Pentair Compli 508/2 M, Compli 108/2 M, Compli 400, Compli 508/2 ME, Compli 520/2 M Instruction Manual

...
EN Instruction Manual
COMPLI
108/2 ME 108/2 M 120/2 M 300 E 400 E 400 508/2 ME 508/2 M 520/2 M 510/4 BW 515/4 BW 525/4 BW 525/2 BW 535/2 BW
1008/2 ME 1008/2 M 1020/2 M 1010/4 BWE 1010/4 BW 1015/4 BW 1025/4 BW 1025/2 BW 1035/2 BW 1210/4 BW 1215/4 BW 1225/4 BW 1225/2 BW 1235/2 BW
JUNG-PUMPEN.DE B 42951-31-1902
ENGLISH
You have purchased a product made by Pentair Jung Pum­pen and with it, therefore, also excellent quality and service. Secure this service by carrying out the installation works in accordance with the instructions, so that our product can perform its task to your complete satisfaction. Please remember that damage caused by incorrect installation or handling will adversely affect the guarantee. Therefore ple­ase adhere to the instructions in this manual!
This appliance can be used by children aged 8 years or over and by persons with limited physical, sensory or intellectual capabilities, or with limited experience and knowledge, pro­vided that they are supervised or have been instructed in the safe use of the appliance and are aware of the dangers involved. Children must not be allowed to play with the ap­pliance. Cleaning and user maintenance must not be carried out by children unless they are supervised.
Damage prevention in case of failure
Like any other electrical device, this product may fail due to a lack of mains voltage or a technical defect. If damage (including consequential damage) can occur as a re­sult of product failure, the following precautions can be taken at your discretion:
• Installation of a water level dependent (under circumstanc- es, mains-independent) alarm system, so that the alarm can be heard before damage occurs.
• Inspection of the collecting tank/chamber for tightness up to the top edge before – or at the latest, during – installation or operation of the product.
Installation of backow protection for drainage units that can be damaged by wastewater leakage upon product fail­ure.
• Installation of a further product that can compensate in case of failure of the other product (e.g. duplex unit).
• Installation of an emergency power generator.
As these precautions serve to prevent or minimise conse­quential damage upon product failure, they are to be strictly observed as the manufacturer’s guideline – in line with the
standard DIN EN specications as state of the art – when using
the product (Higher Regional Court Frankfurt/Main, Ref.: 2 U 205/11, 06/15/2012).
SAFETY INSTRUCTIONS
This instruction manual contains essential information that must be observed during installation, operation and servic­ing. It is therefore important that the installer and the respon­sible technician/operator read this instruction manual before the equipment is installed and put into operation. The manual must always be available at the location where the pump or the plant is installed. Failure to observe the safety instructions can lead to the loss of all indemnity. In this instruction manual, safety information is distinctly la­belled with particular symbols. Disregarding this information can be dangerous.
General danger to people
Warning of electrical voltage
NOTICE!
Danger to equipment and operation
Qualication and training of personnel
All personnel involved with the operation, servicing, inspection
and installation of the equipment must be suitably qualied
for this work and must have studied the instruction manual in
depth to ensure that they are suciently conversant with its
contents. The supervision, competence and areas of respon­sibility of the personnel must be precisely regulated by the op­erator. If the personnel do not have the necessary skills, they must be instructed and trained accordingly.
Safety-conscious working
The safety instructions in this instruction manual, the existing national regulations regarding accident prevention, and any internal working, operating and safety regulations must be ad­hered to.
Safety instructions for the operator/user
All legal regulations, local directives and safety regulations must be adhered to. The possibility of danger due to electrical energy must be pre­vented. Leakages of dangerous (e.g. explosive, toxic, hot) substances must be discharged such that no danger to people or the envi­ronment occurs. Legal regulations must be observed.
Safety instructions for installation, inspection and maintenance works
As a basic principle, works may only be carried out to the equip­ment when it is shut down. Pumps or plant that convey harmful substances must be decontaminated.
All safety and protection components must be re-tted and/or
made operational immediately after the works have been com­pleted. Their effectiveness must be checked before restarting, taking into account the current regulations and stipulations.
Unauthorised modications, manufacture of spare parts
The equipment may only be modied or altered in agreement
with the manufacturer. The use of original spare parts and accessories approved by the manufacturer is important for safety reasons. The use of other parts can result in liability for consequential damage being rescinded.
Unauthorised operating methods
The operational safety of the supplied equipment is only guar­anteed if the equipment is used for its intended purpose. The limiting values given in the "Technical Data" section may not be exceeded under any circumstances.
