Penberthy Level Control Switch, Model MGS-314/314D, Penberthy-EN Manuals & Guides

PENBERTHY MODEL MGS-314 SERIES AND MGS-314D SERIES LEVEL CONTROL SWITCH
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Before installation, these instructions must be read carefully and understood.
TABLE OF CONTENTS
Product warranty ................................................ 1
1 Introduction ............................................. 1
2 Specifications/Approvals ......................... 2
2.1 Enclosure ..................................................... 2
2.2 Switch ........................................................... 2
2.3 Approvals ...................................................... 2
3 Theory of Operation ................................. 2
4 Installation ............................................... 2
4.1 Unpacking..................................................... 2
4.2 Mounting the switch .................................... 3
4.3 Wiring connection ........................................ 3
5 Set-up ...................................................... 4
5.1 Initial test ...................................................... 4
6 Pump-Control Set-up .............................. 4
6.1 Interval relay wiring ..................................... 4
7 Troubleshooting ...................................... 4
7.1 Introduction .................................................. 4
7.2 Switch test .................................................... 4
7.3 Actuation test ............................................... 4
8 Telephone Assistance .............................. 5
9 Model KFA5-SR2-Ex2.W.IR
Interval Relay .......................................... 9
9.1 Operation ...................................................... 9
9.2 Typical applications ..................................... 9
9.3 Connection diagram .................................... 9
Tables and Figures
Figure 1 - MGS-314 Series ................................ 3
Figure 2 - MGS-314D Series ............................. 3
Figure 3 - Control drawing CSA approved
explosion-proof for
MGS-314/314D (7E741-009) ............. 5
Figure 4 - Control drawing CSA approved
intrinsically safe for
MGS-314/314D (7E742-009) ............. 6
Figure 5 - Application 1-Pump-up diagram ..... 7
Figure 6 - Application 2-
Pump-down diagram ........................ 7
Figure 7 - Connection diagram ......................... 7
PRODUCT WARRANTY
Emerson warrants its Penberthy products as designed and manufactured to be free of defects in material and workmanship for a period of one year after the date of installation or eighteen months after date of manufacture, whichever is earliest. Emerson will, at its option, replace or repair any products which fail during the warranty period due to defective material or workmanship.
Prior to submitting any claim for warranty service, the owner must submit proof of purchase to Emerson and obtain written authorization to return the product. Thereafter, the product shall be returned to Emerson, with freight prepaid.
This warranty shall not apply if the product has been disassembled, tampered with, repaired or altered outside of the Emerson factory, or if it has been subjected to misuse, neglect oraccident.
Emerson's responsibility hereunder is limited to repairing or replacing the product at its expense. Emerson shall not be liable for loss, damage, or expenses directly or indirectly related to the installation or use of its products, or from any other cause or for consequential damages. It is expressly understood that Emerson is not responsible for damage or injury caused to other products, building, property or persons, by reason of the installation or use of its products.
This is Emerson's sole warranty and in lieu of all other warranties, expressed or implied which are hereby excluded, including in particular all warranties of merchantability or fitness for a particular purpose.
This document and the warranty contained herein may not be modified and no other warranty, expressed or implied, shall be made by or on behalf of Emerson unless modified or made in writing and signed by the company's president or a vice president.
1 INTRODUCTION
The instructions in this manual pertain to the Penberthy Model MGS-314 or MGS-314D Magnetic Level Meter Switch. The Model MGS-314/314D Series Magnetic Level Meter Switch is designed to detect the passage of the float in a MULTIVIEW™ magnetic liquid level meter, at a specific location. The switch consists of a snap-action switch and a magnetic actuation assembly encased in a watertight (Type 4) or explosion-proof (Type7)enclosure.
