PeerlessBoilers WBV-03-060, WV-05-195, WV-05-175, WBV-04-150, WBV-04-125 Installation, Operation & Maintenance Manual

...
WBV/WV
Boilers
Series
Oil
Installation, Operation & Maintenance Manual
As an ENERGY STAR®Partner, PB Heat, LLC has determined that this product meets the ENERGY STAR guidelines for energy efficiency.
Plastic Jacket
USING THIS MANUAL 1
A. INSTALLATION CLEARANCE . . . . . . . . . . . . .1
B. SPECIAL ATTENTION BOXES . . . . . . . . . . . .1
1. PREINSTALLATION 2
A. CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . .2
B. AIR FOR COMBUSTION AND
VENTILATION . . . . . . . . . . . . . . . . . . . . . . . . .2
C. CHIMNEY / VENT AND DRAFT CONTROL . .3
D. INSTALLATION SURVEY . . . . . . . . . . . . . . . .4
E. PLANNING THE LAYOUT . . . . . . . . . . . . . . . .4
2. BOILER PLACEMENT AND ASSEMBLY 5
A. SETTING THE BOILER . . . . . . . . . . . . . . . . . .5
B. CONNECTING THE FLUE OUTLET . . . . . . . .5
3. WATER PIPING 6
A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
B. SYSTEM COMPONENTS . . . . . . . . . . . . . . . .6
C. SYSTEM PIPING . . . . . . . . . . . . . . . . . . . . . . .9
D. FREEZE PROTECTION . . . . . . . . . . . . . . . . . .9
E. SPECIAL APPLICATIONS . . . . . . . . . . . . . . . .9
F. TANKLESS HEATER OR COVERPLATE . . . . .9
G. CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4. BURNER SETUP & BOILER OPERATION 11
A. BURNER INSTALLATION . . . . . . . . . . . . . . .11
B. BURNER START-UP AND ADJUSTMENT . .11
C. CHECK BOILER CONTROLS . . . . . . . . . . . .11
D. PURGE AIR FROM THE SYSTEM
(WATER BOILERS ONLY) . . . . . . . . . . . . . . .12
5. ELECTRICAL 14
A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . .14
B. WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6. MAINTENANCE 17
A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . .18
B. DAILY MAINTENANCE (WITH BOILER
OPERATING) . . . . . . . . . . . . . . . . . . . . . . . . .18
C. WEEKLY MAINTENANCE (WITH BOILER
OPERATING) . . . . . . . . . . . . . . . . . . . . . . . . .18
D. MAINTENANCE OF SAFETY
RELIEF VALVE . . . . . . . . . . . . . . . . . . . . . . .18
E. MONTHLY MAINTENANCE (WITH BOILER
OPERATING) . . . . . . . . . . . . . . . . . . . . . . . . .18
F. MAINTENANCE – ANNUAL . . . . . . . . . . . . .18
G. WATERSIDE INSPECTION . . . . . . . . . . . . . .19
H. INSPECT HEAT DISTRIBUTION SYSTEM . .19 I. IF A LONG SHUTDOWN IS REQUIRED . . .19
7. BOILER DIMENSIONS & RATINGS 20
8. REPAIR PARTS 22
TABLE OF CONTENTS
TABLE OF CONTENTS
A. INSTALLATION CLEARANCE
Follow the installation instructions provided in this manual in the order shown. The order of these instructions has been set in order to provide the installer with a logical sequence of steps that will minimize potential interferences and maximize safety during boiler installation.
B. SPECIAL ATTENTION BOXES
Throughout this manual you will see special attention boxes intended to supplement the instructions and make special notice of potential hazards. These categories mean, in the judgment of PB Heat, LLC:
USING THIS MANUAL
1
USING THIS MANUAL
In accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, this boiler is equipped with a feature that saves energy by reducing the boiler water temperature as the heating load decreases. This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function.
THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE:
• An external energy management system is installed that reduces the boiler water temperature as the heating load decreases.
• This boiler is not used for any space heating.
• This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/hr or greater.
• This boiler is equipped with a tankless coil.
NOTICE
Indicates special attention is needed, but not directly related to potential injury or property damage.
NOTICE
Indicates a condition or hazard which will cause minor personal injury or property damage.
CAUTION
DANGER
Indicates a condition or hazard which will cause severe personal injury, death or major property damage.
Indicates a condition or hazard which may cause severe personal injury, death or major property damage.