Instructions regarding accident prevention
Before commencing servicing or maintenance works, cordon off the working area and check that the lifting gear is in perfect condition. Never work alone. Always wear a hard hat, safety glasses and safety shoes and, if necessary, a suitable safety belt. Before carrying out welding works or using electrical devices, check to ensure there is no danger of explosion. People working in wastewater systems must be vaccinated against the pathogens that may be found there. For the sake of your health, be sure to pay meticulous attention to cleanliness wherever you are working. Make sure that there are no toxic gases in the working area. Observe the health and safety at work regulations and make
2
sure that a rst-aid kit is to hand.
ENGLISH
In some cases, the pump and the pumping medium may be hot and could cause burns. For installations in areas subject to explosion hazards, special regulations apply!
AREAS OF APPLICATION
The ready to connect compli sewage lifting stations are LGA
certied and are suitable for the disposal of wastewater from
toilets and urinals, and domestic wastewater containing the usual impurities. The tanks can withstand submersion to a depth of not more than 2 m of water and a submersion period of up to 7 days. The control unit cannot withstand submersion, but is splash­proof in accordance with IP 44. If installed in compliance with the regulations and used prop­erly, then this control unit meets the protective requirements of the EMC Directive 2014/30/EU and is suitable for domestic use and connection to a power supply from the grid. When connected to an industrial mains within an industrial operation with power supply provided by a company-own high-voltage
transformer, insucient immunity to interference has to be
expected. When using the pumps, the relevant national laws, regulations and stipulations must be adhered to, for example:
• Sewage disposal units for building and ground drainage systems (e.g. EN 12050 and 12056 in Europe)
• Installation of low voltage systems (e.g. VDE 0100 in Ger- many)
• Safety and working materials (e.g., BetrSichV and BGR 500 in Germany)
Safety in wastewater systems (e.g., GUV-VC5, GUV-R104
and GUV-R126 in Germany)
Electrical systems and operating resources (e.g., GUV-VA3 in Germany)
• Explosion protection EN 60079-0, EN 60079-1, EN 60079-14, EN 60079-17 and EN 1127-1
Scope of supply
Tank with pump(s) and clamp ange for inlet
• Reducer DN 150 / DN 100 for compli 500 and 1000
Slip-on socket pipe for ventilation pipe (compli 1200 exible connection with hose clamps)
Connection ange for pressure pipe
• Flexible connection with hose clamps for the pressure pipe
• Plug-in seal(s) for the diaphragm hand pump or additional DN 50 inlet
• Fixing materials for tank
• Non-return valve for the pressure pipe (compli 300, 500, 1000 and 1200)
• Controls (not compli 300)
Mode of operation: intermittent operation S3; see "Technical Data"
Ventilation: The ventilation pipe must be vented above roof level. Inlet: A wastewater sluice valve must be installed in the inlet at the front of the tank. Pressure pipe: A further wastewater sluice valve must be in­stalled behind the non-return valve in the pressure pipe. If the non-return valve is not included in the scope of delivery of the
pumping unit, then an EN certied swing-type check valve must be tted.
The pressure pipe must be laid in a loop above the local backup level. A pump sump must be provided to facilitate the disposal of wa­ter from the pump installation area. NOTICE! All bolts that are used for xing individual compo- nents to the tank should be tightened with a torque of no more than 6 Nm.
Installing the tank
Close the sluice valve in the inlet (accessory) to prevent any leakage of water during the installation work. compli 300. Select the DN 100 inlet you wish to use and open this inlet at the side or at the top at the markings using a 102 Øhole saw or a jigsaw. Then deburr the edges. Fix the enclosed
clamp ange loosely to the inlet with the hexagon screws. Take the brackets that are used to x the unit in place and
screw them to the tank. Then take the unit with the clamp
ange and push it onto the inlet pipe as far as it will go. Mark the positions of the wall plugs on the oor, then drill the
holes and push in the wall plugs.
Now the clamp ange can be tightened and the unit can be an­chored to the oor using the wood screws and shims.
