Installation and Operation Instructions Document 1195
A subsidiary ofCorporationBRADFORD WHITE
Heating Systems Company
Installation and Operation
Instructions for
™
Pennant
Hydronic Boiler
Model PNCH
Water Heater
Model PNCV
Sizes 200, 300, 400
FOR YOUR SAFETY:This product must be installed and serviced by a professional service technician,
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in flue gases which could cause serious injury, property damage, or
death. Improper installation and/or operation will void the warranty. For indoor installations, as an
additional measure of safety, Laars strongly recommends installation of suitable Carbon Monoxide
detectors in the vicinity of this appliance and in any adjacent occupied spaces.
WARNING
If the information in this manual is not
followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from
a nearby phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call
the fire department.
Installation and service must be performed
by a qualified installer, service agency, or gas
supplier.
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion ou
pour éviter tout dommage matériel, toute blessure
ou la mort.
Ne pas entreposer ni utiliser d’essence ni d’autres
vapeurs ou liquides inflammables dans le voisinage
de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous
servir des téléphones dansle bâtiment où vous
trouvez.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié ou
par le fournisseur de gaz.
9.1 General Information....................................... 36
9.2 Parts List........................................................ 36
Pennant 200, 300, 400
Page 3
SECTION 1.
General Information
USING THIS MANUAL – Because the
Pennant Boilers and Pennant Water Heaters are
identical appliances, with the exception of materials
of manufacture, labels and ultimate use application,
this manual provides information for the proper
installation, operation and maintenance of both
products. Where differences exist between the
application of the appliances and their operation,
the sections pertinent to only one appliance or the
other will be so identied.
In the Commonwealth of Massachusetts, this
appliance must be installed by a licensed plumber or
gas tter.
WARNING
To minimize the risk of electric shock, fire or other
hazards which could result in property damage,
injury, or death. The Pennant hydronic, boiler or
water heater must be installed in accordance with
the procedures detailed in this manual, or the Laars
Heating Systems warranty may be voided. The
installation must conform to the requirements of
the local jurisdiction having authority, and, in the
United States, to the latest edition of the National
Fuel Gas Code, ANSI Z223.1/NFPA54. In Canada,
the installation must conform to the latest edition
of the Natural Gas and Propane Installation Code,
CSA B149.1 and/or applicable local codes. Where
required by the authority having jurisdiction, the
installation of Pennant appliances must conform
to the Standard for Controls and Safety Devices
for Automatically Fired Boilers, ANSI/ASME
CSD-1. Any modifications to the boiler, its gas
controls, or wiring may void the warranty. If field
conditions require modifications, consult the factory
representative before initiating such modifications.
1.1 Introduction
This manual provides information necessary for
the installation, operation, and maintenance of Laars
Heating Systems’ Pennant copper tube appliances,
sizes 200-400 MBTU/hr (larger models are covered
in a separate manual). Read it carefully before
installation.
AVERTISSEMENT
Afin de réduire au minimum les risques de
commotion électrique, de feu ou d’autre nature,
qui pourraient causer des dommages matériels,
des blessures ou des accidents mortels, les
chaudières à eau chaude ou les chauffe-eau
Pennant doivent être installés conformément aux
directives détaillées contenues dans ce manuel, à
défaut de quoi la garantie fournie par Laars Heating
Systems serait annulée. L’installation doit être
conforme aux exigences de la réglementation locale
en vigueur et, aux États-Unis, à l’édition la plus
récente du Natural Fuel Gas Code (Code pour le
gaz combustible naturel) ANSI Z223.1/NFPA54. Au
Canada, l’installation doit respecter les exigences
de la plus récente édition du Code d’installation du
gaz naturel et du propane CSA B149.1, et/ou des
codes locaux de construction en vigueur. Lorsque
la réglementation locale l’exige, l’installation des
appareils électroménagers Pennant doit respecter
les exigences du Standard for Controls and Safety
Devices for Automatically Fired Boilers (Code pour
les équipements de commande et de sécurité des
chaudières à combustion automatique), ANSI/
ASME CSD-1. Toute modification apportée à la
chaudière, aux régulateurs de gaz ou au câblage,
peut compromettre la garantie. Si certaines
conditions particulières rendent des adaptations
nécessaires, consulter un représentant du fabricant
avant d’entreprendre ces modifications.
All application and installation procedures
should be reviewed completely before proceeding with
the installation. Consult the Laars Heating Systems
factory, or local factory representative, with any issues
or questions regarding this equipment. Experience
has shown that most operating issues are caused by
improper installation.
The Pennant appliance is protected against over
pressurization. A pressure relief valve is tted to all
appliances. It is installed on the outlet header, at the
water outlet of the appliance.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P N C A C 1
SERIES
P N C
USAGE
H
V
SIZE
0 2 0 0
0 3 0 0
0 4 0 0
FUEL
N
P
ALTITUDE
A
LOCATION
C
FIRING
MODE
C ON-OFF
K TWO-STAGE
REVISION
1
HEAT
EXCHANGER
B
C
N
P
OPTIONS
CODE
X
L
PUMP
OPTIONS
X
N
S
Page 4
Pennant 200, 300, 400
Page 5
LAARS Heating Systems
IMPORTANT: The inlet gas pressure to the appliance
must not exceed 13 in. w.c. (3.2 kPa).
All installations must be made in accordance
with:
1) In the U.S., the " National Fuel Gas Code "ANSI
Z223.1/NFPA54, Latest Edition and all applicable
local codes as required by the Authorities Having
Jurisdiction (AHJ), or
2) In Canada, the "Natural Gas and Propane
Installation Code", CSA B149.1, latest edition and all
applicable local codes as required by the AHJ.
All electrical wiring is to be done in accordance with:
1). In the U.S., the "National Electrical Code" (NEC),
ANSI/NFPA 70, latest Edition and all applicable local
codes as required by the AHJ, or
2). In Canada, the “Canadian Electrical Code - Part
1”, CSA STD. C22.1 and all applicable local codes as
required by the AHJ.
This appliance must be electrically grounded in
accordance with the applicable codes and standards
referenced above.
1.2 Model Identication
Consult the rating plate on the unit. The
following information describes the model number
structure.
Model Character Designation
16 Pump Options
X = No Pump
N = Pump mounted, normal pump
S = Pump mounted, soft water pump (PNCV only)
1.3 Warranty
Laars Heating Systems’ Pennant appliances are
covered by a limited warranty. The owner should ll
out the warranty registration card and return it to Laars
Heating Systems.
All warranty claims must be made to an
authorized Laars Heating Systems representative or
directly to the factory. Claims must include the serial
number and model (this information can be found
on the rating plate), installation date, and name of
the installer. Shipping costs are not included in the
warranty coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on
the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be
led with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.
B = Glass-lined CI / copper / brz trim (std. PNCV)
C = Glass-lined cast iron / copper (std. PNCH)
N = Glass-lined cast iron / cu-nickel
P = Glass-lined cast iron / cu-nickel / brz trim
15 Option Code
X = Standard unit
L = Low temperature control (std. PNCV)
1.5 Locating the Appliance
The appliance should be located to provide
clearances on all sides for maintenance and inspection.
It should not be located in an area where leakage of
any connections will result in damage to the area
adjacent to the appliance or to lower oors of the
structure.
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
The appliance is design certied by CSAInternational for installation on combustible ooring;
in basements; in closets, utility rooms or alcoves.
Pennant Boilers or Water Heaters must never be
installed on carpeting. The location for the appliance
should be chosen with regard to the vent pipe lengths
and external plumbing. The unit shall be installed such
that the gas ignition system components are protected
from water (dripping, spraying, rain, etc.) during
operation and service (circulator replacement, control
replacement, etc.). When vented vertically, the Pennant
must be located as close as practical to a chimney or
outside wall. If the vent terminal and/or combustion
air terminal terminate through a wall, and there is
potential for snow accumulation in the local area, both
terminals should be installed at an appropriate level
above grade such that blockage of the terminal from
accumulated debris or precipitation is prevented.
Left Side12.52461
Right Side12.52461
Top12.51230
Back12.512**30**
Front12.53691
Vertical
(Category 1)
Vent
Horizontal
(Category 3)
Vent
*1" (2.5 cm) when b-vent is used.
**When vent and/or combustion air connects to the back,
recommended clearance is 36" (91cm).
Vent Collar
Size
incmincmincmftm
Required
Clearance From
Combustible Material
inchescminchescm
6*15.2*
per UL 1738 venting
system supplier's
instructions
Table 2. Clearances.
Horizontal
Vent Pipe
Diameter
Table 1. Horizontal Vent / Combustion Air Parameters.
Recommended
Service Access
Clearance
Intake
Air Collar
& Pipe
Diameter
Max. Pipe
Length
Max. No.
of Elbows
Side Vent
Terminal
Part Number
1.8 Locating Appliance for Correct
Horizontal Vent/Ducted Air Distance
From Outside Wall
The forced draft combustion air blower in the
appliance has sufcient power to pull air and vent
properly when the guidelines for horizontal air and
vent are followed (see Table 1).
NOTE: On some models, the vent collar size is
larger than the size of the vent pipe that can be
used. Vent collar size and horizontal pipe diameters
can be found in Table 1. The larger vent collar
size is to accommodate Category I (vertical) vent
systems.
NOTE: When located on the same wall, the
Pennant combustion air intake terminal must
be installed a minimum of 12" (30cm) below the
exhaust vent terminal and separated by a minimum
of 36 inches (91cm) horizontally.
The air intake terminal must be installed high
enough to avoid blockage from snow, leaves and other
debris.
The dimensions and requirements that are shown
in Table 2 should be met when choosing the locations
for the appliance.
1.6 Locating Pump-Mounted Water Heater
with Respect to Storage Tank(s)
For best results, a pump-mounted Pennant water
heater should be located within 15 feet (4.6m) of the
storage tank(s). The pump is sized for 30 feet (9.1m)
SECTION 2.
Venting and Combustion Air
WARNING
For indoor installations, as an additional measure
of safety, Laars strongly recommends installation of
suitable Carbon Monoxide detectors in the vicinity of
this appliance and in any adjacent occupied spaces.
of piping.
If the appliance must be installed with longer
piping runs, then larger diameter pipe or tubing may be
acceptable. Consult the factory for assistance.
1.7 Locating Pump-Mounted Boiler with
Respect to Return/Supply Header
For the best results, a pump-mounted Pennant
boiler should be located within 15 feet (4.6m) of the
Pour des installations intérieures, Laars
recommande fortement, comme mesure de sécurité
supplémentaire, l’installation de détecteurs de
monoxyde de carbone adaptés dans le voisinage
de l’appareil et dans chacune des pièces habitées
adjacentes.
AVERTISSEMENT
supply and return headers. The pump is sized for 30
feet (9.1m) of piping.
If the appliance must be installed with longer
piping runs, then larger diameter tubing may be
acceptable. Consult the factory for assistance.
2.1 Combustion Air
Pennant boilers and water heaters must have
provisions for combustion and ventilation air in
accordance with the applicable sections addressing
requirements for air for combustion and ventilation of
Side Wall
Combustion
Air Terminal
Part Number
Page 8
Pennant 200, 300, 400
Page 9
LAARS Heating Systems
the National Fuel Gas Code, ANSI Z223.1. In Canada,
the applicable sections of the Natural Gas and Propane
Installation Code (CSA B149.1) must be followed. In
all cases any and all applicable local installation codes
must also be followed.
A Pennant appliance may receive combustion
air from the space in which it is installed, or it can be
ducted directly to the unit from the outside. Proper
ventilation air must be provided in either case.
2.1.1 Combustion Air From Room
In the United States, the most common
requirements specify that the space shall communicate
with the outdoors in accordance with method 1 or 2,
which follow. Where ducts are used, they shall be of
the same cross-sectional area as the free area of the
openings to which they connect.
Method 1: Two permanent openings, one
commencing within 12 inches (30 cm) of the top
and one commencing within 12 inches (30 cm) of
the bottom, of the enclosure shall be provided. The
openings shall communicate directly, or by ducts,
with the outdoors or spaces that freely communicate
with the outdoors. When directly communicating
with the outdoors, or when communicating to the
outdoors through vertical ducts, each opening shall
have a minimum free area of 1 square inch per 4000
Btu/hr (5.5 square cm/kW) of total input rating of all
equipment in the enclosure. When communicating to
the outdoors through horizontal ducts, each opening
shall have a minimum free area of not less than
1 square inch per 2000 Btu/hr (11 square cm/kW) of
total input rating of all equipment in the enclosure.
Table 3 shows data for this sizing method, for each
Pennant model.
Method 2: One permanent opening, commencing
within 12 inches (30 cm) of the top of the enclosure,
shall be permitted. The opening shall directly
communicate with the outdoors or shall communicate
through a vertical or horizontal duct to the outdoors
or spaces that directly communicate with the outdoors
and shall have a minimum free area of 1 square inch
per 3000 Btu/hr (7 square cm/kW) of the total input
rating of all equipment located in the enclosure. This
opening must not be less than the sum of the areas of
all vent connectors in the conned space.
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform
to the requirements in the applicable codes listed
above.
In Canada, consult local building and safety
codes or, in absence of such requirements, follow
CSA B149.1, the Natural Gas and Propane Installation
Code.
Boiler
Model
20050323
30075484
400100645
*Net Free Area in Square Inches / Square cm
Area indicated is for one of two openings; one at oor level
and one at the ceiling, so the total net free area could be
double the gures indicated.
This chart is for use when communicating directly with the
outdoors. For special conditions and alternate methods, refer
to the latest edition of ANSI Z223.1.
Note: Check with louver manufacturers for net free area of
louvers. Correct for screen resistance to the net free area
if a screen is installed. Check all local codes applicable to
combustion air.
Table 3. Combustion Air Openings.