WARNING
2
A. CLEARANCES
Unit may be installed on combustible flooring, provided the boiler is not set on carpet and a metal drip pan is placed under the appliance.
Unit may be installed in a closet with the below clearances. See also Section B, Air for Combustion and Ventilation.
B. AIR FOR COMBUSTION AND
VENTILATION
1. Be certain adequate facilities are available to provide air for satisfactory combustion and ventilation.
2. Appliances Located in Unconfined Spaces.
a. For installation in unconfined spaces with
conventional construction and larger areas such as basements, the supply of air for combustion and ventilation can usually be considered adequate.
PREINSTALLATION
1. PREINSTALLATION
Read carefully, study these instructions before beginning work. It will save time. Study the included drawings. Save these instructions for reference.
This boiler must be installed by a qualified contractor.
The boiler warranty can be voided if the boiler is not installed, maintained and serviced correctly.
Figure 1.1: Appliance Installation Clearances
The equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made, including the current edition of NFPA-31, Standard for the Installation of Oil-Burning Equipment, and in Canada, CSA B139, Installation Code for Oil Burner Equipment. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
NOTICE
Do not tamper with boiler controls.
CAUTION
DANGER
Do not install this appliance on carpeting.
Do not install this appliance where gasoline or other flammable liquids are stored or are in use. Do not store clothing or combustible materials on or against the venting system or jacket.
WARNING
Never burn garbage or paper in the unit, and never leave combustible material around it.
CAUTION
3
3. Appliances Located in Confined Spaces. a. All air from inside the building: Provide two
permanent openings communicating directly with an additional room. If all air for combustion and ventilation is to come from within the building: two openings, one near the ceiling and one near the floor of the boiler room shall be provided with the minimum free area of each opening equal to 140 sq. in. per gallon of oil burned.
b. If all air for combustion and ventilation is to
come from outside the building: two openings, one near the ceiling and one near the floor of the boiler room shall be provided with the minimum free area of each opening equal to 35 sq. in. per gallon of oil burned.
If ducts are used to convey the air, areas of 35 sq. in. per gallon of oil burned for vertical ducts or 70 sq. in. per gallon of oil burned for horizontal ducts are to be provided. Ducts shall have the same area as the free area of the openings to which they are connected.
4. Special Conditions: If the boiler is located in areas
with exhaust fans, direct-fired water heaters or fireplaces can create conditions for unsatisfactory combustion or venting, special provisions must be made.
5. Specially Engineered Installations: The size of the
combustion air openings in this section may not apply to specially engineered systems. These systems are to be designed to ensure adequate supply of air for combustion and ventilation.
C. CHIMNEY / VENT AND DRAFT CONTROL
1. Draft Requirement – Minimum draft required in the
vent system is -0.03" to -0.03" W.C. depending on boiler model, see Table 7.1 (Section 7). This draft is necessary to provide the necessary draft over fire of
-0.01" to -0.02" W.C. See discussion in paragraph 5 below regarding draft.
2. A barometric draft control is recommended for
regulation of overfire draft. Follow manufacturer's instructions to locate and adjust the control.
3. Inspect the existing chimney or vent system. Make sure it is in good condition. Inspect chimney liner and repair or replace if necessary.
4. The vent system and installation must be in accordance with the current edition of the American National Standard ANSI/NFPA 211, "Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances," or applicable provisions of the local building codes. Typical minimum chimney size is 8" x 8", 15 feet high, unless otherwise allowed by code. If the vent system is not sized properly, the burner may not operate properly. This can cause poor combustion, sooting and odors to occur.
5. Background Information Regarding Draft: Modern boilers operate with higher efficiencies than
older boilers. Smaller flueways, as well as bars, pins and fins are designed into modern boilers to transfer as much heat as possible from the hot gases to the water or steam and prevent heat loss up the chimney. However, these design features result in higher pressure, or draft loss, in the boiler.
This draft loss must be taken into account when installing an oil boiler into a new or old chimney. New chimneys are less likely to have poor draft. However, they must have sufficient draft to support combustion. A -0.06" draft is desirable and preferred. Older chimneys may require a replacement liner to have them perform well enough to support combustion.
For Example:
The above readings are "cold" readings (before the boiler and chimney are heated up).
Note also that the higher the firing rate on a unit which has multiple firing rates, the higher the draft required. For example, increasing the firing rate 1/4 gallon may increase the draft loss in a unit by approximately +0.01".
