PeerlessBoilers LCE Series Installation, Operation & Maintenance Manual

Page 1
LC/LCE
Gas/Oil Boilers – Steam
Series
Oil, Gas &
Installation, Operation & Maintenance Manual
Page 2
USING THIS MANUAL
A. INSTRUCTION MANUALS . . . . . . . . . . . . . . .1
B. SPECIAL ATTENTION BOXES . . . . . . . . . . . .1
1. PREINSTALLATION
A. ACCESSIBILITY CLEARANCES . . . . . . . . . . .2
B. CLEARANCE FROM COMBUSTIBLE
CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . .3
C. COMBUSTION AND VENTILATION AIR . . . .3
D. CHIMNEY OR VENT . . . . . . . . . . . . . . . . . . . .3
E. BOILER SETTING . . . . . . . . . . . . . . . . . . . . . .4
F. INSTALLATION SURVEY . . . . . . . . . . . . . . . .5
G. PLANNING THE LAYOUT . . . . . . . . . . . . . . . .5
H. VERIFY COMPONENTS . . . . . . . . . . . . . . . . .5
2. PLACE THE BOILER
A. PACKAGED BOILER . . . . . . . . . . . . . . . . . . .10
B. ASSEMBLED BLOCK BOILER . . . . . . . . . . .10
C. KNOCKDOWN BOILER – PLACING
THE SECTIONS . . . . . . . . . . . . . . . . . . . . . .10
D. INSTALL COILS OR PLATES . . . . . . . . . . . .17
E. HYDROSTATIC TEST THE BOILER . . . . . . .17
F. APPLY CLEANOUT COVER PLATES . . . . . .19
G. INSTALL FLUE COLLAR . . . . . . . . . . . . . . . .19
H. INSTALL FLUE BAFFLES . . . . . . . . . . . . . . .20
I. INSTALL CHAMBER LINER . . . . . . . . . . . . .20
3. PIPE THE BOILER
A. PREPARATION . . . . . . . . . . . . . . . . . . . . . . .21
B. SUPPLY AND RETURN PIPING . . . . . . . . . .21
C. LOW SYSTEM TEMPERATURE . . . . . . . . . .21
D. MULTIPLE BOILER INSTALLATIONS . . . . . .22
4. ASSEMBLE THE JACKET
A. PREPARE THE PARTS . . . . . . . . . . . . . . . . .25
B. APPLY JACKET SIDES AND CORNERS . . .25
C. APPLY JACKET FRONT PANELS . . . . . . . . .25
D. APPLY JACKET REAR PANEL . . . . . . . . . . .25
E. APPLY JACKET TOP PANELS . . . . . . . . . . .25
F. APPLY PLATES AND LABELS . . . . . . . . . . .25
5. VENTING 27
6. INSTALL THE BURNER
A. BURNER APPLICATION . . . . . . . . . . . . . . . .27
B. INSTALL BURNER MOUNTING PLATE . . . .27
C. MOUNT THE BURNER . . . . . . . . . . . . . . . . .27
7. CONNECT FUEL PIPING
A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . .29
B. INSTALL FUEL OIL PIPING . . . . . . . . . . . . .29
C. INSTALL GAS SUPPLY PIPING . . . . . . . . . .29
D. TEST GAS SUPPLY PIPING . . . . . . . . . . . . .29
8. INSTALL CONTROLS AND TRIM
A. INSTALL SAFETY VALVES . . . . . . . . . . . . .31
B. INSTALL BLOWDOWN VALVE . . . . . . . . . . .31
C. INSTALL LOW WATER CUTOFF(S) . . . . . . .31
D. INSTALL PRESSURE CONTROLS . . . . . . . .31
E. PIPE TANKLESS HEATERS(S) . . . . . . . . . . .31
F. CONNECT SUPPLY WIRING . . . . . . . . . . . .31
G. INSTALL CONTROL WIRING . . . . . . . . . . . .32
9. STARTING THE BOILER
A. CHECK THE PIPING . . . . . . . . . . . . . . . . . . .39
B. FILL THE BOILER . . . . . . . . . . . . . . . . . . . . .39
C. RUN BURNER CHECK-OUT . . . . . . . . . . . . .39
D. CHECK BOILER CONTROLS . . . . . . . . . . . .39
E. CLEAN THE BOILER . . . . . . . . . . . . . . . . . . .39
10. MAINTENANCE
A. PLACING BOILER IN OPERATION . . . . . . . .42
B. TO SHUT DOWN THE BOILER . . . . . . . . . .42
C. MAINTENANCE – ANNUAL . . . . . . . . . . . . .42
D. MONTHLY MAINTENANCE . . . . . . . . . . . . .43
E. DAILY MAINTENANCE . . . . . . . . . . . . . . . . .43
11. BOILER RATINGS & DIMENSIONS 44
12. REPAIR PARTS
A. SERIES LC BOILER ASSEMBLY . . . . . . . . .47
B. SERIES LCE BOILER ASSEMBLY . . . . . . . .50
TABLE OF CONTENTS
TABLE OF CONTENTS
Page 3
1
A. INSTRUCTION MANUALS
The Series LC/LCE Installation, Operation & Maintenance Manual is divided into four basic sections:
