Pelco C578M-A User Manual

®
System 9760
®
CM9760-HS
Hot Switch
Installation/
Operation Manual
C578M-A (4/05)
USA and Canada: Tel (800) 289-9100 • FAX (800) 289-9150
International Customers: Tel +1(559) 292-1981 • FAX +1(559) 348-1120
CONTENTS
SECTION 1.0: INTRODUCTION
1.1 HS DEFINED .......................................................................................................................... 6
1.2 CC1 CONNECTION GROUPS ............................................................................................... 7
1.3 HS HARDWARE THUMBNAIL ................................................................................................ 8
1.4 SUBUNIT HIGHLIGHTS .........................................................................................................8
THE CCC (COMPUTER CHANGEOVER CONTROL) ........................................................ 9
THE CPS (COMPUTER PERIPHERAL SWITCH) .............................................................. 10
THE SEU (SERIAL EXPANSION UNIT) ............................................................................. 12
MASTER/SLAVE STATUS FOR CC1 ................................................................................. 13
1.5 INSTALLATION PREVIEW ..................................................................................................... 14
OTHER REMARKS: ............................................................................................................ 14
INSTALLATION CHECKLIST: ............................................................................................. 14
SECTION 2.0: INSTALLATION
2.1 PHYSICAL .............................................................................................................................. 16
9700-CC1 TO CCC (CONTROL GROUP) .......................................................................... 16
9700-CC1 TO CPS (DIAGNOSTIC GROUP) ..................................................................... 17
9700-CC1 TO SEU (EXPANSION GROUP) ....................................................................... 18
DIP SWITCH SETTINGS .................................................................................................... 19
2.2 POWER-UP AND INITIALIZATION ........................................................................................ 20
SECTION 3.0: OPERATION
3.1 PRELIMINARY REMARKS .................................................................................................... 21
3.2 TERMS AND DEFINITIONS .................................................................................................. 21
3.3 OPERATOR TOOLS .............................................................................................................. 22
LEDS ................................................................................................................................... 22
FRONT PANEL BUTTONS ................................................................................................. 23
3.4 OPERATOR RESPONSES AND METHODS.........................................................................25
SYSTEM FAULTS ............................................................................................................... 25
DIAGNOSTIC MONITOR AND SYSTEM WINDOW USE .................................................. 26
SYSTEM UPDATE PROCEDURE ...................................................................................... 29
SECTION 4.0: APPENDICES
INTRODUCTORY REMARKS ............................................................................................ 31
APPENDIX 4.1 HS ADDITION TO AN EXISTING CONFIGURATION
(No Hot Switch Currently Installed) ..................................................................... 31
APPENDIX 4.2 HS UPDATE (PREVIOUS MODEL OF HOT SWITCH INSTALLED) ................. 32
APPENDIX 4.3 HS UPDATE (CURRENT MODEL HOT SWITCH INSTALLED) ......................... 33
APPENDIX 4.4 HS AND NETWORK-INTERFACED CONFIGURATIONS .................................. 34
APPENDIX 4.5 DATA CABLE PARAMETERS ............................................................................. 36
SECTION 5.0: GENERAL
5.1 SPECIFICATIONS ................................................................................................................. 40
5.2 SEU CONNECTION TEMPLATE ........................................................................................... 42
2 C578M-A (4/05)
LIST OF ILLUSTRATIONS
SECTION 1.0: INTRODUCTION
1-1. HS Block Diagram ................................................................................................................ 6
1-2. CC1 Connection Groups ...................................................................................................... 7
1-3. HS Rear Views and CCC Subunit Front Panel .................................................................... 8
1-4. Data Cable Identification ...................................................................................................... 9
1-5. Data Cable Wiring ................................................................................................................ 9
1-6. COM 2 Port Options ............................................................................................................ 11
1-7. SEU Port Relationships ......................................................................................................12
1-8. Port Connection Mnemonic ................................................................................................. 13
1-9. RJ-45 Pin Detail .................................................................................................................. 13