Square inchesSquare cm
Each Opening*
2.1.2 Intake Combustion Air
The combustion air can be taken through the
wall, or through the roof. When taken from the wall, it
must be taken from out-of-doors by means of the Laars
horizontal wall terminal (see Table 1). When taken
from the roof, a eld-supplied rain cap or an elbow
arrangement must be used to prevent entry of rain
water (see Figure 2).
Use single-wall galvanized pipe, per Table
4, for the combustion air intake (see Table 1 for
appropriate size). Route the intake to the heater as
directly as possible. Seal all joints with tape. Provide
adequate hangers. The unit must not support the
weight of the combustion air intake pipe. Maximum
linear pipe length allowed is 50 feet (15.2m). Three
elbows have been calculated into the 50-foot (15.2m)
linear run. Subtract 10 allowable linear feet (3.0m) for
every additional elbow used (see Table 1). When fewer
Figure 2. Combustion Air and Vent Through Roof.
Pennant 200, 300, 400
Page 9
than 3 elbows are used, the maximum linear pipe
length allowed is still 50 feet (15.2m).
Joint Sealing Permanent duct tape or aluminum tape
Table 4. Required Combustion Air Piping Material.
The connection for the intake air pipe is on the
lter box. The Pennant appliances may have venting
and combustion air ducting attached to the top or the
back. They are shipped with the connections at the
top. For attaching either or both pipes to the back,
the mounting anges are reversible by removing the
mounting screws and orienting the anges in the
desired position. Replace the screws after positioning
anges. Run a bead of silicone around the collar and
slide the pipe over the collar. Secure with sheet metal
screws.
In addition to air needed for combustion, air
shall also be supplied for ventilation, including all air
required for comfort and proper working conditions
for personnel. The Pennant loses less than 1 percent of
its input rating to the room, but other heat sources may
be present.
2.2 Venting
2.2.1 Vent Categories
Depending upon desired Pennant venting, it may
be considered a Category I or a Category III appliance.
In general, a vertical vent system will be a Category
I system. However, in rare instances, a Pennant’s
vertical vent system may be considered Category
III. In the U.S., the National Fuel Gas Code (ANSI
Z223.1), or in Canada the Natural Gas and Propane
Installation Code (CSA B149.1), denes a Category I
vent system, and includes rules and tables to size these
vent systems. If the Pennant’s vertical vent system
does not satisfy the criteria for Category I venting, it
must be vented as a Category III system.
All Pennant vent systems which discharge
horizontally (without the use of a power venter) are
considered Category III vent systems.
2.2.2 Category I Vent
When vented as a Category I appliance, the
vent system must conform to the National Fuel Gas
Code (ANSI Z223.1-Latest Edition) in the U.S., or in
Canada, to the Natural Gas and Propane Installation
Code (CSA B149.1 latest edition). The vent system
must be sized and installed for a Category I FanAssisted Appliance.
If chimney height is greater than 25 feet, or
if multiple units are vented into the same vertical
vent, a barometric damper must be installed on each
appliance, such that the ue draft does not exceed
(negative) 0.1 in. w.c.
If using a power venter for any type of Category
I venting, the draft should be set between (negative)
0.01 and 0.05 in. w.c.
2.2.3 Common Venting Systems
Pennant units are Category I fan-assisted when
vented vertically and adhering to all applicable codes.
Pennant units are not allowed to be vented into a
common horizontal vent system, unless a properly
sized vent fan is used, and the common vent system
is properly designed by the vent fan manufacturer or
a qualied engineer. When common venting Pennant
fan-assisted unit with other appliances through
one shared vertical duct called a “common vent”,
special care must be taken by the installer to ensure
safe operation. In the event that the common vent
is blocked, it is possible, especially for fan-assisted
devices, to vent backwards through non-operating
appliances sharing the vent, allowing combustion
products to inltrate occupied spaces. If the
appliances are allowed to operate in this condition,
serious injury or death may occur.
WARNING
Operation of appliances with a blocked common
vent may lead to serious injury or death. Safety
devices must be implemented to prevent blocked
common vent operation. If safe operation of all
appliances connected to a common vent cannot
be assured, including prevention of spillage of flue
gasses into living spaces, common venting should
not be applied, and appliances should each be
vented separately.
AVERTISSEMENT
Le fonctionnement d’appareils connectés à un
évent commun bouché peut provoquer de sérieuses
blessures corporelles ou la mort. Des dispositifs de
sécurité doivent être mis en place pour empêcher
que les appareils soient utilisés avec un évent
commun bouché. Si un fonctionnement sécuritaire
de tous les appareils reliés à un évent commun et si
la prévention des dégagements accidentels de gaz
de combustion dans des zones habitées ne peuvent
pas être assurés, un évent commun ne doit pas
être mis en place et les appareils doivent être munis
d’évents individuels séparés.
It is for this reason that, in addition to
following proper vent sizing, construction and safety
requirements from the National Fuel Gas Code,
ANSI Z223.1 or in Canada, from the Natural Gas and
Propane Installation Code (CSA B149.1) as well as
all applicable local codes, it is required that installers
provide some means to prevent operation with a
blocked common vent. It is suggested that a blocked
vent safety system be employed such that if the switch
Page 10
Pennant 200, 300, 400
Page 11
LAARS Heating Systems
from one appliance trips due to excessive stack spill
or back pressure indicating a blocked vent condition,
that all appliances attached to the vent be locked out
and prevented from operating. Note that the Pennant
is equipped with a blocked vent safety (pressure)
switch, as shipped. However, this safety switch has
only been designed and tested to be effective in
installations where the Pennant is vented separately
and NOT common vented with other appliances. As an
additional precaution, it is recommended that a Carbon
Monoxide (CO) alarm be installed in all enclosed
spaces containing combustion appliances. If assistance
is required in determining how a blocked vent safety
system should be connected to a LAARS product,
please call Applications Engineering at the Rochester
phone number on the back cover of this manual.
Refer to the installation and operating
instructions on all appliances to be common vented
for instructions, warnings, restrictions and safety
requirements. If safe operation of all appliances
connected to a common vent cannot be assured,
including prevention of spillage of ue gases into
living spaces, common venting should not be applied,
and appliances should each be vented separately.
2.2.4 Category III Vent
When the Pennant is vented with horizontal
discharge, it must be installed per this installation
manual and the venting system manufacturer’s
installation instructions. The vent system must be
sealed stainless steel, per Table 5.
TermDescription
PipeMust comply with UL Standard 1738 such
as Type AL29-4C Stainless Steel
(either insulated or non-insulated).
Joint
Sealing
Table 5. Required Horizontal Venting Material.
Follow vent manufacturer's instructions.
50 linear feet (15.2m) of pipe. Subtract 10 allowable
linear feet (3.0m) for every additional elbow used.
2.3 Locating Vent & Combustion Air
Terminals
2.3.1 Side Wall Vent Terminal
The appropriate Laars side wall vent terminal
must be used, and is listed in the installation and
operation manual. The terminal provides a means of
installing the vent piping through the building wall,
and must be located in accordance with ANSI Z223.1/
NFPA 54 and applicable local codes. In Canada, the
installation must be in accordance with CSA B149.1
and local applicable codes. Consider the following
when installing the terminal:
1. Figure 3 shows the requirements for mechanical
vent terminal clearances for the U.S. and Canada.
2. Locate the vent terminal so that vent gases cannot
be drawn into air conditioning system inlets.
3. Locate the vent terminal so that vent gases cannot
enter the building through doors, windows,
gravity inlets or other openings. Whenever
possible, locations under windows or near doors
should be avoided.
4. Locate the vent terminal so that it cannot be
blocked by snow. The installer may determine
that a vent terminal must be higher than the
minimum shown in codes, depending upon local
conditions.
5. Locate the terminal so the vent exhaust does
not settle on building surfaces or other nearby
objects. Vent products may damage such surfaces
or objects.
6. If the boiler or water heater uses ducted
combustion air from an intake terminal located
on the same wall, locate the vent terminal at least
3 feet (0.9m) horizontally from the combustion
air terminal, and locate the vent terminal at least
1 foot (0.3m) above the combustion air terminal.
Route the vent pipe to the heater as directly as
possible. Seal all joints and provide adequate hangers
as required in the venting system manufacturer’s
installation instructions. Horizontal portions of the
venting system must be supported to prevent sagging
and may not have any low sections that could trap
condensate.
The unit must not support the weight of the vent
pipe. Horizontal runs must slope downwards not less
than inch per foot (2 cm/m) from the unit to the vent
terminal.
L’appareil ne doit pas supporter le poids de la
gaine d’évent. Les parties horizontales doivent être
installées avec une pente de 2 cm/m (1/4 inch par pied)
descendant de l’appareil vers la sortie de l’évent.
Reference Table 1 for the size of the Category
III vent system. Up to three elbows can be used with
WARNING
The outdoor vent terminal gets hot. Unit must be
installed in such a way as to reduce the risk of
burns from contact with the vent terminal.
AVERTISSEMENT
La sortie d’évent à l’extérieur devient très chaude.
Elle doit être installée de façon à réduire le risque
de brûlures au contact de l’extrémité de l’évent.
Pennant 200, 300, 400
Page 11
U.S. Installations (see note 1) Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch, 12 inches (30 cm) 12 inches (30 cm)
deck, or balcony
B= Clearance to window or door that may Direct Vent Only: 12 inches (30 cm)
be opened Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm)
to side of opening; 1 foot (30 cm) above opening
C= Clearance to permanently closed window See note 4 See note 5
D= Vertical clearance to ventilated soft located
above the terminal within a horizontal See note 4 See note 5
distance of 2 feet (61cm) from the center line of the terminal
E= Clearance to unventilated soft See note 4 See note 5
F= Clearance to outside corner See note 4 See note 5
G= Clearance to inside corner See note 4 See note 5
H= Clearance to each side of center line See note 4 3 feet (91 cm) within a height 15 feet
extended above meter/regulator assembly above the meter/regulator assembly
I= Clearance to service regulator vent outlet See note 4 3 feet (91 cm)
J= Clearance to non mechanical air supply Direct Vent Only: 12 inches (30 cm)
inlet to building or the combustion air inlet Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm)
to any other appliance to side of opening; 1 foot (30 cm) above opening
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) 6 feet (1.83 m)horizontally
L= Clearance above paved sidewalk or paved Vent termination not allowed in this location Vent termination not allowed in thisdriveway located on public property location
M= Clearance under veranda, porch, deck, See note 4 12 inches (30 cm) (see note 3)or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
4. For clearances not specied in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of
the gas supplier.
5. For clearances not specied in CSA B149.1, clearance is in accordance with local installation codes and the requirements of the gas
supplier.
Figure 3. Vent Terminal Clearance.
Page 12
Pennant 200, 300, 400
Page 13
LAARS Heating Systems
Important Note: Massachusetts Code
Requirement.
From Massachusetts Rules and Regulations 248
CMR 5.08:
(a) For all side wall horizontally vented gas
fueled equipment installed in every dwelling,
building or structure used in whole or in
part for residential purposes, including those
owned or operated by the Commonwealth and
where the side wall exhaust vent termination
is less than seven (7) feet above nished grade
in the area of the venting, including but not
limited to decks and porches, the following
requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE
DETECTORS.
At the time of installation of the side wall
horizontal vented gas fueled equipment, the
installing plumber or gastter shall observe that
a hard-wired carbon monoxide detector with
an alarm and battery back-up is installed on
the oor level where the gas equipment is to be
installed. In addition, the installing plumber or
gastter shall observe that a battery operated or
hard-wired carbon monoxide detector with an
alarm is installed on each additional level of the
dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment.
It shall be the responsibility of the property
owner to secure the services of qualied licensed
professionals for the installation of hard-wired
carbon monoxide detectors.
a. In the event that the side wall horizontally
vented gas fueled equipment is installed
in a crawl space or an attic, the hard-wired
carbon monoxide detector with alarm and
battery back-up may be installed on the next
adjacent oor level.
b. In the event that the requirements of this
subdivision cannot be met at the time of
completion of installation, the owner shall
have a period of thirty (30) days to comply
with the above requirements; provided,
however, that during said thirty (30) day
period, a battery operated carbon monoxide
detector with an alarm shall be installed.
3. SIGNAGE.
A metal or plastic identication plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent
terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall
read, in print size no less than one-half () inch
in size, “GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION.
The state or local gas inspector of the side
wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon
monoxide detectors and signage installed in
accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is
exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the
most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontal vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure
used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS
– GAS EQUIPMENT VENTING SYSTEM
PROVIDED. When the manufacturer of
Product Approved side wall horizontally
vented gas equipment provides a venting
system design or venting system components
with the equipment, the instructions provided
by the manufacturer for installation of the
equipment and the venting system shall
include:
1. Detailed instructions for the installation of the
venting system design or the venting system
components; and
2. A complete parts list for the venting system
design or venting system.
2. APPROVED CARBON MONOXIDE
DETECTORS.
Each carbon monoxide detector as required
in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certied.
(d) MANUFACTURER REQUIREMENTS
– GAS EQUIPMENT VENTING SYSTEM
NOT PROVIDED. When the manufacturer
of a Product Approved side wall horizontally
vented gas fueled equipment does not
provide the parts for venting the fuel gases,
but identies “special venting systems”, the
following requirements shall be satised by
the manufacturer:
Pennant 200, 300, 400
Page 13
1. The referenced “special venting system”
instructions shall be included with the appliance
or equipment installation instructions; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instructions.
(e) A copy of all installation instructions for all
Product Approved side wall horizontally
vented gas fueled equipment, all venting
instructions, all parts lists for venting
instructions, and/or all venting design
instructions shall remain with the appliance
or equipment at the completion of the
installation.
2.3.2 Side Wall Combustion Air Terminal
The Laars side wall combustion air terminal
(listed in Table 1) must be used when the unit takes
its combustion air through a duct from a side wall.
Consider the following when installing the terminal:
1. Do not locate the air inlet terminal near a source
of corrosive chemical fumes (e.g., cleaning uid,
chlorinated compounds, etc.)
