PENBERTHY SIGHT FLOW INDICATORS
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Before installation these instructions must be fully read and understood
TABLE OF CONTENTS
Product Warranty ...........................................2
1 About the Manual ...................................2
2 Introduction ............................................2
2.1 Features and Specifications ...................... 2
Operating Temperatures ........................... 3
2.3 Application Data ......................................... 3
3 Inspection and Performance
Confirmation ...........................................4
3.1 Receiving Inspection................................... 4
3.2 User's Rating Inspection ............................ 4
4 Installation .............................................4
4.1 Effect of Related Piping and Precautions ... 4
4.2 Positioning of Specific Models ................... 4
4.3 Bolt Torque ................................................. 4
5 Operation ................................................5
5.1 Pre-Operational Check. ............................. 5
5.2 Hydrostatic Pressure Test ......................... 5
5.3 Operating..................................................... 5
6 Maintenance ...........................................6
6.1 Preventative Maintenance ......................... 6
6.2 Maintenance Procedures. .......................... 6
6.3 Troubleshooting .......................................... 7
7 Removal-Disassembly-Reassembly ......7
7.1 Disassembly ................................................ 7
7.2 Reassembly................................................. 7
8 Disposal at End of Useful Life .................8
9 Telephone Assistance ............................8
10 Exploded Parts Drawing .........................9
TABLES AND FIGURES
Table 1 Design Ratings at Maximum and
Minimum Operating Temperatures .... 3
Table 2 Bolt Torque Values .............................. 5
Figure 1 Bolt Tightening Sequence ................... 5
Figure 2 Pipe Threads ........................................ 7
Figure 3 Bolt Loosening Sequence .................... 7
Figure 4 Exploded Parts Drawing ...................... 9
Emerson.com/FinalControl
© 2018 Emerson. All Rights Reserved. VCIOM-07125-EN 19/01
PENBERTHY SIGHT FLOW INDICATORS
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
PRODUCT WARRANTY
Emerson warrants its Penberthy products as designed and manufactured by Emerson to be free of defects in the material and workmanship for a period of one year after the date of installation or eighteen months after the date of manufacture, whichever is earliest. Emerson will, at its option, replace or repair any products which fail during the warranty period due to defective material or workmanship.
Prior to submitting any claim for warranty service, the owner must submit proof of purchase to Emerson and obtain written authorization to return the product. Thereafter, the product shall be returned to Emerson, with freight paid.
This warranty shall not apply if the product has been disassembled, tampered with, repaired or otherwise altered outside of Emerson factory, or if it has been subject to misuse, neglect or accident.
The responsibility of Emerson hereunder is limited to repairing or replacing the product at its expense. Emerson shall not be liable for loss, damage or expenses related directly or indirectly to the installation or use of its products, or from any other cause or for consequential damages. It is expressly understood that Emerson is not responsible for damage or injury caused to other products, buildings, personnel or property, by reason of the installation or use of its products.
1 ABOUT THE MANUAL
This manual has been prepared as an aid and guide for personnel involved in installation or maintenance. All instructions must be read and understood thoroughly before attempting any installation, operation or maintenance.
IMPORTANT
Penberthy does not have any control over the manner in which its sight flow indicator is handled, installed, or used, and Penberthy cannot and does not warrant or guarantee that the sight flow indicator is suitable or compatible with the user's specific application.
WARNING
Always wear safety glasses when installing, servicing or operating a sight flow indicator. Failure to follow any instruction could possibly result in a malfunction of the sight flow indicator or glass breakage with resulting sudden release of pressure causing serious personal injury or property damage.
2 INTRODUCTION
2.1 Features and Specifications
Penberthy sight flow indicators are designed for the observation of flow in a process line. They are available in a variety of models, sizes, and connection styles. The user should refer to Penberthy dimension sheets to determine specific models and connection styles available.