1-10. SEU Master/Slave Wiring Diagram ..................................................................................... 13
1-11. Basic Hookup, Wire Routes ................................................................................................ 15
SECTION 2.0: INSTALLATION
2-1. Data Cable Wiring Detail
2-2. Diagnostic Group, Cabling Detail .........................................................................................17
2-3. External Expansion Cabling Detail ....................................................................................... 18
2-4. DIP Switch Configuration ..................................................................................................... 19
2-5. Initialization Status, Default .................................................................................................. 20
SECTION 3.0: OPERATION
3-1. System Window Online Status ............................................................................................. 26
SECTION 4.0: APPENDICES
A4-1. Hot Switch Comparison Summary .....................................................................................32
A4-2. HS-NIU Connections ......................................................................................................... 34
A4-3. Hot Switch Interfaced NIU .................................................................................................. 35
A4-4. Data Rate vs. Cable Length............................................................................................... 36
A4-5. Keyboard (Local Hookup) .................................................................................................. 37
A4-6. Remote Wiring a CM9760-KBD ......................................................................................... 38
SECTION 5.0: GENERAL
5-1. CM9760-HS Dimension Drawing ......................................................................................... 41
LIST OF TABLES
SECTION 3.0: OPERATION
A LED Activity ............................................................................................................................... 23
B Front Panel Button Operation ................................................................................................... 24
C System FAULT Response ......................................................................................................... 25
D Diagnostic Displays .................................................................................................................. 27
E System Update of Hardware/Software, Starting from Default Mode ........................................ 29
SECTION 4.0: APPENDICES
Table A4-A. (TIA/EIA-422*) Cable Example .................................................................................. 39
C578M-A (4/05) 3
(This page intentionally left blank.)
4 C578M-A (4/05)
IMPORTANT SAFEGUARDS AND WARNINGS
Prior to installation and use of this product, the following WARNINGS should be observed.
1. Installation and servicing should only be done by qualified service personnel and conform to all local codes.
2. Unless the unit is specifically marked as a NEMA Type 3, 3R, 3S, 4, 4X, 6, or 6P enclosure, it is designed for indoor use only and it must not be installed where exposed to rain and moisture.
3. The installation method and materials should be capable of supporting four times the weight of the unit and equipment.
4. Only use replacement parts recommended by Pelco.
5. After replacement/repair of this unit’s electrical components, conduct a resistance measurement between line and exposed parts to verify the exposed parts have not been connected to line circuitry.
6. If the unit has fuses, replace fuses only with the same type fuses for continued protection against risk of fire.
The product and/or manual may bear the following marks:
This symbol indicates that dangerous voltage constituting a risk of electric shock is present within this unit.
This symbol indicates that there are important operating and maintenance instructions in the literature accompany­ing this unit.
CAUTION:
RISK OF ELECTRIC SHOCK.
DO NOT OPEN.
Please thoroughly familiarize yourself with the information in this manual prior to installation and operation.
REGULATORY NOTICES
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
RADIO AND TELEVISION INTERFERENCE
This equipment has been tested and found to comply with the limits of a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However there is no guarantee that the interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
You may also find helpful the following booklet, prepared by the FCC: “How to Identify and Resolve Radio-TV Interference Problems.” This booklet is available from the U.S. Government Printing Office, Washington D.C. 20402.
Changes and modifications not expressly approved by the manufacturer or registrant of this equipment can void your authority to operate this equipment under Federal Communications Commission’s rules.
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
C578M-A (4/05) 5
9760 HS COMMUNICATIONS
PARAMETERS
CC1 to HS Interface: (Comm Parameters)
Equipment # 16 Baud Rate 9600 Parity EVEN
NIU to HS Interface:
(Comm Parameters)
Equipment # 41 Baud Rate 9600 Parity EVEN
20052
NOTE:
For those familiar with device attachment to 9700 Systems, a convenient reference box is provided in the left margin that lists the communication parameters for hot-switch-interfaced nodes (CC1 to HS), and for hot-switch-interfaced NIUs (NIU to HS). Refer to
and Networked Interfaced Configurations
IMPORTANT NOTE:
Appendix 4.2 HS Update (Previous Model of Hot Switch Installed)
between previous and current models are highlighted.
