Page 37
USER MANUAL
interval
FAULTS CAUSE TASKS TO BE CARRIED OUT
Water level high, triggering
level alarm E1 with high
absorption
Damaged electronics
Contact the assistance centre
Block of the humidifier with
E2 alarm
Functional fault of humidity
duct sensor
Verify humidity duct sensor condition
The humidifier produces not
much steam
One of phases is interrupted Check absorption on all phases
Block of the humidifier with
E3 alarm
Lack of water more than 30
minutes of continuous request
Check that water supply system is
working
Block of the humidifier with
E3 alarm
Lack of water more than 30
minutes of continuous request
Make sure there is no leaking from
damaged pipes
Block of the humidifier with
E3 alarm
Lack of water more than 30
minutes of continuous request
Check the solenoid valve was not
damaged or disconnected
Humidifier is on and
functioning but display E5
error
Drain control autotest failed
(pre-alarm). Solve the problem
before next test which is
executed every 10 hours of
electrode functioning.
Verify that drain of bottom of cylinder
is not obstructed and pump is not
broken or disconnected.
Alarm is automatically resetted at next
drain control autotest which happens
every 10 hours of electrode functioning
or when humidifier is switched off.
Unit block with E6 alarm
(not stoppable sonorous
signalation)
Drain control autotest failed for
second time. Humidifier enters
in stand-by mode to avoid
damaging of the unit.
Switch off the humidifier, solve
the problem and then switch on
again.
Verify that drain of bottom of cylinder
is not obstructed and pump is not
broken or disconnected.
Alarm is resetted when humidifier is
switched off.
In a Master/slave
humidifiers configuration
the MASTER unit is on and
working but signals E7
alarm
In a Master/slave humidifiers
configuration the Master unit do
not find a connected slave.
This alarm does not stop the
normal working.
Check connections between master unit
and slave unit.
Check second level parameters MS e
Ad related to Master/slave
configuration.
In case of connection restore the alarm
is automatically reset.
In a Master/slave
humidifiers configuration
the slave unit is blocked and
signals E8 alarm
In a Master/slave humidifiers
configuration slave unit has lost
the communication with
connected Master.
This alarm blocks the slave unit.
Check connections between master unit
and slave unit.
Check second level parameters MS e
Ad related to Master/slave
configuration.
In case of connection restore the alarm
is automatically reset.
Humidifier differential
protection upstream the line
intervenes
Water presence on lower part of
humidifier because of a fault or
after a maintenance that cause an
earth leakage of the unit.
Lead the unit to safety following the
instructions at chap. 7.2.
To wipe carefully all wet parts and
reactivate the unit.