Emerson.com © 2019 Emerson. All Rights Reserved. VCIOM-03387-EN 22/07
PENBERTHY MODEL MGS-314 SERIES AND MGS-314D SERIES LEVEL CONTROL SWITCH
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
2 SPECIFICATIONS/APPROVALS
2.1 Enclosure
Watertight (Type 4) and explosion-proof (Type 7) cast aluminum housing; Nitrile (NBR) O-ring
2.2 Switch Output:
MGS-314 Series: SPDT (Form C) switch output:
125
5 amps at
/
250 Vac, non-inductive load
MGS-314D Series: DPDT (2x Form C) switch
125
output: 10 amps at Repeatability: Better than
/
250 Vac, non-inductive load
1
/
32"
Response time: <100 milliseconds Operating temperature:
-40 to 365°F (-40 to 185°C) - with third party approvals (CSA)
-40 to 645°F (-40 to 340°C) - without third party approvals Ambient temperature range: -4 to 104°F (-20 to 40°C)
Dead band: ± ½"
2.3 Approvals Models: MGS-314-C/MGS-314D-C
CSA Approved Ex d
Explosion-proof for: Division 1, 2; Class I; Groups B, C, D; Class II; Groups E, F, G; Class III; Type 4 When installed in accordance with control drawing 7E741-009 (Figure 3)
CSA Approved Ex ia
Intrinsically safe for: Division 1, 2; Class I; Groups A, B, C, D; Class II; Groups E, F, G; Class III; Type 4 When installed in accordance with control drawing 7E742-009 (Figure 4)
3 THEORY OF OPERATION
While reading the theory of operation refer to Figure 1 (MGS-314 Series) or Figure 2 (MGS-314D Series) for the location of the components. The description is based on a sideview. With the liquid level below the switch, the toggle magnet should be at position 'A'. It is held in this position by an attractor near the magnet at the bottom of the toggle. As the float ascends and passes the switch, thedraw between the float magnet and toggle magnet is sufficient to overcome the attractor. Consequently, the toggle moves to position 'B' and is held in place by a second attractor. The movement of the toggle causes the switch (orswitches) to change state. As the float descends with the liquid level it passes the switch and the process described is reversed. The toggle returns to position 'A' and the switch returns to its original state.
4 INSTALLATION
4.1 Unpacking
Upon receiving the Model MGS-314/314DSeries Magnetic Level Meter Switch, check all components carefully for damage incurred in shipping. If damage is evident or suspected, do not attempt installation. Flameproof joints are not to be repaired. Notify the carrier immediately and request a damage inspection. Check each item against the packing list.
2
PENBERTHY MODEL MGS-314 SERIES AND MGS-314D SERIES LEVEL CONTROL SWITCH
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
FIGURE 1 MGS-314 SERIES
Toggle Toggle
Position 'A' Position 'B'
FIGURE 2 MGS-314D SERIES
Toggle
Position 'A'
4.2 Mounting the switch
Due to shipping vibration, it is possible the magnet toggle will not be in the 'normal' position for proper operation. If this occurs, simply cycle the float past the switch once. Thiswill initialize it automatically.
1. Measure the distance from the top of the indicating scale, on the magnetic level meter, to the top of the communicating chamber. Record this distance.
2. Loosen the clamps holding the indicating scale to the communicating chamber.
3. Open the mounting band supplied with the MGS-314/314D Series and put it around the communicating chamber, under the indicating scale.
4. Place the MGS-314/314D Series on the communicating chamber with the cooling fins facing 180° away from the communicating chamber and with the conduit opening facing down.
Toggle
Position 'B'
5. Put the mounting band between the cooling fins in the channel provided.
6. Loosely tighten the mounting band. Move the MGS-314/314D Series either up or down to the desired position, and tighten the band.
7. The switch must be mounted within the indication range for the magnetic gauge. The mounting band for the switch should be a minimum of 1" inside the indication range. This will insure sufficient float movement to operate the switch.
8. If more than one switch is used on a single magnetic gauge, the minimum recommended distance between mounting bands is 3".
9. Adjust the position of the indicating scale so that the distance from the top of the scale to the top of the communicating chamber is the same as in Step 1. Tighten the clamps holding the indicating scale to the communicating chamber.
4.3 Wiring connection
1.
If you are using conduit for the switch wiring use a conduit seal with a drain or a drip-loop to prevent condensate from entering the housing. Condensate can cause electrical shorts.
The switch housing has a ½" NPT-F
connection for the wiring conduit.
2.
We recommend attaching an aluminum condulet, via a 300 Series stainless steel nipple, to the conduit opening of the switch housing. This will give you an accessible point to terminate the control wires. DO NOT USE any ferromagnetic material such as: carbon steel, duplex, 400 Series stainless steel or castiron.
3
PENBERTHY MODEL MGS-314 SERIES AND MGS-314D SERIES LEVEL CONTROL SWITCH
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
5 SET-UP
DANGER!
Energizing the switch with the cover removed can cause ignition of flammable materials or atmospheres, resulting in personal injury, death or property damage. Do not apply power to the switch while performing these tests.
5.1 INITIAL TEST
Wire color
Model Toggle orientation
Toggle at position 'A' MGS-314 Series
MGS-314D Series
(liquid level below switch)
Toggle at position 'B'
(liquid level above switch)
Toggle at position 'A'
(liquid level below switch)
Toggle at position 'B'
(liquid level above switch)
Black Red Blue Orange White Violet
Open Closed NA NA NA
Common
Common
(for blue
and white)
Closed Open NA NA NA
Common
(for orange
and violet)
Closed Open Open Closed
Open Closed Closed Open
Use an ohmmeter to verify the conditions above. If these conditions do not exist, go to Section 7.
6 PUMP-CONTROL SET-UP
By combining two MGS-314/314D Series switches with the interval relay (WE77/Ex-JR) you can achieve intrinsically safe pump-control.