THIS IS EMERSON'S SOLE WARRANTY AND IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED WHICH ARE HEREBY EXCLUDED, INCLUDING IN PARTICULAR ALL WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
This document and the warranty contained herein may not be modified and no other warranty, expressed or implied, shall be made by or on behalf of Emerson unless made in writing and signed by the General Manager or Director of Engineering of Emerson.
2
PENBERTHY SIGHT FLOW INDICATORS
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
2.2 Design Ratings at Maximum and Minimum Operating Temperatures
TABLE 1 - MAXIMUM DESIGN RATINGS WITH TEMPERED GLASS
Gasket Material
®
Body material Temp rating
Iron -20°F [-29°C] to +100°F [38°C] 250 [1.72] 250 [1.72] 250 [1.72]
at +500°F [260°C] 170 [1.17] 170 [1.17] 170 [1.17]
Bronze -20°F [-29°C] to +150°F [66°C] 225 [1.55] 225 [1.55] 225 [1.55]
at +400°F [204°C] 170 [1.17] 170 [1.17] 170 [1.17]
Carbon steel -20°F [-29°C] to +100°F [38°C] 285 [1.97] 285 [1.97] 285 [1.97]
at +500°F [260°C] 170 [1.17] 170 [1.17] 170 [1.17]
316 Stainless steel -300°F [-184°C] to +100°F [38°C] 275 [1.90] 275 [1.90] 275 [1.90]
at +500°F [260°C] 170 [1.17] 170 [1.17] 170 [1.17]
Body material Temp rating
Iron -20°F [-29°C] to +100°F [38°C] 250 [1.72] 250 [1.72] 250 [1.72] 250 [1.72]
at +250°F [121°C] 225 [1.55] at +300°F [149°C] 215 [1.48] at +400°F [204°C] 200 [1.38] 200 [1.38]
Bronze -20°F [-29°C] to +150°F [66°C] 225 [1.55] 225 [1.55] 225 [1.55] 225 [1.55]
at +250°F [121°C] 205 [1.41] at +300°F [149°C] 195 [1.34] at +400°F [204°C] 170 [1.17] 170 [1.17]
Carbon steel -20°F [-29°C] to +100°F [38°C] 285 [1.97] 285 [1.97] 285 [1.97] 285 [1.97]
at +250°F [121°C] 245 [1.69] at +300°F [149°C] 230 [1.59] at +400°F [204°C] 200 [1.38] 200 [1.38]
316 Stainless steel -20°F [-29°C] to +100°F [38°C] 275 [1.90]
-65°F [-54°C] to +100°F [38°C] 275 [1.90] 275 [1.90]
-300°F [-184°C] to +100°F [38°C] 275 [1.90] at +250°F [121°C] 225 [1.55] at +300°F [149°C] 215 [1.48] at +400°F [204°C] 195 [1.34] 195 [1.34]
Teflon
Viton
®
psig [MPa] IFG-5500
®
Gasket Material
psig [MPa]
PCTFE Neoprene
Grafoil
®
®
Buna "N"
To determine maximum allowable working pressure for a specific temperature within the design limits stated above, the user should refer to Penberthy dimension sheets, or when provided, the specifically stated design limits on a Penberthy product proposal.
2.3 Application Data
NOTE
For specific application data within the above ranges, consult the Penberthy product proposal for the specific model and size sight flow indicator, or request Penberthy to supply the applicable Technical Data Bulletin.
WARNING
Never exceed these design ratings or application data limits. Exceeding design ratings or application data limits can cause serious personal injury or property damage.
3
PENBERTHY SIGHT FLOW INDICATORS
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
3 INSPECTION AND PERFORMANCE CONFIRMATION
3.1 Receiving Inspection
Upon receipt of sight flow indicator, check all components carefully for damage incurred in shipping. If damage is evident or suspected, do not attempt installation. Notify carrier immediately and request a damage inspection.
3.2 Users' Rating Inspection
The user should confirm that:
1. The sight flow indicator model number and
pressure/temperature rating stamped on nameplate (163) conforms to the description on the user's purchase order.
2. The operating conditions described in
the purchase order agree with the actual conditions at the installation site.
