Raychem WinterGard self-regulating heating cables provide convenient, reliable freeze protection for a wide variety of pro­fessionally installed residential and commercial water-pipe and roof-and-gutter de-icing applications in nonhazardous areas. This data sheet is designed to assist in cable and accessory selection and basic circuit design of pipe-freeze-prevention applications.
Self-Regulating Heating Products Application and Design Guide (H53585), the H900 Power Connection Kit, the H908 Plug-in Power Connection Kit, and the H921 120-V ground-fault protect­ed junction box.
For detailed information on roof and gutter de-icing applica­tions, please refer to the WinterGard Wet Design, Installation
and Maintenance Guide (H56804). Complete design guidelines, installation instructions, and safety information are provided in the Commercial and Residential
Construction
Water-proof outer jacket (black)
H612, H622 only
Pipe Applications
16 AWG bus wires
Conductive core (black)
Inner jacket (blue or red)
Tinned copper braid
Water pipes in dry areas: H311/H611/H621
Water pipes in wet areas and refrigeration
H612/H622
condensate drains:
Product Specifications and Data
WinterGard Wet H612050 H612100 H612250 H612500 H6121000
WinterGard H311100 H311250
WinterGard Plus H611050 H611100 H611250
WinterGard Plus H621050 H621100 H621250
Service voltage 120 V 120 V 240 V 120 V 240 V Power output at 40°F (W/ft) 3 6 6 6 6 Power output in refrigeration condensate
drains at 32°F (W/ft)
n/a n/a n/a 8 8
Weight per 100 ft (lb) 6 6 6 7 7 Nom. cable width (in) 0.380 0.380 0.380 0.415 0.415 Nom. cable thickness (in) 0.180 0.180 0.180 0.215 0.215 Bus wire gauge (AWG) 16 16 16 16 16
Braid wire gauge equivalent (AWG) 14 14 14 14 14
Insulating jacket type Modified polyolefin Outer jacket type n/a n/a n/a Modified polyolefin Maximum exposure temp. (°F) 150 150 150 150 150 Environment Use only in ordinary (nonhazardous) areas. Do not expose to any chemicals. Agency approvals
*
1 = UL System Listed 718K Pipe Heating Cable; 2 = UL System Listed 877Z De-Icing and Snow Melting Equipment; 3 = CSA Certified LR21133
WARNING:
WinterGard systems must be installed correctly to ensure proper operation and to prevent shock or fire. Carefully read and follow the Commercial and Residential Self-Regulating Heating Products Application and Design Guide and the H900 series connection kit installation instructions.
• Use only in ordinary (nonhazardous) areas. Do not
expose to any chemicals, oil or grease.
*
1, 3 1, 3 1, 3 1, 2, 3 1, 2, 3
• In wet areas, use only WinterGard Wet.
• To minimize the danger of fire from sustained elec­trical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of Pentair Thermal Management, agency approvals, and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection.
• This selection guide does not take the place of the installation instructions included in the Commercial and Residential Self-Regulating Heating Products Application and Design Guide and in the H900 series accessory kits.
• System approvals and performance are based on the use of only H900 series accessories with WinterGard heating cables. These accessories must be used. Do not substitute parts.
WinterGard Wet H622050 H622100 H622250 H622500 H6221000
2
0 20
40
0
2
4
6
8
10
60 80 100
Pipe temperature (F)
Power output (W/ft)
H6XX
H3XX
WinterGard Selection Guide
Circuit Sizing Guide
WinterGard Power Temperature Curves
Maximum heater length (ft)
Circuit breaker
Heating cable type 0°F 32°F 40°F WinterGard 120 V
H311 on pipe
rating (A)
15 150 250 20 200 250
per circuit at start-up temperature
30 250 250
WinterGard Plus 120 V H611 on pipe
15 125 150 20 140 195 30 200 200
WinterGard Plus 240 V H621 on pipe
15 200 255 20 250 340 30 375 400
WinterGard Wet 120 V H612 on pipe
15 125 150 20 140 195 30 200 200
WinterGard Wet 120 V H612 in refrigeration condensate drains
WinterGard Wet 240 V H622 on pipe
15 100 125 20 125 165 30 150 200 15 200 255 20 250 340 30 375 400
WinterGard Wet 240 V H622 in refrigeration condensate drains
Note: Maximum circuit lengths are based on start-up load. Steady-state amps per foot is dependent upon heating cable temperature.
15 200 250 20 250 320 30 305 400
Catalog References
Catalog Numbers
H X X X XXX
Reel length (ft): 50 100 250 500 1000
Cable construction: 1 = Braided metal
shield only 2 = Waterproof polyolefin outer jacket over metal shield
Nominal voltage: 1 = 120 Vac 2 = 240 Vac
Nominal wattage (watts/ft): 3 6
Cable type
Catalog number
Cable construc­tion*
Watts/ft (on 40°F metal pipe)
Nominal voltage
WinterGard H311 H311100 1 3 120
H311250 1 3 120
WinterGard Plus H611
H611050 1 6 120 H611100 1 6 120 H611250 1 6 120
WinterGard Plus H621
H621050 1 6 240 H621100 1 6 240 H621250 1 6 240
WinterGard Wet H612 H612050 2 6 120
H612100 2 6 120 H612250 2 6 120 H612500 2 6 120 H6121000 2 6 120
WinterGard Wet H622 H622050 2 6 240
H622100 2 6 240 H622250 2 6 240 H622500 2 6 240 H6221000 2 6 240
*
Construction: 1 = braided metal shield only; 2 = waterproof polyolefin outer jacket over braid.
**
TruckPak consists of 100-foot cable reel, 2 power connections, 1 splice/tee kit, 1 roll application tape, 10 "Electric
Traced" labels.
EN-RaychemWinterGardSelection-AR-H5523509/13
Package type**
®
TruckPak
box 250-ft reel 50-ft box TruckPak box 250-ft reel 50-ft box TruckPak box 250-ft reel 50-ft box TruckPak box 250-ft reel 500-ft reel 1000-ft reel 50-ft box TruckPak box 250-ft reel 500-ft reel 1000-ft reel
2 / 4THERMAL MANAGEMENT SOLUTIONS
Loading...
+ 1 hidden pages