SECTION 1.0: INTRODUCTION
1.1 HS DEFINED
The CM9760-HS (Hot Switch) provides single-node, switching control between two CM9700-CC1 matrix switches. The default HS package consists of three subunits*, interconnected via in out, DB37, male-to-male, molded cables that form a common bus for the subunits. These units provide the interfaced system with operational redundancy.
Failure of the controlling matrix switch (designated the Master) passes control to the backup (designated the Slave). Conversely, if the Slave unit fails, control remains with the Master unit. Any system failure generates a system error that lights the FAULT LED (visual), and turns on an accompanying audible tone. The audible signal is automatic unless turned off by DIP switch 1-1 (see Figure 2-4, DIP Switch Configuration) and the external devices connected to the CPS and SEU output ports.
Appendix 4.4, HS
, for more information.
Users upgrading from previous hot switch models should consult
, where important differences
.
Figure 1-1 depicts the basic physical relationship between the HS, the interfaced CC1s,
* The Serial Expansion Unit (SEU) is one of these units. However, it varies in number from one
(default), up to a possible eight units, depending on system configuration. Additional SEU units are physically added to the hot switch via the HS common bus. Two SEU units are needed to interface a fully populated CC1 (four Sercom cards containing a total of 32 ports). Future development may require more than 32 Sercom ports to be interfaced. When that happens, SEU units (up to eight total) can be added to the common bus to accommodate the increase in Sercom port population.
HS
CC1 A
CC1 B
HS CONTROL
DIAGNOSTIC PERIPHERAL
EXTERNAL
EXPANSION
INPUT
AB C
INPUT
AB C
Figure 1-1. HS Block Diagram
Diagnostic equipment connected to CPS output ports display the status of HS health. Other devices, connected to SEU output ports are under CC1 A or CC1 B control. For this reason, the interfaced matrix switches must be hardware-software clones of each other in order for either to control the same set of devices and to ensure a smooth transfer if a control transition (changeover) occurs.
Matrix switch equality is assured in the following manner:
Both switches must physically interface the HS in the same way. All cables and connections on
the A-side, switch-to-HS interface, are duplicated on the B-side. Basic interface requirements are discussed in installation subsection setup, are discussed in
Section 4.0 Appendices.
2.1 Physical
. Additional installation issues, beyond basic
CCC
CPS
INPUT
SEU
INPUT
OUTPUT
OUTPUT
20057
The physical equivalence of the matrix switches is likewise mirrored in their respective software
configuration file sets (Comms, Monitor, Camera, etc.) that are used to initialize and operate each switch. Both sets must be identical.
Refer to the CM9700-MGR Getting Started Software Guide, on-screen help, or Online Help for information about programming configuration files.
6 C578M-A (4/05)
1.2 CC1 CONNECTION GROUPS
The rear view of a matrix switch (referenced in the block diagram of Figure 1-1) is shown in Figure 1-2. Outputs destined for HS connections can be categorized, corresponding to the designated functions of the subunits to which they are attached on the hot switch. For discussion purposes, these outputs are partitioned into three groups: the Control group, the Diagnostic-Peripheral group and the External Expansion group.
CC1 A
PRINTER
COM 1 COM 2
MODEL
SERIAL
VOLTS WATTS
FREQ AMPS
TO THE
SEU
EXTERNAL
EXPANSION
GROUP
TO THE
CPS
DIAGNOSTIC-PERIPHERAL GROUP
Figure 1-2. CC1 Connection Groups
TO THE
CCC
CONTROL
GROUP
20058
C578M-A (4/05) 7
1.3 HS HARDWARE THUMBNAIL
Figure 1-3 expands the HS portion of Figure 1-1 to illustrate an uncluttered, thumbnail rear view of the hot switch subunits that comprise a default HS configuration. Connection cable destinations from each CC1 (matrix switch), referenced in the previous figure, are attached to the appropriate side (CC1 ‘A’ or CC1 ‘B’) of the hot switch subunits. The subunit acronyms have the following meanings: the CCC (Computer Changeover Control), the CPS (Computer Peripheral Switch) and the SEU (Serial Expansion Unit).
