Appendix B (Safety) ................................................... 13
READ AND FOLLOW ALL INSTRUCTIONS.
• Read this manual completely before attempting installation.
• Risk of Electric Shock. Install the ozone unit and any metallic plumbing associated with the unit at least
5 ft from the inside wall of tub or pool.
• Risk of Electric Shock. Connect this ozone generator in accordance with the installation instructions.
Do not install within an enclosure that would restict ventilation.
• (Applicable to cord/plug connected units only) Risk of electric shock. Connect only to a properly grounded, grounding type receptacle.
• Do not bury cord.
• Warning – To reduce the risk of electric shock, replace damaged cord immediately.
• Follow all applicable electrical codes.
• Electric shock hazard. Be sure to turn power OFF at power source before any service work is performed.
Failure to do so could result in serious injury or death.
• Warning – Short term inhalation of high concentrations of ozone and long term inhalation of low
concentrations of ozone can cause serious harmful physiological effects. DO NOT inhale ozone gas
produced by this device.
• For your safety, do not store or use gasoline, chemicals or other flammable liquids or vapors near this
or any other appliance.
• A spontaneous and violent ignition may occur if oil, grease or greasy substances come in
contact with oxygen under pressure. These substances must be kept away from oxygen
regulators, cylinder valves tubing and connections, and all other oxygen equipment.
SAVE THESE INSTRUCTIONS!
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
1
SECTION 1 General Information
Description
The IntelliZone™ Commercial Ozone Gererator (Models
CD-15G and CD-25G (521659, 521660, 521761 and
521762) described in this manual is designed to provide
the benefits of ozonated water in an environmentally
safe and effective manner. The high quality, specially
engineered components ensure efficient ozone output
and reliable performance.
Thos ozone generator is safe and harmless
to your equipment if installed properly.
24.1 613
A
31112.3
24.4 620
A
DIM "A" = 6 [152] MIN CLEARANCE
11.7 297
DOOR SWING
621R24.5
SECTION 2 Installation
Location
The ozone generator is designed for either floor or wall
mounting in a clean, protected area, either indoors or
outdoors. Locate generator out of reach of sprinklers or
drainage spouts. Allow sufficient access for maintenance
and all tubing and electrical wires. The generator must
not be placed in locations where ambient ozone levels
exceed 0.01 PPM.
Mounting
NOTE: Do not remove compressor packing material until unit has been mounted.
Wall Mount Option
1. Attach two mounting brackets to wall using anchors appropriate for mounting surface.
See Figure 2.
2. Using 1/4"-20 bolts (with washers as shown) secure generator to mounts.
Floor Mount Option
1. Use the four 1/4"-20 bolts with washers to secure feet to bottom of cabinet.
2. Stand upright and securely fasten to concrete slab using appropriate anchors and bolts.
39.2 995
MOUNTING
BRACKETS (2)
1024.0
MIN. CLEARANCE
(IF WALL MOUNTED) 4.0 102
Figure 1
Specifications
For detailed specifications refer to the ozone generator specification label located on the inside
of the door on the unit.
Location Requirements*:Mounting: Floor or wall mount in a clean, protected
area using supplied brackets.
Ventilation: Room should provide 6 air changes per hour
Ambient Temp.: 40–100˚F (5–38˚C)
* Protection from weather elements must be provided
for outdoor installations. Operating outside of the
recommended temp. ranges may result in damage
not covered under the manufacturer’s warranty.
Figure 2: Wall Mount
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
2
Electrical
Refer to the units specification label and local electrical codes for information on proper electrical
connection.
120V ModelsMain power circuit: Unit is supplied with a standard power cord. Plug cord into standard
120V grounded, gounding type receptacle only.
230V ModelsMain power circuit: 230V models are supplied with an IEC 6032 C-14 Type power receptacle. A power cord, having at least a 10AMP rating, with
a IEC 60320 C-13 Type plug and a country specific
plug is required to power generator.
Figure 3: Country Specific Plug
(Australia shown for reference only)
Plumbing
Ozone gas is introduced to the circulation line using
a venturi in-line injector. Suction developed by the
venturi injector allows the generator to operate safely under vacuum. See installation manual
for Model 521683 or 521684 for proper venturi installation.
2. Connect opposite end of ozone tubing to injector
suction port. (Suction port fitting: 3/8" stainless
steel compression fitting.) See Figure 4.
NOTE: The ozone gas supply line must be
made of PTFE or stainless steel and have a
back flow prevention device (such as a check
valve) installed between the ozone generator
cabinet and the point of injection to prevent water from backing up into the generator
system. An ozone supply check valve is included with the Model 521683 or 521684 system.