3. The actual operating conditions at the
installation site are within the application data shown on the Penberthy Technical Data Bulletin referred to above.
4. The materials of construction of the sight
flow indicator are compatible with both the contained fluid and surrounding atmosphere in the specific application.
4.1 Effect of Related Piping and Precautions
1. Do not impose system piping loads on sight flow indicator. Unit is not designed to be a load bearing component. Piping must be supported and aligned with sight flow indicator end connections to reduce the possibility of stresses imposed on the unit.
2. Locate the sight flow indicator where it can be easily seen.
3. Locate the sight flow indicator away from areas where objects may be dropped, thrown, or generally allowed to effect contact with the viewing window glass.
4. Locate the sight flow indicator so it is protected from dust, grit, tools, and any other objects which may scratch, chip, or break the viewing window glass.
5. Locate the sight flow indicator so it is protected from external thermal shock, such as would be imposed on a unit in a high temperature application when exposed to a cold air blast or a cold water wash.
WARNING
Failure to mount, protect, and locate sight flow indicator as described above can cause serious personal injury or property damage.
IMPORTANT
If the size, model or performance data of the sight flow indicator as received does not conform with any of the criteria above, do not proceed with installation. Contact an authorized Penberthy distributor for direction on what to do.
4 INSTALLATION
Use qualified experienced personnel who are familiar with this equipment and thoroughly understand all the instructions in this manual for the installation of this equipment.
Refer to Penberthy dimension sheets or Penberthy product proposal to obtain dimensional information for the specific size and model sight flow indicator.
WARNING
Do not proceed with installation unless the glass has been examined and is free of imperfections, and the connections and inside of the sight flow indicator have been cleaned and are free of any foreign materials. Glass that is chipped or scratched is weakened and should not be used under any circumstances. Pressure/temperature ratings within Table 1 are no longer valid for glass that is weakened. Failure to comply may cause a sudden release of pressure with resulting severe personal injury or property damage.
4.2 Positioning of Specific Models
1. Flapper models may be mounted in a horizontal plane provided the flapper closes over the inlet port by gravity when there is no flow.
2. Plain or rotator models may be mounted in any acceptable position.
3. Drip tube models should be mounted in a vertical plane with the flow arrow pointing downward.
4.3 Bolt Torque
IMPORTANT
Prior to any bolt torque checks, the sight flow indicator must be relieved of all pressure or vacuum, been allowed to reach ambient temperature, and been drained or purged of all fluids. Bolt torque is vital to the proper operation of a sight flow indicator. Gaskets compress over a period of time; therefore, bolt torque should be checked, and bolt torque values should be brought up to those recommended in Table 2 by following the bolt tightening sequence Figure 1.
Check the exploded view Figure 4 for the location of the liquid inlet and outlet connections, and for the location and direction of the flow arrow to insure correct hook up.
4
PENBERTHY SIGHT FLOW INDICATORS
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
TABLE 2 - BOLT TORQUE VALUES
Unit Size in inches
¼ & ⅜ 2 to 3 [3 to 4] 2 to 4 [3 to 6] 2 to 4 [3 to 6] 2 to 3 [3 to 4] 2 to 4 [3 to 6] ½ & ¾ 2 to 4 [3 to 6] 3 to 5 [4 to 7] 5 to 7 [7 to 10] 3 to 5 [4 to 7] 3 to 5 [4 to 7] 1 3 to 6 [4 to 8] 5 to 8 [7 to 11] 9 to 12 [12 to 16] 4 to 7 [6 to 10] 5 to 8 [7 to 11] 1¼ & 1½ 7 to 10 [10 to14] 10 to 13 [14 to 18] 18 to 21 [24 to 29] 9 to 12 [13 to 17] 11 to 14 [15 to 19] 2 14 to 17 [19 to 23] 20 to 23 [28 to 32] 35 to 38 [48 to 52] 18 to 21 [25 to 29] 21 to 24 [29 to 33] 2½ & 3 33 to 36 [45 to 49] 49 to 52 [67 to 71] 88 to 91 [119 to 123] 43 to 46 [59 to 63] 50 to 53 [68 to 72] 4 56 to 59 [76 to 80] 79 to 82 [108 to 112] 136 to 138 [184 to 189] N/A 81 to 84 [110 to 114] 6 126 to 130 [171 to 176] 170 to 174 [231 to 236] 278 to 282 [377 to 382] N/A 174 to 177 [236 to 240] 8 145 to 150 [197 to 204] 207 to 210 [281 to 285] 294 to 299 [399 to 405] N/A 211 to 216 [287 to 293]
Neoprene
®
Buna "N", Viton
Tempered Glass Tempered Glass Tempered Glass Tempered Glass Tempered Glass
®
Teflon
®
Gasket material ft•lb [N•m]
IFG-5500
®
Grafoil
®
PCTFE
WARNING
Failure to comply with the proper torquing sequence or force value can lead to leakage, gasket blow-out or glass breakage resulting in gage failure, serious personal injury or property damage.