Note that the CCC front panel is included in this illustration. Operation buttons for the user are located there. Also shown is the 37-pin, D-type, molded cable, used to create common bus connectivity between the subunits. (Except for the CPS, one DB37 cable is supplied with each subunit). Front panels for the CPS and SEU are similar to that shown for the CCC (minus the operation buttons), with labeling appropriate to each unit.
PIN 19
PIN 1
PIN 37
1
PIN 20
DB37/M-M HOT SWITCH INTERCONNECT BUS CABLE (SUPPLIED)
2.5 FT (.76 M) CCC-SEU
CM9760-SEU
1 CC1 A 8 1 CC1 B 8 1 EQUIPMENT 8
IN
OUT
9
1
CC1 A CC1 B EQUIPMENT
IN
OUT
COM 1 COM 2
AT
VGA PRINTER
KBD
COM 1 COM 2
AT
KBD
VGA PRINTER
COM 1 COM 2
AT
KBD
VGA PRINTER
1
IN
OUT
A
C C 1
A
B
B
LOGGING PRNTR
120-240 VAC 50/60 Hz
16
CM9760-CPS
CM9760-CCC
(FRONT PANEL) CM9760-CCC
SELECT
PWR
SYSTEM
9760
FAULT
A
B
AB
CC1
KVD
CM9760-CCC HOT SWITCH
Made in USA
20059
Figure 1-3. HS Rear Views and CCC Subunit Front Panel
1.4 SUBUNIT HIGHLIGHTS
The main characteristics and functions of each subunit of the HS are discussed in the following paragraphs. Important points that need to be understood for a successful installation are discussed.
8 C578M-A (4/05)
NOTE:
When upgrading to the current hot switch from a previous model, note the following. The data cable, previously used to connect RJ-45 port 5 on each switch and the corresponding COM 1 [S1] and COM 2 [S2] ports on the hot switch, cannot be substituted here.
9700-CC1
SERCOM PORT
DATA
CONNECTION
OUTPUT (RJ-45)
18 27
72 81
(SEE FIGURE 2-1)
MATRIX
SWITCHES HOT SWITCH
THE CCC (Computer Changeover Control)
The CCC subunit is the heart of the hot switch. Data connections between the interfaced CC1s (matrix switches) and the HS are located here. Two connector types that correspond to two communication types for the data line to the CCC are provided: RJ-45 or DB9. You can use either, but the connector type chosen determines the communication protocol you must use and vice versa. Both are illustrated in Figure 1-5. In the top portion of Figure 1-5, the RJ-45 data line connection (one from each switch) is shown. If RS-422 communication is chosen, the data cable from a port on matrix switch CC1 ‘A’ (an RJ-45 Sercom port, usually port 5) is run to the RJ-45 CC1 A port on the CCC. A similar cable is run from CC1 ‘B’ to the RJ-45 CC1 B port on the same CCC. These cables are re­versed or “flipped” and utilize pins 1, 2, 7, and 8 as depicted in Figure 1-4. Alternately, in the bottom portion of Figure 1-11, the RS-232 data line connection is shown. A DB9 cable is run from either the COM 1 or COM 2 port (on the respective CC1 ‘A’ or CC1 ‘B’ switch) to the appropriate (CC1 A or B) DB9 port on the CCC. The cables for the DB9 data connection runs are not supplied. Pelco recommends that RS-422 communication be used whenever possible. The cables for the RS-422 data connections are provided.