All other compli units must be slid onto the inlet pipe, together
with the clamp ange, as far as possible and then aligned. If a DN 150 side inlet is used, the inlet must rst be opened
at the marked position using a hole saw, Ø 152, and then de­burred. The standard inlet must then be closed using a closure kit (accessory) and the switch-on level must be reset. In the case of compli 500 and 1000, the inlet can be reduced
from DN 150 to DN 100 if the enclosed reducer is rst of all t­ted to the clamp ange. Tighten the hexagon screws on the clamp ange. Mark the positions of the holes for xing the tank to the oor,
then drill the holes. Insert the wood screw, together with the washer and wall plug, into the drill hole in the tank and tighten it. NOTICE! Ensure that the tank does not become deformed due to overtightening the screws, otherwise this could result in leakage.
The tanks for compli 1200 units are additionally xed with two
brackets at the sides.
Installing the ventilation
Connect the ventilation pipe to the top right of the tank using the DN 70 slip-on socket pipe and vent it above roof level. For compli 1200, cut off the top right Ø 78 mm pipe connection at the marking and deburr it. After this, connect the ventilation pipe
with the DN 70 exible connector and vent it above roof level.
INSTALLATION
The pump must be installed so that it is buoyancy-proof and free-standing. At least 60 cm free working space must be pro­vided around and above the parts that require access for op­eration or maintenance.
Installing the pressure pipe
Fit the following to the discharge ange:
1. Non-return valve (if not included in scope of supply)
2. Stop valve (accessory)
3. Connection ange and
4.
connect the pressure pipe with the exible connector and
loop it over the local backup level.
3
ENGLISH
Emergency drainage connection, DN 50, vertical
This inlet is used to connect a diaphragm hand pump. Open the pipe connection at the marking using a hole saw. Then deburr the edges. Put the plug-in seal, 58/50, into place. Push the inlet pipe, with an external diameter of 50 mm, into the tank through the plug-in seal. The distance from the bot­tom of the tank must be at least 50 mm. Fix the diaphragm hand pump to the wall in an easily accessi­ble position. Connect it to the pushed-in pipe and then connect the pressure pipe to the diaphragm hand pump. Here, too, the pressure pipe must be looped over the local backup level.
Additional inlet, DN 50, horizontal
Using a hole saw, open the additional inlet by cutting along the pre-cut groove. Deburr the edges. Put the plug-in seal, 58/50, into place. Push the inlet pipe, with an external diameter of 50 mm, into the tank through the plug-in seal. NOTICE! The pipes that connect to the low-level inlets on the
side of the unit must be tted with a bend, as close to the unit
as possible. The pipe invert of this bend must be at a height
of at least 180 mm above the oor on which the unit is xed.
Air pockets in the connecting pipe can cause run-off problems and the water could back-up. To prevent back-ups, the inlet pipe must be vented at its highest point. The ventilation pipe can be connected into the tank ventilation.
Alternating current (AC) units
Only connect the pump to electrical sockets that have been installed properly in a dry room, above the backup level, in ac-
cordance with the regulations, and are tted with at least a 16
A (delay) fuse.
Three-phase current units
For the electrical connection of the sewage disposal unit, a
ve pole CEE power socket is required. This must be located in a dry room above the backup level (3/N/PE~230/400 V).
NOTICE! Only slow-blow fuses or automatic fuses with C cha­racteristics are to be used as pre-fuses for the pump.
Installing the control unit (not compli 300)
Only operate the control unit in dry rooms above the backup level, and keep the housing closed at all times. The control unit must be easily accessible to enable it to be checked at any time. High humidity and condensation can destroy the controls!
Switching levels
The switch-on and switch-off points have been factory set for the standard inlet height for the various units.
If you select a different inlet height, then you must redene the
switch-on point (not compli 300) as otherwise backpressure may occur in the inlet. The other switching points for the alarm (+2 cm) and, in the case of duplex units, peak load (+4 cm) are then reset automat­ically by the control unit.
ELECTRICAL CONNECTION
NOTICE! Only qualied electricians may carry out electrical
works to the pump or the controls.
WARNING!
Before carrying out any works: disconnect the pump and the controls from the mains and take steps to ensure that they cannot be emergized again. NOTICE! Never put the mains plug in water! If water gets into the plug, this can cause malfunctions and damage. The standards applicable in each case (e.g. EN), the country-
specic regulations (e.g. VDE in Germany), and the regulations
of the local supply network operator must be observed. Observe the operating voltage (see the type plate)! The units have a level controller that switches the pump on and off depending on the level of the water. An integrated alarm system beeps if there is a malfunction, even if this is only tem­porary. If the pump overheats, the motor cuts out due to the winding thermostat. After the thermostat has switched off the system, pull out the mains plug before remedying the fault, since the device can switch itself on again automatically if the power is still connected. A direct malfunction message is not gener
ated.