Figure 4: Plumbing Schematic - Example of Swimming Pool Application
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
3
Cooling WaterCooling Water Flow: .1 Gpm (.4 Lpm) Colling water Pressure: 15–40 psi (103–275 kPa)
Cooling Water Temp.: 5–90˚F (10–32˚C)
1/4" FPT connections are supplied on the generator. See Figure 4, 5a, 6a. Be sure that
the tubing is appropriately matched with the marked
inlet and outlet ports. Carefully match and connect
to water plumbing as shown in Figure 4. Alternate
method using connections at injector may be used.
SECTION 3 Operation
Initial System Start-Up
Upon completing all of the generator system connections, you are ready to begin start-up procedures.
1. Check electrical fittings.
2. Check for proper voltage.
3. Turn on circulation pump.
4. Check for leaks.
5. With the ozone isolation valve closed, adjust the
injector bypass valve and/or filtration sidestream
valve to flow water through the injector.
6. Check cooling water.
7. Open the ozone isolation valve.
8. Turn main power switch to "ON" position.
9. Adjust injector by-pass to attain required vacuum.
(Red "Vacuum" light will go out.) Gas flow (as indicated by the flow meter on the door of the unit) should correspond with the rating listed
for the specific model on the specification label.
Normal Operation
With the power switch on, the system’s compressors and cooling fans will start-up, the oxygen concentrator will begin operating, and the output solenoid valve will open. With the injector adjusted to attain the correct gas flow, the ozone generator should be producing ozone and injecting it into the process line.
Both (2) green indicator lights should be lit. If an optional ORP Controller is installed, it should be displaying a reading from the sensor probe and will automatically cycle the generator on and
off as needed to maintain water quality. Residual
ORP levels will vary per application.
However, the system will not start under any of
the following conditions:
1. The system will not start-up if the door is not secured. A door interlock switch is incorporated
into the system enclosure.
2. If the optional ORP/DO3 controller is installed the
system will not produce ozone if the measured
level is already above the setpoint of the controller.
3. The system will not produce ozone if there is not
enough vacuum being generated by water flow
through injector. The red "Vacuum" light will go
out when proper vacuum is attained.
If you experience complications, see APPENDIX
A, TROUBLESHOOTING GUIDE or call
800.831.7133 for assistance.
System Shut-Down
The ozone generator is a specialized water cooled device that must be properly protected during shut-down/storage periods. The following sequence of steps must be used for servicing or for storage.
1. Toggle the main system power switch to the “OFF” position to shut-down generator.
2. Close the ozone isolation valve to prevent water
back flow.
3. After the generator has been shut-down, the process water circulation pump may be turned
off.
4. If the system is going to be shut-down and stored during freezing weather, it is very important that the cooling water be drained to protect it from rupture or damage.
NOTE: Process water flow must not be shut-
down when the ozone generator is operating.
Doing so may cause water to backflow into
the system and damage the generator cells.
SECTION 4 Maintenance & Service
System Electro-Mechanical Overview
Refer to Figure 5a and 6a for component locations.
Indicator Lights
1. Main Power: Green light indicates that power is
being supplied to the ozone generator.
2. Ozone Power: Green light indicates that power
is being supplied to the high voltage Corona Discharge circuits and that ozone is being produced.
3. Vacuum: Red light indicates a low vacuum fault
condition. (Refer to APPENDIX A TROUBLESHOOTING).
4. High Coolant Temperature: Red light indicates
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
4
cell temperature is over 110F - resulting from loss of cooling water flow. (Refer to APPENDIX
"B", TROUBLESHOOTING GUIDE.)
5. Water Backflow Detected: Red light indicates water backflow from injector into generator. (Refer to APPENDIX "B", TROUBLESHOOTING
GUIDE.)
External Components
1. Main Power Switch: Power switch is used for system start-up and shut-down. Switch activates
the control system allowing the generator to
start up.
2. Flowmeter: Flowmeter controls and indicates
the oxygen flow through the system.
3. Circuit Breaker: Circuit breaker protects the generator from over current conditions. Push
the breaker button to reset.
Internal Components
1. Variable Output Switch (optional): Adjusts high voltage power supplied to the ozone generator module controlling ozone output concentration. Located on the outside of the enclosure door.
External Devices that Control Ozone Production
The devices turn ozone production on or off based on programmed level set points. Refer
to Figure 5b and 6b for connection details.
1. ORP Controller (optional): The ORP controller
receives a millivolt (mV) signal from the ORP sensor mounted in the process water line. ORP
(Oxidation-Reduction Potential) is a measure of the relative oxidation strength of the water.