2. Locate the terminal so that it will not be subject
to damage by accident or vandalism.
3. Locate the combustion air terminal so that it
cannot be blocked by snow. The National Fuel
Gas Code requires that it be at least 12 inches (30
cm) above grade, but the installer may determine
it should be higher, depending upon local
conditions.
4. If the Pennant is side-wall vented to the same
wall, locate the vent terminal at least 3 feet
(0.9m) horizontally from the combustion air
terminal, and locate the vent terminal at least 1
foot (0.3m) above the combustion air terminal
(see Figure 3).
2.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the
vent must extend at least 3 feet (0.9m) above the point
at which it penetrates the roof. It must extend at least
2 feet (0.6m) higher than any portion of a building
within a horizontal distance of 10 feet (3.0m), and high
enough above the roof line to prevent blockage from
snow. When the combustion air is taken from the roof,
the combustion air must terminate at least 12" (30cm)
below the vent terminal (see Figure 2).
2.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
eld-supplied rain cap or an elbow arrangement must
be used to prevent entry of rain water (see Figure 2).
The opening on the end of the terminal must be at least
12" (30cm) above the point at which it penetrates the
roof, and high enough above the roof line to prevent
blockage from snow. When the vent terminates on the
roof, the combustion air must terminate at least 12"
(30cm) below the vent terminal.
2.4 Common Vent Test — Boilers
When an existing boiler is removed from a
common venting system, the common venting system
is likely to be too large for proper venting of the
appliances remaining connected to it.
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances
remaining connected to the common venting system
are not in operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
non blockage or restriction, leakage, corrosion
and other deciencies which could cause an
unsafe condition.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other
spaces of the building. Turn on clothes dryers
and any appliance not connected to the common
venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close replace dampers.
4. Place in operation the appliance being
inspected. Follow the lighting instructions.
Adjust thermostat so appliance will operate
continuously.
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use
the ame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting
system properly vents when tested as outlined
above, return doors, windows, exhaust fans,
replace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so that the installation
conforms with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 and/or CSA B149.1,
Natural Gas and Propane Installation Codes.
When resizing any portion of the common
venting system, the common venting system
should be resized to approach the minimum size
as determined using the appropriate tables in
Appendix F in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CSA B149.1, Natural
Gas and Propane Installation Codes.
Page 14
Pennant 200, 300, 400
Page 15
LAARS Heating Systems
2.4 Vérication des évents communs
— Chaudières
Lorsqu’une chaudière existante est déconnectée
du réseau d’évents commun, ce réseau d’évents
commun devient probablement trop grand pour
les appareils qui lui restent connectés. Lorsqu’une
chaudière existante est retirée, les étapes suivantes
doivent être accomplies pour chaque appareil qui
reste connecté au réseau d’évents commun utilisé,
alors que les autres appareils qui sont encore
connectés au réseau commun d’évents ne sont pas en
fonctionnement.:
1. Sceller toutes les ouvertures non utilisées du
système d'évacuation.
2. Inspecter de façon visuelle le système
d'évacuation pour déterminer la grosseur et
l'inclinaison horizontale qui conviennent et
s'assurer que le système est exempt d'obstruction,
d'étranglement, de fuite, de corrosion et autres
défaillances qui pourraient présenter des risques.
3. Dans la mesure du possible, fermer toutes les
portes et les fenêtres du bâtiment et toutes les
portes entre l'espace où les appareils toujours
raccordés au système d'évacuation sont installés
et les autres espaces du bâtiment. Mettre en
marche les sécheuses, tous les appareils non
raccordés au système d'évacuation common
et tous les ventilateurs d'extraction comme
les hottes de cuisinière et les ventilateurs des
salles de bain. S'assurer que ces ventilateurs
fonctionnent à la vitesse maximale. Ne pas faire
fonctionner les ventilateurs d'été. Fermer les
registres des cheminées.
4. Mettre l'appareil inspecté en marche. Suivre les
instructions d'allumage. Réegler le thermostat de
façon continue.
5. Faire fonctionner le brûleur principal pendant
5 min ensuite, déterminer si le coupe-tirage
déborde à l'ouverture de décharge. Utiliser la
amme d'une allumette ou d'une chandelle ou la
fumée d'une cigarette, d'un cigare ou d'une pipe.
6. Une fois qu'il a été déterminé, selon la méthode
indiquée ci-dessus, que chaque appareil
raccordé au système d'évacuation est mis à l'air
libre de façon adéquate. Remettre les portes
et les fenêtres, les ventilateurs, les registres de
cheminées et les appareils au gaz à leur position
originale.
7. Tout mauvais fonctionnement du système
d'évacuation commun devrait être corrigé
de façon que l'installation soit conforme au
National Fuel Gas Code, ANSI Z223.1/NFPA
54 et (ou) aux codes d'installation CSA-B149.1.
Si la grosseur d'une section du système devrait
être modié, le système devrait être modié pour
respecter les valeurs minimales des tableaux
pertinents de l'appendice F du National Fuel Gas
Code, ANSI Z223.1/NFPA 54 et (ou) les codes
d'installation CSA-B149.1
2.5 Vent Terminals for Outdoor Units
For outdoor applications, the vent and
combustion air openings must be covered with proper
terminals to prevent rain, snow and other objects from
falling into the Pennant.
Outdoor Vent / Air kit part numbers are shown in
Table 6. These kits contain parts for both combustion
air inlet and exhaust vent connections. An angled sheet
metal assembly with louvers replaces the sheet metal
assembly with the air collar. An adapter, a 12" length
of pipe, and a rain cap are included for the exhaust
vent opening.
If local codes allow, Laars kits are not required
for outdoor units. The installer may use 12" of
appropriately sized galvanized single wall or b-type
vent pipe and a rain cap for the exhaust vent. In
addition, an appropriately sized galvanized 90° elbow,
positioned with the opening facing down, may be used
on the combustion air inlet.
Model (Size)Outdoor Vent and
Air Terminal Kit
200CA003001
300CA003002
400CA003003
Table 6. Vent / Air Kits for Outdoor Units.
SECTION 3.
Gas Supply and Piping
3.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or oor stands, not by the appliance.
The Pennant’s gas train allows the user to pipe
the gas from either the right side or the left side of
the unit. As shipped, the right side of the gas train is
capped off, and there is a manual valve on the left side.
If desired, the manual valve on the left side of the gas
train may be moved to the right side, and the cap on
the right side may be moved to the left.
Review the following instructions before
proceeding with the installation.
1. Verify that the appliance is tted for the proper
type of gas by checking the rating plate. Pennant
appliances are equipped to operate at elevations
up to 10,000 feet (3050m). Pennant appliances
may be adjusted to operate properly at altitudes
above 2500 feet (see Section 6.5.2) and the input
will be reduced if the heating value of the gas
supply is below sea level values.
2. The maximum inlet gas pressure must not
exceed 13" w.c. (3.2kPa). The minimum inlet gas
pressure is 5 in. w.c. (1.2 kPa).
3. Refer to Table 7, size supply.
4. Run gas supply line in accordance with all
applicable codes.
Pennant 200, 300, 400
Page 15
5. Locate and install manual shutoff valves in
accordance with state and local requirements.
6. A sediment trap must be provided upstream of
the gas controls.
7. All threaded joints should be coated with
piping compound resistant to action of liqueed
petroleum gas.
8. The appliance and its individual shutoff valve
must be disconnected from the gas supply piping
during any pressure testing of that system at test
pressures in excess of 0.5 psig (3.45 kpa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 0.5 psig (3.45 kpa).
10. The appliance and its gas connection must be
leak tested before placing it in operation.
11. Purge all air from gas lines.
WARNING
Do not use open flame to check for leaks. An open
flame could lead to explosion, which could result in
property damage, serious injury or death.
AVERTISSEMENT
Ne recherchez pas les fuites avec une flamme nue.
Une flamme nue peut provoquer une explosion qui
peut causer des dommages matériels, de sérieuses
blessures corporelles ou la mort.
NOTE: The Pennant appliance and all other gas
appliances sharing the gas supply line must be
firing at maximum capacity to properly measure
the inlet supply pressure. The pressure can be
measured at the supply pressure port on the gas
valve. Low gas pressure could be an indication of
an undersized gas meter, undersized gas supply
lines and/or an obstructed gas supply line.
SECTION 4A.
Water Connections —
Pennant Boiler
4A.1 Heating System Piping:
Hot Supply Connections — Boiler
NOTE: This appliance must be installed in a closed
pressure system with a minimum of 12 psig (82.7
kPa) static pressure at the boiler.
Hot water piping should be supported by suitable
hangers or oor stands. Do not support piping with
this appliance. Due to expansion and contraction of
copper pipe, consideration should be given to the type
of hangers used. Rigid hangers may transmit noise
through the system resulting from the piping sliding in
the hangers. It is recommended that padding be used
when rigid hangers are installed. Maintain 1" clearance
to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size)
to a drain or in a manner to prevent injury in the event
of pressure relief. Install an air purger, an air vent,
a diaphragm-type expansion tank, and a hydronic
ow check in the system supply loop. Minimum ll
pressure must be 12 psig (82.7 kPa). Install shutoff
valves where required by code.
Suggested piping diagrams are shown in Figures
4, 5, 6, 7 and 8. These diagrams are meant only as a
guide. Components required by local codes must be
properly installed.
Note the recommended location of the
temperature sensor on the diagrams; you must provide
a location for the additional sensor shipped with the
Pennant. This sensor may be strapped onto pipe from
1" to 4" diameter, or inserted into an immersion well.
Model and
Gas Type0-100'
200 natural1"3.2 cm1"3.2 cm1"3.2 cm
200 propane1"2.5 cm1"2.5 cm1"3.2 cm
300 natural1"3.2 cm1"4.0 cm1"4.0 cm
300 propane12.5 cm1"3.2 cm1"3.2 cm
400 natural1"3.2 cm1"4.0 cm2"5.0 cm
400 propane1"3.2 cm1"3.2 cm1"4.0 cm
Notes:
1. These gures are based on 1/2" (0.12 kPa) water column pressure drop.
2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe ttings must be considered when determining gas pipe sizing.
Distance from Gas Meter or Last Stage Regulator
0-31 m100-200'31-61m200-300'61-91m
Table 7. Gas Piping Size.
Page 16
Pennant 200, 300, 400
Page 17
PRIMARY/SECONDARY MANDATORY FOR ALL
VARIABLE FLOW SYSTEMS
INSTALLAIR VENTS AT HIGH POINTS IN SYSTEM
PIPING & SIZING OF EXPANSION TANK
PER TANK MANUFACTURER'S INSTRUCTIONS
DIMENSION "C" (COMMON PIPING) TO BE FOUR
PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)
BOILER CIRCUIT PIPING MUST BE EQUAL
TO
BOILER WATER CONNECTION SIZE
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS
PUT BOILER CONTROL SENSOR IN THE SYSTEM
C
SYSTEM PUMP
MAKE-UP
COLD WATER
SUPPLY
SYSTEM
PUMP LOCATION FOR
PUMP-MOUNTED UNITS
RETURN
SYSTEM
SUPPLY WHEN USING THIS PIPING STYLE.
MINIMUM BOILER INLET WATER TEMPERATURE
MUST BE AT LEAST 120°F.
C
CAUTION: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING, CHECK
WITH LOCAL CODES
AND ORDINANCES FOR
ADDITIONAL REQUIREMENTS.
CHECK VALVE
TEMPERATURE
SENSOR
VALV
E
PURGE
VALVE
THERMOMETER
GLOBE VALVE
EXPANSION TANK
WITH
AIR SCOOP AND
AUTO AIR VENT
PUMP
PRESSURE REDUCING VALVE
W/ FAST FILL BYPASS
3-WAY VALVE
C
SYSTEM PUMP
MAKE-UP
COLD WATER
SUPPLY
SYSTEM
PUMP LOCATION FOR
PUMP-MOUNTED UNITS
RETURN
SYSTEM
PRIMARY/SECONDARY MANDATORY FOR ALL
VARIABLE FLOW SYSTEMS
INSTALLAIR VENTS AT HIGH POINTS IN SYSTEM
PIPING & SIZING OF EXPANSION TANK
PER TANK MANUFACTURER'S INSTRUCTIONS
DIMENSION "C" (COMMON PIPING) TO BE FOUR
PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)
BOILER CIRCUIT PIPING MUST BE EQUAL
TO
BOILER WATER CONNECTION SIZE
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS
PUT BOILER CONTROL SENSOR IN THE SYSTEM
SUPPLY WHEN USING THIS PIPING STYLE.
MINIMUM BOILER INLET WATER TEMPERATURE
MUST BE AT LEAST 120°F.
C
ADJUSTMENT PROCEDURE TO MAINTAIN
120°F INLET TEMP:
1.
Turn on boiler and open valves A& B.
2. After steady-state operation,
if T1 is less
thanslowly close valve
B until T1
climbs to 120°F
.
3. If
T1 is greater than 120°F, slowly close
until
T1 drops to 120°F.
4. Check after system operating temperature
has
stabilized. Make final adjustments.
120°F
,
valve
A
A
B
T1
B
A
T1
CHECK VALVE
TEMPERATURE
SENSOR
VALVE
PURGE
VALV
E
THERMOMETER
GLOBE VALVE
EXPANSION TANK
WITH
AIR SCOOP AND
AUTO AIR VENT
PUMP
PRESSURE REDUCING VALVE
W/ FAST FILL BYPASS
3-WAY VALVE
CAUTION: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING, CHECK
WITH LOCAL CODES
1. Connect the cold water supply to the inlet
connection of an automatic ll valve.
2. Install a suitable back ow preventer between the
automatic ll valve and the cold water supply.
3. Install shut off valves where required.
NOTE: The boiler, when used in connection with a
refrigeration system, must be installed so the chilled
medium is piped in parallel with the boiler with
appropriate valves to prevent the chilled medium
from entering the boiler.