1. Preinstallation (Section 1)
2. Installation (Sections 2 through 8)
3. Start-Up (Section 9)
4. Maintenance (Section 10)
B. SPECIAL ATTENTION BOXES
Throughout this manual you will see special attention boxes intended to supplement the instructions and make special notice of potential hazards. These categories mean, in the judgment of PB Heat, LLC:
Indicates special attention is needed, but not directly related to potential personal injury or property damage.
NOTICE
Indicates a condition or hazard which will or can cause minor personal injury or property damage.
CAUTION
DANGER
Indicates a condition or hazard which will cause severe personal injury, death or major property damage.
USING THIS MANUAL
USING THIS MANUAL
Indicates a condition or hazard which may cause severe personal injury, death or major property damage.
WARNING
Page 4
A. ACCESSIBILITY CLEARANCES
1. Clearances for service and from combustible surfaces are the same for the LCE as for the LC. The following recommendations allow for reasonable access to the boiler. Follow local codes and requirements when setting actual layout. See Figure 1.1.
a) For installing, removing and servicing the burner:
provide 48" between the front of the boiler and any adjacent wall or other appliance.
b) For access to the top of the boiler for cleaning
flueways: provide 24" above top of jacket.
c) For accessing and servicing of level controls and
inspection tappings (if used): provide 24" minimum from the right side of the boiler to any wall or obstruction.
d) For installation of jacket: provide at least 12"
from the left side of the boiler to any wall or obstruction. More clearance may be needed for longer boilers unless the jacket is pre-assembled before placing the boiler.
e) For installation and removal of tankless heaters:
provide 45" between the end of the boiler and any adjacent wall of obstruction. [This provides for all available tankless coils. The spacing can be closer for Heater Number X-1020 (allow 30") or Heater Number X-1021 (allow 35")].
The equipment must be installed in accordance with installation requirements of the authority having jurisdiction or, in the absence of such requirements, to the current edition of the
National Fuel Gas Code
, ANSI
Z223.1/NFPA 54.
Where required by the authority having jurisdiction, the installation must conform to
American Society of
Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers,
ASME CSD-1.
NOTICE
PREINSTALLATION
1. PREINSTALLATION
Carefully read these instructions before beginning work. Understand all aspects of the installation. Contact your PB Heat, LLC sales representative or customer service for help in answering questions.
This boiler must be installed by a qualified contractor. The boiler warranty can be voided if the boiler is not installed, correctly.
Figure 1.1: Clearance Requirements
2
Page 5
B. CLEARANCE FROM COMBUSTIBLE
CONSTRUCTION
Provide the following minimum clearances to combustible construction. See Figure 1.1.
1. Sides: 6"
2. Rear of Jacket: 6"
3. Front of Jacket: 24"
4. Top of Jacket: 24"
5. Steam and Hot Water Pipes: 6"
6. Vent or Chimney Connector: 18"
C. COMBUSTION AND VENTILATION AIR
1. The installation must provide adequate air for combustion and ventilation.
2. Unless the boiler room construction and natural air infiltration are sure to provide all the air needed, provide an opening or duct to the outside with a free cross sectional area of at least 1 square inch per 4000 Btuh input for all installed appliances. At high altitude, increase this requirement 4% for each 1000 feet above sea level.