As ozone is added to the water system the ORP
level will rise. As ozone is used up in the water
system the ORP level will drop. The ORP controller continuously analyzes the sensor signal, compares it to the setpoint that has been programmed, indicates the ORP level on
the digital display, and relays the signal to the ozone generator.
2. Dissolved Ozone Monitor (optional): Monitoring system designed for the continuous
measurement of ozone gas in solution. The operating range of the system may be selected
by the user from 0-2.00 PPM or from 0-20.00
PPM. The basic sensing element used is
polarographic membraned sensor which
measures ozone directly.
External Devices that Control System Power
The devices turn power to the ozone generator
on or off. Examples of such devices would be an
ambient ozone monitor or flow switch. Refer to
Figure 5b and 6b for connection details.
Internal Components
1. Ozone Cell Assembly: Cells are made of two
aluminum halves. Enclosed in the aluminum
halves are a ceramic tube, coil type high voltage
electrode and a PTFE rod.
2. High Voltage Supply(s): Power supplies raise incoming line voltage and frequency to deliver it
to the cells. Each power supply is rated at 100W.
3. Air Compressors: Compressors produce and
supply compressed air to oxygen concentrator.
4. Oxygen Concentrator: Supplies concentrated,
dry, oxygen feed gas to the ozone generator.
5. Low Limit Vacuum Switch: If the vacuum in the ozone output supply line falls below 1.5 in. Hg
the switch will open causing the system to shut
down.
6. Vacuum Regulator: Regulates the oxygen flow into the generator cell based on a vacuum
setpoint (factory set to 3-5 in. Hg). When the sufficient suction is being developed by the injectors downstream the regulator will allow full
flow to pass. As suction is reduced, flow is restricted proportionally to maintain the vacuum
set point. If suction is lost completely, flow is
cut off.
7. Water Backflow: The backflow detector senses water present in ozone tubing in generator. If
water is detected, system will close solenoid
valve to prevent additional water backflow from
occuring. Water in the generator will cause
severe damage to the high voltage electrodes.
8. Ventilation Fan: Cooling fan operates when main power switch is “ON”.
9. Air Filter: Filter cleans ventilation air entering
the enclosure.
10. Door Interlock Switch: Interlock switch will shut down entire system if door is opened. Securing the door will bring the system back
into operation.
11. Relay Panel: Contains control relays for system interlocks, indicator lights and main power control.
12. Hour Meter: Indicates total system operating time in hours.
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
5
Figure 5a: Component Locations (ALL MODELS EXCEPT 521761 and 521762)
Relay Panel
Remove jumper if ORP controller or dissolved
ozone monitor is used. Connect dry contact
leads from controller/monitor or leave open
if 5 pin external interface connector is used.
Remove jumper and connect dry contact leads
if external device is used. (ambient ozone, flow
switch, etc.)
Figure 5b: Connection Details for External Control Devices (ALL MODELS EXCEPT 521761 and 521762)
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
6
AIR COMPRESSOR
FANS
HIGH VOLTAGE
POWER SUPPLIES
OXYGEN
CONCENTRATOR
VACUUM REGULATOR
& SOLENOID VALVE
OZONE CELL
ASSEMBLY
COOLING WATER OUT
COOLING WATER IN
COMPRESSOR
AIR FILTER
DOOR SWITCH
OZONE OUT
AIR INTAKE SCREENS (3)
HOUR METER
INDICATOR
LIGHTS
FLOW METER
VACUUM & PRESSURE
SWITCHES
BACK FLOW PREVENTER
& SOLENOID VALVE
RELAY PANEL
ON/OFF SWITCH
OPTIONAL
VARIABLE
OUTPUT SWITCH
5 PIN EXTERNAL
INTERFACE
CONNECTOR
RECEPTACLE
IEC 60320 C-14
CIRCUIT
BREAKERS (2)
Figure 6a: Component Locations
K3
Relay Panel
K5
K1
K2
K4
Remove jumper if ORP controller or dissolved
ozone monitor is used. Connect dry contact
leads from controller/monitor or leave open
if 5 pin external interface connector is used.
Remove jumper and connect dry contact leads
if external device is used. (ambient ozone, flow
switch, etc.)
Figure 6b: Connection Details for External Control Devices
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
7
Preventative Maintenance Schedule
Regular maintenance should be performed to avoid
damage to the system, more costly repairs and to keep the warranty active. For instance, the compressor should be rebuilt every 8,750 hours to prevent the reduction in air-pressure and flow.
If the compressor is not rebuilt, oxygen concentrator
sieve beds will become plugged and unusable, creating more costly problems. If the generator cells are not cleaned or replaced annually, a lower
ozone output will result.
DAILY:Check ozone generator for proper operation.
- Make sure no red indicator lights are lit.