5 OPERATION
5.1 Pre-Operational Check
1. Check that all installation instructions have been completed.
2. Check that bolts have been torqued to their proper limits as stated in Section 4.3.
3. Check that glass is clean and free of any damage as described in Section 4.0.
4. Check to determine that all connections are pressure tight.
5.2 Hydrostatic Pressure Test
1. Take all precautions necessary to handle the possibility of leakage.
2. Hydrostatic pressure test installation to at least 50 psig (340 kPaG), and correct any leakage before proceeding.
5.3 Operating
Sight flow indicator installations should be brought into service slowly to avoid excessive shock or stress on glass. Rapid pressurization of a sight flow indicator can cause glass breakage with resulting sudden release of pressure, causing serious personal injury or property damage.
1
4
FIGURE 1 Bolt tightening sequence
3
2
5
PENBERTHY SIGHT FLOW INDICATORS
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
6 MAINTENANCE
in detecting some of these conditions, Use only qualified, experienced personnel who are familiar with this equipment and thoroughly understand all the instructions in this manual for all maintenance.
WARNING
Do not proceed with any maintenance unless the sight flow indicator has been relieved of all pressure or vacuum, has been allowed to reach ambient temperature and has been drained or purged of all fluids. Failure to do so could result in a sudden release of pressure causing serious personal injury or property damage.
6.1 Preventative Maintenance
Create maintenance schedules, safety manuals, and inspection details for each specific installation of a sight flow indicator.
On all installations, regularly check the following items for purposes of maintenance:
1. Glass, for cleanliness and signs of damage
or wear.
2. Shields, if used, for signs of clouding, wear,
or deterioration.
3. Sight flow indicator for signs of leakage at
gaskets, or at connections.
4. Sight flow indicator, for signs of internal or
external corrosion.
5. Bolt torque values.
which will glisten more brightly than the surrounding glass when reflecting light. Detection of any such problem areas or any surface wear is sufficient evidence of damage. Immediately take sight flow indicator out of service. Do not proceed with operation of sight flow indicator until the glass has been replaced with a glass replacement kit by following the Disassembly-Reassembly instructions in Section 7.0.
2. Shields
Shields which show any signs of clouding,
wear, or deterioration are an indication that the sight flow indicator glass has been exposed, or could soon become exposed to the contained fluid. Immediately take sight flow indicator out of service. Do not proceed with operation of sight flow indicator until shields and glass have been replaced by following the Disassembly-Reassembly instructions in Section 7.0.
Determine upon evaluation of your own operating experience the appropriate maintenance schedule necessary for the specific application. Realistic maintenance schedules can only be determined with full knowledge of the services and application situation involved.