The boiler piping system of a hot water heating
boiler connected to heating coils located in air
handling appliances where they may be exposed to
refrigerated air circulation must be equipped with ow
control valves or other automatic means to prevent
gravity circulation of the boiler water during the
cooling cycle.
A boiler installed above radiation level, or as
required by the authority having jurisdiction, must be
provided with a low water cutoff device either as a part
of the boiler or at the time of boiler installation.
4A.3 Water Flow Requirements — Boiler
A hydronic heating (closed loop) application
recirculates the same uid in the piping system. As a
result, no new minerals or oxygen are introduced into
the system. To ensure a proper operating temperature
leading to long boiler life, a ow rate has been
established based on the uid temperature rise for this
specic size boiler.
Pump-mounted boilers can be ordered for use in
primary secondary piping systems. The pumps used
are sized for the head loss through the heater, plus 30
feet (9.1 m) of full-sized piping (same size as boiler
outlet) and a normal number of ttings.
Notes: gpm = gallons per minute, lpm = liters per minute,
H/L = head loss, ft = head loss in feet,
m = head loss in meters.
Maximum temperature rise is 35°F (19°C), as shown.
Head loss is for boiler’s heat exchanger only.
N/R = not recommended.
20°F25°F30°F35°F
flow
H/L
gpm
feet
11°C14°C17°C19°C
ow
H/L mow
lpm
Table 8. Water Flow Requirements - PNCH.
flow
H/L
flow
H/L
gpm
feet
gpm
feet
H/L mow
lpm
H/L mow
lpm
flow
gpm
lpm
H/L
feet
H/L
m
Pennant 200, 300, 400
Page 19
Table 8 species water ow rates for boilers,
which will enable the user to size a pump. The head
loss shown is for the heater only, and the user will
need to add the head loss of the system piping to
properly size the pump.
The minimum inlet water temperature for the
Pennant is 120°F (49°C) to avoid condensing on the
copper coils.
4A.4 Freeze Protection — Boiler
Boiler installations are not recommended in
areas where the danger of freezing exists unless proper
precautions are made for freeze protection. A non
toxic, heating system, anti-freeze may be added to
the hydronic system provided that the concentration
does not exceed 50% and the anti freeze contains an
anti foamant. When a 50/50 mixture is used, increase
the water ow requirements by 15%, and increase the
head loss requirements by 20%.
Power outage, interruption of gas supply, failure
of system components, activation of safety devices,
etc., may prevent a boiler from ring. Any time a
boiler is subjected to freezing conditions, and the
boiler is not able to re, and/or the water is not able
to circulate, there is a risk of freezing in the boiler
or in the pipes in the system. When water freezes,
it expands. This can result in bursting of pipes in the
system, or damage to the boiler, which could result in
leaking or ooding conditions.
IMPORTANT NOTES: Different glycol products
may provide varying degrees of protection. Glycol
products must be maintained properly in a heating
system, or they may become ineffective. Consult
the glycol specifications, or the glycol manufacturer,
for information about specific products,
maintenance of solutions, and set up according to
your particular conditions. Never use ethylene glycol
(automotive antifreeze).
SECTION 4B.
Water Connections —
Pennant Water Heater
4B.1 Water System Piping —
Water Heater
Hot water piping should be supported by suitable
hangers or oor stands. Do not support piping with
this appliance. Due to expansion and contraction of
copper pipe, consideration should be given to the type
of hangers used. Rigid hangers may transmit noise
through the system resulting from the piping sliding in
the hangers. It is recommended that padding be used
when rigid hangers are installed.
The Pennant can be used with several different
types of readily available storage tanks. A pump draws
water from the storage tank and pumps the water
through the heater and back into the tank. Pumpmounted units have a circulating pump built into the
water heater. The pumps used are sized for the head
loss through the heater, plus 30 feet (9.1 m) of fullsized piping (same size as boiler outlet) and a normal
number of ttings. Pumps used on pump-mounted unit
are sized for soft/normal or hard water, so make sure
a pump-mounted unit matches the water quality of the
installation.
Pipe the outlet from the heater’s relief valve
such that any discharge from the relief valve will be
conducted to a suitable place for disposal when relief
occurs. Do not reduce line size or install any valves in
this line. The line must be installed to allow complete
drainage of both the valve and the line.
Suggested piping diagrams are shown in Figures
9, 10, 11 and 12. These diagrams are meant only as a
guide. Components required by local codes must be
properly installed.
Note the recommended location of the
temperature sensor on the diagrams. The Pennant is
shipped with an additional sensor that can be used for
more full-featured domestic water heating control. To
get these features, you must provide a location for the
additional sensor. It can be strapped to a pipe from 1"
to 4" diameter, or inserted into a tank immersion well.
The minimum inlet water temperature for the
Pennant is 120°F (49°C) to avoid condensing on the
copper coils.
4B.2 Hot Water Supply Piping —
Water Heater
Follow the tank manufacturer’s guidelines for
completion of the hot water system connections.
NOTE: A listed temperature and pressure relief
valve listed as complying with the Standard
for Relief Valves and Automatic Gas Shutoff
Devices for Hot Water Supply Systems (ANSI
Z21.22/CSA 4.4), of suitable discharge capacity
must be installed in the separate storage tank
system.
If the Pennant water heater is installed in a closed
water supply system, such as one having a backow
preventer in the cold water supply line, the relief valve
may discharge periodically, due to thermal expansion.
Means (such as a properly-sized expansion tank) shall
be provided to control thermal expansion. Contact the
water supplier or local plumbing inspector on how to
control this situation.
Page 20
Pennant 200, 300, 400
Page 21
NOTES:
5. CAUTION: PUMP SIZING MUST BE BASED UPON WATER HARDNESS AT
JOB SITE
1. OPTIONAL CWMU & RECIRC. LINE LOCATION.
2. LOCATE PENNANT DHW SENSOR OR REMOTEAQUASTAT
WELL IN LOWER 1/3 OF TANK.
3. BACK FLOW PREVENTER MAY BE REQUIRED. CHECK LOCAL CODES.
4. THERMAL EXPANSION TANK MAY BE REQUIRED. CHECK LOCAL CODES.
SUPPL
Y
RECIRC.
CWMU
1
CAUTION: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING, CHECK
WITH LOCAL CODES AND ORDINANCES FOR
ADDITIONAL REQUIREMENTS.
CHECK VALVE
THERMOMETER
TEMPERATURE
SENSOR
GLOBE VALVE
EXPANSION TANK
3-WAY VALVE
VALV
E
PRESSURE REDUCING
VALV
E
PUMP
PRV
TPR
V
WATER CATEGORY
GRAIN HARDNESS PER GALLON
PPM / 17.1 = Grains Per Gallon
KEY:
S = SOFT
N =
NORMAL
H =
HARD
1 THROUGH 7.5
7.6 THROUGH 17
OVER 17
2
3
4
SUPPL
Y
RECIRC.
CWMU
CAUTION: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING, CHECK
WITH LOCAL CODES AND ORDINANCES FOR
ADDITIONAL REQUIREMENTS.
NOTES:
6. CAUTION: PUMP SIZING MUST BE BASED UPON WATER HARDNESS AT
JOB SITE
1. OPTIONAL CWMU & RECIRC. LINE LOCATION.
2. LOCATE PENNANT DHW SENSOR OR REMOTEAQUASTAT
WELL IN LOWER 1/3 OF TANK.
3. BACK FLOW PREVENTER MAY BE REQUIRED. CHECK LOCAL CODES.
4. THERMAL EXPANSION TANK MAY BE REQUIRED. CHECK LOCAL CODES.
5. COMMON PIPING, SHOWN WITH HEAVY LINES, MUST BE SIZED
FOR MAXIMUM COMBINED HEATER FLOW RATE.
WATER CATEGORY
GRAIN HARDNESS PER GALLON
PPM / 17.1 = Grains Per Gallon
KEY:
S = SOFT
N =
NORMAL
H =
HARD
1 THROUGH 7.5
7.6 THROUGH 17
OVER 17
1
5
3
4
2
CHECK VALVE
THERMOMETER
TEMPERATURE
SENSOR
GLOBE VALVEEXPANSION TANK
3-WAY VALVE
VALV
E
PRESSURE REDUCING
VALV
E
PUMP
PRV
TPR
V
LAARS Heating Systems
Figure 9. Water Heater Piping — One Heater, One Tank.
Figure 10. Water Heater Piping — Multiple Heaters, One Tank.
Pennant 200, 300, 400
CAUTION: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING, CHECK
WITH LOCAL CODES AND ORDINANCES FOR
ADDITIONAL REQUIREMENTS.
NOTES:
5. CAUTION: PUMP SIZING MUST BE BASED UPON WATER HARDNESS AT
JOB SITE
1. OPTIONAL CWMU & RECIRC. LINE LOCATION.
2. LOCATE PENNANT DHW SENSOR OR REMOTEAQUASTAT
WELL IN LOWER 1/3 OF TANK.
3. BACK FLOW PREVENTER MAY BE REQUIRED. CHECK LOCAL CODES.
4. THERMAL EXPANSION TANK MAY BE REQUIRED. CHECK LOCAL CODES.
RECIRC.
CWMU
SUPPL
Y
WATER CATEGORY
GRAIN HARDNESS PER GALLON
PPM / 17.1 = Grains Per Gallon
KEY:
S = SOFT
N =
NORMAL
H =
HARD
1 THROUGH 7.5
7.6 THROUGH 17
OVER 17
2
2
3
4
1
CHECK VALVE
THERMOMETER
TEMPERA
TURE
SENSOR
GLOBE VALVEEXPANSION TANK
3-WAY VALVE
VALV
E
PRESSURE REDUCING
VALV
E
PUMP
PRV
TPRV
CAUTION: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING, CHECK
WITH LOCAL CODES AND ORDINANCES FOR
ADDITIONAL REQUIREMENTS.
NOTES:
6. CAUTION: PUMP SIZING MUST BE BASED UPON WATER HARDNESS AT
JOB SITE
1. OPTIONAL CWMU & RECIRC. LINE LOCATION.
2. LOCATE PENNANT DHW SENSOR OR REMOTEAQUASTAT
WELL IN LOWER 1/3 OF TANK.
3. BACK FLOW PREVENTER MAY BE REQUIRED. CHECK LOCAL CODES.
4. THERMAL EXPANSION TANK MAY BE REQUIRED. CHECK LOCAL CODES.
5. COMMON PIPING, SHOWN WITH HEAVY LINES, MUST BE SIZED
FOR MAXIMUM COMBINED HEATER FLOW RATE.
RECIRC.
CWMU
SUPPL
Y
WATER CATEGORY
GRAIN HARDNESS PER GALLON
PPM / 17.1 = Grains Per Gallon
KEY:
S = SOFT
N =
NORMAL
H =
HARD
1 THROUGH 7.5
7.6 THROUGH 17
OVER 17
2
2
3
4
1
5
CHECK VALVE
THERMOMETER
TEMPERATURE
SENSOR
GLOBE VALVE
EXPANSION TANK
3-WAY VALVE
VALV
E
PRESSURE REDUCING
VALV
E
PUMP
PRV
TPR
V
Page 21
Figure 11. Water Heater Piping — One Heater, Multiple Tanks.
Figure 12. Water Heater Piping — Multiple Heaters, Multiple Tanks.
4. gpm = gallons per minute, lpm = liters per minute, ft = head loss in feet, m = head loss in meters
5. Head loss is for heater's heat exchanger only
4B.3 Water Flow Requirements —
Water Heater
In a water heating application (an open system),
new water is constantly being introduced. With the
new water comes a fresh supply of minerals that can
gpmftTemp Rise °FlpmmTemp. Rise °C
SNHSNHSNHSNHSNHSNH
Table 9. Water Flow Requirements - PNCV.
When the system requires water for heating at
temperatures higher than required for other uses,
an anti-scald mixing or tempering valve shall be
installed to temper the water for those uses in order
to reduce scald hazard potential.
be deposited on the unit’s heat exchanger. This is
commonly known as scaling. The amount of minerals
will depend upon the hardness of the water. Water can
also be aggressive, and can erode metals, including
copper, if the water is moved too quickly. The water
ow requirements for the Pennant water heater are
based upon the hardness of the water. The water ow
is kept high enough to prevent scaling, but low enough
to prevent tube erosion. For extremely soft or hard
water, cupro-nickel tubes are available. Contact a
Laars representative if you have questions or concerns
about water quality.
Pump-mounted water heaters can be ordered
with standard pumps for soft or normal water or with
pumps for hard water. The pumps used are sized for
the head loss through the heater, plus 30 feet (9.1m)
of full-sized piping (same size as heater outlet) and a
normal number of ttings.
4B.5 Freeze Protection — Water Heater
Although Pennant water heaters are designcertied for outdoor installations, such installations
are not recommended in areas subject to freezing
temperatures, unless proper precautions are taken.
Power outage, interruption of gas supply, failure
of system components, activation of safety devices,
etc., may prevent a heater from ring. Any time a
heater is subjected to freezing conditions, and the
heater is not able to re, and/or the water is not
able to circulate, there is a risk of freezing in the
heater or in the pipes in the system. When water
freezes, it expands. This can result in bursting of pipes
in the system, or damage to the heater, which could
result in leaking or ooding conditions.
Contact the local factory representative or Laars
for additional information.
Table 9 species water ow rates for water
heaters, which will enable the user to size a pump. The
head loss shown is for the heater only, and the user
will need to add the head loss of the piping system to
SECTION 5.
Electrical Connections
properly size the pump.
WARNING
4B.4 Combined Water Heating (potable)
and Space Heating — Water Heater
NOTE: These systems are not allowed in the
Commonwealth of Massachusetts.
Piping and components connected to this water
heater for the space heating application shall be
suitable for use with potable water.
Toxic chemicals, such as used for boiler
treatment, shall not be introduced into the potable
water used for space heating.