- Make sure flow meter is indicating proper
air flow.
MONTHLY:
1. Inspect compressor air filter.
- Replace quarterly
2. Remove and clean air filter or intake screens See Figure 7.
- Remove filter cover plate to access filter.
- Rinse filter in warm, soapy water and blow dry.
- Replace filter.
- For models 521761 and 521762, remove and
clean intake screens.
3. Perform general cleaning of cabinet interior.
Troubleshooting
See APPENDIX A TROUBLESHOOTING.
NOTE: Knowledge of electrical applications is required for trouble shooting. Contact a certified electrician if you are unsure of your ability to service the equipment. If any condition persists,
call 800.831.7133 for technical assistance.
Contact Information
For Technical assistance:Call: 800.831.7133
Visit: www.pentaircommercial.com
www.pentairpool.com
SECTION 5 Replacement Parts &
Order Information
Ordering information
For replacement parts call 800.831.7133
Be prepared with the following information:
• Customer Name
• Customer Address
• Model Number
• Serial Number
EVERY 8,750 HOURS:
1. Rebuild compressor. Kit Avaiable. See Section 5
for ordering information.
2. Replace/Service Check Valve(s) and Solenoid
Valves.
3. Replace ozone cell O-rings and inspect ozone
cells.
IN TAKE SC RE EN
BO TTO M OF
CD CA BI NE T
Figure 7: Filter or Intake Screen Removal for Cleaning
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
8
APPENDIX A
TROUBLESHOOTING
TROUBLESHOOTING
FOR CD-15G & 25G SERIES
OZONE GENERATORS
The following information can help resolve problems that might arise in operation of the CD-15G & 25G
Series ozone generators. It contains three main sections that when used together provide a basic overview
of the ozone generator layout, troubleshooting table for common problems, and electrical, pneumatic, and
hydraulic order diagrams. If you still need help, call 800.831.7133.
.
Note: Always disconnect the ozone generator from the power source before attempting service or repair.
Image 1: Ozone Generator Component Locations (CD-25GV model shown)
12
15
2
22
3
11
21
19
10
26
20
29
30
18
8
17
9
24
5
6
14
31
25
7
1
28
27
23
16
13
4
32
1. 5-Pin connector (not shown) 12. Door switch 23. Power switch
10. Cooling block assembly 21. Ozone power supplies
11. Cooling water in & out fittings 22. Ozone solenoid valve
32. Variable ozone output control
(optional)
TSG CD-15G & 25G 1 of 44-1529-01_Rev.A
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
Table 1: Troubleshooting (for best results follow the table order)
Problem (Indication) Possible Cause Corrective Action
1. Unit does not start
(main power light is off and no
sound is coming from the unit)
2. Unit is in vacuum fault
(vacuum light is on)
3. Unit is in high temperature fault
(high coolant temperature light is
on)
4. Unit is in backflow fault
(water backflow detected light is on)
5. Unit does not flow gas
(flowmeter at bottom of scale)
6. Unit ozone production does not
start
(both
ozone power and vacuum
lights are off)
7. Unit does not provide effective
sanitation
(both
main power and ozone power
lights are on)
a. Unit is not supplied power
b. Unit door switch is open Close unit door
c. Unit power switch is in off position Turn power switch on
d. Unit circuit breaker is tripped Reset circuit breaker
a. Inadequate vacuum is supplied to
unit
b. Unit S.S. check valve has failed Clean or replace S.S. check valve
c. Unit vacuum switch has failed Replace vacuum switch
d. Unit vacuum regulator requires
adjustment or has failed
a. Unit thermal switch has tripped
b. Unit thermal switch has failed Replace thermal switch
a. Water has returned from injection
point and triggered unit back flow
float switch
a. Unit flowmeter valve is closed Adjust flowmeter valve open
b. Unit jumper(s) at TB1 are removed
(optional system control hookup, e.g.
flow switch and/or ambient O3)
c. Unit fuse is blown Replace fuse
d. Unit pressure switch is not active
e. Unit orifice is plugged Clean or replace orifice
f. Unit solenoid valve(s) has failed Clean or replace solenoid valve(s)
g. Unit flowmeter ball is stuck on
bottom of sight tube
h. Unit vacuum regulator requires
adjustment or has failed
a. Unit jumper at TB4 is removed
(optional external ozone control
hookup, e.g. ORP or dissolved O3,
directly wired or through 5-Pin)
a. Unit variable ozone output control
setting is too low (optional feature)
b. Leak in plumbing that dilutes
applied ozone dose
c. Low gas flow and/or low oxygen
concentration
d. Unit ozone cell has reached
service life or failed
e. Unit ozone power supply has failed Replace power supply
Connect unit to power source
Turn power source breaker on
Reset power source G.F.C.I.