6.1 Interval relay wiring
MGS-314 Series
For pump-up action connect the red and black wires from the high level switch to Terminals 1 and 2. Connect the red and black wires from the low level switch to Terminals 8 and 9. The jumpers should be between Terminals 3 and 4, and Terminals 6 and 7. For pump-down action connect the high level switch to Terminals 8 and 9, and the low level switch to Terminals 1 and 2. Leave the jumpers in the same position as pump-up action. For technical information on the WE77/Ex-JR see Appendix A. Two 10 kΩ resistors must be installed in parallel across the leads as close to the MGS-314 Series Switches as possible. One across leads 1 and 2, the other across leads 8 and 9.
MGS-314D Series (Assume the toggle is at position 'A' for the following directions)
For pump-up action connect one common and a corresponding open connection from the high level switch to Terminals 1 and 2. Connect the same color combination from the low level switch to Terminals 8 and 9. The jumpers should be between Terminals 3 and 4, and Terminals 6 and 7. For pump-down action connect the high level switch to Terminals 8 and 9, and the low level switch to Terminals 1 and 2. Leave the jumpers in the same position as pump-up action. For technical information on the WE77/Ex-JR see Appendix A.
Two 10 kΩ resistors must be installed in parallel across the leads as close to the MGS-314D Series Switches as possible. One across leads 1 and 2, the other across leads 8 and 9.
7 TROUBLESHOOTING
7.1 Introduction
The Penberthy Magnetic Level Meter Switch is designed to give you years of unattended service. However, failure of electrical equipment can occur. Sound maintenance practices require periodic inspection of the instrument to ensure it is in good working order.
DANGER!
Energizing the switch with the cover removed may cause ignition of flammable materials or atmospheres, resulting in personal injury, death or property damage. Do not apply power to the switch while performing these tests.
7.2 Switch test
With the switch toggle at position 'A' use an ohmmeter to verify the conditions in section5.1. If these conditions are not met remove the (9) socket head cap screws holding the housing together. With the ohmmeter still connected, close the switch manually. If the switch still doesn't change state, it is defective. Go to Section8.
7.3 Actuation test
If the switch works (see Section 7.2) check the toggle magnet [MGS-314 Series] or toggle magnet/cam (MGS-314D Series). It should travel freely with a minimum of lateral (side-to-side) motion. This can be adjusted by loosening or tightening the two dog point setscrews that the toggle magnet pivots on (MGS-314 Series) only. If the nylon tips are damaged replace the setscrews.
4
PENBERTHY MODEL MGS-314 SERIES AND MGS-314D SERIES LEVEL CONTROL SWITCH
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
8 TELEPHONE ASSISTANCE
If you are having problems with Penberthy Level Meter Switch, notify the local Penberthy distributor, or call the factory direct at (281) 274-4400 and ask for an applicationsengineer.
To help us to assist you more effectively, please have as much of the following information as possible when you call:
• Instrument model # (MGS-314/314D Series)
• Name of the company from whom you purchased the switch
• Invoice # and date
• Process material
• Process temperature
• Brief description of the problem
• Checkout procedures (from the instruction manual) that failed
If attempts to solve your problem fail, you may be requested to return your instrument to the factory for testing. You must obtain a return authorization (R.A.) number from your authorized Penberthy distributor prior to returning your unit. Failure to do so will result in the unit being returned to you, without being tested and freight collect. To obtain an R.A. number collect the following information:
• Reason for return
• Person to contact at your company
• 'Ship-to' address
FIGURE 3 CONTROL DRAWING CSA APPROVED EXPLOSION-PROOF FOR MGS-314/314D (7E741-009)
HAZARDOUS AREA NON-HAZARDOUS AREA
CLASS I DIV 1 GROUP B, C, D CLASS II DIV 1 GROUP E, F, G CLASS III DIV 1
Models MGS-314-C
MGS-314D-C
18"
A flame path seal-off shall be installedwithin 18 in. of enclosure.
Wiring to be in accordance with National Electrical Code (NEC) pertinentparts of the 500 Series of article5 or local codes as applicable.
There will be a minimum charge applied for evaluation of non-warranty units. You will be contacted before any repairs are performed if they will result in additional charges in excess of the minimum. If you return a unit that is under warranty but not defective, the minimum charge will apply.