3. The boiler room must never be under negative pressure. If exhaust fans or other equipment can cause a negative pressure in the boiler room, the air openings and equipment design must be engineered to assure a neutral or slightly positive pressure in the boiler room at all times of operation. If the equipment design and air openings cannot assure this, then the boiler must be located in an isolated room.
4. Using combustion air dampers:
a) If motorized dampers are used on the
combustion and ventilation air openings, wire them such that they must open when the boiler tries to operate. They must include a switch which prevents the boiler from operating if they do not open. See Figure 1.2.
D. CHIMNEY OR VENT
1. Inspect the existing chimney or vent system. Make sure it is in good condition. Inspect chimney liner and repair or replace if necessary.
2. The vent system and installation must be in accordance with the current edition of the American National Standard ANSI/NFPA 211, “Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances”, or applicable provisions of the local building codes. The venting requirements for the LCE are the same as for the LC. Figure 1.3 shows the top flue outlet required on LCE boilers.
3. Chimney/Vent Operation: The vent system must be sized and installed to remove all combustion products. If the vent system is not sized properly, the burner may not operate properly. This can cause poor combustion or sooting to occur.
4. If the vent terminates in an area where wind­generated downdrafts are likely, install a suitable vent cap which can control wind effects.
5. This boiler is designed to fire only with a pressurized fire box. The breeching and vent may be sized for negative, neutral or positive pressure (no more than
0.l inches water column at the boiler outlet) as desired. But negative pressure overfire can cause lifting of the flame and poor combustion or overheating of the boiler crown sheet.
6. Forced draft breechings and vents must be sealed and of heavy gauge steel construction and must comply with all applicable codes of construction.
7. The vent diameter and minimum height for stub vents are listed in the Ratings and Dimensions Section of this manual. Always extend vent terminations at least 3 feet above the roof line. See Figure 1.3.
3
PREINSTALLATION
Figure 1.2: Motorized Vent Damper Interlock Figure 1.3: Vent Termination, Typical
Failure to provide adequate venting can result in severe property damage, personal injury or death.
WARNING
Page 6
4
8. Exterior Vents: a) Insulate sufficiently to ensure adequate draft and
to prevent vent damage due to condensation.
9. Vent Connection to Boiler: a) Support the weight of the vent system
independently of the boiler flue connection.
b) Provide support of the vent connector
(breeching) at maximum 12 foot intervals to prevent sagging and to provide a minimum upward slope of 1/4" per foot.
10. Do not vent natural draft appliances in a combined
vent which operates under positive pressure.
11. Draft Regulator: Install a barometric draft regulator
where using high chimney or any high draft vent. This is needed to prevent causing negative draft in the boiler. Excess draft will cause flame lifting and possible impingement.
12. The Draft Damper for the LCE boiler is a separate
piece, shipped in the Top Flue Outlet Carton.
a) Install the Draft Damper as close as possible to
the boiler flue outlet. It can be installed vertically or horizontally provided that the connecting vent piping and fittings are designed and installed for pressurized service.
b) Secure the damper to the vent with screws and
seal the joints with a bead of high temperature silicone sealant (found in Section Assembly Kits).
c) The vent must be installed so it can be
disconnected and the Top Flue Outlet removed for proper cleaning of the flueways.
E. BOILER SETTING
1. If the boiler room floor is not level or if additional structural support is needed, provide a good, level foundation for the boiler with the minimum dimensions given in Table 1.1. The flooring and structural support system must be suitable for the operating weight of the boiler and any connected piping. Place the Steel Channels on the foundation as shown in Figure 1.4.
2. Do not operate the boiler until the foundation, if new concrete, has thoroughly cured. The concrete might be damaged if heated too quickly due to the entrained moisture remaining.
3. If the boiler is installed in a penthouse or if wiring of any sort is run underneath the boiler foundation, construct the foundation with provision for air flow underneath between the main floor and the top of the boiler foundation.
a) An acceptable foundation would be concrete
blocks laid with the openings lined up.
Do not install this boiler on carpeting or any combustible flooring. A significant fire hazard could result, with potential for property damage, personal injury or death.
