Pennco 15096HWD, 15045HWD Installation Guide

SERIES 15B CAST iRON GAS FIRED BOILERS
FOR FORCED HOT WATER
MODEL NUMBERS: 15045,15070,15096,
15120,15145,15175, 15195,15245,15295
PENNCO BOILERS 85 Middle Rd. Dunkirk. NY 14048 Ph: (7161 366-5500
Fax: (7161 366-1209
www. ecrinternational.com
R International Brand Ic_/
An/SO 9001-2000 Certified Company
F N 1305026, Rev. 1.1 [03/05]
P/N# 1305026, Rev 1 1 [03/05] Printed in USA. Made In USA
Safety Symbols and Warnings 3 Ratings and Data 4
Installation Procedure 5
Ventilation and Combustion Air 6 Connecting Supply and Return Piping 8
Vent Installation 10 Vent System Modification 10
Vent Damper Installation and Instructions 11 Connecting Gas Service 12 Electrical Wiring 12
Thermostat Installation 12 Lighting Instructions 15
Normal Sequence of Operation 17 General Instructions 18
Checking Gas Input Rate to Boiler 20 Boiler Exploded View 21 Replacement Parts Lists 22
Conversion Kits 27
MPORTANT: Read the following mstructlon_
OMPLETELY before mstalhngll
1. Keep boilerarea clear and free from combus- tible materials, gasoline and other flammable vapors and liquids.
2. DO NOT obstruct air openings to the boiler
room.
3. Modification, substitution or elimination
of factory equipped, supplied or specified components may result in property damage,
personal injury or the loss of life.
4. TO THE OWNER - Installation and service of this boiler must be performed by a quali-
fied installer.
KEEP THIS MANUAL NEAR BOILER )
, RETAIN FOR FUTURE REFERENCE
The following defined symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels
nediCates an imminently hazardous situation_
hich, if not avoided, WiLL result in death or I
dicates a potentially hazardous situation I
hich, if not avoided, COULD result in death I
serious injury, j
5. TO THE INSTALLER - Leave all instructions with the boiler for future reference.
6. When this product is installed in the Corn= monwealth of Massachusetts the installation
must be performed by a Licensed Plumber or
k,Licensed Gas Fitter.
All installations of boilers and venting should be done only by a qualified expert and in accordance with the appropriate Pennco manual. Installing or venting a boiler or any
other gas appliance with improper methods or materials may result in serious injury or death due to fire or to asphyxiation from poisonous gases such as carbon monoxide
which is odorless and invisible.
_J
J
i
dicates a potential hazardous situation I
hich, if not avoided, MAY result in minor or I
oderate injury. It may also be used to alert I
gainst unsafe practices, j)
(if _" ,,_ ,,
- o¢®@
C S A Certified Tested For 100 LBS
For Natural Gas Or Propane ASME
/_,,orkln g Pressure
15045 45,000 37,000 32,000 243 1 15 15070 70,000 57,000 50,000 365 2 15 15096 96,000 79,000 69,000 481 2 30 15120 120,000 98,000 85,000 603 3 30 15145 145,000 119,000 I03,000 7t9 3 30
15175 175,000 141,000 I23,000 829 4 30 31 49 7.2 80.5% 80% 15195 195,000 157,000 137,000 957 4 30 30 47 7.2 80.5% 80% 15245 245,000 197,000 171,000 1,t89 5 30 30 47 8.8 80.5% 80% 15295 295,000 237,000 206,000 1,368 6 60 30 47 I0.4 80.5% 80%
HAll boilers are design certified for installation on noncombustible floor.
--For installation on combustible floors use combustible floor kit
--Recommended chimney height 20 feet In special cases where conditions permit, chimney height may be reduced to 10 feet Refer to the latest revision of NFGC part 11.
--Electric service to be 120 Volts, 15 Am ps, 60 Hz
--The MEA number for the this boiler is 39-86-E Vol VIII
§ For elevations above 2000 feet, ratings should be reduced at a rate of 4% for each 1000 feet above sea level 1 Base on 170° temperature in radiators
:1:Tank sized for non-ferrous baseboard or radiant panel systems. Increase size for cast iron baseboard and radiation
--Net I=B=R ratings include 15% allowance for normal piping and pick-up load Manufacturer should be consulted on installations having other than normal piping and pick-up requirements
** For equivalent square feet of radiation, divide I=B=R output by 150.
STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, High Limit Control, Vent Damper Relay, Theraltimeter Gauge, Circulator With Return Piping To Boiler, Main Gas Burners, Combination 24 Volt Gas Control dnciudes Automatic Gas Valve, Gas Pressure Regulator, Automatic Pilot, Safety Shutoff, Pilot Flow Adjustment, Pilot
Filter), A.S.M.E. Relief Valve, Drain Cock, Spill Switch, Rollout Switch, Automatic Vent Damper Not Shown Are: Wiring Harness, Thermocouple, Nondinting Safety Pilot. OPTIONAL EQUIPMENT: Intermittent Electbc Ignition PHot System.