Redening the switch-on level (not compli
300)
Shut down the system temporarily and set the Manual-0-Au­tomatic switch to “0”. The switch-on point can be adjusted via the “analogue evaluator K1” module on the right-hand side in the control unit. Remove the transparent cover of the module temporarily. On the analogue evaluator there are three LEDs, labelled P1, P2 and P3.
– P1 = Diagnosis function – P2 on = Water level higher than switching off height but still
lower than switching on height
– P3 on = Water level has reached switching on level Fill the collection chamber with water up to the bottom edge of the inlet opening. Only P2 should be lit. If P3 is also lit, a read­justment must be made. Turn the small adjusting screw beneath P1, giving it one or two
full turns clockwise. Then take the oat switch, submerge it below the switch-off point in the chamber and allow it to oat
up again. If P3 is still lit, give the adjusting screw another full
turn clockwise and submerge the oat switch again.
Repeat this procedure until P3 is no longer lit, then turn the ad­justing screw carefully back in the anticlockwise direction until the exact point where P3 lights up again. The switch-on point has then been set.
Alarm system
Malfunction messages are given both optically as well as acoustically. The standard mains-dependent alarm system re­ports motor faults in the pump (red LED, not AD 00 or compli
300). At the same time a built-in acoustic alarm sounds. This acoustic signal can only be turned off by remedying the fault or by totally deactivating it. If an acoustic signal would be inappropriate at the installation site in question, an alarm signal can be relayed via the poten­tial-free contact (terminals 40 and 41) on the circuit board (in
4
the plug in the case of compli 300). The potential-free contact
ENGLISH
of the centralised alarm can be loaded with a maximum of 5 A / 250 VAC. The contact opens after the fault has been remedied.
OPERATION
Battery pack for alarm system (not compli
300)
The alarm device is mains-dependent in its standard version, i.e. it is not possible to trigger a high-water alarm in the event of a power failure. To enable the alarm device to work even if there is a power failure, a rechargeable battery pack must be used. Open the transparent cover. Connect the battery pack to the connection clip, and use the existing cable ties to attach it to the intended position (G1) on the PCB. The battery pack can supply the alarm system with power for about 1 hour in case of permanent alarm. After return of the mains voltage, the battery pack is charged again automatically. An empty battery is ready for operation within approx. 24 hours. It is fully charged after about 100 hours. Check the function of the battery pack at regular intervals! To do so, disconnect the unit from the mains and trigger a high­water alarm. The volume of the acoustic signal must not be-
come signicantly quieter over a period of several minutes.
The service life is about 5 years. Note the insertion date on the battery pack and after ve years the battery pack should be re­placed as a precautionary measure.
CAUTION!
Only use the 9V-NiMh battery supplied by the manufacturer! If dry-cell batteries or Lithium batteries are used there is a dan­ger of explosion!
Time meter
An optional time meter can be tted in the control unit (not
compli 300). To do so, shorten the connections of the time me­ter to approx. 8 mm and insert them into the four sockets at location BSZ on the printed circuit board. If there is no time meter indication after switching on the unit again, rotate the time meter through 180°.
Shutting down the internal alarm buzzer
Not compli 300. Remove the sealed jumper (BRX/BRX1). To prevent the jumper from getting lost, attach it to a pin of the two-pole pin connector.
External alarm buzzer (accessory)
Open the transparent cover on the control unit. An additional separate acoustic 12 VDC signal transmitter with a current consumption of not more than 30 mA can be con­nected to terminals “S+” and “S-”. The internal alarm buzzer can either be switched on or off. In the case of compli 300, a mains-independent alarm device
can be tted as an accessory. There is a mounting base on the
tank for this purpose.
In the case of duplex units: External 230V~ ashing light or warning light (accessory)
Connect a 230V~ lamp (1 A max.) to terminals N and 41. Lay an insulated wire bridge from terminal U~ to terminal 40.
The electric circuit is protected by F1. Set Jumper BRX2 as follows: Flashing light without BRX2
(Continuous ===) Warning light with BRX2 (Flashing (_Π_Π_ )
Test run and functional check
1. Open the maintenance cover of the tank.
2. Open the shut-off valves in the inlet and the pressure pipe.
3. Connect the unit to the power supply and observe the indi-
cation for the rotating eld direction.
4. Fill the tank up to the switch-on level.
5. The pump will now switch on and empty the tank. Observe
the pumping process through the maintenance opening.
6. Lift the oat of the level controller slowly by hand until it is
above the switch-on point and hold it there until the alarm is triggered.
