Pentair CD-15G, CD-25G Installation And User Manual

INTELLIZONE
COMMERCIAL OZONE GENERATOR
Models CD-15G, CD-25G - All Models
INTELLIZONE
COMMERCIAL OZONE SYSTEM
ADVANCED SANITATION S OLUTIONS
TM
IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS
INSTALLATION AND
USER'S GUIDE
TABLE OF CONTENTS
SECTION 1 General Information
Description .....................................................................1
Specifications .................................................................1
SECTION 2 Installation
Location ..........................................................................1
Mounting .........................................................................1
Electrical .........................................................................2
Plumbing .........................................................................2
SECTION 3 Operation
Initial System Start-Up ....................................................3
Normal Operation ...........................................................3
System Shut-Down .........................................................3
IMPORTANT SAFETY INSTRUCTIONS
SECTION 4 Maintenance & Service
System Electro-Mechanical Overview ........................... 3
PM Schedule ................................................................. 7
Troubleshooting ............................................................. 7
Contact Information ....................................................... 7
SECTION 5 Replacement Parts & Order Info
Ordering Information...................................................... 7
Warranty ..................................................................... 8
Appendix
Appendix A (Troubleshooting Guide) ............................ 8
Warranty .................................................................... 12
Appendix B (Safety) ................................................... 13
READ AND FOLLOW ALL INSTRUCTIONS.
• Read this manual completely before attempting installation.
• Risk of Electric Shock. Install the ozone unit and any metallic plumbing associated with the unit at least 5 ft from the inside wall of tub or pool.
• Risk of Electric Shock. Connect this ozone generator in accordance with the installation instructions. Do not install within an enclosure that would restict ventilation.
• (Applicable to cord/plug connected units only) Risk of electric shock. Connect only to a properly grounded, grounding type receptacle.
• Do not bury cord.
• Warning – To reduce the risk of electric shock, replace damaged cord immediately.
• Follow all applicable electrical codes.
• Electric shock hazard. Be sure to turn power OFF at power source before any service work is performed. Failure to do so could result in serious injury or death.
• Warning – Short term inhalation of high concentrations of ozone and long term inhalation of low concentrations of ozone can cause serious harmful physiological effects. DO NOT inhale ozone gas produced by this device.
• For your safety, do not store or use gasoline, chemicals or other flammable liquids or vapors near this or any other appliance.
A spontaneous and violent ignition may occur if oil, grease or greasy substances come in contact with oxygen under pressure. These substances must be kept away from oxygen regulators, cylinder valves tubing and connections, and all other oxygen equipment.
SAVE THESE INSTRUCTIONS!
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
1
SECTION 1 General Information
Description
The IntelliZone™ Commercial Ozone Gererator (Models CD-15G and CD-25G (521659, 521660, 521761 and
521762) described in this manual is designed to provide the benefits of ozonated water in an environmentally safe and effective manner. The high quality, specially engineered components ensure efficient ozone output and reliable performance.
Thos ozone generator is safe and harmless to your equipment if installed properly.
24.1 613
A
31112.3
24.4 620
A
DIM "A" = 6 [152] MIN CLEARANCE
11.7 297
DOOR SWING
621R24.5
SECTION 2 Installation
Location
The ozone generator is designed for either floor or wall mounting in a clean, protected area, either indoors or outdoors. Locate generator out of reach of sprinklers or drainage spouts. Allow sufficient access for maintenance and all tubing and electrical wires. The generator must not be placed in locations where ambient ozone levels exceed 0.01 PPM.
Mounting
NOTE: Do not remove compressor packing material until unit has been mounted.
Wall Mount Option
1. Attach two mounting brackets to wall using anchors appropriate for mounting surface. See Figure 2.
2. Using 1/4"-20 bolts (with washers as shown) secure generator to mounts.
Floor Mount Option
1. Use the four 1/4"-20 bolts with washers to secure feet to bottom of cabinet.
2. Stand upright and securely fasten to concrete slab using appropriate anchors and bolts.
39.2 995
MOUNTING BRACKETS (2)
1024.0
MIN. CLEARANCE
(IF WALL MOUNTED) 4.0 102
Figure 1
Specifications
For detailed specifications refer to the ozone generator specification label located on the inside of the door on the unit.
Location Requirements*: Mounting: Floor or wall mount in a clean, protected area using supplied brackets. Ventilation: Room should provide 6 air changes per hour Ambient Temp.: 40–100˚F (5–38˚C)
* Protection from weather elements must be provided for outdoor installations. Operating outside of the recommended temp. ranges may result in damage not covered under the manufacturer’s warranty.