9760-CCC A- OR B-SIDE INPUT (RJ-45)
IN
A
OUT
C C 1
B
A
B
COMPARED “COLOR RUN”
IS IN OPPOSITE DIRECTION
BROWN BROWN
FLIPPED VS STRAIGHT CABLE WIRING
FLIPPED CABLE
REVERSE CABLE
TO IDENTIFY A CABLE TYPE, PHYSICALLY ORIENT THE RJ-45 CABLE AS DEPICTED IN THE ILLUSTRATION. ORIENT THE CABLE CONNECTORS SIDE-BY-SIDE, TAB SIDE DOWN. USE THE COLOR-RUN OF THE WIRES TO DETERMINE CABLE TYPE.
OR
Figure 1-4. Data Cable Identification
LOGGING PRNTR
COMPARED “COLOR RUN”
IS IN SAME DIRECTION
BROWN BROWN
STRAIGHT CABLE
OR
PARALLEL
120-240 VAC 50/60 Hz
20053
CM9700-CC1 A
RJ-45
SERCOM
PORT
CM9700-CC1 B
RJ-45
SERCOM
PORT
RS-422 RECOMMENDED
OR
CM9760-CCC
CM9700-CC1 A
COM 1
OR
COM 2
COMMUNICATION PARAMETER CONNECTIONS
CM9700-CC1 B
RS-232 AVAILABLE
COM 1
OR
COM 2
EITHER COM 1 OR COM 2 (ON THE MATRIX SWITCH SIDE) CAN BE USED. IF COM 1 IS CHOSEN, BOTH SWITCHES MUST USE COM 1, OR ELSE BOTH MUST USE COM 2.
1
1
CM9760-CCC
RJ-45
A
RJ-45
B
DB9
A
DB9
B
SEE FIGURES 1-11 AND 2-1
MATRIX SWITCHES HOT SWITCH
CC1 A OR B
CM9700-CC1
COM PORT DATA
CONNECTION OUTPUT (DB9)
PIN 2 (RX) PIN 2 (RX) PIN 3 (TX) PIN 3 (TX) PIN 5 (GND) PIN 5 (GND)
CM9760-CCC A- OR B-SIDE
INPUT (DB9)
1
COM 1 COM 2
PRINTER
CM9760-CCC (REAR VIEW)
Figure 1-5. Data Cable Wiring
1
PIN 5
PIN 9
PIN 6 PIN 1
IN
A
C C 1
OUT
B
DB9/F-M
CC1-CCC (RS-232)
COM 1/COM 2 (CC1) TO
DB9 A/B (CCC)
CROSSOVER CABLE
PIN 1 PIN 6
PIN 9 PIN 5
A
LOGGING PRNTR
B
C578M-A (4/05) 9
In addition to communications, there are number of additional functions handled by the CM9760-CCC.
POWER The power-input connector, fuse, and ON/OFF switch are located here. Input
power for the entire HS originates here. Power is distributed to the CPS and SEU subunits via DB37 common bus connections.
LOGGING PRINTER PORT This is used, if desired, as an output logging device for system or status reports
related to hot switch operation only. The port supports dot matrix printers capable of IBM or Epson emulation modes, such as the Okidata 320 (non-turbo) and the Okidata 390 (turbo) or 391 (turbo).
LEDs The FAULT, A, and B LEDs are located on the front panel of the unit. These give
visual indications of system status with respect to control, mode of operation, and system failure. See the
LEDs
section of
3.3 Operator Tools.
FRONT PANEL BUTTONS The front panel buttons are utilized by the operator for responding to system
errors, for checking system status, and for operational control when changes are made to system hardware and/or software. See the of
3.3 Operator Tools
.
Front Panel Buttons
section
THE CPS (Computer Peripheral Switch)
CC1 A CC1 B EQUIPMENT
IN
OUT
The connectors on the rear of the CPS are divided into three duplicate sections. Each section contains
an AT KBD connector, a VGA connector, a PRINTER connector, a COM 1 connector (port), and a COM 2 connector (port).
