 1 8
016640081
2
3 152770305 35' CORD ASSEMBLY 10-4 1
152770315 35' CORD ASSEMBLY 8-4 SOOW 1
152770325 35' CORD ASSEMBLY 8-4 W 1
152770335 35' CORD ASSEMBLY 6-4 1
000650031
4
001780041
5
6
009750171 RING – RETAINING 1
070720002
7
009750031
8
001500291
9
001500241
10
11 142990021 KEY – 1/8 SQ. VARIES
070700002
12
Part Description
PLUG – PIPE, 3/8 1
UPPER BEARING – BALL 1
SCREW-HHC 4
HOUSING – SEAL 1
RING – RETAIN. (EXT) 1
O-RING, 1/8 x 3.359 ID #2-237 1
O-RING, 1/8 x 8.984 ID #2-270 2
HOUSING – BEARING 1
Qty.
Ref.
No.
Part
No.
084720085
13
070690002
14
000640041
15
16 12672A001 CONNECTOR – SPLICE 3
001500071
17
000730011
18
001500121
19
20 19101A021 SCREW – HHC, 3/8-16UNC x 1-1/2 2
060000211
21
070740003
22
009200011
23
081000005
24
25
002390251
19103A062
Part Description
SEAL FAILURE ASS’Y 1
HOUSING – MOTOR 1
SPRING – BEARING ADJ. 1
O-RING, 1/8 x 2.234 ID #2-228 1
CONNECTOR – WIRE 3
O-RING, 1/8 x 3.734 ID #2-240 1
WIRE W/TERMINAL 1
RING – RETAINING 1
SEAL – UPPER, CARBON CERAMIC 1
SEAL – LOWER, CARBON CERAMIC 1
SCREW – HHC, 1/2-13UNC x 3-1/2 S4P, H3H and H4H
SCREW – HHC, 1/2-13 UNC x 3-1/4 S4M, S4MRC and S4HRC
Qty.
Ref.
No.
26
27
28 007360061 SPACER VARIES
29 010060011 CONNECTOR (STATOR W/CONN. BOX) VARIES
30 008530001 CONNECTOR VARIES
31 024940001 CONNECTOR – WIRE VARIES
4
4
Motor Parts List
S4M and S4MRC – 4-Pole 1750 RPM
Item Description
A1 Connection Box 071380015 071380015 071380005 071380005 071380015 071380015 A2 Rotor/Shaft Ass’y 141420115 141390115 141390115 141390115 141390115 141440115 A3 Stator 141420011 141402031 141400031 141400031 141406031 141440011
5 HP
230/1/1750
5–7.5 HP
200/3/1750
5–7.5 HP
230/3/1750
5–7.5 HP
460/3/1750
5–7.5 HP
575/3/1750
230/1/1750
7.5 HP
Part
No.
083460033
083460011
000650311
08565A027
151760007
Part Description
KEY, 3/8 S4P, H3H and H4H 1
KEY, 3/8 S4M, S4MRC and S4HRC 1
BEARING – BALL S4P, H3H and H4H
BEARING – BALL S4M, S4MRC and S4HRC
LIFTING BAIL 1
Qty.
1
1
Item Description
A1 Connection Box 071380015 071380005 071380005 071380015 071380015 071380005 071380005 071380015 A2 Rotor/Shaft Ass’y 141410115 141410115 141410115 141410115 141410115 141410115 141410115 141410115 A3 Stator 141412031 141410031 141410031 141416031 141432031 141430031 141430031 141436031
10 HP
200/3/1750
10 HP
230/3/1750
10 HP
460/3/1750
10 HP
575/3/1750
15 HP
200/3/1750
15 HP
230/3/1750
15 HP
460/3/1750
575/3/1750
S4M and S4MRC – 6-Pole 1150 RPM
Item Description
A1 Connection Box 071380015 071380005 071380005 071380015 A2 Rotor/Shaft Ass’y 141390115 141390115 141390115 141390115 A3 Stator 142972031 142970031 142970031 142976031
3 & 5 HP
200/3/1150
3 & 5 HP
230/3/1150
3 & 5 HP
460/3/1150
3 & 5 HP
575/3/1150
S4P, H3H and H4H – 1750 RPM
Item Description
A1 Connection Box 071380015 071380015 071380015 071380005 071380005 071380015 071380015 071380015 A2 Rotor/Shaft Ass’y 141420145 141420145 141390155 141390155 141390155 141390155 141440155 141410155 A3 Stator 141422011 141420011 141402031 141400031 141400031 141406031 141440011 141412031
Item Description
A1 Connection Box 071380005 071380005 071380015 071380015 071380005 071380005 071380015 A2 Rotor/Shaft Ass’y 141410155 141410155 141410155 141410155 141410155 141410155 141410155 A3 Stator 141410031 141410031 141416031 141432031 141430031 141430031 141436031
5 HP
200/1/1750
10 HP
230/3/1750
5 HP
230/1/1750
10 HP
460/3/1750
5 & 7.5 HP
200/3/1750
10 HP
575/3/1750
5 & 7.5 HP
230/3/1750
15 HP
200/3/1750
5 & 7.5 HP
460/3/1750
15 HP
230/3/1750
5 & 7.5 HP
575/3/1750
15 HP
460/3/1750
7.5 HP
230/1/1750
15 HP
575/3/1750
200/3/1750
S4HRC – 3450 RPM
Item Description
A1 Connection Box 071380015 071380005 071380005 071380015 071380015 071380005 071380005 071380015 A2 Rotor/Shaft Ass’y 141450115 141450115 141450115 141450115 141450115 141450115 141450115 141450115 A3 Stator 141452031 141450031 141450031 141456031 141462031 141460031 141460031 141466031
10 HP
200/3/3450
10 HP
230/3/3450
10 HP
460/3/3450
10 HP
575/3/3450
15 HP
200/3/3450
15 HP
230/3/3450
15 HP
460/3/3450
575/3/3450
15 HP
10 HP
15 HP
8
Page 9
30
3
A1 1
28
2
6
4
A2
A3
22
19
31
18
17
29
16
15
14
11
21
27
5
25
24 7 8
23
20
13
12
9A2
10
9
Page 10
Wet Ends Parts List
B4
B3 B2
S4HRC H4H
B4
B3 B2
S4MRC
B4
B3 B2
S4M
B4
B5
B1
S4P
B3
B2
B4
B5
B4
B5 B1
B1
B3 B2
B3 B2
H3H
Item Description S4M S4P S4HRC S4MRC H4H H3H
B1 O-RING, 1/8 x 9.984 ID #2-274 – B2 SCREW – CAP B3 WASHER – IMPELLER SST B4 VOLUTE B5 SPACER
– IMPELLER
