Pentair FreezGard CCH-1C, FreezGard CCH-2C Installation Instructions Manual

Page 1
FreezGard
WARNING:
SELF-REGULATING CRANKCASE HEATER INSTALLATION INSTRUCTIONS
DESCRIPTION
FreezGard crankcase heaters are intended for professional installation on refrigeration compressors up to 5 horsepower and 40 inches or less in circumference.
MODELS AVAILABLE
CCH-1C For use with 120 Vac power supply CCH-2C For use with 208 – 277 Vac power supply
ADDITIONAL MATERIALS REQUIRED
UL Listed or CSA Certified junction box and appropriate connection accessories.
GENERAL REQUIREMENTS
• FreezGard heaters are intended for use on refrigeration compressors. For any other applications, call Pentair Thermal Management for assistance.
APPROVALS
–G
• FreezGard heaters may be used only on metal hermetic compressors up to 40 inches in circumference.
• Never use on any compressor that may exceed 150°F.
• Do not use an extension cord to power the crankcase heater.
• Electrical connections must be in accordance with the National Electrical Code and must be protected from rain and other water.
• Prior to installing the heater, clean the compressor surface and inspect for and remove any sharp surfaces that may damage the heater.
• FreezGard cables must be installed by professional HVAC or refrigeration technicians or equivalent.
• Ground-fault circuit breakers such as the Square D QO-EPD, QOB-EPD, or equivalent, with a 30-mA trip level, should be used. For technical assistance or availability, call Pentair Thermal Management at (800) 545-6258.
FIRE AND SHOCK HAZARD: This heater is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the installation instructions.
THERMAL BUILDING SOLUTIONS
• To minimize the danger of fire from sustained electrical arcing if the crankcase heater is damaged or improperly installed, ground-fault equipment protection must be used on each branch circuit supplying power to the crankcase heater. Arcing may not be stopped by conventional circuit breakers.
• Do not damage the heating cable, strap, or electrical lead wires. Remove any damaged cables from service immediately.
EN-RaychemFreezGardCrankCase-IM-H5559306/16
• Leave these Installation Instructions with the user for future reference.
• If you have any questions about how to use or install this crankcase heater, please call Pentair Thermal Management at (800) 545-6258.
1 / 2
Page 2
1
2
• Disconnect all electrical power to the unit. Slip heater around the compressor casing and position close to the bottom.
3
• Connect black wires to power and neutral, and the green wire to ground.
• Feed adjusting strap through ratchet end and hand tighten to secure heater to casing.
CAUTION: Do not use excessive force or strap may break.
NORTH AMERICA
Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526 Fax: +1.650.474.7711 thermal.info@pentair.com
Pentair and FreezGard are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.
© 1997-2016 Pentair.
EUROPE, MIDDLE EAST, AFRICA
Tel: +32.16.213.511 Fax: +32.16.213.603 thermal.info@pentair.com
ASIA PACIFIC
Tel: +86.21.2412.1688 Fax: +86.21.5426.2917 cn.thermal.info@pentair.com
EN-RaychemFreezGardCrankCase-IM-H5559306/16
WWW.PENTAIRTHERMAL.COM
LATIN AMERICA
Tel: +1.713.868.4800 Fax: +1.713.868.2333 thermal.info@pentair.com
2 / 2THERMAL BUILDING SOLUTIONS
Loading...