"A"
.....kB" _
"C"
30 47 2.4 82% 80% 33 50 4.0 82% 80% 30 47 4.0 82% 80% 31 49 5.6 82% 80%
30 47 5.6 82% 80%
'_D"
25 5/16"
"Z'
. ,1 d ,
.oi
4"
5j ......
-o i
col
1 ]/4IIREURN
%
t
U U
15045 ½" 11.250 5.625 4.000 27.125 20.469 4.969 1¼" 15070 ½" 15.125 7.562 5.000 28.125 20.969 4.969 1¼" 15096 ½" 15.125 7.562 5.000 28.125 20.969 4.969 1¼" 15120 ½" 19.000 9.500 6.000 29.125 21.469 5.469 1¼" 15145 ½" 19.000 9.500 6.000 29.125 21.469 5.469 1¼"
15175 ½" 22.875 11.438 7.000 30.125 21.969 5.969 1¼" 15195 ½" 22.875 11.438 7.000 30.125 21.969 5.969 1¼" 15245 ¾" 26.750 13.375 8.000 31.125 22.469 6.969 1¼" 15295 ¾" 30.625 15.312 9.000 32.125 22.969 8.969 1¼"
* Propane Gas Inlet (All Units) 1/2"
1 1/4"
t
-oi
1. The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the latest revision of the National Fuel Gas Code, ANSI Z223. (Available from the American Gas Association, 8501 E. Pleasant
Valley Road, Cleveland, Ohio 44134). Reference should also be made to local gas utility regulations
and other codes in effect in the area in which the installation is to be made. When installed in Canada:
The latest revision of the CAN 1-B 149.1 and/or B 149.2
Installation Codes for Gas-Burning Equipment and/or
local codes.
2. Where required bythe authority having jurisdiction, the installation must conform to American Society
of Mechanical Engineers Safety Code for Controls and Safety Devices ForAutomaticatly Fired Boilers,
ANSI/ASME No.CSD-1.
3. This boiler series is classified as a Category 1and the vent installation shall be in accordance with Part
7 of the National Fuel Gas Code noted above when installed in the United States. In Canada refer to
the CAN1-B149.1 and or B149.2 Installation Codes for Gas-Burning Equipment. Also refer to applicable provisions of the local building codes.
4. This boiler has met safe lighting and other performance criteria with the gas manifold and control
assembly on the boiler per the latest revision of ANSI Z21.13/CGA 4.9.
5. The boiler shall be installed such that the gas ignition system components are protected from
water(dripping, spraying, rain, etc.)during appliance operation and service, (circulator replacement, condensate trap, control replacement, etc.).
7. Allow 24 inches at the front and right side for servicing and cleaning.
8. When installed in a utility room, the door shoutd be
wide enough to allow the largest boiler part to enter, or to permit replacement of another appliance such
as a water heater.
9. FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY - For installation on combustible
flooring special base part no. 325-2-8.00 must be
used. The boiler can not be installed on carpeting. Minimum clearances to combustible construction
are:
TOP ................................................... 18 IN.
FRONT ...................................... ALCOVE *
FLUE CONNECTOR ........................... 6 IN.
REAR ................................................... 8 IN.
CONTROL SIDE .................................. 9 IN.
OTHER SIDE ....................................... 3 IN.
NOTE: Greater clearances for access should
supersede fire protection clearances.
* The definition of an Alcove is a three sided space with
no wall in front of the boiler. TheANSI standard for an alcove is 18 inches from the front of an appliance to
the leading edge of the side walls as shown below.
MINIMUM CLEARANCES TO COMBUSTIBLE CON-
STRUCTION (AS SEEN FROM ABOVE)
6. Locate boiler on level, solid base as near the chimney as possible and centrally located with respect
to the heat distribution system as practical.