WARNING
Figure 1.4: Foundation Layout
PREINSTALLATION
Page 7
5
b) If the foundation must be a concrete slab, use an
air cell high temperature insulating board, at least 1/2" inch thick, with aluminum backing, aluminum side up. 1/2" inch thick high temperature millboard with aluminum backing is acceptable as well. Place the insulating board on the slab between the steel channels.
F. INSTALLATION SURVEY
For new and existing installations, a Steam Installation Survey is available from PB Heat, LLC. The survey will provide information on how a steam boiler works with your specific system and will provide an overview of steam system operation in general.
You can also use this survey to locate system problems which will have to be corrected. To obtain copies of the Steam Installation Survey, contact your PB Heat representative or download it from PeerlessBoilers.com.
G. PLANNING THE LAYOUT
Prepare sketches and notes of the layout to minimize the possibility of interferences with new or existing equipment, piping, venting and wiring.
H. VERIFY COMPONENTS
1. Packaged: All components should be inside crate. In some cases the burner may be shipped separately. Optional equipment, such as barometric draft dampers, may also be shipped separately.
2. Knockdown: All components shipped for field assembly. See Table 1.2 for standard components. See Tables 1.3 through 1.7 for optional components.
a) Channel Rails
b) Sections
c) Assembly Kit Carton(s): Includes flow port
gaskets, tie rods with hardware, high temperature rope, and cleanout cover plates.
d) Flue Box Carton: Includes flue box, rear flue
cover plate (LCE only), rear observation assembly and port cover plates.
e) Baffle Carton
i) LC: Includes baffles, combustion chamber
liner, rating label
ii) LCE-21 through LCE-24: Baffles
f) Jacket Cartons: Includes ASME plate
g) Draft Damper (LCE only)
h) Label Carton (LCE only)
i) Burner Mounting Plate
j) Trim Carton: Includes safety relief valve and
temperature-pressure gage
k) Control Carton: Limit controls
l) Tankless Heater(s)
m) Additional controls and fittings
3. Assembled Block: Same as knockdown except channel rails, sections and assembly kit cartons are assembled into a block as a single shipping level component.
Table 1.1: Foundation Lengths
LC-04 LC-05 LC-06 LC-07 LC-08 LC-09 LC-10 LC-11
LC-12 LCE-13 LCE-14 LCE-15 LCE-16 LCE-17 LCE-18 LCE-19 LCE-20 LCE-21 LCE-22 LCE-23 LCE-24
Model
Foundation Length, Inches
37¹⁵⁄₁₆
43
48¹⁄₁₆
53¹⁄₈
58⁵⁄₁₆
63³⁄₈
68⁷⁄₁₆
73¹⁄₂
78⁹⁄₁₆
83³⁄₄
88¹³⁄₁₆
93⁷⁄₈ 98¹⁵⁄₁₆ 104¹⁄₈
109³⁄₁₆
114¹⁄₄
119⁷⁄₁₆
124¹⁄₂
129⁹⁄₁₆
134⁵⁄₈
139¹¹⁄₁₆
PREINSTALLATION
Page 8
6
PREINSTALLATION
Table 1.2A: Series LC Shipping List
Panels
Top/Side
Hardware
Panels
Front/Rear
Contents
See Below
Contents
See Below
Assembly Kit Ctns. Jacket Cartons (Tbl 1.4 Options)Flue Ctn.
Baffle
3" Tap.
1"
LWCO
Chamber Liner
1
LC-6017
1
LC-6016
Hardware
1
Item 2
LC-5004
Item 1
1
LC-1022
1
LC-1023
Carton
Interm.
1
Interm.