6.2 Maintenance Procedures
1. Glass
WARNING
Regular and careful attention must be given
to the cleaning and inspection of glass. Glass that is etched or even slightly scratched is weakened and may break under pressure. Design ratings listed in Section 2.2 are no longer valid for sight flow indicators that contain scratched, worn, or otherwise damaged glass, and such glass must be immediately replaced. Failure to comply can cause serious personal injury or property damage.
a. Keep glass clean using a commercial
glass cleaner and a soft cloth. DO NOT use wire brushes, metal scraper, or any device which could scratch the glass.
b. Inspect the surface of the glass for any
signs of clouding, etching, scratching, or physical damage such as bruises, checks or corrosion that penetrates the outer surface of the glass. Shining a light at approximately a 45° angle will aid
6
PENBERTHY SIGHT FLOW INDICATORS
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
3. Gasket Leaks Gasket leaks must be immediately repaired.
Do not proceed with operation of a sight flow indicator until glass, gaskets and cushions have been replaced by following the Disassembly-Reassembly instructions in Section 7.0.
4. Connection Leaks Leaks at a flanged or threaded connection
should be corrected by tightening the bolts at the connection, or by taking the sight flow indicator out of service and remaking the connection with Teflon all male pipe threads as shown in Figure 2
®
tape or equivalent on
.
5. Corrosion It is the user's responsibility to choose
a material of construction compatible with both the contained fluid and surrounding atmosphere in the user's specific application. If internal or external corrosion are present, an investigation must immediately be carried out by the user as to the cause of the problem, including consulting with an authorized Penberthy distributor.
6. Bolt Torque Bolt torque schedules should be developed
by checking bolt torque values daily until an appropriate cycle becomes apparent. The maximum torque is always maintained while not exceeding maximums at any time as shown in Table 2.
6.3 Troubleshooting
Problem: Glass or shield becomes etched or
clouded in service.
Cause: Fluid being handled is not compatible
with the glass or shield material.
Cure: Install shields that are unaffected by
fluid.
WARNING
Once a sight flow indicator has been
disassembled, all glass, gaskets, cushions, and
shields (where used) must be disposed of since
they are permanently deformed by compression.
Do not under any circumstances re-use those
items since they can cause leaks or high stress
points resulting in glass breakage. If re-used, the
glass can break causing serious personal injury or
property damage.
7.2 Reassembly
a. Refer to exploded view Figure 4.
b. Prepare for installation of new glass (48) by
first cleaning the gasket seating surfaces on body (11) and the cushion seating surfaces on glass covers (1). This should be done using a soft metal scraper (preferably brass) to remove all burrs, rust, and bits of old gasket or cushion which may be present. Exercise extreme care to avoid gouging or scarring gasket or cushion seating surfaces
WARNING
Failure to prepare gasket or cushion seating
surfaces described above can result in leaks or
glass breakage with resulting serious personal
injury or property damage.
c. Upon receipt of glass, inspect each piece
individually for shipping damage. During inspection, and during any subsequent handling of glass, care must be exercised to keep glass (especially the polished faces) from contacting each other or any other surfaces including table tops. If shipping damage is evident or suspected, notify carrier immediately and request a damage inspection. Glass should be kept in original wrap within original box until ready to use.
Tape
1-2
Threads
FIGURE 2 Pipe threads
4
1
FIGURE 3 Bolt loosening sequence
2
3
Direction
of Wrap
Problem: Glass continually breaks in service. Cause: Warped body as a result of
mechanical or thermal stresses.
Cure: Replace sight flow indicator.
7.0 REMOVAL-DISASSEMBLY-REASSEMBLY
WARNING
Do not proceed with the removal or disassembly of sight flow indicator from connecting piping unless the sight flow indicator has been relieved of all pressure or vacuum, has been allowed to reach ambient temperature and has been drained or purged of all fluids. Failure to do so can cause serious personal injury or property damage.
7.1 Disassembly
a. Sight flow indicators should be
disassembled by holding sight flow indicator firmly and loosening bolts by following the bolt loosening sequence shown in Figure 3.