7. Then close the maintenance opening with the cover and
seal.
8. Check to ensure that the tank, ttings and pipes are water-
tight, by carrying out several switching runs.
Automatic operation
Automatic operation is the normal operating mode of the unit. The rocker switch must be set to “Automatic”. The integrated level controller switches the pump on and off depending on the water level in the tank. A green LED lights up when the pump is operating (in the case of compli 300 when it is ready for opera­tion).
NOTICE! If unusually large quantities of wastewater ow into
the unit (e.g. when a pool is drained), partially close the shut­off valve at the inlet until the unit can operate normally again, switching on and off, (not pumping continuously, since this could overheat the pump motor).
Manual operation
Set the rocker switch to “Hand”. The pump will now operate permanently and independently of the wastewater level. The pumping out operation should therefore be observed through the maintenance opening.
Shutting down
Set the rocker switch to “0”. This shuts down the pump. The alarm system remains ready for operation.
DANGER!
Do not use the position “0” of the selector switch for repair and maintenance work on the control and pump, but always unplug the unit from the mains.
Inspection
To maintain operational reliability, carry out a visual inspection of the unit, including the pipe connections, once a month.
MAINTENANCE
Maintenance and inspection of this product must be carried out in accordance with EN 12056-4. To ensure continued reli­ability of service, we recommend that you take out a service contract. NOTICE! The maintenance of the sewage lifting station and maintenance measures are carried out by specialists at inter­vals of 3 months in commercial premises, multi-family homes in 6 months or 12 months in family homes.
5
ENGLISH
WARNING!
Before carrying out any works: disconnect the pump and the controls from the mains and take steps to ensure that they cannot be energized again.
WARNING!
Check the cable for mechanical or chemical damage. A dam­aged or kinked cable must be replaced. We recommend that the following works be included in the service:
1. Check the connection points for watertightness and in-
spect the areas surrounding the unit and the ttings.
2. Operate the shut-off valves and check that they move eas­ily. Adjust and grease them if necessary.
3. Open and clean the swing-type check valve; check the seat and ball (valve)
4. Clean the pump and the pipes where they connect to the unit; check the impeller and the bearings.
CAUTION!
5. Worn impellers can have sharp edges.
6. Oil check. If necessary top up or change oil (if oil chamber available).
7. Clean the inside of the tank (as necessary, or if especially required); remove any grease, for example.
8. Check the condition of the collecting tank.
9. Flush the system through with water once every 2 years.
10. Inspect the electrical section of the unit. The control unit itself is maintenance-free, but if a rechargeable battery is
tted, then it should be checked regularly to ensure that it
is in good working order. To do so, unplug the unit from the
mains and lift the oat of the level controller slowly by hand
and hold it there until the alarm is triggered. In addition,
clean the oat if necessary.
When all the servicing tasks have been performed, carry out a test run and then put the unit back into operation. The service must be documented, giving details of the important data and of all the tasks carried out.
Oil check
(Only applies for units 08/2, 25/2 and 35/2). First of all, unscrew the hexagon screws or Allen screws around the pump and lift the pump and impeller off the tank. The drain plug is labelled “Öl”. In order to check the mechanical seal, the oil, including any residue, must be drained from the oil reservoir and collected in a clean measuring container.
• If the oil is contaminated with water (milky), an oil change must be carried out. Check again after a further 300 operat­ing hours, but at the very latest after 6 months!
• However, if the oil is contaminated with both water and pol- lutants, then not only the oil must be replaced, but the me­chanical seal as well.
For monitoring the oil reservoir, it is also possible to retrot the
electrode of our “DKG” seal leak detector in place of the “DKG” sealing screw.
pumped, the oil changes should be carried out at correspond­ingly shorter intervals. Use HLP hydraulic mineral oil, viscosity class 22 to 46, e.g. Mo­bil DTE 22, DTE 24, DTE 25, to replace the oil in the oil reservoir. The quantity of oil required is 380 cm³ for the MultiCut pumps UC 08/2 M and UC 25/2 M, and 1000 ml for the MultiFree pumps UC 25/2 BW and 35/2 BW.
NOTICE! The oil reservoir may only be lled with the specied quantity of oil. Overlling will result in the pump being rendered
inoperable.