LC-1000-1
A
A
A
LC-04
86031
86030
86040
86050
85004
86005
1
1
1
1
1
1
B
LC-6017-1
LC-6016
A
LC-5004
B
LC-1022-1
LC-05
LC-1023
LC-1000-1
86032
86030
86040
86051
85105
86005
1
1
1
1
1
1
B
LC-6017-1
LC-6016
A
LC-5004
B
LC-1022-1
LC-05
LC-1023-1
LC-1000-1
86032
86030
86040
86051
85005
86005
1
1
1
1
1
1
C
LC-6017-2
LC-6016
B
LC-5004-1
C
LC-1022-2
LC-06
LC-1023-2
LC-1000-1
86033
86030
86041
86052
85006
86005
1
1
1
1
1
1
D
LC-6017-3
LC-6016
B
LC-5004-1
D
LC-1022-3
LC-07
LC-1023-3
LC-1000-1
86034
86030
86041
86053
85007
86005
1
1
1
1
1
1
1
1
B
LC-6017-1
A
LC-6017
LC-6016
B
LC-5004-1
B
LC-1022-1
A
LC-1022
LC-08
LC-1023-4
LC-1000-1
86032
86031
86030
86041
86051
86050
85008
86005
2
1
1
2
1
1
B
LC-6017-1
LC-6016
C
LC-5004-2
B
LC-1022-1
LC-09
LC-1023-5
LC-1000-1
86032
86030
86042
86051
85009
86005
1
1
1
1
1
1
1
1
C
LC-6017-2
B
LC-6017-1
LC-6016
C
LC-5004-2
C
LC-1022-2
B
LC-1022-1
LC-10
LC-1023-6
LC-1000-1
86033
86032
86030
86042
86052
86051
85010
86005
2
1
1
2
1
1
1
C
LC-6017-2
LC-6016
C
LC-5004-2
C
LC-1022-2
LC-11
LC-1023-7
LC-1003
LC-1000-1
86033
86030
86042
86052
85011
86008
86005
1
1
1
1
1
1
1
1
1
D
LC-6017-3
C
LC-6017-2
LC-6016
C
LC-5004-2
D
LC-1022-3
C
LC-1022-2
LC-12
LC-1023-8
LC-1003
LC-1000-1
86034
86033
86030
86042
86053
86052
85012
86008
86005
Plain
Interm.
Back
Standard Sections (See Table 1.3 for Options)
Front
Rail
Bundle
Channel
Boiler
Model
Number
1
1
1
1
Quantity
LC-1000
LC-1007
LC-1001
Label
Par t N o.
86004
86022
86000
90160
Stock Code
LC-04
2
LC-1000
1
LC-1007
1
LC-1001
1
Par t N o.
Quantity
LC-05R
Label
2
86004
1
86022
1
86000
1
90161
Quantity
Stock Code
LC-05
LC-1000
LC-1007
LC-1001
Label
Par t N o.
3
86004
1
86022
1
86000
1
90161
Quantity
Stock Code
LC-06
LC-1000
LC-1007
LC-1001
Label
Par t N o.
4
86004
1
86022
1
86000
1
90162
Quantity
Stock Code
LC-07
LC-1000
LC-1007
LC-1001
Label
Par t N o.
5
86004
1
86022
1
86000
1
90163
Quantity
Stock Code
LC-08
LC-1000
LC-1007
LC-1001
Label
Par t N o.
6
86004
1
86022
1
86000
1
90164
Quantity
Stock Code
LC-09
LC-1000
LC-1007
LC-1001
Label
Par t N o.
7
86004
1
86022
1
86000
1
90165
Quantity
Stock Code
LC-10
LC-1000
LC-1007
LC-1001
Label
Par t N o.
7
86004
1
86022
1
86000
1
90166
Quantity
Stock Code
LC-11
LC-1000
LC-1007
LC-1001
Label
Par t N o.
8
86004
1
86022
1
86000
1
90167
Quantity
Stock Code
LC-12
LC-1000
LC-1007
LC-1001
Label
Par t N o.
86004
86022
86000
90168
Stock Code
Mounting Hardware
1 Assembly Kit Cartons Contents: Flow Port Gaskets, Silicone Sealant, Tie Rods, Washers, Tie Rod Nuts, Section Seal Rope, Rope Adhesive or Spray Adhesive, Cleanout Plates,
2 Flue Box Carton Contents: Flue Box, Seal Rope, Observation Assembly, Coil Cover Plates, Cover Plate Gaskets, Mounting Hardware
Page 9
7
PREINSTALLATION
Table 1.2B: Series LCE Shipping List
85013
LCE-8028
A
90523
S-5007-3
E
86094
LCE-6023
B
86032
LCE-6017-1
A
86031
LCE-6017
86030
LCE-6016
D
86043
LC-5011
E
86054
C
86052
1
1
1
2
1
1
1
1
1
Label
Rating
1
Draft
Damper
1
1
Panels
Top/Side
Hardware
Chamber Liner
1
1
Panels
Hardware
Front/Rear
1
Item 1
Contents
See Below
1
Mounting Hardware
Assembly Kit Cartons Jacket Cartons (See Table 1.4 for Options)Flue Ctn. Lbl. Ctn.