COM 1 COM 2
AT
VGA PRINTER
KBD
COM 1 COM 2
AT
KBD
VGA PRINTER
COM 1 COM 2
AT
KBD
VGA PRINTER
20055
Each duplicate section is labeled. From left to right, they are the CC1 ‘A’ section, the CC1 ‘B’ section, and the EQUIPMENT section. The first two (CC1 ‘A’ and CC1 ‘B’) are connection input destinations for the corresponding switch it interfaces—one from the A-side, and one from the B-side switch. The third section (EQUIPMENT) provides the connectors to which the following standard diagnostic devices can be attached:
1. An AT keyboard (to the AT KBD connector)
2. A VGA monitor (to the VGA connector)
3. A system printer (to the PRINTER connector)
4. A PC W/Pelco MGR software (to the COM 1 port)
As a user, you are always connected (through either one matrix switch or the other) to the diagnostic tools that are attached to the EQUIPMENT output ports. The switch through which you operate (the one in control and designated the Master) is normally granted automatic access to those devices (default). If control is switched, the backup switch (Slave) becomes the designated Master, roles are reversed, and the output diagnostic connections change to follow suit. This happens automatically if DIP switch 1-2 is ON and DIP 1-6 is OFF (default). See Figure 2-4, DIP Switch Configuration.
Note that only four diagnostic devices are listed for the five available output ports. Two of the five output ports deserve further comment.
COM 1 is reserved for the connection of the PC with MGR software (see Figure 1-11). COM 2 can be used in two ways:
1. As a “user” defined configuration for the connection of devices and/or electronic equipment to the COM 2 A and B inputs and to the COM 2 EQUIPMENT output port. The COM 2 ports are D-type, 25-pin connectors, and can be used for the connection of user-optioned equipment. Applied voltages to COM 2 connector pins should not exceed 25 VDC. For this use, the operation of the COM 2 port is not necessary for the successful operation of any function of the HS. Insert A of Figure 1-6 is a diagrammatic drawing of the wiring of the COM 2 connectors.
2. For the connection (to the EQUIPMENT section’s COM 2 output port) of an RS-232, DT (Data Translator). As part of the CPS package, three DB25 (female) to DB9 (male) adapters are pro­vided for this purpose (along with the associated cabling for the A- and B-side inputs to these adapters).
10 C578M-A (4/05)
This allows users with existing RS-232 DT devices to retain that configuration capability in the new HS. Figure 1-6 highlights the geometry of this hookup.
Additional DTs of the same type must be connected to CC1 Sercom ports (via SEU output ports of the HS) and require RS-232 to -422 converters.
20078
Figure 1-6. COM 2 Port Options
A couple of working rules with respect to diagnostic tool availability are in order here. During default operation (see Figures 2-4 and Figure 2-5) diagnostic tools attached to EQUIPMENT output ports “follow” the switch in control. Under these conditions, the following results can be expected when the described operation is performed:
1. You can view, at will, the diagnostic activity for either switch (Master or Slave) regardless of the operational mode (including default) as long as that switch is online. This is done by pressing the KVD (Keyboard, Video, Data) A (or B) button located on the front panel of the CM9760-CCC for the A- or B-side diagnostic view you want to see (see Table B, Front Panel Button Operation). When the KVD button is pressed, you will view the devices connected to the AT KBD, and VGA port connections for the side (A or B), (Master or Slave) that you selected. It is important to note that the PRINTER, COM 1, and COM 2 ports do not follow KVD activity under any circumstances.
2. If the diagnostic view is switched manually via the KVD button, as in (1), it remains there until
(a) the operator manually switches back to the opposite side, or until
(b) the system forces a change due to a system fault. A system fault may or may not result in a
return to the original diagnostic view. That depends on which switch becomes the desig­nated Master when the changeover, if deemed necessary, occurs. This is determined by the HS itself. It occurs automatically as the result of configuration settings and is not under user control.
3. Any system change (as noted in 2b) co-opts any existing diagnostic view and any resulting change occurs under the control of the HS and not the operator. Moreover, the HS controls and automatically transfers ALL ports (including COM 1 and COM 2) to the control of the designated Master in the event of a system failure.