7
PENBERTHY SIGHT FLOW INDICATORS
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
WARNING
Bumping or sliding of glass against each other or against other surfaces can result in glass breaking, scratching, or chipping. Glass that is broken is dangerous and useless and should be disposed of in a safe manner determined by the user. Glass that is chipped or scratched is weakened and should not be used under any circumstances. Pressure/temperature ratings within Table 1 are no longer valid for glass that is weakened. Using broken, chipped or scratched glass can cause serious personal injury or property damage.
d. Place the sight flow indicator in a horizontal
position and assemble the components as shown in Figure 4. Install band (331) around glass and place glass centered within the body and cover.
e. Threads on bolts (137) and nuts (4) must be
clean of paint, rust, and scale. Apply a light coat of oil to the threads and insert bolts through nameplate and two (2) covers, and install nuts finger tight.
f. Use a torque wrench to tighten the bolts.
Tighten bolts in increments of 3 ft•lb [4 N•m] or 50% of torque value as shown in Table 2, whichever is smaller. Continue tightening sequence at 3 ft•lb [4 N•m] max. torque until values in Table 2 are reached.
g. Gaskets will become compressed a short
time after bolts are tightened and torque values will decrease. Therefore, the sight flow indicator must be retorqued after 24 hours in service to values established in Table 2 for the specific model sight flow indicator.
WARNING
Do not re-torque a sight flow indicator while under pressure. A sight flow indicator in service must be freed of all pressure or vacuum, allowed to reach ambient temperature and drained or purged of all fluids before re-torque is performed. Failure to follow this procedure can result in serious personal injury or property damage.
Metal, glass and polymers should be recycled
whenever possible. Refer to order and Emerson
Material Specification sheets for materials
ofconstruction.
9 TELEPHONE ASSISTANCE
If you are having difficulty with your Sight
Flow Indicator, contact your local Penberthy
distributor. You may also contact the factory
direct at (956) 430-2500 and ask for an
applications engineer. So that we may assist
you more effectively, please have as much of
the following information available as possible
when you call:
Model #
Name of the company from whom you
purchased the Sight Flow Indicator Invoice # and date Process conditions (pressure, flow rates,
tank shape, etc) A brief description of the problem Trouble shooting procedures that failed
If attempts to solve your problem fail, you may request to return your Sight Flow Indicator to the factory for intensive testing. You must obtain a Return Authorization (R.A.) number from Emerson before returning anything. Failure to do so will result in the unit being returned to you without being tested, freight collect. To obtain an R.A. number, the following information (in addition to that above) isneeded:
Reason for return Person to contact at your company "Ship To” address
There is a minimum charge for evaluation of non-warranty units. You will be contacted before any repairs are initiated should the cost exceed the minimum charge. If you return a unit under warranty, but is not defective, the minimum charge will apply.
h. Refer to Section 4.0 Installation and Section
5.0 Operation when returning sight flow indicator to service.
8 DISPOSAL AT END OF USEFUL LIFE
Penberthy Sight Flow Indicators are used in a variety of fluid applications. By following the appropriate federal and industry regulations, the user must determine the extent of preparation and treatment the Sight Flow Indicator must incur before its disposal. A Material Safety Data Sheet (MSDS) may be required before disposal services accept certain components.
®
Grafoil
is a registered trademark of Graftech, Inc.
IFG-5500
®
is a registered trademark of Garlock Neoprene®, Teflon® and Viton® are registered trademarks of E. I. duPont de Nemours andCompany PCTFE (formerly known as Kel-F
®
- a registered trademark of the 3M Company) now manufactured by Daikin
8
PENBERTHY SIGHT FLOW INDICATORS
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
10 EXPLODED PARTS DRAWING
REF NO. ITEM MIN. QTY.
7 Gasket 2 48 Glass 2 8 Cushion 2 9 Shield 2 * Shields are optional
To ensure proper operation, use Penberthy spare parts.
PARTS LIST
Item
137 Bolt 163 Nameplate 128 Pin 115 Spacer 106 Rotator 115A Spacer 125 Washer 11 Body 7 Gasket 9 Shield 48 Glass 8 Cushion 1 Cover 4 Nut 43 Flapper 171 Tube 331 Band
Typical
drip-tube
type
Typical rotator
type
Typical flapper
type
FIGURE 4
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Penberthy is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.