PREINSTALLATION
Old
Installation
New
Installation
Comments
Chimney
Draft
-0.04" -0.04"
No change, but older chimneys (especially unlined ones) have leaks which reduce draft.
Boiler
Design
Pressure
Drop
+0.01" +0.01"
Required for mandated efficiency increases.
Draft
Over Fire
-0.03" -0.00"
The old installation would have had a higher temperature in the chimney [as high as 800 degrees vs. 400 degrees F], which would increase the draft.
Do not install this appliance where corrosive materials, such as ammonia, chlorine, water softener salt, etc. are stored.
CAUTION
An oil-fired unit shall be connected to a flue having sufficient draft at all times, to assure safe proper operation of the unit.
CAUTION
4
D. INSTALLATION SURVEY
For new and existing installations, a Water Installation Survey or a Steam Installation Survey is available from P.B. Heat, LLC. The surveys will provide information on how the boiler works with your specific system and will provide an overview of boiler system operation in general.
You can also use this survey to locate system problems which will have to be corrected. To obtain copies of these Surveys, contact your PB Heat representative or download it from PeerlessBoilers.com.
E. PLANNING THE LAYOUT
Prepare sketches and notes of the layout of the installation. Include boiler location, venting system, existing piping and wiring. Show existing equipment that may interfere with installation of new equipment.
PREINSTALLATION
5
A. SETTING THE BOILER
1. Provide a level foundation, located as close as possible to the center of the heating system.
2. Refer to Figure 8.1 for exploded view of boiler while checking and/or assembling parts of the boiler.
3. On packaged boilers, open burner mounting plate (item 5) at this time to make certain the target wall (item 2) is seated in the back of the combustion chamber. (WBV-04™/WV-05™) Ceramic fiber blanket base liner (item 3) should be lying flat on bottom of combustion chamber between target wall and burner mounting plate. Close burner mounting plate.
4. See clearance information in Section 1, "Preinstallation."
B. CONNECTING THE FLUE OUTLET
The WBV-03™ and WBV-04™ boiler models may be installed as a rear flue outlet unit or a top flue outlet unit. Packaged WBV-03™ and WBV-04™ boiler models are shipped as rear flue outlet and may be converted. The WV-05™ boiler model is only available as a top flue outlet unit. On Knockdown boilers, the flue outlet components are located in the water trim or steam trim carton.
1. If converting to a top flue application on a packaged boiler, remove top jacket panel and remove the large knockout in the jacket top panel. A stub vent will be required to extend the vent above the jacket top panel (not provided).
2. Remove the rear outlet cover plate (Item 13 Figure
8.1) and mount the flue collar to the flue collector plate (Item 11 Figure 8.1) with the 4 #12 screws.
3. Attach the rear outlet cover plate (item 13) to the rear outlet opening using four (4) 5/16" bolts and washers provided.
2. BOILER PLACEMENT AND ASSEMBLY
BOILER PLACEMENT AND ASSEMBLY
6
A. GENERAL
1. Follow these instructions closely in order to be sure that the boiler operates as it is intended. Water piping is extremely important to the system operation.
2. Size water supply and return piping in accordance with system requirements.
3. If the WBV/WV™ boiler is replacing and existing boiler, make sure that the system piping is thoroughly cleaned and free from debris before installing this boiler.
4. Install this boiler so that the oil burner and limit controls are protected from water (dripping, spraying, etc.) during operation and service.
5. The WBV/WV™ boiler is designed to operate in a closed loop hydronic system under forced circulation. However, there is no minimum water flow rate for this boiler.
B. SYSTEM COMPONENTS
Figure 3.1 shows the symbol key for the piping diagrams in this section. The following are brief descriptions of system components.
1. Pressure/Temperature Gauge: A combination pressure/temperature gauge is provided with each WBV/WV™ boiler to be mounted in the supply (outlet) piping as shown in figure 3.2. Most local codes require this gauge.
2. Air Elimination: Closed loop hydronic systems require air elimination devices. As the system water is heated, dissolved oxygen and other gases will separate from the liquid. An air elimination device (such as a TACO Vortech Air Separator) is required to remove the dissolved gases preventing corrosion in the piping system and eliminating noise.
3. WATER PIPING
WATER PIPING
Figure 3.1: Symbol Key
Loading...
+ 18 hidden pages