C578M-A (4/05) 11
THE SEU (Serial Expansion Unit)
1 CC1 A 8 1 CC1 B 8 1 EQUIPMENT 8
IN
OUT
9
The SEU subunit of the HS, like that of the CPS, is also divided into three sections. Devices connected to the SEU EQUIPMENT output ports are under the control of only one CC1 at a time. The controlling switch is designated the Master, regardless of mode (synchronous or asynchronous). Unlike the CPS, however, there are no predefined port designations for SEU Sercom input ports that physically correspond to the port designations as they are defined by physical location on any 9760-CC1 matrix switch. On the matrix switch, port 5 is port 5 and is always located at the “port 5” position, and so on.
The physical relationship between matrix switch Sercom outputs and the A/B inputs on the SEU are defined by the following statements:
1. The function of each Sercom input port on the SEU (CC1 ‘A’ or CC1 ‘B’) is characterized by whatever is plugged into it.
2. A specific physical relationship (depicted in Figure 1-7) exists internally between SEU Sercom inputs (A or B) and associated SEU EQUIPMENT outputs.
The Sercom ports on the SEU shown in Figure 1-7 are isolated and numbered (for explanatory purposes); the ports on the SEU are physically related as illustrated.
RELAY ACTIVATION FOLLOWS THE CC1 IN CONTROL (MASTER)
A
16
20085
CC1 A CC1 B EQUIPMENT
A1 A2 A3 A4 A5 A6 A7 A8
A9 A19 A11 A12 A13 A14 A15 A16
B
B1 B2 B3 B4 B5 B6 B7 B8
B9 B19 B11 B12 B13 B14 B15 B16
E1 E2 E3 E4 E5 E6 E7 E8
E9 E19 E11 E12 E13 E14 E15 E16
20062
Figure 1-7. SEU Port Relationships
The depiction above shows CC1 ‘A’ input A1, connected to the output device attached to E1.
The physical relationship depicted above is repeated for all corresponding physical port locations; that is, A2 is related to B2 and the output E2 in the same way that A1 is related to B1, and the E1 output.
This relationship holds true for the remaining port locations: A3-A16, B3-B16, and E3-E16.
In line with the port relationship just discussed, you must also maintain corresponding equipment integrity with respect to the input port locations chosen for attaching A- and B-side input cables. This is so that output control, from either matrix switch, of a device connected to a specific SEU output port, corresponds, in fact, to the same physical device.
For example: If a matrix bay is hardware-software configured for attachment to port 7 on 9700-CC1 A, then it also must be configured the same for port 7 on 9700-CC1 B, since the CC1s must be hardware­software clones of each other. If you then run a cable from 9700-CC1 A, port 7, to the CC1 ‘A’ side of the SEU and attach it to the A1 port, then you must also run a corresponding cable from 9700-CC1 B, port 7, to the CC1 ‘B’ side of the SEU and attach it to port B1. The matrix bay itself, is connected to the corre­sponding output port, E1, on the SEU.
As indicated above, the configured outputs of 9700-CC1 ports can be plugged into any input port on the appropriate SEU, as long as you allow for the physical constraint illustrated in Figure 1-7, above.
12 C578M-A (4/05)
A NOTE OF CAUTION: Random attachment of cabling between CC1s and SEUs can lead to confu-
A
A
sion about what is attached where. It is suggested that you map the physical port arrangement found in your CC1 outputs to those utilized on the SEU (as far as that is possible). One method is to mentally rotate the SEU (clockwise or counterclockwise, it does not matter) and associate the port locations you use on the SEU to those existing on the CC1. In Figure 1-8 , the CC1 ‘A’ side of the SEU is shown rotated counterclockwise. You can extend the use of this visual mnemonic to the SEU’s B side, the output, and additional SEUs, if needed (also see the NOTE in Figure 1-8).