Figure 2: Wall Mount
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
2
Electrical
Refer to the units specification label and local electrical codes for information on proper electrical connection.
120V Models Main power circuit: Unit is supplied with a standard power cord. Plug cord into standard 120V grounded, gounding type receptacle only.
230V Models Main power circuit: 230V models are supplied with an IEC 6032 C-14 Type power receptacle. A power cord, having at least a 10AMP rating, with a IEC 60320 C-13 Type plug and a country specific plug is required to power generator.
Figure 3: Country Specific Plug
(Australia shown for reference only)
Plumbing
Ozone gas is introduced to the circulation line using a venturi in-line injector. Suction developed by the venturi injector allows the generator to operate safely under vacuum. See installation manual for Model 521683 or 521684 for proper venturi installation.
Ozone Gas Line
1. Connect ozone tubing to generator outlet fitting. (3/8" stainless steel compression fitting.)
2. Connect opposite end of ozone tubing to injector suction port. (Suction port fitting: 3/8" stainless steel compression fitting.) See Figure 4.
NOTE: The ozone gas supply line must be made of PTFE or stainless steel and have a back flow prevention device (such as a check valve) installed between the ozone generator cabinet and the point of injection to prevent water from backing up into the generator system. An ozone supply check valve is included with the Model 521683 or 521684 system.
Figure 4: Plumbing Schematic - Example of Swimming Pool Application
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
3
Cooling Water Cooling Water Flow: .1 Gpm (.4 Lpm) Colling water Pressure: 15–40 psi (103–275 kPa) Cooling Water Temp.: 5–90˚F (10–32˚C)
1/4" FPT connections are supplied on the generator. See Figure 4, 5a, 6a. Be sure that the tubing is appropriately matched with the marked inlet and outlet ports. Carefully match and connect to water plumbing as shown in Figure 4. Alternate method using connections at injector may be used.
SECTION 3 Operation
Initial System Start-Up
Upon completing all of the generator system connections, you are ready to begin start-up procedures.
1. Check electrical fittings.
2. Check for proper voltage.
3. Turn on circulation pump.
4. Check for leaks.
5. With the ozone isolation valve closed, adjust the injector bypass valve and/or filtration sidestream valve to flow water through the injector.
6. Check cooling water.
7. Open the ozone isolation valve.
8. Turn main power switch to "ON" position.
9. Adjust injector by-pass to attain required vacuum. (Red "Vacuum" light will go out.) Gas flow (as indicated by the flow meter on the door of the unit) should correspond with the rating listed for the specific model on the specification label.
Normal Operation
With the power switch on, the system’s compressors and cooling fans will start-up, the oxygen concentrator will begin operating, and the output solenoid valve will open. With the injector adjusted to attain the correct gas flow, the ozone generator should be producing ozone and injecting it into the process line.
Both (2) green indicator lights should be lit. If an optional ORP Controller is installed, it should be displaying a reading from the sensor probe and will automatically cycle the generator on and off as needed to maintain water quality. Residual ORP levels will vary per application.
However, the system will not start under any of the following conditions:
1. The system will not start-up if the door is not secured. A door interlock switch is incorporated into the system enclosure.
2. If the optional ORP/DO3 controller is installed the system will not produce ozone if the measured level is already above the setpoint of the controller.
3. The system will not produce ozone if there is not enough vacuum being generated by water flow through injector. The red "Vacuum" light will go out when proper vacuum is attained.
If you experience complications, see APPENDIX A, TROUBLESHOOTING GUIDE or call
800.831.7133 for assistance.
System Shut-Down
The ozone generator is a specialized water cooled device that must be properly protected during shut-down/storage periods. The following sequence of steps must be used for servicing or for storage.
1. Toggle the main system power switch to the “OFF” position to shut-down generator.
2. Close the ozone isolation valve to prevent water back flow.
3. After the generator has been shut-down, the process water circulation pump may be turned off.
4. If the system is going to be shut-down and stored during freezing weather, it is very important that the cooling water be drained to protect it from rupture or damage.
NOTE: Process water flow must not be shut-
down when the ozone generator is operating. Doing so may cause water to backflow into the system and damage the generator cells.