Checking the cutting clearance
Only for pumps with cutting system. The housing screws for
the pump, and the connecting and xing screws of the instal­lation must be checked to ensure they are xed securely. They
should be tightened if necessary. If the pump performance decreases, or if increasingly loud noises can be heard during operation, or if the cutting perfor­mance decreases (the pump tends to become blocked), the impeller and cutting system must be checked for wear by an expert and replaced if necessary. Using a suitable tool, e.g. feeler gauge, the cutting clearance between the cutting rotor and the cutting plate can be meas­ured. A cutting clearance of over 0.2 mm must be reduced.
Adjustment of the cutting clearance
1. Block the cutting rotor with a piece of wood and unscrew the central hexagon socket screw.
2. Take off the compression piece, the cutting rotor and an ad­justing washer and then attach the compression piece and the cutting rotor again.
3. Block the cutting rotor and tighten again with the hexagon socket screw (tightening torque 8 Nm).
4. Check the freedom of movement of the cutting rotor and the cutting clearance again (max. 0.2 mm). If the cutting clearance is still too big, a further adjusting washer must be removed. Steps 1-4 must be repeated.
Changing the oil
(Only applies for units 08/2, 25/2 and 35/2). To ensure opera-
tional liability, the rst oil change should be carried out after
300 operating hours, with further oil changes carried out after every 1000 operating hours. If the number of operating hours is very low, an oil change should still be carried out at least once a year. If wastewater with strongly abrasive constituents is being
6
QUICK TIPS FOR REMEDYING
ENGLISH
FAULTS
support service.
• There is no water left in the tank. Fill with a small amount of water.
Note: If the LED lights up briey after the pumping opera- tion, this is not a sign of a malfunction.
The unit isn’t working
• Check the mains voltage, the fuse and the ground fault cir- cuit interrupter. Replace defective fuses only with fuses with the same nominal value! If the fuse triggers again, call a
qualied electrician or our customer support service.
• The internal 2 A glass tube fuse (delay) for the 230/12V con- trol transformer, the motor contactor and the 230V AC pow­er supply are faulty. Replace defective fuses only with fuses with the same nominal value!
• If the mains cable is damaged, it may only be replaced by the manufacturer.
If the oat switch is obstructed, close the inlet shut-off valve, open the maintenance cover and clear the blockage.
If the alarm is triggered and the unit does not work:
• The thermostat in the motor windings may have switched off the system because the pump is obstructed. In this case, close the shut-off valve at the inlet, drain the tank, pull out the mains plug, remove the pump module, and clear the blockage.
Decreased pumping performance
• Check that the shut-off valve in the pressure pipe is fully open.
If the pressure pipe is blocked, ush water through the pres- sure pipe to clear it.
• If the non-return valve is blocked, empty the pressure pipe and clean the non-return valve.
• If the ventilation system is blocked, clean the ventilation hose that leads from the pump tank and check the drilled holes.
• If the unit works normally when it starts pumping, but be-
comes very loud towards the end, then a qualied electrician must redene the switch-off point in the control unit.
Pump "snores" and does not switch itself off (not compli 300)
• The switch-off point of the unit is too low.
Unscrew the three xing screws on the level monitoring at the
front of the collecting tank. By carefully rotating it to the right the switch-off point can be set to a higher level. Retighten the screws. The switch-off level is reached during pumping when the LED2 goes off. NOTICE! It may also be necessary to re-adjust the switch-on level (please refer to the section “Redening the switch-on le­vel”).
Indicator “Drehfeld falsch" (Wrong rotating eld) lights up
• Mains phase sequence is wrong or phase is absent - thus lower or absent pump delivery. The mains connection must
be corrected by a qualied electrician only.
Indicator “Störung Pumpe" (Pump failure) lights up (not compli 300)
• The pump is protected by an integrated circuit breaker which switches off the pump if it overloads or motor fault. After this has been triggered, the control unit
has to be opened by a qualied electrician in order to press
the reset button.
if there is an electric
Indicator “Hochwasser" (High water) lights up (not compli 300)
• Water level in the tank too high because of low pump ow rate or excessive inow. Remove any obstructions in the pump or pressure pipe and/or eliminate the excessive inow.
LED P1 on the analogue evaluator is permanently lit up (not compli 300)
• There is a fault in the level monitoring. Call our customer
7
Technische Daten - Technical data -Caractéristiques techniques- Technische Gegevens - Dati tecnici - Dane techniczne - Technické údaje - Technické údaje ­Műszaki adatok -Date tehnice - 技术指标
compli 100
compli 300
8
compli 400
compli 500
9
compli 500 M
compli 1000
10
compli 1000 M
compli 1200
11
12
Loading...
+ 28 hidden pages