20
CC1 ‘A’
12
SEU
CC1 ‘A’
5
13
CC1 ‘A’
IMPORTANT
NOTE: ALTHOUGH THE METHOD CHOSEN FOR KEEPING SEU PORT CONNECTIONS STRAIGHT IS,
T BEST, ARBITRARY, PELCO RECOMMENDS THAT
IT IS BEST TO FOLLOW A DESIGNATED TEMPLATE
S AN AID IN TRACKING SEU PORT CONNECTIONS. ONE IS PROVIDED FOR YOU AT THE BACK OF THIS MANUAL. IT IS CALLED THE SEU CONNECTION TEMPLATE.
Figure 1-8. Port Connection Mnemonic
MASTER/SLAVE STATUS FOR CC1
Sercom port 1 on the CC1-A or CC1-B side of the SEU subunit may be wired to provide the current status of the CM9760-HS. This wiring connection will allow for monitoring that alerts the user to primary (master) CPU (CC1) failure. When the secondary (slave) CPU assumes primary control, the user can be alerted remotely via the closure of an external alarm. This connection is made by constructing an RJ-45 terminated wire (not provided) and shorting pins 1 and 2 (CC1-A) or pins 7 and 8 (CC1-B) together on the CC1 side side port 1. See Figures 1-9 and 1-10.
CC1 A PORT #1
(PIN 1 & 2 SHORTED)
MASTER
1 CC1 ‘A’ 8 1 CC1 ‘B’ 8 1 EQUIPMENT 8
IN
OUT
9
only
. The CC1 port (A or B) is connected to the EQUIPMENT
PIN 8
PIN 1
Figure 1-9. RJ-45 Pin Detail
OR
CC1 A PORT #1
(PIN 7 & 8 SHORTED)
SLAVE
EQUIPMENT PORT #1
ALARM OUT
16
Figure 1-10. SEU Master/Slave Wiring Diagram
C578M-A (4/05) 13
1.5 INSTALLATION PREVIEW
Figure 1-11 combines elements of previous illustrations into what is essentially a wire routing of the block diagram of Figure 1-1. This is an overview of the physical geometry of an HS integrated into a basic, default system configuration. 1-11 into its logical component groupings, where cabling requirements for each section are isolated and examined in detail. Cabling in the current model hot switch is rather straightforward.
Other Remarks:
In addition to basic hookup, which covers the information needed for a new, single-node installation, the following configuration processes are discussed in
HS addition to an existing configuration, (no hot switch currently installed)
HS update, (previous model of hot switch installed)
HS update (current model hot switch installed)
HS and networked configurations
Installation Checklist:
The basic install process for integrating a hot switch within a single system node can be broken down into the following steps:
1. Mount the components of the hot switch (standard rack-mount) in such a way as to take advantage of the equipment that will attach to each unit. At the same time, be mindful of the rela­tively short interconnect cables that form the common bus between the subunits of the HS. Install the interconnect cables that form the common bus (see Figure 1-3 for a picture of this cabling). Install the power cord on the CM9760-CCC, but do not apply power to the unit.
2. Connect all remaining cabling that is required for your system node. Follow, in order, all items of
2.1 Physical in Section 2.0 Installation
and two located behind the front panel of the CM9760-CCC subunit (see Figure 2-4).
Section 2.1 Physical
of the manual, for instructions. Configure DIP switch one
in
Section 2.0 Installation
Section 4.0 Appendices
.
, breaks up Figure
3. Install all required software. Ensure that duplicate sets of configuration files for the interfaced matrix switches are installed on the respective hard drives of each switch. Check to make sure that port references to attached equipment match the equipment actually attached to those ports. Refer to the appropriate sections of the latest version of the MGR programming for general information on filling out configuration files. Refer to the appropriate sections of the latest revision of the matrix switch manual (C541M), for information on installing configuration files and other items related to file manipulation. Be sure to add the hot switch to the COMMS configuration file, if not already done.
4. After all cabling and software is installed, apply power to the HS and all attached equipment and let the systems initialize (see
2.2 Power-up and Initialization
in
Section 2.0 Installation
).
14 C578M-A (4/05)
Loading...
+ 30 hidden pages