5
PENBERTHY MODEL MGS-314 SERIES AND MGS-314D SERIES LEVEL CONTROL SWITCH
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
FIGURE 4 CONTROL DRAWING CSA APPROVED INTRINSICALLY SAFE FOR MGS-314/314D (7E742-009)
TWO WIRE ENTITY CONTROL DRAWING
HAZARDOUS AREA Use CSA certified safety barriers: CLASS I DIV 1 GROUP A, B, C, D
CLASS II DIV 1 GROUP E, F, G CLASS III DIV 1
MODEL MGS-314-C
1
/
or
2
MGS-314D-C
MAG. SWITCH
NO or NC
Vmax = 40 Vdc Imax = 150 mA
C
= 0 nF
i
L
= 0 mH
i
TB1
COM
NON-HAZARDOUS AREA
Intrinsic safety
barrier
R < 1Ω
User wiring
Unused NO or NC lead shall be blind terminated and insulated. The intrinsic safety barrier parameters must meet the following requirements: Voc 40 V or Isc 150 mA; Ca Cleads; La Lleads
C
Leads
L
Leads
OR
THREE WIRE ENTITY CONTROL DRAWING
HAZARDOUS AREA
Use CSA certified safety barriers:
CLASS I DIV 1 GROUP A, B, C, D CLASS II DIV 1 GROUP E, F, G CLASS III DIV 1
Model MGS-314-C
1
/
or
2 MGS-314D-C
MAG. SWITCH
NO
TB1 NC
COM
Vmax = 40 Vdc Imax = 150 mA
C
= 0 nF
i
L
= 0 mH
i
C
Leads
L
Leads
MGS-314-C CONNECTIONS MGS-314D-C CONNECTIONS
Blue White Violet Red
NO
NC
Black Black
Green
C
Case
Ground
Blue
Green
NON-HAZARDOUS AREA
Intrinsic safety
barrier
Multiple channel
R < 1Ω
NC
NO
1
C
NC
1
2
1
CASE
GROUND
NO
C
2
User wiring
Orange
2
Red
One multiple channel intrinsic safety barrier must be used. The barrier parameters must meet the following requirements: Vt 40 V or It 150 mA; Ca Cleads; La Lleads
Installation shall conform to the manufacturer's instructions supplied with the intrinsic safety barrier as well as the National Electric Code and ANSI/ISA-RP 12.6 or CSA C22 "Installation of Intrinsically Safe Instrument Systems in Hazardous (classified) Locations."
Maximum non-hazardous area voltage must not exceed 250 Vrms or Vdc.
For IS. installation temperature shall not exceed 225°F (107°C).
6
PENBERTHY MODEL MGS-314 SERIES AND MGS-314D SERIES LEVEL CONTROL SWITCH
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS - APPENDIX B
9 MODEL KFA5-SR2-Ex2.W.IR INTERVAL RELAY
9.1 Operation
Mode condition
Lead breakage monitor: built-in circuitry monitors both control circuits for lead breakage. If the current in one of the two control circuits falls below 0.1 mA, the relay will de-energize.
Output relay condition at power supply interruption: when power is reconnected, the
output relay returns to its state prior to the interruption.
9.2 Typical applications
1. Pump-up application with two MGS-314/314D Magnetic Level Meter Switches
Level 1: Relay energized Level 2: Relay remains energized Level 3: Relay de-energizes Level 4: Relay remains de-energized Level 5: Relay energizes
2. Pump-down application with two MGS-314/314D Magnetic Level Meter Switches
Level 1: Relay de-energized Level 2: Relay remains de-energized Level 3: Relay energizes Level 4: Relay remains energized Level 5: Relay de-energizes
9.3 Connection diagram
Two 10 kΩ resistors (R1) must be installed in parallelacross the leads as close to the MGS-314/314D switches as possible. Oneacross leads 1 and 3, the other across leads 4and 6.
Two 1 k
Ω resistors (R2) must be installed in
series with leads 3 and 6.
FIGURE 5 APPLICATION 1 - PUMP-UP DIAGRAM
Level 3
Level 2, 4
Level 1, 5
High level sensor
Low level sensor
FIGURE 6 APPLICATION 2 - PUMP-DOWN DIAGRAM
Level 3
Level 2, 4
Level 1, 5
High level sensor
Low level sensor
FIGURE 7 CONNECTION DIAGRAM
MGS-314
MGS-314
R1 10 KΩ ± 5%
R1 10 KΩ ± 5%
1
2
3
4
5
6
1
2
3
4
5
6
Intinsically-Safe Input
1
R2
1 KΩ
R2
1 KΩ
2
3
4
5
6
KFA5-SR2-Ex2.W.IR
KFA5-SR2-Ex2.W.IR
KFA5-SR2-Ex2.W.IR
8
Output 1
7
9
11
Output 2
10
12
14
Supply 120 Vac
15
8
7
Output 1
9
11
Output 2
10
12
14
Supply 120 Vac
15
8
7
Output 1
9
11
10
Output 2
12
14
Suppy 120 Vac
15
VCIOM-03387 © 2019, 2022 Emerson Electric Co. All rights reserved 07/22. Penberthy is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Electric Co. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Electric Co. product remains solely with the purchaser.
Emerson.com
7
Loading...