This water heater when used to supply potable
water shall not be connected to any heating system
The appliance must be electrically grounded in
accordance with the requirements of the authority
having jurisdiction or, in the absence of such
requirements, with the latest edition of the National
Electrical Code, ANSI/NFPA 70, in the U.S. and
with latest edition of CSA C22.1 Canadian Electrical
Code, Part 1, in Canada. Do not rely on the gas
or water piping to ground the metal parts of the
boiler. Plastic pipe or dielectric unions may isolate
the boiler electrically. Service and maintenance
personnel, who work on or around the boiler, may
be standing on wet floors and could be electrocuted
by an ungrounded boiler.
or component(s) previously used with a non-potable
water heating appliance.
Pennant 200, 300, 400
L1
L2
P1
P2
1
2
3
4
6
POWER SUPPLY, HOT LEG,
115/230VAC SINGLE PHASE
FIELD-SUPPLIED OR
FACTORY-MOUNTED
PUMP
, 120VAC 1HP MAX, 230VAC 3/4HP MAX
115VAC HOT
115VAC NEUTRAL
TRANSFORMER
TIME DELAY
RELAY,
K1
BK
TEMPERATURE CONTROL
IGNITION CONTROL
POWER
CALL
FOR
HEA
T
AIR
FLOW
HIGH
LIMIT
STAGE 1
STAGE 2
WA
TER
FLOW
REMOTE
LED BOARD
F1
F2
24
VA
C
FV+
FV-
S1
120
L1 L2
S2
FS
TH PSW
GND
VAL
240
1
2
3
4
5
6
5
4
3
2
1
BLOWER
9
8
7
6
5
4
3
2
1
R
R
Y
G
THERMISTOR #1
IGNITER
2AMP
FUSE
LOCAL/REMOTE
SWITCH
BK
BK
R
BL
LWCO
JUMPER
OTHER INTERLOCKS
JUMPER
THERMISTOR #2
DR
Y REMOTE
ALARM CONTACTS,
CLOSE ON ALARM
AIR FLOW
BLOCKED
VENT
SWITCH
MV
MV
MV
MV
REMOTE TEMPERATURE
CONTROL, CONNECT TO
DR
Y CONTACTS ONLY
BR
BR
V
GY
R
Y
R
Y
R
Y
Y
R
BR
R
O
BK/Y
V
GY
BL
BL
Y
BR
BL
GY
V
W
BK
GY
BK
W
G
W
G
BK
Y
Y
V
Y
R
R
BK
BL
GY
BL
ON/OFF
SWITCH
LED
LED
LED
LED
LED
LED
LED
LED
LED
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
COM
COM
NO
NC
1
2
G
8
7
6
5
4
3
2
1
3
2
1
BK
G
V
GY
R
Y
Y
Y
Y
P
GY
V
BR
BR
V
BL/W
Y
GY
BR
BL/W
BL/W
GY
GY
BL
BL
BL
BR
BR
BL
O
O
BR
BL
R
R
O
BL
REMOTE
LOCAL
COM
R
Y
Y
Y
R
R
BK
BK
BK
R
W
BK
W/R
W/BK
K2
BK/Y
-/4
R
+/5
COM
NC
Y
R
BK/Y
FLOW
SWITCH
HIGH
LIMIT
FUSIBLE LINK
(200 ONL
Y)
BK/Y
V
BL/W
NO
COM
1
P
BR
BL/W
P
P7
P1
P2
CPU
P3
AUXILLIARY
(CONTROL LOOP
2)
CONTACT CLOSURE
STAGE 1
STAGE 2
(2-ST
AGE
UNITS ONLY)
AUXILLAR
Y
ALARM
M
VALVE
STAGE 1
VALV
E
STAGE 2
(2-STAGE
UNITS ONL
Y)
POWER SUPPLY, NEUTRAL
LEG,
115/230VAC SINGLE PHASE
BLK - BLACK
BK/Y
- BLACK WITH YELLOW
TRACE
BL
- BLUE
BL/W
- BLUE WITH WHITE
TRACE
BR - BROWN
G-
GREEN
GY
- GRAY
O- ORANGE
P-
PINK
R-
RED
V-
VIOLET
W-
WHITE
Y-
YELLOW
115V FIELD WIRED
115V FACTORY WIRED
24V FIELD WIRED
24V FACTORY WIRED
INTERNAL CIRCUITRY
BK
BK
W
W
Page 23
L’appareil doit être relié à la terre conformément
aux exigences de la réglementation locale ou,
en l’absence d’une telle réglementation, à la plus
récente édition du National Electrical Code (Code
national de l’électricité) ANSI/NFPA 70 aux ÉtatsUnis, et à la plus récente édition du Code Canadien
de l’électricité 1
AVERTISSEMENT
ère
partie (Canadian Electrical
Code Part 1) CSA C22.1, au Canada. N’utilisez
pas les tuyauteries d’eau ou de gaz pour mettre
à la terre les pièces métalliques de la chaudière;
des tuyauteries en plastique ou des raccords
union diélectriques peuvent isoler électriquement
la chaudière. Les employés qui sont appelés à
travailler sur la chaudière ou autour peuvent être
électrocutés par une chaudière qui n’est pas mise à
la terre.
Figure 13. Wire Connection Diagram
Page 24
Pennant 200, 300, 400
Page 25
L1
S1
IGN
CTRL
S2
L2
IGN
CTRL
120 VA
C
CNTRL
C1
MV
TH
AIR FLOW
SWITCH
PSW
GAS VALVE 2
(IF EQUIPPED)
STAGE 2
GAS VALVE 1
STAGE
1
WATER FLOW
FLOW
SWITCH
OTHER
INTLKS
JMPR
F1
F2
IGN
CTRL
FUSE
120 VAC
24 VA
C
BLOWER
PUM
P
HOT
PUMP
NEU
PUMP
(IF EQUIPPED)
AIR FLOW
24V
GND
IGNITION BOARD
BAS
C1
BAS
NO1
MANUAL
RESET
HIGH
LIMIT
LWCO
JMPR
LWCO
COM
LWCO
NO
(IF LWCO IS
SUPPLIED JMPR
REMOVED)
MAIN POWER
SWITCH
24V
GND
TEMP CONTROL
7
8
5
6
L1
L2
11
12
DRY ALARM
CONTACTS
3
4
CLASS 2 120/24VAC
50VATRANSFORMER
COM
K2
CALL FOR HEAT
K2A
POWER ON
P1
P2
FUSIBLE LINK
(200
ONLY)
9
10
BLOCKED
VENT
SWITCH
TDR 1
24V
TDR 3
GND
TIME DELAY RLY
TDR
6
INITIATE
TDR
2
COM
TDR 4
NO
TIME DELAY RLY
POWER ON
IGNITOR
STAGE 2 INITIATE
(IF EQUIPPED)
THERMISTOR #1
THERMISTOR #2
LED
LED
REMOTE
LED
LED
HIGH LIMIT
LED
LED
LED
LED
LED
LOCAL
REMOTE
5
1
2
LOOP 2
CONTACTS
FAN PROVE
SWITCH
CNTRL
NO1
STAGE 1 INITIATE
IG
N
CTRL
IGN
CTRL
IGN
CTRL
MAIN VALVE
CNTRLC2CNTRL
NO2
CNTRL
RT1+
CNTRL
RT1-
CNTRL
C3
CNTRL
RT2+
CNTRL
IND+
CNTRL
IND-
CNTRL
RT2-
CNTRL
INP+
CNTRL
INP-
CNTRL
NO3
CNTRL
C4
CNTRL
NO4
LAARS Heating Systems
Figure 14. Wiring Schematic (Ladder Diagram).
Pennant 200, 300, 400
Page 25
Single pole switches, including those of safety
controls and protective devices must not be wired in a
grounded line.
All electrical connections are made in the eld
wiring terminal strip, which is located to the left of the
blower.
NOTE: All internal electrical components have been
pre-wired. No attempt should be made to connect
electrical wires to any other location except the
wiring box.
5.1 Main Power
Connect a 15 amp. fused, 120-volt supply to the
main power switch (hot leg is connected directly to
switch). Neutral leg is connected directly to the white
wire. Ground wire can be connected to the grounding
screw in the box or on the switch.
Wiring diagrams are shown in Figures 13 and 14.
5.2 Field Wiring
Terminal strips are supplied for eld wiring
connections under the ip-up control panel.
Connections must be made as specied by the
Connection Diagram (Figure 13). The following may
be connected to the terminal strips as eld wiring:
Temperature Sensor: The sensor supplied loose
with the Pennant is installed in the piping or tank, per
the suggested piping diagrams. The sensor, Thermistor
2, is connected to the “9” and “10” terminals.
Field Installed Pump: A pump contactor can be
wired to the “P1” and “P2” terminals. These terminals
are attached to dry contacts of an adjustable delay
on break relay. The contacts may be used to switch a
larger pump contactor or can be used to directly switch
the hot leg of a circulator pump, up to 1hp at 120 VAC
or 3/4hp at 240 VAC.
Note that in some cases, the pump is run
continuously.
External Alarm: An external power supply and
alarm can be connected to the “1” and “2” terminals.
In the event of an ignition time out, a contact closure
occurs across these terminals.
BAS Connections: To use an external control
to call Pennant units for heat, connect to terminals
"3" and "4". Then put the Local/Remote Switch in the
"Remote" mode.
Other Field Interlocks: To install other eldwired switches (proving switches, ow switches, etc.),
remove the jumper between the terminals labeled “7”
and “8”.
Auxiliary Contacts: The contacts between
terminals “11” and “12” will close whenever Loop 2
is enabled and there is a call for heat on Loop 2. Use
these terminals to enable eld devices under these
circumstances
SECTION 6.
Operating Instructions
6.1 Filling the Boiler System
1. Ensure the system is fully connected. Close all
bleeding devices and open make-up water valve.
Allow system to ll slowly.
2. If make-up water pump is employed, adjust
pressure switch on pumping system to provide
a minimum of 12 psi (81.8 kPa) at the highest
point in the heating loop.
3. If a water pressure regulator is provided on the
make-up water line, adjust the pressure regulator
to provide at least 12 psi (81.8 kPa) at the highest
point in the heating loop.
4. Open bleeding devices on all radiation units
at the high points in the piping throughout
the system, unless automatic air bleeders are
provided at such points.
5. Run system circulating pump for a minimum of
30 minutes with the boiler shut off.
6. Open all strainers in the circulating system,
check ow switch operation, and check for
debris. If debris is present, clean out to ensure
proper circulation.
7. Recheck all air bleeders as described in Step 4.
8. Check liquid level in expansion tank. With the
system full of water and under normal operating
pressure, the level of water in the expansion tank
should not exceed of the total, with the balance
lled with air.
9. Start up boiler according to the procedure in this
manual. Operate the entire system, including the
pump, boiler, and radiation units for one (1) hour.
10. Recheck the water level in the expansion tank. If
the water level exceeds of the volume of the
expansion tank, open the tank drain, and drain to
that level.
11. Shut down the entire system and vent all
radiation units and high points in the system
piping, as described in Step 4.
12. Close make-up water valve and check strainer in
pressure reducing valve for sediment or debris
from the make-up water line. Reopen make-up
water valve.
13. Check gauge for correct water pressure and also
check water level in the system. If the height
indicated above the boiler insures that water is at
the highest point in the circulating loop, then the
system is ready for operation.
14. Refer to local codes and the make-up water
valve manufacturer’s instructions as to whether
the make-up water valve should be left open or
closed.
Page 26
Pennant 200, 300, 400
Page 27
LAARS Heating Systems
15. After placing the unit in operation, the ignition
system safety shutoff device must be tested.
First, shut off the manual gas valve, and call
the unit for heat. After the pre-purge and ignitor
heat-up time, the main gas terminals will be
energized, attempting to light, for seven (7)
seconds, and then will de-energize. The unit will
attempt to light two more times, and then will go
into lockout mode. Second, turn the power off
and then on again, open the manual gas valve
and allow the unit to light. While the unit is
operating, close the manual gas valve and ensure
that power to the main gas valve has been cut.
16. Within three (3) days of start-up, recheck all air
bleeders and the expansion tank as described in
Steps 4 and 8 above.
Important: The installer is responsible for identifying
to the owner/operator the location of all emergency
shutoff devices.
WARNING
Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to replace
any part of the control system and any gas control
that may have been under water.
AVERTISSEMENT
N’utilisez pas cet appareil si l’une de ses pièces
est passée sous l’eau. Appelez tout de suite un
technicien en entretien et en réparation pour
inspection de l’appareil et remplacement des
pièces du système de commande, et des pièces de
commande du circuit gaz, qui sont passées sous
l’eau.
6.2 Pennant Controller
Pennant 200-400 units feature a custom-
congured digital control system that is capable of
monitoring the temperature in two different loops.
Loop 1 is the Pennant loop, which uses thermistor
1, mounted in the inlet of the Pennant. Loop 2 is a
secondary loop, using the auxiliary thermistor (called
thermistor 2) provided loose with the Pennant.
Thermistor 2 can be installed where the user
chooses (in a tank, or in system piping, etc.) and is
connected to Pennant terminals 9 and 10. It is activated
in the Pennant controller menu (see section 6.6).
Auxiliary contacts in the Pennant controller will close
when Loop 2 calls for heat, and these contacts can be
used to energize a pump relay, or other device that the
user chooses.
6.3 Local / Remote Switch
A call for heat can be initiated by the Pennant
controller, or by an external controller. When an
external controller, such as a tank aquastat or multiple
boiler control, is used, it is connected between
Pennant terminals 3 and 4. With the switch in the
Remote position, the external controller is included
in the Pennant sequence of operation, and the Remote
indicator light on the front panel is illuminated. If
an external control is not used, put the switch in the
Local position, and terminals 3 and 4 are left out of the
sequence.
6.4 Sequence of Operation
The amber “Ready” light on the front panel
indicates that the control system is energized. Upon a
call for heat, the green “Call for Heat” indicator on the
front panel will light.