_ 9"_ 3"
18"
1
COMBUSTION AIR REQUIREMENTS (Minimum Square Inches Requirement)
i iii ,ii!o iiiB
15045 I00 10 I3 25 15070 I00 15 I9 38
15096 I00 20 25 50 15120 I25 25 32 63 15145 I50 30 38 75
15175 I75 35 44 88 15195 200 40 50 I00
15245 250 50 63 I25 15295 300 60 75 150
* A space whose volume is not less than 50 cubic feet per 1000 BTU per hour of all appliances installed in that space (cubic feet of space = height x width x length)
** A space whose volume is less than 50 cubic feet per 1000 BTU per hour of a!t appliances installed in that space (cubic feet of space = height x width x length)
1. Ventilation of the boiler room must be adequate to provide sufficient air to properly support combustion per the latest revision of the National Fuel Gas Code,
ANSI Z223.1 section 5.3.
i c,R
i3
4. When air for combustion and ventilation is from inside buildings, the confined space shall be provided
with two permanent openings, one starting 12 inches from the top and one 12 inches from the bottom of the enclosed space. Each opening shall have a minimum free area of I square inch per 1000 BTU per hour of
the total input rating of all appliances in the enclosed space, but must not be less than 100 square inches. These openings must freely communicate directly with other spaces of sufficient volume so that the
combined volume of all spaces meets the criteria
for an unconfined space. (Figure 1)
ANSI Z223.1 section 1.7), the boiler area should be considered as a confined space.
In this case air for combustion and ventilation
shall be provided according to Step 5. Ifthere
is any doubt, install air supply provisions in
accordance with the latest revision of the
National Fuel Gas Code.
3. When a boiler is installed in an unconfined space in a building of unusually tight
construction, air for combustion and ventilation must be obtained from outdoors
or from spaces freely communicating with the outdoors. A permanent opening or openings having a total free area of not less than 1
square inch per 5000 BTU per hour of total
input rating of all appliances shall be provided. Ducts may be used to convey makeup air
from the outdoors and shall have the same cross-sectional area of the openings to which
they are connected.
I FIGURE 1 !
2. When a boiler is located in an unconfined space in a building or conventional construction frame, masonry or metal building, infiltration normally is adequate to provide air for combustion and ventilation. However, if the equipment is located in a building of unusually tight construction (See the National Fuel Gas Code,
5. When the boiler is installed in a confined space and all air is provided from the outdoors the confined
space shall be provided with one or two permanent openings according to methods A or B. When ducts
are used, they shall be of the same cross sectional area as the free area of the area of the openings
to which they connect. The minimum dimension of
rectangular air ducts shall be not less than 3 x 3 inches or 9 square inches.
A. When installing two openings, one must
commence within 12 inches from the top and
the other within 12 inches from the bottom of the enclosure. The openings shall communicate
directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. One of the following methods must
be used to provide adequate air for ventilation and combustion.
1. When directly communicating with the
outdoors, each opening shall have a minimum
free area of 1 square inch per 4,000 BTU per
hour of total input rating of all equipment in the enclosure. (Figure 2)
3. If horizontal ducts are used, each opening and duct shall have a minimum free area 1
square inch per 2,000 BTU per hour of total input rating of all appliances in the enclosed space. (Figure 4)
CHIMNEY
OR
GAS VENT
CH MNEY
OUTLET/ J
AIR
VENTFIPE
............... VENTLATIOn
VENTLATON LOUVERS
(EACH ENDQF ATTIC:}
LOUVEnSFort
\
IFGORE21
2. When communicating with the outdoors by means of vertical ducts, each opening shall
have a minimum free area of 1 square inch per
4,000 BTU per hour of total input rating of all
appliances in the enclosed space. (Figure 3)
VFNT LAT ON LOUVERS
(EACH END OF ATTIC} ....
CHIMNEY
i y" i_ii
".......ii ii
i!i}!}i}i}iEJ}i:}iii!iiiiii}!iiiiiiii¸:}i!}i}i}i}i:}ii{¸i¸i!!i¸ii! iiii!i!!iiiiiE!i}iiikfi!!¸U}:}i!}:::i
B. One permanent opening, commencing within 12 inches of the top of the enclosure, shall be permitted where the equipment has clearances
of at least 1 inch from the sides, 1 inch from the
back, and 6 inches from the front of the boiler.
The opening shall directly communicate with the outdoors or shall communicate through a
vertical or horizontal duct to the outdoors or
spaces (crawl or attic) that freely communicate
with the outdoors. The openings must have a
minimum free area of I square inch per 3000 Btu per hour of the total input rating of all equipment
located in the enclosure. The free area must be no less than the sum of the areas of all vent
connectors in the confined space.
[]ZI } i IZ]_ZZZIiZiZZZI i IZ]IZZZILZI i !