Verify power source voltage is
within unit specification
Connect unit to vacuum source
(injector)
Adjust injector to provide more
vacuum
Fix leak or obstruction in plumbing
between injector and unit
Call service department for
assistance
Reduce supplied cooling water
temperature and/or increase flow
rate
Obstruction or scaling in cooling
block assembly (clean or replace)
Disconnect ozone line between
injector and unit at ozone output
fitting, drain BFPD vessel, and
replace SS check valve
Re-install jumper(s) and/or verify
system control(s) are operational
Verify unit plumbing between
oxygen concentrator and pressure
switch is securely connected
Replace compressor air filter
Rebuild compressor
Replace oxygen concentrator
Repair or replace flowmeter
Call service department for
assistance
Re-install jumper and/or verify
external ozone control is
operational
If so equipped, increase ozone
output setting
Fix leak in plumbing (inside unit
and/or between unit and injector)
Replace unit compressor air filter
Clean or replace unit orifice
Clean or replace unit check valve
Rebuild unit compressor
Replace unit oxygen concentrator
Replace ozone cell
9
TSG CD-15G & 25G 2 of 44-1529-01_Rev.A
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
10
TSG CD-15G & 25G 3 of 44-1529-01_Rev.A
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
11
TSG CD-15G & 25G 4 of 44-1529-01_Rev.A
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
12
LIMITED WARRANTY
Pentair Aquatic Systems warrants the IntelliZone
521761 and 521762) as follows:
Limited Warranty: Pentair warrants the (Models CD-15G and CD-25G (521659, 521660, 521761 and 521762) to be free from defects in
material and/or workmanship for a period of two (2) years from the original date of installation.
Exceptions that shall result in Pentair’s denial of a warranty claim:
1. Damage caused by careless handling, improper repackaging, or shipping.
2. Damage due to misapplication, misuse, abuse or failure to operate equipment as specified in the (Models CD-15G and
CD-25G (521659, 521660, 521761 and 521762) Installation and User’s Guide.
3. Damage caused by failure to install products as specified in the (Models CD-15G and CD-25G (521659, 521660, 521761 and 521762) Installation and User’s Guide.
4. Damage due to unauthorized product modifications or alterations, or failure to use Pentair original replacement parts.
5. Damage caused by negligence, or failure to properly maintain products as specified in the (Models CD-15G and CD-25G (521659, 521660, 521761 and 521762) Installation and User’s Guide.
6. Damage caused by failure to maintain water chemistry in conformity with the standards set forth in the (Models CD-15G and CD-25G (521659, 521660, 521761 and 521762) Installation and User’s Guide.
7. Damage caused by water scaling, freezing or any conditions causing inadequate water circulation.
8. Accidental damage, fire, acts of God, or other circumstances outside the control of Pentair.
• This warranty extends to the original retail owner (Customer) only, beginning on the date of installation and is not enforceable by any other party. Proof of purchase and/or date of installation will be required for all warranty claims. Customer agrees to pay
all shipping charges to Pentair.
• Warranties by others: Some products incorporate components manufactured by other manufacturers. Some of these provide warranties in addition to the warranty provided herein. In all such cases a copy of that warranty will be provided with the product
To the extent protection provided under any such third party warranty exceeds the Limited Warranty provided herein, the Customer must look only to that other manufacturer for the additional warranty protection.
Warranty Obligations of Pentair: Should a defect in workmanship and/or material in any item covered by this warranty
become evident during the term of the warranty, then upon the Customer following the procedures set forth below, Pentair will, at
its option, repair or replace such item or part at its own cost and expense. Pentair’s maximum obligation under this warranty is
limited to the repair and replacement of the (Models CD-15G and CD-25G (521659, 521660, 521761 and 521762). Pentair disclaims all other expressed or implied warranty obligations.
™
Commercial Ozone Gererator (Models CD-15G and CD-25G (521659, 521660,
Pentair is not, however, responsible under this warranty for any cost of shipping or transportation of the equipment or parts thereof to or
from Pentair’s Technical Service Department. Also, Pentair is not liable for any loss of time, inconvenience, incidental expenses such
as telephone calls, labor or material charges incurred in connection with the removal or replacement of the equipment, or any other
incidental or consequential damages, including but not limited to damage to pool equipment or any surface in or around the pool in
which the (Models CD-15G and CD-25G (521659, 521660, 521761 and 521762) is installed.
PLEASE NOTE: Some states do not allow the exclusion or limitation of incidental, or consequential damages, so the above limitation or
exclusion may not apply to you.