The pump time delay relay will receive a signal
to initiate. If the unit is pump-mounted, the pump
will be energized. The pump terminals on the eldwiring terminals strip will energize a eld pump that
is properly interlocked with the Pennant. The green
“Water Flow” indicator on the front panel will light,
once proper ow has been established by the water
ow switch.
Once the water ow switch makes, if all of the
safety interlocks are closed, the ignition module will
energize the blower(s) for a 15-second pre-purge,
followed by a 40-second period to allow the ignitor to
heat.
The ignition control energizes the blower. The
blower pressurizes the air box (which supplies air to
the burners) and closes the normally-open contact
on the airow pressure switch. The blocked vent
pressure switch senses the pressure in the exhaust
plenum. This switch opens if the pressure is excessive
(as an indicator of a blocked vent). When these two
pressure switches are closed, voltage is sent to the
PSW terminal on the ignition control, which allows the
ignition module to proceed with the ignition sequence.
If the airow proving circuit is not proven, the
ignition module will lock out, and the temperature
controller will display the air ow fault, AFF. The
ignition control LED will display its one-ash
sequence, as well. Section 6.5 describes the result of
air ow faults in more detail.
When the ignition control gets the signal at the
PSW terminal, it will energize its MV terminal, which
sends power to the stage one (or on/off) main valve.
The green Stage 1 indicator on the front panel will
light.
After a 7-second trial for ignition, the ignitor
switches to ame sense mode. If a ame is not
detected, the gas valve will close and the ignition
module will attempt ignition again (up to two more
times, for a total of three attempts.) If all three
attempts fail, the ignition control will lock out.
If ame is sensed, the burner will continue to
re as long as there is a call for heat, and none of the
safety circuit is interrupted.
Pennant 200, 300, 400
Page 27
If there is a call for stage 2 on a 2-stage unit, that
valve will be energized, and the addition burner stage
will be indicated on the front panel with a green stage
2 light.
If there is a loss of ame signal during a
successful ring sequence, the ignition control will
remove power from the gas valves, and then attempt to
light up to two more times. If successful, the Pennant
will re normally. If unsuccessful, the ignition control
will lock out.
Ignition lockout is noted on the ignition control
LED with a three-ash sequence and is noted on the
temperature control by displaying LOC.
When the call for heat is satised, the gas
valve(s) closes, and the blower starts a 45 second
post-purge. Any pump connected to the Pennant pump
time delay relay will continue to run for the time delay
period (dialed by the user, 0.1 to 10 minutes).
6.5 Ignition Control Reaction to Air Flow /
Blocked Vent Pressure Switch
Air ow and blocked vent status are continuously
monitored by the Pennant ignition control, at the
control’s PSW terminal.
At the start of an ignition sequence, if the ignition
control sees power at PSW for 30 seconds, but the
combustion blower has not yet been energized by the
control (F1 and F2), an air ow fault is signaled. The
ignition control will remain in this fault mode, with
the blower off. If the power to PSW is removed while
there is still a call for heat, the ignition sequence will
start again, but the main valves will not be energized
until PSW sees power during the ignition sequence.
At the start of an ignition sequence, the control
sends the combustion blower output (F1 and F2). If the
control does not see power at PSW for more than 30
seconds, an airow fault is signaled, and the control
will remain in this fault mode, with the blower on. If
proper airow is later detected on PSW, the control
begins a pre-purge and a normal trial for ignition.
If the PSW signal is lost while the Pennant is
ring, the control will immediately de-energize the
gas valve terminal (MV). The blower will remain on
for the post-purge period (45 seconds), and the control
will continue to monitor the PSW input. If the signal
is detected during the post-purge period, a normal trial
for ignition will begin, starting with the 15-second
pre-purge. If the signal is not detected during the postpurge, the control will lockout with the blower off.
6.6 Programming the Temperature Control
6.6.1 Initial Controller Start-Up
When the Pennant is rst powered up, the
temperature control display will show “801” (for a
water heater) or “802” (for a boiler) for approximately
one second. The default temperature parameter “°F1”
is then displayed for approximately one second, which
indicates that the default temperature parameter is
from thermistor 1, and is displaying in °F. Then, the
temperature at thermistor 1 will be displayed.
To display the temperature at thermistor 2, push
either the upper or lower button on the temperature
controller, to the right of the display. Thermistor 2
reading will be displayed for 5 seconds. To make the
thermistor 2 reading the default display, or to show the
temperatures in °C, program the control as shown in
sections 6.6.6 and 6.6.7.
6.6.2 Display Denitions
Tables 10 and 11 also show this information,
consolidated for quick reference.
Default Temperature Display – This is what
the user chooses to have displayed normally on
the controller. It can be either the temperature at
thermistor 1 (rt1) or at thermistor 2 (rt2) if used. While
the default temperature is displayed, the user may look
at the other temperature by pressing the upper or lower
button on the control. To access the programming
menu from here, press and hold the upper and lower
buttons at the same time until “SEL” is displayed.
SEL – Displayed when the upper and lower
buttons on the control are pressed and held while
the default temperature is displayed. This indicates
that you are entering the programming mode. When
the buttons are released, the rst menu item, Ch1, is
displayed. If no buttons are pressed in 30 seconds, the
control will return to the default display.
Ch1 – Control loop 1 (thermistor 1). This is the
rst display shown after entering the programming
mode. It is related to the Pennant temperature sensor,
thermistor 1. To view or make changes to the Ch1
parameters, press and hold the upper and lower
buttons at the same time. The sub menu items are
then displayed, one after another at approximately
two-second intervals. When the buttons are released,
the parameter that is showing can be changed by
pressing the upper or lower buttons. The new value is
functional immediately. To get to the next parameter,
press and hold both buttons again. After 30 seconds of
no button activity, the displays goes back to the default
temperature.
SP1 – Control loop 1 (Pennant) temperature set
point. Factory default is 165°F (74°C) for boilers,
and 130°F (54°C) for water heaters. It is adjustable
130°F to 220°F (54°C to 104°C) for boilers and 130°F
to 190°F (54°C to 88°C) for water heaters. Stage 1
is energized when the temperature at the Pennant
sensor is less than or equal to SP1-td1. Stage 1 is deenergized when the temperature at the Pennant sensor
is greater than, or equal to SP1.
td1 – Control loop 1 (Pennant) temperature set
point differential. Factory default is 10°F (6°C) for
boilers and 5°F (3°C) for water heaters. It is adjustable
from 2°F to 20°F (1°C to 11°C). This denes the
temperature below the setpoint that stage 1 is
energized on a fall in temperature.
Page 28
Pennant 200, 300, 400
Page 29
LAARS Heating Systems
Display Symbol
Main
Menu
SEL
Ch1
Ch2
Menu
Sub
°F1
(°C1)
SP1
td1
St2
StdStage 2 Delay
En2Status of Ch2on or oFFon
Function
Selected
Default
Temperature
Display (dEF)
Ch1
Temperature
Set Point
On/Off
Temperature
Differential
Stage 2
Temperature
Differential
Adjustment
Range
N/A°F1
130°F to
220°F
(54°C to
104°C)
2°F to 20°F
(1°C to 11°C)
0°F to 20°F
(0°C to 11°C)
0 to 300
seconds
Factory
Default
165°F
10°F
10 s
5°F
Description
°F1 indicates the temperature sensed by thermistor 1 is
normally displayed.
When the upper and lower buttons are pressed and
held, SEL is displayed, indicating that you are entering
the programming mode of the controller.
Stage 1 energized when the temperature is less than or
equal to SP1-td1.
Stage 1 energized when the temperature is less than or
equal to SP1-td1.
As long as stage 1 is successful, stage 2 is energized
Std seconds after the temperature is less than or equal
to SP1-td1-St2. If St2=0, stage 2 is energized after the
Std time delay.
As long as stage 1 is successful, stage 2 is energized
Std seconds after the temperature is less than or equal
to SP1-td1-St2. If St2=0, stage 2 is energized after the
Std time delay.
Enables or disables loop 2, so the Pennant control
knows whether or not to recognize that input.
Ch2
SP2
td2
ICE
EP
dEF
UnI
Table 10. Water Heater Parameters
Temperature
Set Point
On/Off
Temperature
Differential
Enable
response
to low temp
detection
Enable
auxiliary
exercise
Default
Temperature
Display
Selection
Units Selection
– Temperature
Scale
35°F to 240°F
(2°C to
116°C)
2°F to 20°F
(1°C to 11°C)
on or oFFon
on or oFFon
rt1 or rt2
Sensor
Temperature
°F or °C°FToggles between displaying values in °F and °C.
180°F
5°F
rt1
Auxiliary is energized when the temperature is less than
or equal to SP2-td2
Auxiliary is energized when the temperature is less than
or equal to SP2-td2
Enables and disables the low temp assistance. Auxiliary
is energized when the temperature is less than 40°F
(4°C) and is de-energized when it is greater than 45°F
(7°C).
Enables and disables the auxiliary exercise. When
EP=on, the auxiliary is energized for one minute if it has
not been energized over the last 72 hours.
Toggles between which sensor is used for the default
display temperature. rt1 is thermistor 1. rt2 is thermistor
2.
Pennant 200, 300, 400
Page 29
Display Symbol
Main
Menu
SEL
Ch1
Ch2
Menu
(°C1)
Sub
°F1
SP1
td1
St2
StdStage 2 Delay
En2Status of Ch2on or oFFon
Function
Selected
Default
Temperature
Display (dEF)
Ch1
Temperature
Set Point
On/Off
Temperature
Differential
Stage 2
Temperature
Differential
Adjustment
Range
N/A°F1
130°F to
220°F
(54°C to
104°C)
2°F to 20°F
(1°C to 11°C)
0°F to 20°F
(0°C to 11°C)
0 to 300
seconds
Factory
Default
165°F
10°F
5°F
10 s
Description
°F1 indicates the temperature sensed by thermistor 1 is
normally displayed.
When the upper and lower buttons are pressed and
held, SEL is displayed, indicating that you are entering
the programming mode of the controller.
Stage 1 energized when the temperature is less than or
equal to SP1-td1.
Stage 1 energized when the temperature is less than or
equal to SP1-td1.
As long as stage 1 is successful, stage 2 is energized
Std seconds after the temperature is less than or equal
to SP1-td1-St2. If St2=0, stage 2 is energized after the
Std time delay.
As long as stage 1 is successful, stage 2 is energized
Std seconds after the temperature is less than or equal
to SP1-td1-St2. If St2=0, stage 2 is energized after the
Std time delay.
Enables or disables loop 2, so the Pennant control
knows whether or not to recognize that input.
Ch2
SP2
td2
ICE
EP
dEF
UnI
Table 11. Boiler Parameters
Temperature
Set Point
On/Off
Temperature
Differential
Enable
response
to low temp
detection
Enable
auxiliary
exercise
Default
Temperature
Display
Selection
Units Selection
– Temperature
Scale
35°F to 240°F
(2°C to 116°C)
2°F to 20°F
(1°C to 11°C)
on or oFFon
on or oFFon
rt1 or rt2
Sensor
Temperature
°F or °C°FToggles between displaying values in °F and °C.
180°F
5°F
rt1
Auxiliary is energized when the temperature is less than
or equal to SP2-td2
Auxiliary is energized when the temperature is less than
or equal to SP2-td2
Enables and disables the low temp assistance. Auxiliary
is energized when the temperature is less than 40°F
(4°C) and is de-energized when it is greater than 45°F
(7°C).
Enables and disables the auxiliary exercise. When
EP=on, the auxiliary is energized for one minute if it has
not been energized over the last 72 hours.
Toggles between which sensor is used for the default
display temperature. rt1 is thermistor 1. rt2 is thermistor
2.
Page 30
Pennant 200, 300, 400
Page 31
LAARS Heating Systems
St2 – Stage 2 temperature differential, for 2-stage
units. Factory default is 5°F (3°C). It is adjustable
from 0°F to 20°F (0°C to 11°C). Stage 2 (high re) is
energized after the Std time delay, which begins when
the Pennant sensor reads less than or equal to SP1-td1St2. When set at 0°F/C, stage 2 is energized using only
the time delay Std.
Std – Stage 2 time delay. Default is 10 seconds.
It is adjustable from 0 to 300 seconds. Std and St2
work together to determine when stage 2 (high re) is
activated on a two-stage unit.
Ch2 – Control loop 2 (thermistor 2). It is
accessed by pressing and holding the upper and lower
buttons, so that SEL appears, and then pressing one
of the buttons to scroll until Ch2 appears. This allows
programming access for the auxiliary thermistor.
En2 – Status of control loop 2, either on or off.
Default is on. Thermistor 2 will not be recognized
when En2 is off. (ICE and EP can override Ch2.)
SP2 – Control loop 2 (auxiliary) temperature
setpoint. Factory default is 180°F (82°C) for boilers,
and 125°F for water heaters. It is adjustable 35°F to
240°F (2°C to 116°C) for boilers and 65°F to 190°F
(18°C to 88°C) for water heaters. The Pennant is called
for heat and the auxiliary contacts are closed when
the temperature at the secondary sensor is less than or
equal to SP2-td2. The Pennant call for heat ends, and
the auxiliary contacts are opened when the temperature
at the secondary sensor is greater than, or equal to SP2.
td2 – Control loop 2 (auxiliary) temperature
setpoint differential. Factory default is 5°F (3°C). It
is adjustable from 2°F to 20°F (1°C to 11°C). This
denes the temperature below the setpoint that the
Pennant is called for heat and the auxiliary contacts are
closed on a fall in temperature.
ICE – Enables response from the low temperature
protection feature. It can be turned on or off, and the
default is on. When it is enabled, the Pennant is called
for heat and the auxiliary contacts are energized when
the temperature sensor detects less than 40°F (4°C),
and are de-energized when the temperature rises above
45°F (7°C).