005680021 005680021 029210041 005680021 005680021 005680021 080230001 080230001 080230011 080230001 080230001 080230001 070680015 137210015 082120002 070800002 151470015 151470002
070710152 (6.88) 137220192 (7.13) 070710232 (7.38) 137220252 (8.38) 070710122 (7.88) 137220062 (8.50) 070710102 (8.88) 137220052 (9.00)
001500471
137720003
137220012 (10.00)
– 082130082 (4.69) 070810082 (6.75) 082130042 (5.00) 070810022 (8.00) 082130052 (5.69) 070810012 (8.50)
070810092 (8.75) 070810002 (9.00)
001500471 001500471
137720003 137720003 151460202 (8.13) 151460062 (8.50) 151460052 (8.75) 151460012 (9.75)
– –
151460032 (9.25)
151460002 (10.00)
10
Page 11
THIS PAGE INTENTIONALLY LEFT BLANK
Page 12
STANDARD LIMITED WARRANTY
Pentair Hydromatic® warrants its products against defects in material and workmanship for a period of 12 months from the date of shipment from Pentair Hydromatic or 18 months from the manufacturing date, whichever occurs first – provided that such products are used in compliance with the requirements of the Pentair Hydromatic catalog and technical manuals for use in pumping raw sewage, municipal wastewater or similar, abrasive-free, noncorrosive liquids.
During the warranty period and subject to the conditions set forth, Pentair Hydromatic, at its discretion, will repair or replace to the original user, the parts that prove defective in materials and workmanship. Pentair Hydromatic reserves the right to change or improve its products or any portions thereof without being obligated to provide such a change or improvement for prior sold and/or shipped units.
Start-up reports and electrical schematics may be required to support warranty claims. Submit at the time of start up through the Pentair Hydromatic website: http://forms.pentairliterature.com/startupform/startupform.asp?type=h. Warranty is effective only if Pentair Hydromatic authorized control panels are used. All seal fail and heat sensing devices must be hooked up, functional and monitored or this warranty will be void. Pentair Hydromatic will cover only the lower seal and labor thereof for all dual seal pumps. Under no circumstance will Pentair Hydromatic be responsible for the cost of field labor, travel expenses, rented equipment, removal/reinstallation costs or freight expenses to and from the factory or an authorized Pentair Hydromatic service facility.
This limited warranty will not apply: (a) to defects or malfunctions resulting from failure to properly install, operate or maintain the unit in accordance with the printed instructions provided; (b) to failures resulting from abuse, accident or negligence; (c) to normal maintenance services and parts used in connection with such service; (d) to units that are not installed in accordance with applicable local codes, ordinances and good trade practices; (e) if the unit is moved from its original installation location; (f) if unit is used for purposes other than for what it is designed and manufactured; (g) to any unit that has been repaired or altered by anyone other than Pentair Hydromatic or an authorized Pentair Hydromatic service provider; (h) to any unit that has been repaired using non factory specified/ OEM parts.
Warranty Exclusions: PENTAIR HYDROMATIC MAKES NO EXPRESS OR IMPLIED WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. PENTAIR HYDROMATIC SPECIFICALLY DISCLAIMS THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR ANY PARTICULAR PURPOSE.
Liability Limitation: IN NO EVENT SHALL PENTAIR HYDROMATIC BE LIABLE OR RESPONSIBLE FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES RESULTING FROM OR RELATED IN ANY MANNER TO ANY PENTAIR HYDROMATIC PRODUCT OR PARTS THEREOF. PERSONAL INJURY AND/OR PROPERTY DAMAGE MAY RESULT FROM IMPROPER INSTALLATION. PENTAIR HYDROMATIC DISCLAIMS ALL LIABILITY, INCLUDING LIABILITY UNDER THIS WARRANTY, FOR IMPROPER INSTALLATION. PENTAIR HYDROMATIC RECOMMENDS INSTALLATION BY PROFESSIONALS.
Some states do not permit some or all of the above warranty limitations or the exclusion or limitation of incidental or consequential damages and therefore such limitations may not apply to you. No warranties or representations at any time made by any representatives of Pentair Hydromatic shall vary or expand the provision hereof.
1101 MYERS PARKWAY 490 PINEBUSH ROAD, UNIT 4 ASHLAND, OHIO 44805 CAMBRIDGE, ONTARIO, CANADA N1T 0A5 PH: 855-274-8947 PH: 800-363-7867
WWW.HYDROMATIC.COM
Warranty Rev. 12/13
Loading...