Flow Port Gaskets, Silicone Sealant,
1
Rope Adhesive or Spray Adhesive, Cleanout Plates,
Tie Rods, Washers, Tie Rod Nuts, Section Seal Rope,
85014
LCE-8028-1
A
90523
S-5007-3
E
86094
LCE-6023
B
86032
LCE-6017-1
86030
LCE-6016
D
86043
LC-5011
E
86054
D
86053
1
LCE-8028-2
1
S-5007-3
1
LCE-6023
1
LCE-6017-2
1
LCE-6017-1
1
LCE-6016
1
LC-5011
1
1
1
85016
LCE-8028-3
A
90523
S-5007-3
E
86094
LCE-6023
C
86033
LCE-6017-2
86030
LCE-6016
D
86043
LC-5011
E
86054
B
86051
1
1
1
2
1
1
1
1
1
1
1
85015
1
A
90523
1
E
86094
C
86033
2
B
86032
1
86030
1
D
86043
E
86054
1
B
86051
2
A
86050
85017
LCE-8028-4
A
90523
S-5007-3
E
86094
LCE-6023
B
86032
LCE-6017-1
A
86031
LCE-6017
86030
LCE-6016
D
86043
LC-5011
E
86054
C
86052
B
86051
1
1
1
3
1
1
1
2
85018
LCE-8028-5
B
90524
S-5007-4
E
86094
LCE-6023
B
86032
LCE-6017-1
86030
LCE-6016
E
86044
LC-5012
E
86054
C
86052
1
1
1
1
2
1
1
1
1
1
85019
LCE-8028-6
B
90524
S-5007-4
E
86094
LCE-6023
C
86033
LCE-6017-2
B
86032
LCE-6017-1
86030
LCE-6016
E
86044
LC-5012
E
86054
D
86053
C
86052
1
1
1
2
2
1
1
1
2
85020
LCE-8028-7
B
90524
S-5007-4
E
86094
LCE-6023
B
86032
LCE-6017-1
A
86031
LCE-6017
86030
LCE-6016
E
86044
LC-5012
E
86054
D
86053
1
1
1
3
1
1
1
1
1
1
1
85021
LCE-8028-8
B
90524
S-5007-4
E
86094
LCE-6023
B
86032
LCE-6017-1
A
86031
LCE-6017
86030
LCE-6016
E
86044
LC-5012
E
86054
D
86053
B
86051
A
86050
1
1
1
4
1
1
1
1
2
85022
LCE-8028-9
B
90524
S-5007-4
E
86094
LCE-6023
B
86032
LCE-6017-1
86030
LCE-6016
E
86044
LC-5012
E
86054
D
86053
B
86051
1
1
1
1
3
1
1
1
1
1
1
85023
LCE-8028-10
B
90524
S-5007-4
E
86094
LCE-6023
C
86033
LCE-6017-2
B
86032
LCE-6017-1
86030
LCE-6016
E
86044
LC-5012
E
86054
D
86053
C
86052
B
86051
1
LCE-8028-11
1
S-5007-4
1
LCE-6023
2
LCE-6017-2
2
LCE-6017-1
1
LCE-6016
1
LC-5012
1
1
2
85024
B
90524
E
86094
C
86033
B
86032
86030
E
86044
E
86054
D
86053
C
86052
Baffle
Carton
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Label
Par t No.
1
86022
6
86004
2
86008
1
86005
3
86100
1
86000
2
90169
Quantity
Stock Code
LCE-14
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Par t No.
1
6
Plain
Interm. Back
1
3" Tap.
Interm.
1
1"
LWCO
Interm.
3
Top
Flue
Interm.
Standard Sections (See Table 1.3 for Options)
1
Front
2
Rail
Bundle
Channel
Quantity
Boiler
Model
Number
LCE-13
Label
1
86022
7
86004
2
86008
1
86005
3
86100
1
86000
2
90162
Quantity
Stock Code
LCE-15
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Label
Par t No.