No Other Warranties: TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW, PENTAIR DISCLAIMS ALL OTHER
WARRANTIES, WHETHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Procedure for Obtaining Performance: In order to obtain the benefits of this warranty, the Customer who made the original retail
purchase must contact the Pentair Technical Service Department upon discovery of the defect, but in no event later than the expiration
date of the warranty period provided in this warranty. Upon receipt of this communication, Pentair will promptly notify the Customer
of the address to which the defective item may be shipped. The Customer shall then ship the item, freight prepaid, to the address
indicated, together with a "RETURN GOODS AUTHORIZATION" form obtained from Pentair Technical Service and a brief description of
the problems encountered. Unauthorized returns will not be accepted. Freight must be prepaid by customer.
Warranties or Representations by Others: No dealer or other third party entity has any authority to make any warranties or
representations concerning Pentair or its products. Accordingly, Pentair is not responsible for any such warranties or representations.
Other Rights: This warranty gives you specific legal rights and you may also have other rights, which vary from state to state. This
warranty supersedes all previous publications.
Pentair Aquatic Systems.
1620 Hawkins Ave. Sanford, NC 27330 - 10951 W. Los Angeles Ave. Moorpark, CA 93021 - Phone 800-831-7133 - Fax 800-284-4151
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
APPENDIX - SAFETY
OZONE Material Safety Data Sheet
SECTION I: MATERIAL IDENTIFICATION
IDENTITY: OZONE (Gaseous)ISSUED: February, 1992
FORMULA: O3 REVISED: April 3, 2012
Description (origin/uses): Occurs in atmosphere from UV light action on oxygen at high altitude. Commercially obtained by
passing air between electrodes carrying a high voltage alternating current. Also found as a by-product in welding areas, high
voltage equipment, or UV radiation.
Ozone is used as an oxidizing agent in air and water disinfection: for bleaching textiles, oils, and waxes; organic synthesis as in
processing certain perfumes, vanillin, camphor; for mold and bacteria control in cold storage
Cautions:A powerful oxidizing agent, ozone generally exists as a gas and is highly chemically reactive. Inhalation produces
various degrees of respiratory effects from irritation to pulmonary edema (fluid in lungs) as well as affecting the eyes, blood, and
central nervous system.
Manufacturer/Supplier: On-site generation, equipment available from various suppliers, including:
DEL Ozone
3580 Sueldo Street
Phone: (805) 541-1601
FAX: (805) 541-8459
San Luis Obispo, CA 93401
SECTION II: INGREDIENTS AND HAZARDS
.
13
Ozone, CAS No. 10028-15-6: NIOSH RTECS No. RS8225000
TWA: 0.1 ppm (0.2 mg/m
Category 1: Local Irritant
Peak Exposure Limit: 0.2 ppm
5 min momentary value, 8 per shift
3
)
3
)
Other Designations: Triatomic oxygen: CAS No. 10028-15-6, NIOSH RTECS No. RS8225000
SECTION III: PHYSICAL DATA
Boiling Point: . . . . . . .
Vapor Pressure: . . . . .
Vapor Density (
Solubility in Water: . . .
AIR = 1):
-169 F
>1 ATM
1.6
0.49 ml @ 32 F (0 C),
3 ppm @ 20 C
Appearance and Odor: Colorless to blue gas (greater than -169 F): characteristic odor often associated with electrical sparks or
lightning in concentrations of less than 2 ppm and becomes disagreeable above 1-2 ppm. CAUTION: Olfactory fatigue develops
rapidly, so do not use odor as a preventative warning device.
Melting Point: . . . . . . . .
% Volatile by Volume: . .
Molecular Weight: . . . . .
pH: . . . . . . . . . . . . . . . .
Critical Temperature: . .
-315.4 F (-193 C)
100%
48 Grams/Mole
Not Listed
10.22 F (-12.1 C)
SECTION IV: FIRE AND EXPLOSION HAZARD DATA
Flash Point: . . . . . . . .
Extinguishing Media: .
Special Fire Fighting Procedures: Wear a self contained breathing apparatus with full face pieces operated in a pressure-
demand or other positive-pressure mode.
Unusual Fire/Explosion Hazards: Decomposition of ozone into oxygen gas, (O
Nonflammable
Use large amounts of water spray or fog to put out fires involving ozone. Use appropriate fire-fighting
techniques to deal with surrounding material.
), can increase strength of fire.
2
SECTION V: REACTIVITY DATA
Stability: Ozone is not stable. Hazardous polymerization cannot occur.
Chemical Incompatibilities: Ozone is chemically incompatible with all oxidizable materials, both organic and inorganic.