6. In calculating free area using louvers, grilles or
screens for the above, consideration shall be given to their blocking effect. Screens used shall not be
smatter than 1/4 inch mesh. If the free area through
a design of louver or grill is known, it should be used in calculating the size opening required to provide
the free area specified. If the design and free area
is not known, it may be assumed that wood louvers
will have 20-25% free area and metal louvers and grilles will have 60-75% free area. Louvers and grilles
should be fixed in the open position or interlocked with the boiler so they are opened automatically during the boiler operation.
MPORTANT: Circulators in the foltowing"_
tustrations are mounted on the system supply I ide, but mounting on the system return side is I
!soaccep!ab!ep! e: )
1. Connect supply and return piping as suggested in Figure 5 when the boiler is used in connection with
refrigerated systems•
P_ESSU_E
/ VALVE
G_TE
,,VALVE
_'_tE
i
,,_TE
:E:
vA,_ ,
E _SCN
5. Hot water boilers and system must be filled with
water and maintained to a minimum pressure of 12
pounds per square inch.
6. Bypass piping is an option which gives the ability
to adjust the supply boiler water temperature to fit the system or the condition of the installation• This
method of piping, however, is not typically required
for baseboard heating systems• Typical installations where bypass piping is used are as follows:
A. This method is used to protect boilers from
condensation forming due to low temperature return water• Generally noticed in large converted
gravity systems or other large water volume
systems• (Figure 6)
BYPASS PIPING
suPP
FIGURE 5 I
A. The chilled medium MUST BE PIPED IN PARALLEL with the boiler•
B. Use appropriate valves to prevent the chilled medium from entering the heating boiler•
- During heating cycle open valves A and B, close valves C and D.
- During cooling cycle, open valves C and D, close valves A and B.
C. Maintain a minimum clearance of one inch to hot water pipes•
2. When the boiler is connected to heating coils located in air handling units where they may be exposed to
refrigerated air circulation, the boiler piping system
MUST BE supplied with flow control valves or other
automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
........' :i_ii
_ESSU_E
,'_V,kp,'E
.... :ii ....
::. , :: ,
B
_ALTE C _
PUROE V_LVE
IF'GURE01
B. These methods are used to protect systems using radiant panels and the material they are encased in from high temperature supply
water from the boiler and protect the boiler from
condensation. (Figures 7-8)
NOTE#l: When using bypass piping, adjust
vatvesAand B until desired system temperature
is obtained•
NOTE#2: Bypass loop must be same size piping as the supply and return piping.
3. Hot water boilers installed above radiation level must be provided with a low water cut-off device•
4. When a boiler is connected to a heating system
that utilizes multiple zoned circulators, each circulator
must be supplied with a flow control valve to prevent
gravity circulation•
7. Installation using circulators and zone valves are shown in Figures 9-10. Forfurther piping information refer to the I=B=R Installation and Piping Guide•
MIXING VALVE PIPING
FL
S,STEr4
, T=_,IPE_£TURE
S,sUC_=
=r,ESSURE
_EDU,S,r_a
GATE
,h,ALVE
4; -.
,_L',
"/AL_'E
i
PRIMARY SECONDARY PIPING WITH BYPASS
C_RCU_£TC,_
S_ST_4
M_x _ TE_IPERATURE
,_LVE
_LC,W V£LVE _,
a£uaE
_L,'E
O_E
P ESSdRE R_DUO O
VA:,
[ FIGURE 7]
HOT ¢_/_TER INLET OJTLET x
THER /_L TR/_p
qRING FOR THER; O TAT
Pur!P "_O TROL
(OLD %ATER
PURaE _1
BOILER INSTALLATION WITH CIRCULATORS
FLO'A
CONTRC L
/_L FS
] RELEFVALVE
PURG V_LvE
> i
T/_NK CR
S_STEM RETgRN
PrPiNG
t FIGURE 9 J
:4:#.
FEED
,',ATER
GATe /VALVE
/VALVE
FIGURE 8 ]
PRESSiJRL
REDdCING
ilia'ZZZZZ£
pL_iRC_E ,_
V£LVE
PURGE
HOT CATER OUTLET
THERMAL TR#P
f\
CRNG FOR
THERMOSTAT / PUMP CONTROL
BOILER INSTALLATION WITH ZONE VALVES
COLD W_TER
INLET
PURGE
'/_L' E
T_NK ZONE
,_L'E
RELIEF /_L,E
S_'3TEM
RETdRN PIPING
FIGURE I0]
C:_R ,!
FEED
(,_TER
PRcSSiJRE
GATe /VALVE
/VALVE
REDUCING
/
CHECK
VALVE [ \ /
EXDA 51ON
TANK
ill
PURGE ALE
Loading...
+ 18 hidden pages