EP – Enables the exerciser feature. It can be
turned on or off, and the default is on. When it is
enabled, the auxiliary contacts are closed for one
minute, if they have not been closed over the last 72
hours.
dEf – Default temperature display. Factory
default is rt1, which is the temperature at the Pennant
sensor (thermistor 1). The user may choose rt2, which
is the temperature at the auxiliary sensor (thermistor
2). To access this, press and hold both upper and lower
buttons. When “SEL” is displayed, press either the
upper or lower button, until “dEf” is displayed.
UnI – Allows the user to choose between °F and
°C. Factory default is °F. To access this, press and
hold both upper and lower buttons. When “SEL” is
displayed, press either the upper or lower button, until
“UnI” is displayed.
6.6.3 Changing Control Loop 1
Parameters
There are four parameters that affect the
operation of control loop 1. SP1 is the setpoint. td1
is the temperature differential. St2 is the stage 2
differential (when applicable) and Std is the stage 2
time delay. To change any of these parameters:
1. While the default temperature is displayed, press
and hold the upper and lower buttons together
until SEL is displayed.
2. Release the buttons, and CH1 will be displayed.
3. Within 30 seconds, press and hold the upper and
lower buttons together until the parameter you
want to change is displayed.
4. Release the buttons to displayed the value of that
parameter.
5. Within 30 seconds, press the upper button
to increase the value, or the lower button to
decrease the value of the parameter.
6. When the desired value is shown, stop pushing
the buttons. The revised value is effective
immediately.
7. In 30 seconds of button inactivity, the display
reverts back to the default temperature, and the
new value is stored in nonvolatile memory.
6.6.4 Enabling and Disabling Control
Loop 2
The Pennant must be told to recognize control
loop 2, which uses thermistor 2. To enable or disable
control loop 2:
1. While the default temperature is displayed, press
and hold the upper and lower buttons together
until SEL is displayed.
2. Release the buttons, and CH1 will be displayed.
3. Within 30 seconds, press the upper (or lower)
button. CH2 will be displayed.
4. Within 30 seconds, press and hold the upper and
lower buttons together until En2 is displayed.
5. Release the buttons. The current state, on or oFF,
will be displayed.
6. Within 30 seconds, press the upper (or lower)
button to toggle the En2 state, between on and
oFF.
7. When the desired state is shown (on for enable,
and oFF for disable), stop pushing the buttons.
The revised state is effective immediately.
8. In 30 seconds of button inactivity, the display
reverts back to the default temperature, and the
En2 selection is stored in nonvolatile memory.
6.6.5 Changing Control Loop 2
Parameters
There are ve parameters that affect the
operation of control loop 1. En2 is the status. SP2 is
the setpoint. td2 is the temperature differential. ICE
Pennant 200, 300, 400
Page 31
enables response to low temperature detection. EP
enables energizing of the auxiliary contacts for the
exercize feature. To change any of these parameters:
1. While the default temperature is displayed, press
and hold the upper and lower buttons together
until SEL is displayed.
2. Release the buttons, and CH1 will be displayed.
3. Within 30 seconds, press the upper (or lower)
button. CH2 will be displayed.
4. Within 30 seconds, press and hold the upper and
lower buttons together until the parameter you
want to change is displayed.
5. Release the buttons to displayed the value of that
parameter.
6. Within 30 seconds, press the upper button
to increase the value, or the lower button to
decrease the value of the parameter, or to toggle
the selection.
7. When the desired value is shown, stop pushing
the buttons. The revised value is effective
immediately.
8. In 30 seconds of button inactivity, the display
reverts back to the default temperature, and the
new value is stored in nonvolatile memory.
6.6.6 Changing the Default Temperature
Selection
You may change what is normally displayed on
the temperature control to show the temperature at
either thermistor 1 or thermistor 2:
1. While the default temperature is displayed, press
and hold the upper and lower buttons together
until SEL is displayed.
2. Release the buttons, and CH1 will be displayed.
3. Within 30 seconds, press the upper (or lower)
button. CH2 will be displayed.
4. Within 30 seconds, press the upper (or lower)
button. dEf will be displayed.
5. Within 30 seconds, press and hold the upper and
lower buttons together until the current default
(rt1 or rt2) is displayed.
6. Release the buttons.
7. Within 30 seconds, press the upper (or lower)
button to toggle the dEf selection, between rt1
and rt2.
8. When the desired thermistor is shown (rt1
is thermistor 1, and rt2 is thermistor 2), stop
pushing the buttons. In 30 seconds of button
inactivity, the display shows the selected default
temperature, and the selection is stored in
nonvolatile memory, as the default temperature
display.
6.6.7 Changing the Display Units
You may change what is normally displayed on
the temperature control to show the temperature in
either °F or °C:
1. While the default temperature is displayed, press
and hold the upper and lower buttons together
until SEL is displayed.
2. Release the buttons, and CH1 will be displayed.
3. Within 30 seconds, press the upper (or lower)
button. CH2 will be displayed.
4. Within 30 seconds, press the upper (or lower)
button. dEf will be displayed.
5. Within 30 seconds, press the upper (or lower)
button. UnI will be displayed.
6. Within 30 seconds, press and hold the upper and
lower buttons together until the current default
(°F or °C) is displayed.
7. Release the buttons.
8. Within 30 seconds, press the upper (or lower)
button to toggle the UnI selection, between °F
and °C.
9. When the desired unit is shown, stop pushing the
buttons. In 30 seconds of button inactivity, the
display shows the selected default temperature
with the selected units, and the selection is stored
in nonvolatile memory, as the default temperature
units.
6.7 Operating the Burner and Set-Up
6.7.1 Set-Up for 0 to 2500 Feet Altitude
The setup must be checked before the unit is put
in operation. Problems such as failure to start, rough
ignition, strong exhaust odors, etc. can be due to
improper setup. Damage to the Pennant resulting from
improper setup is not covered by the limited warranty.
1. Using this manual, make sure the installation
is complete and fully in compliance with the
instructions.
2. Determine that the appliance and system are
lled with water and all air has been bled from
both. Open all valves.
3. Observe all warnings on the Operating
Instructions label and turn on gas and electrical
power to appliance.
4. Switch on the appliance power switch located on
the right side of the unit.
5. The Pennant will enter the start sequence, as long
as the unit is being called for heat. The blower
and pump come on for pre-purge, then the ignitor
warm-up sequence starts and after the ignitor
warm-up is complete and all safety devices are
veried, the gas valves open. If ignition doesn’t
occur, check that there is proper gas supply.
Wait 5 minutes and start the unit again. During
initial start up, air in the gas line may cause the
Pennant to "lock out" during the rst few trials
Page 32
Pennant 200, 300, 400
Page 33
LAARS Heating Systems
for ignition. If the ignition control locks out, reset
by cycling the power off and on using the main
power switch on the right side of the cabinet.
6. When the unit is running, the supply gas pressure
must be checked. Inlet gas pressure must not
exceed 13 in. w.c. (3.2 kPa). The minimum inlet
gas pressure is 5 in. w.c. (1.2 kPa) and 8 in. w.c.
(2 kPa) for LP.
7. Once the inlet gas pressure is veried, the
outlet gas pressure from each valve (manifold
gas pressure) must be checked, and adjusted, if
necessary. The manifold gas pressure must be 3.0
in. w.c. (0.62 kPa) for natural gas and 9.0 in. w.c.
(2.2 kPa) for LP.
8. Complete the setup by checking the CO2 at the
outlet of the unit. The CO2 should be 8% for
natural gas, or 9.2% for LP.
9. After placing the appliance in operation, the
Burner Safety Shutoff Device must be tested.
To test:
(a) Close gas shutoff valve with burner
operating.
(b) The ame will go out and blower will
continue to run for the post purge cycle.
Three attempts to light will follow. Ignition
will not occur as the gas is off. The ignition
control will lockout, and will have to be
reset by cycling the power before the unit
will operate.
(c) Open gas shutoff valve. Restart the
appliance. The ignition sequence will
start again and the burner will start. The
appliance will return to its previous mode
of operation.
6.7.2 High Altitude Adjustment and
Set-Up
High altitude adjustment must not be made on
appliances operating at elevations below 2500 ft. (762
m).
No orice changes are required to adjust the
Pennant appliances for high altitude. High altitude
adjustment is accomplished by adjustment of the air
shutter. A CO2 or O2 analyzer is required to make these
adjustments.
Start the adjustment process by checking the CO2
in the “as installed” condition. Adjust the air shutter(s)
so that the CO2 is about 8% or the O2 is about 6.8%
for appliances operating on natural gas. For appliances
operating on LP Gas adjust the air shutter(s) so that the
CO2 is about 9.2% or the O2 is about 6.8%.
If the appropriate CO2 / O2 levels cannot be
achieved by adjusting the air shutter. Contact the
Technical Services Department at (800) 900-9276.
The amount of derate will vary depending on
heating value of the fuel and the elevation at the
installation site.
Caution
Should any odor of gas be detected, or if the gas
burner does not appear to be functioning in a
normal manner, close main shutoff valve, do not
shut off switch, and contact your heating contractor,
gas company, or factory representative.
Attention
Si vous sentez une odeur de gaz ou si le brûleur
à gaz ne parait pas fonctionner de manière
normale, fermez la vanne d’isolement, ne fermez
aucun interrupteur, et appelez votre entreprise de
chauffage, la compagnie de gaz ou un représentant
du fabricant..
6.8 Shutting Down the Pennant
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. If freezing is anticipated, drain the Pennant and
be sure to also protect building piping from
freezing.
This step to be performed by a qualied
service person.
6.9 To Restart the Pennant
If drained, follow Section 6.1 in this manual for
proper lling and purging.
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
4. Set the aquastat or thermostat to its lowest
setting.
5. Open all manual gas valves.
6. Reset all safety switches (pressure switch,
manual reset high limit, etc.).
7. Set the temperature controller to the desired
temperature setting and switch on electrical
power.
8. Burner will go through a pre-purge period and
ignitor warm-up period, followed by ignition.
SECTION 7.
Maintenance
7.1 System Maintenance
1. Lubricate the system water-circulating pump, if
required, per the instructions on the pump.
2. If a strainer is employed in a pressure reducing
valve or the piping, clean it every six months.
3. Inspect the venting system for obstruction or
leakage at least once a year. Periodically clean
the screens in the vent terminal and combustion
air terminal (when used).
Pennant 200, 300, 400
Page 33
4. Keep the appliance area clear and free from
combustible materials, gasoline, and other
ammable vapors and liquids.
5. If the appliance is not going to be used for
extended periods in locations where freezing
normally occurs, it should be isolated from the
system and completely drained of all water. All
systems connected to it should also be drained or
protected from freezing.
6. Low water cutoffs, if installed, should be
checked every 6 months. Float type low water
cutoff should be ushed periodically.
7. Inspect ue passages, and clean with brushes/
vacuums, if necessary. Sooting in ue passages
indicates improper combustion. Determine the
cause and correct.
8. Inspect the vent system and air intake system,
and if the vent system is Category III, ensure
that all joints are sealed properly. If joints need
to be resealed, follow venting manufacturer's
instructions to clean and reseal vent system.
7.2 Appliance Maintenance and
Component Description
Only genuine Laars replacement parts should be used.
Caution
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
Attention
Lors d’entretien ou de réparation des commandes,
étiquetez tous les câbles avant de les déconnecter.
Des erreurs de câblage peuvent provoquer des
fonctionnements incorrects et dangereux. Après
toute intervention d’entretien ou de réparation,
vérifier que l’appareil fonctionne correctement.
The gas and electric controls on the appliance
are engineered for long life and dependable operation,
but the safety of the equipment depends on their
proper functioning. It is strongly recommended that
a qualied service technician inspect the basic items
listed below every year.
a. Ignition control
b. Ignitor
c. Water temperature control
d. Automatic gas valve
e. Pressure switches and tubing
f. Blower
g. High limit
h. Pump (if required)
i. Low water cutoff
j. Relays
k. Flow switch
l. Gas train
m. Control components
7.2.1 Burners
Close main manual gas valve before proceeding.
Checking the burners for debris - Remove the ignitor/
burner access panel and ignitor, and inspect the
burners through the ignitor hole using a ashlight to
illuminate. If there is any indication of debris on the
burners that is visible, all the burners will need to be
inspected more thoroughly. Remove the gas manifold
assemblies and the burner assemblies. Inspect the
burners. Clean burners, if necessary, by blowing
compressed air from the outside of the burners into
the center of the burner. A dirty burner may be an
indication of improper combustion or dirty combustion
air. Determine the cause, and correct. Replace the
burners in the reverse order.
7.2.2 Filter
The lter used in the Pennant is washable and has
an 80% arrestance rating. Since the lter is washable,
it will only need replacement occasionally. If lter
replacement is needed, it should only be replaced with
a factory part. Inspect the air lter monthly, or more
often in dirty environments. If there is debris on the
air lter, remove it from the lter frame, and wash
it with mild soap and water. Ensure that the lter is
completely dry before reinstalling.
7.2.3 Gas Valves
The gas valves are designed to operate with
supply pressures of 4-13 in. w.c. (1.0 to 3.2 kPa).
To remove a valve, shut off 120-volt power
and the manual gas shutoff valve. Remove the front
panels from the unit. Disconnect the wires to the valve.
Disengage the unions before and after the valve, and
remove the valve. Pull the pipe nipples from the inlet
and outlet of the valve, and clean the threads on the
pipe nipples for reuse. Apply new tape or pipe dope
to the pipe nipples (threaded joints should be coated
with piping compound resistant to action of liqueed
petroleum gas), and reinstall in reverse order. Turn
on manual gas shutoff valve and 120 volt power and
check appliance operation and tightness of gas valve
connections.
7.2.4 Manual Reset High Limit Control
The high limit switch is a manual reset, nonadjustable switch with a remote bulb-type sensor.
Switches for water heaters and low temperature boiler
models are set at 200°F. Switches for standard boilers
are set at 240°F.
The control is located behind the front door, on a
panel in front of the blower. The probe is in the outlet
side of the header.