Conditions to Avoid: Ozone is unstable at room temperatures and spontaneously decomposes to oxygen gas. Avoid ignition
sources such as heat, sparks, and open flame. Keep away from strong reducing agents and combustible materials such as
grease, oils, and fats.
Products of Hazardous Decomposition: Ozone spontaneously decomposes to oxygen gas, even at room temperatures.
4-0697_ Rev.C
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
14
SECTION VI: HEALTH HAZARD DATA
Carcinogenicity: Ozone is not listed as a carcinogen by the NTP, IARC, or OSHA.
Primary Entry: Inhalation
Target Organs: Respiratory system, eyes, blood.
Summary of Risks: There is no true threshold limit and so no exposure (regardless of how small) is theoretically without effect
from ozone’s strong oxidative ability. Ozone passes straight to the smallest bronchioles and alveoli and is not absorbed by
mucous membranes along the way. Initial small exposure may reduce cell sensitivity and/or increase mucous thickness
producing a resistance to low ozone levels. Short exposure to 1-2 ppm concentrations causes headache as well as irritation to
the respiratory tract. but symptoms subside when exposure ends. High concentrations of ozone produce severe irritation of the
eyes and respiratory tract. Exposure above the ACGIH/OSHA limits produce nausea, chest pain, coughing, fatigue, reduced
visual acuity, and pulmonary edema. Symptoms of edema from excessive exposure can be delayed one or more hours.
Inhalation of >20 ppm for an hour or more (>50 ppm for 1/2 hour) can be fatal.
Acute Effects: Acute damage from ozone appears to be mainly from its oxidizing effect on contact with tissue.
Chronic Effects: Respiratory disease. Deleterious effects on lungs and acceleration of tumors have been reported.
Medical Conditions Generally Aggravated by Long-Term Exposure: History of respiratory or heart disorders.
First Aid: Remove from ozone containing air, get prompt medical help*, administer oxygen if necessary.
Eye Contact - Gently lift eyelids and flush eyes continuously with flooding amounts of water for 15 minutes or until transported to a
medical facility*.
Inhalation - Remove exposed person to fresh air, support breathing, administer humidified oxygen as needed, get medical help*.
Ingestion - Highly unlikely since ozone is a gas until -169 F,
* GET MEDICAL ASSISTANCE = APPROPRIATE IN-PLANT, PARAMEDIC, or COMMUNITY. Get prompt medical assistance for
further treatment, observation, and support after first aid.
SECTION VII: PRECAUTIONS FOR SAFE HANDLING AND USE
Steps to be Taken in Case of Spill/Leak:
1. Discontinue production
2. Isolate and vent area
3. Immediately notify personnel
4. Deny entry
5. Follow applicable OSHA regulations
Disposal: Provide ventilation to dilute and disperse small amounts of ozone (below OSHA PELs) to outside atmosphere. Follow
federal, state, and local regulations.
Handling/Storage Precautions: Ensure proper personnel training and establish emergency procedures.
Chemical Name DISSOLVED OZONE GAS IN WATER 0 TO 2 PPM
Product Description AQUEOUS SOLUTION OF OZONE DISSOLVED IN POTABLE WATER
D.O.T. Shipping
Classification
NON REGULATED
I PHYSICAL DATA
Boiling Point 212 F Freezing Point 32 F
Specific Gravity 1.0 Solubility in Water COMPLETE
Evaporation Rate APPROX 1 Physical Form LIQUID
Appearance & Odor COLORLESS (CLEAR) WATER WITH FRESH, ASEPTIC ODOR
II HAZARDOUS INGREDIENTS
MATERIAL HAZARD CAS # % BY WT ACGIH TLV OSHA PEL
None
III FIRE AND EXPLOSION HAZARD DATA
Flash Point NA Method NA Auto Ign. Temp. NA
Flammable Limits in
Air
Extinguishing Media
Unusual Fire &
Explosion Hazards
Special Fire Fighting
Procedures
NON APPLICABLE Lower NA Upper NA
NON APPLICABLE
NONE
NONE
4-1444-01_Rev.C
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
16
Page 2 of 3
Material Safety Data Sheet Cont.
Product NameAQUEOUS OZONE SOLUTION
IV HEALTH HAZARD DATA
Threshold Limit Value NOT DETERMINED
Route of Exposure Inhalation Ingestion Skin Eye Not Hazardous
Eye Contact Hazard
Ingestion Hazard
Inhalation Hazard
Skin Contact Hazard
Skin Absorption Hazard
Effects of Acute
Exposure
Effects of Chronic
Exposure
If exposure to water containing aqueous solution of ozone causes irritation to eyes, flush eyes with
Eye Contact
Skin Contact
Inhalation
plenty of clean, ozone free, running water for at least 15 minutes, lifting the upper and lower lids
occasionally. Remove contact lenses if worn. Seek medical attention if irritation persists.