SECTION 4 Maintenance & Service
System Electro-Mechanical Overview
Refer to Figure 5a and 6a for component locations. Indicator Lights
1. Main Power: Green light indicates that power is being supplied to the ozone generator.
2. Ozone Power: Green light indicates that power is being supplied to the high voltage Corona Discharge circuits and that ozone is being produced.
3. Vacuum: Red light indicates a low vacuum fault condition. (Refer to APPENDIX A TROUBLESHOOTING).
4. High Coolant Temperature: Red light indicates
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
4
cell temperature is over 110F - resulting from loss of cooling water flow. (Refer to APPENDIX "B", TROUBLESHOOTING GUIDE.)
5. Water Backflow Detected: Red light indicates water backflow from injector into generator. (Refer to APPENDIX "B", TROUBLESHOOTING GUIDE.)
External Components
1. Main Power Switch: Power switch is used for system start-up and shut-down. Switch activates the control system allowing the generator to start up.
2. Flowmeter: Flowmeter controls and indicates the oxygen flow through the system.
3. Circuit Breaker: Circuit breaker protects the generator from over current conditions. Push the breaker button to reset.
Internal Components
1. Variable Output Switch (optional): Adjusts high voltage power supplied to the ozone generator module controlling ozone output concentration. Located on the outside of the enclosure door.
External Devices that Control Ozone Production The devices turn ozone production on or off based on programmed level set points. Refer to Figure 5b and 6b for connection details.
1. ORP Controller (optional): The ORP controller receives a millivolt (mV) signal from the ORP sensor mounted in the process water line. ORP (Oxidation-Reduction Potential) is a measure of the relative oxidation strength of the water. As ozone is added to the water system the ORP level will rise. As ozone is used up in the water system the ORP level will drop. The ORP controller continuously analyzes the sensor signal, compares it to the setpoint that has been programmed, indicates the ORP level on the digital display, and relays the signal to the ozone generator.
2. Dissolved Ozone Monitor (optional): Monitoring system designed for the continuous measurement of ozone gas in solution. The operating range of the system may be selected by the user from 0-2.00 PPM or from 0-20.00 PPM. The basic sensing element used is polarographic membraned sensor which measures ozone directly.
External Devices that Control System Power The devices turn power to the ozone generator
on or off. Examples of such devices would be an ambient ozone monitor or flow switch. Refer to Figure 5b and 6b for connection details.
Internal Components
1. Ozone Cell Assembly: Cells are made of two aluminum halves. Enclosed in the aluminum halves are a ceramic tube, coil type high voltage electrode and a PTFE rod.
2. High Voltage Supply(s): Power supplies raise incoming line voltage and frequency to deliver it to the cells. Each power supply is rated at 100W.
3. Air Compressors: Compressors produce and supply compressed air to oxygen concentrator.
4. Oxygen Concentrator: Supplies concentrated, dry, oxygen feed gas to the ozone generator.
5. Low Limit Vacuum Switch: If the vacuum in the ozone output supply line falls below 1.5 in. Hg the switch will open causing the system to shut down.
6. Vacuum Regulator: Regulates the oxygen flow into the generator cell based on a vacuum setpoint (factory set to 3-5 in. Hg). When the sufficient suction is being developed by the injectors downstream the regulator will allow full flow to pass. As suction is reduced, flow is restricted proportionally to maintain the vacuum set point. If suction is lost completely, flow is cut off.
7. Water Backflow: The backflow detector senses water present in ozone tubing in generator. If water is detected, system will close solenoid valve to prevent additional water backflow from occuring. Water in the generator will cause severe damage to the high voltage electrodes.
8. Ventilation Fan: Cooling fan operates when main power switch is “ON”.
9. Air Filter: Filter cleans ventilation air entering the enclosure.
10. Door Interlock Switch: Interlock switch will shut down entire system if door is opened. Securing the door will bring the system back into operation.
11. Relay Panel: Contains control relays for system interlocks, indicator lights and main power control.
12. Hour Meter: Indicates total system operating time in hours.
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
5
Figure 5a: Component Locations (ALL MODELS EXCEPT 521761 and 521762)
Relay Panel
Remove jumper if ORP controller or dissolved ozone monitor is used. Connect dry contact leads from controller/monitor or leave open if 5 pin external interface connector is used.
Remove jumper and connect dry contact leads if external device is used. (ambient ozone, flow switch, etc.)
Figure 5b: Connection Details for External Control Devices (ALL MODELS EXCEPT 521761 and 521762)
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
Loading...
+ 15 hidden pages