Page 34
Pennant 200, 300, 400
Page 35
LAARS Heating Systems
To reset the switch, unscrew the black cover that
is over the reset button, and push the button. Replace
the cover after the switch is reset.
To replace, shut off power to the appliance.
Remove the cover that is over the button, and remove
the nut that is around the button. Pull the control
through the panel, and remove the spade terminals.
Replace in reverse order.
7.2.5 Temperature Control
The temperature control works with the ignition
control to ensure proper operation of the Pennant.
To replace the control, shut off the 120-volt power
to the appliance. Remove the cover from the control
panel, and remove the mounting screws to remove the
controller. Replace in reverse order.
7.2.6 Ignition Control
The ignition control controls the hot surface
ignitor and proves that the ame signal is appropriate
for powering the gas valves. It also controls the
blower’s pre-purge and post-purge.
To replace a control, shut off the 120-volt power
to the appliance. Remove the cover from the control
panel. Remove the electrical connectors from the
ignition control. Take out the controller’s mounting
screws, and pull the controller out. Replace in reverse
order.
7.2.9 Flow Switch
The Pennant uses a paddle-type ow switch to
ensure that the unit has water ow before ignition is
allowed. To replace the ow switch, turn off the 120volt power to the appliance. Isolate the boiler or water
heater from the system by closing the isolation valves.
Caution
Water may be hot enough to scald. Allow water to
cool before proceeding.
Attention
L’eau peut être chaude au point de vous brûler.
Laissez refroidir l’eau avant d’intervenir.
Release pressure in the system by actuating
the pressure relief valves or eld supplied boiler
drain valve. Remove cover from the ow switch
and disconnect the wires. Unthread the ow switch
from piping. Ensure the new ow switch paddles are
trimmed to the same size as the original paddles, and
reinstall in the reverse order. For boiler and other static
pressure systems, restore the system pressure to the
original setting, (or 10 psi minimum).
7.2.10 Heat Exchanger Coil
7.2.7 Ignitor
The ignitor used is a 120v “Hot Surface” type.
It is energized whenever there is a call for heat and
switched off when ignition is established and the ame
has been sensed. To replace the ignitor, shut off the
120-volt power to the appliance, remove the ignitor/
burner access panel, disconnect the Molex connector,
remove the two mounting screws on the ignitor ange,
and pull the ignitor out. Install in reverse order, always
using a new ignitor gasket with the replacement
ignitor.
Caution
Ignitor gets hot. To avoid injury, handle the ignitor
with caution.
Attention
Le dispositif d’allumage devient très chaud.
Manipulez le dispositif d’allumage avec précaution.
7.2.8 Transformer
The Pennant’s transformer is not capable of
supplying control voltage for external devices such
as zone valves, which must have their own separate
power supply. Should a transformer need replacing,
shut off the 120-volt power. Unplug the transformer
wires, remove the mounting screws and remove the
transformer. Replace transformer in the reverse order.
WARNING
Black carbon soot buildup on a dirty heat exchanger
can be ignited by a random spark or flame thereby
creating a risk of fire or explosion. To prevent this
from happening, dampen the soot deposits with a
wet brush or fine water spray before servicing the
heat exchanger.
AVERTISSEMENT
L’accumulation de suie sur un échangeur thermique
sale peut s’enflammer au contact d’une étincelle ou
d’une flamme et présenter un risque d’incendie ou
d’explosion. Afin d’empêcher que cela se produise,
humidifier les dépôts de suie à l’aide d’une brosse
mouillée ou par une pulvérisation fine d’eau avant
d’effectuer l’entretien de l’échangeur thermique.
The Pennant has a premixed burner system.
These systems provide the burners with sufcient air
for complete combustion, and black carbon sooting is
seldom experienced. If sooting is suspected, view ports
for inspection of the heat exchanger are provided on
the side of the boiler. In the unlikely event that there is
a buildup of black carbon soot or other debris on the
heat exchanger, clean per the following:
1. Disconnect the electrical supply to the unit.
2. Turn off the gas supply by closing the manual gas
valve on the heater.
Pennant 200, 300, 400
Page 35
3. Disconnect and remove the wires, conduit and
sensors from all components that are attached to
the inlet/outlet header.
4. Isolate the heat exchanger from the water supply.
5. Disconnect the header anges from the inlet and
outlet.
6. Allow the heat exchanger to drain. Remove the
venting and remove the top, by removing the
screws that attach the top to the side panels.
Remove the side panels.
7. Remove the heat exchanger from the unit.
NOTE: Heat exchangers are heavy and may
require two people to remove to avoid personal
injury.
8. Clean the heat exchanger: A light accumulation
of soot or corrosion on the outside of the heat
exchanger can be easily removed. Use a wire
brush to remove loose soot and scale from the
heat exchanger.
9. NOTE: While the heat exchanger is out of the
unit, inspect the rewall refractory insulation.
Replace if necessary.
10. Inspect the inside of the copper tubes for scale
buildup. Scale can build up on the inner surface
of the heat exchanger tubes, which can restrict
water ow. If the tubes show signs of scaling,
clean the internal surface.
11. Reassemble in the reverse order, and check
appliance operation after start-up.
NOTE: The warranty does not cover damage
caused by lack of required maintenance, lack of
water flow, or improper operating practices.
SECTION 8.
Trouble Shooting
8.1 Resolving Lockouts
There are many causes of lockouts. The three
most common causes are: (1) inadequate gas supply,
(2) poor combustion, (3) ignitor failure.
1. Inadequate gas supply: Before proceeding, ensure
that the gas supply has not been shutoff or the LP
tank (LP boilers) is not empty. Then, restart the
boiler and observe the operational cycle. After
a 15-second fan pre-purge, the ignitor will heat
up for 40 seconds, and then the unit will light.
If it does not, check the gas supply pressure to
the appliance, after resetting the appliance and
attempting another start-up. The gas pressure to
the appliance must be above 5 in. w.c. (1.2 kPa)
throughout the entire start-up cycle. If it is not,
correct the supply problem (check gas valves or
supply piping). If the supply pressure is adequate,
consult the factory for assistance.
2. Poor Combustion: Poor combustion should be
suspected if there is a strong ue gas odor. The
odor may result from an improper gas/air ratio
(high or low O2 or CO2). Pennant appliances
operate best with 45% excess air (8% CO2 on
natural gas, 9.2% CO2 on LP). Check the CO2 of
the appliance and adjust if necessary.
3. Ignitor failure: If the boiler goes through a
normal start cycle but combustion does not
occur, ignitor failure should be suspected. Check
the ignitor by unplugging the ignitor plug and
measuring the ignitor resistance. It should be
50-80 ohms. If the resistance is not 50-80 ohms,
replace the ignitor. If the resistance is correct,
reset the boiler and check for 120 VAC at the
ignitor plug during the start cycle. If there is no
voltage, replace the faulty ignitor wire harness or
the ignition control.
8.2 Delayed Ignition — Possible Causes
A defective burner can cause a delayed ignition.
If the gas supply pressure is proper and the gas
valves are functioning properly, then burners should
be inspected. There should be no distortion or
perforations in the burners outside of the active burner
port area. Replace if indicated.
8.3 Short Cycling — Boiler
Boiler short cycling is caused when the load
on the boiler system swings rapidly causing frequent
cycling between call for heat and satised conditions.
This condition is greatly reduced on two stage units
or stage controlled multiple boiler systems which can
change heat input to better match the load. If short
cycling is a problem, it may be due to an oversized
boiler, improper control strategy, incorrect set points
or a load distribution problem. The boiler controls
must be set such that the heating loop temperature
setpoint, SP2 (if used), does not interfere with the
setpoint of the boiler operating control, SP1. If the
set points are correct and the system design, controls
scheme, etc. are xed, the temperature differentials
may be increased to reduce short cycling. If desired
temperature response is not achievable without short
cycling it may be necessary to install a buffer tank
in the system. Contact your Laars representative to
discuss possible remedies.
8.4 Short Cycling — Water Heater
Short cycling will generally occur only in
combination space heating and water heating
applications when the water heater is operating in the
space-heating mode. If the heating load drops below
the minimum input of the water heater for an extended
period, the water heater will have a tendency to short
cycle. If short cycling is frequently experienced,
regardless of the control’s attempt to limit it, the
heating load should be redistributed to control it.
Page 36
Pennant 200, 300, 400
Page 37
LAARS Heating Systems
If short cycling occurs in a water heater
application, it is probably caused by undersized
piping between the water heater and the storage tank
or by some other factor that restricts proper water
ow through the water heater. The cause should be
determined and corrected.
8.5 High Gas Consumption
Appliances operating with an improper air/fuel
ratio are very inefcient and consequently, have
very high gas consumption. Because efciency is
high when the CO2 is high (or O2 is low), appliances
operating with low CO2 or high O2 (especially LP
appliances) consume more gas. Adjust the CO2 or O2
for optimum efciency. If no combustion analyzing
equipment (CO2 or O2) is available then a proper
adjustment of the air/fuel ratio (CO2 or O2) cannot be
accomplished. The CO2 should be 8% at high re for
natural gas and 9.2% at high re for LP. To check the
CO2, rst verify that the supply gas pressure is within
5 to 13 in. w.c. (1.2 to 3.2 kPa). With the Pennant
running with all stages ring, set the air box pressure
to 1.8 in. w.c. (0.42 kPa) (as a starting point), by
adjusting the air shutter(s) at the intake of the fan(s).
Check the CO2, and adjust the air shutters if further
adjustment to the CO2 is needed.
8.6 Troubleshooting Pennant Controls
The eld wiring board along with the diagnostic
LEDs can be used to troubleshoot the Pennant
controls. Terminals on the eld wiring board are
provided as test points and allow troubleshooting of
most Pennant control functions from a single location.
The terminals are identied in the Ladder Wiring
Schematic (Figure 14).
Certain control elements may be connected in the
eld to the eld wiring board. In addition to the ladder
wiring schematic, refer to the Connection Diagram
(Figure 13) to verify that eld connections have been
made correctly.
The Pennant temperature control and ignition
control both have fault indicators. The temperature
control fault codes are shown in Table 12. The ignition
control fault codes are shown in Table 13.
signal received (K1 energizes and
the contacts close, but 24V is not
shown on the downstream side of
the K1 contact) (This code is normal
when operating in "Remote" mode.)
I-FIgnitor fault signal received from
ignition control
AFFAir ow fault
FLEFlame error – ame detected with
no call for heat
LocIgnition lockout signal received from
ignition control
ItoIgnition time-out
P1HRT1 sensor shorted or high out-of-
range temperature signal received
P1LRT1 sensor open or low out-of-
range temperature signal received
P2HRT2 sensor shorted or high out-of-
range temperature signal received
P2LRT2 sensor open or high out-of-
range temperature signal received
Table 12. Fault Codes.
LED State Indication
Steady On Control Fault
1 FlashAir Flow Fault
2 FlashesFlame Attempt With No Call For Heat
3 FlashesIgnition Lockout
4 FlashesBurner On
Table 13. Ignition Control LED Description
SECTION 9.
Replacement Parts
Only genuine Laars replacement parts should be used.
9.1 General Information
To order or purchase parts for the Laars Pennant,
contact your nearest Laars dealer or distributor. If
they cannot supply you with what you need, contact
Customer Service (see back cover for address,
telephone and fax numbers).
9.2 Parts List
Pennant 200, 300, 400
ItemDescriptionModel 200Model 300Model 400
COMBUSTION CHAMBER COMPONENTS
See Figure 15
1Base Assembly2C10003C10004C1000
2Support, Tile Notch2C20193C20194C2019
3Chamber, Refractory, Heat ExchangerT2108802T2108803T2108804
4Assembly, Front Panel, Combustion Chamber2C20233C20234C2023
5Panel, Rear, Combustion Chamber2C20063C20064C2006
6Panel, Top, Combustion Chamber2C20013C20014C2001
7Chamber, Right Side, Bottom2C22012C22012C2201
8Chamber, Left Side, Bottom2C26012C26012C2601
9Chamber, Side, Top2C20022C20022C2002
10Panel, Right Side, Air Box2C20162C20162C2016
11Panel, Left Side, Air Box2C20152C20152C2015
12Weldment, Duct, Blower2C25002C25002C2500
13Panel, Top, Air Box2C20083C20084C2008
14Plate, Spacer, Burner/Manifold2C20173C20174C2017
15Panel, Front, Air Box2C20093C20094C2009
16Assembly, Exhaust Vent, Vertical2C21003C21004C2100
17Weldment, Flue2C23002C23002C2300
18Assembly, Air Shutter, Blower2C50002C50002C5000
19Assembly, Filter Housing2C38002C38002C3800
20Media, Filter2C38032C38032C3803
21Clip, Retaining, Filter MediaF2022300F2022300F2022300
22Hose, Duct, Flexible, 4” Dia.P0101402P0101403P0101404
23Blower/MotorE0254000E0254000E0254000
24Gasket, BlowerS2104400S2104400S2104400
25Assembly, Sight Glass109560001095600010956000
26Ignitor, Hot SurfaceW2002300W2002300W2002300
27Gasket, BurnerS2102300S2102300S2104300
28Burner, Main (Pressure Port)L0063301L0063301L0063301
29Burner, Main L0063300L0063300L0063300
30Gasket, Blower DuctS2104500S2104500S2104500
31Kit, Insulation, Combustion ChamberT2015808T2015809T2015810
32Gasket, Flue HousingS2104600S2104600S2104600
Page 37
JACKET COMPONENTS
See Figure 16
40Panel, Front, Jacket2C33203C33204C3320
41Panel, Rear, Jacket2C32203C32204C3220
42Panel, Top, Jacket2C30213C30214C3021
43Panel, Jacket, Control Access2C30193C30194C3019
44Panel, HX Side Access, Jacket2C36202C36202C3620
45Panel, Right Side, Upper, Jacket2C36212C36212C3621
46Panel, Right Side, Jacket2C35202C35202C3520
47Panel, Left Side, Jacket2C34202C34202C3420