Not likely to become irritated unless repeatedly exposed to large volumes of material. If irritation
develops, rinse affected area with ozone free potable water. If irritation continues seek medical
advice.
Inhalation of mists could lead to irritation of lungs. If symptoms develop, move individual away from
exposure and into fresh air. If symptoms persist, seek medical attention.
Exposure may cause mild eye irritation, but is not expected.
Not Hazardous
Inhalation is not likely to be a primary route of exposure but could become irritating if
aerosols are exposed to individual for extended period of time.
No skin irritation is expected from short term exposure.
No published data indicates this product is absorbed through the skin.
Mild skin or eye irritation.
Repeated exposure of the skin to concentrated product should be avoided to prevent
irritation and drying of the skin.
V EMERGENCY AND FIRST AID PROCEDURES
Ingestion
Incompatibility
(Materials to Avoid)
Conditions
to Avoid
Hazardous
Decomposition
Stability STABLE UNSTABLE Hazardous Polymerization MAY OCCUR WILL NOT OCCUR
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
NA
Natural rubber (may degrade, or “dry”, rubber components over extended periods of exposure)
NONE KNOWN
NONE
VI REACTIVITY DATA
4-1444-01_Rev.C
Material Safety Data Sheet Cont.
Product NameAQUEOUS OZONE SOLUTION
VII SPILL OR LEAK PROCEDURES
Steps To Be Taken
If Material Is Released
Or Spilled
NONE
17
Page 3 of 3
Waste Disposal
Method
DISPOSE OF THE SAME AS POTABLE RINSE WATER
VIII SPECIAL PROTECTIVE INFORMATION
Respiratory Protection
(Specify Type)
Local
Ventilation
Exhaust
Mechanical
(general)
Protective Gloves NOT REQUIRED
Eye Protection NOT REQUIRED
Other Protective
Equipment
Precautionary
Labeling
NOT REQUIRED FOR NORMAL USE OF THIS PRODUCT
PREFERABLE Special NA
OK Other NA
NOT REQUIRED
Certified testing of DEL Ozone systems by NSF (National Sanitation Foundation) has shown that
under normal conditions of use, aqueous solutions containing low levels of ozone gas dissolved in
potable water do not present a safety hazard when contact to the individual is incidental. When
used in a room with normal ventilation, levels of ozone gas being released into the air have been
shown by NSF to be well below the periodic exposure levels established by OSHA for worker
safety through the use of DEL’s ozone management technology.
IX SPECIAL PRECAUTIONS
Precautions To Be
Taken In Handling
This material safety data sheet is provided as an information resource only. It should not be taken as a warranty or representation for which the preparer
assumes legal responsibility. While we believe the information contained herein is accurate and compiled from sources believed to be reliable, it is the
responsibility of the user to investigate and verify its validity. The buyer assumes all responsibility of using and handling the product in accordance with
applicable federal, state, and local regulations.
Aqueous solutions of ozone in potable water should not be sprayed as an aerosol (i.e. >20psi) to
avoid releasing higher levels of ozone gas into the work area. The decay rate of ozone gas is a
function of temperature and exposure to organic material. Certified testing has shown that when
ozone gas has been properly dissolved in ambient temperature (or colder (33 – 70 °F)) potable
water at a level not exceeding 2 mg/l (ppm) using DEL’s ozone management technology, the rate
at which ozone is released from the water as ozone gas is below the PEL established for gaseous
ozone.
Rev. Date 03/26/12
4-1444-01_Rev.C
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
18
Notes
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
Notes
19
INTELLIZONE™ COMMERCIAL OZONE GENERATOR Installation and User's Guide
This document is subject to change without notice.
1620 Hawkins Ave., Sanford, NC 27330 • (919) 566-8000
10951 West Los Angeles Ave., Moorpark, CA 93021 • (805) 553-5000
All Pentair trademarks and logos are owned by Pentair, Inc. Pentair Aquatic Systems™ and IntelliZone™ are
trademarks and/or registered trademarks of Pentair Water Pool and Spa, Inc. and/or its affiliated companies in the
United States and/ or other countries. Unless expressly noted, names and brands of third parties that may be used in
this document are not used to indicate an affiliation or endorsement between the owners of these names and brands
and Pentair Water Pool and Spa, Inc. Those names and brands may be the trademarks or registered trademarks of
those third parties. Because we are continuously improving our products and services, Pentair reserves the right to
change specifications without prior notice. Pentair is an equal opportunity employer.
*521810*
P/N 521810 Rev A - 6/4/12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.