1
86022
8
86004
2
86008
1
86005
3
86100
1
86000
2
90163
Quantity
Stock Code
LCE-16
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Label
Par t No.
1
86022
8
86004
3
86008
1
86005
3
86100
1
86000
2
90163
Quantity
Stock Code
LCE-17
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Label
Par t No.
1
86022
9
86004
3
86008
1
86005
3
86100
1
86000
2
90164
Quantity
Stock Code
LCE-18
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Label
Par t No.
1
86022
10
86004
3
86008
1
86005
3
86100
1
86000
2
90164
Quantity
Stock Code
LCE-19
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Label
Par t No.
1
86022
10
86004
4
86008
1
86005
3
86100
1
86000
2
90165
Quantity
Stock Code
LCE-20
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Label
Par t No.
1
1
86022
11
86004
4
86008
1
86005
3
86100
1
86000
2
90165
Quantity
Stock Code
LCE-21
LCE-1074
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Label
Par t No.
1
86113
1
86022
12
86004
4
86008
1
86005
3
86100
1
86000
2
90166
Quantity
Stock Code
LCE-22
LCE-1074
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Label
Par t No.
1
86113
1
86022
13
86004
4
86008
1
86005
3
86100
1
86000
2
90166
Quantity
Stock Code
LCE-23
LCE-1074
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Label
Par t No.
1
86113
1
86022
14
86004
4
86008
1
86005
3
86100
1
86000
2
90167
Quantity
Stock Code
LCE-24
LCE-1074
LC-1007
LC-1000
LC-1003
LC-1000-1
LCE-1056
LC-1001
Label
Par t No.
86113
86022
86004
86008
86005
86100
86000
90167
Stock Code
1 Flue Box Carton Contents: Top Flue Plate, Rear Flue Cover, Seal Rope, Observation Assembly, Coil Cover Plates, Cover Plate, Gaskets, Mounting Hardware
Page 10
8
PREINSTALLATION
Note: Boilers with inspection tappings in front and back sections only use standard cartons.
Table 1.4: Standard and Optional Jacket Cartons,
Top/Side Panels
A B C D
E
Jacket Label
86031 86032 86033 86034 86094
Standard
(No Inspection
Tappings)
86101 86102 86103 86104 86097
With Inspection
Tappings
Table 1.3: Standard and Optional Sections for Knockdown Boilers
Table 1.5A: Burner Mounting Plates
Model
CF-800 CF-1400 CF-2300 301CRD 702CRD 801CRD
S4.2 R6.2 R6.3 R8.1 R8.2 R8.3
C1
C2 J15A J30A J50A
JB1
Boiler Model
86070*
86070*
86070*
86071
86072
86071
LC-04
86070*
86070*
86070*
86071
86072
86071
LC-05R
86069*
86069*
86078
86071
86072
86071
LC-05
86069*
86069*
86078
86071
86072
86071
LC-06
86069*
86069*
86079
86071
86072
86071
LC-07
86074*
86069*
86079
86076
86077 86075
LC-08
86074*
86073
86079
86076
86077 86075
LC-09
86074*
86073
86079
86076
86077 86075
LC-10
86074*
86073
86079
86076
86077 86075
LC-11
86074*
86073
86079
86076
86075
LC-12
Beckett
Carlin
Gordon
Piatt
Power
Flame
Webster
* Standard Burner Mounting Plate
Sections
15 psig Steam MAWP
Standard w/Inspection Tappings
Par t # Stock Code Part # ITP Stock Code
Front
LC-1001 86000 LC-1013 86010
Intermediate
LC-1000 86004 LC-1014 86014
LWCO Intermediate
LC-1000-1 86005 LC-1014-2 86092
Top Flue Intermediate
LCE-1056 86100 LCE-1064 86110
3" Tapped Intermediate
LC-1003 86008 LC-1015 86016
Closed Back
LC-1007 86022 LC-1016 86018
Coil Back
LC-1002 86036 LC-1017 86026
Page 11
9
PREINSTALLATION
Table 1.7: Control Cartons
Table 1.6: Trim Cartons
1 Safety Relief Valve selection based on capacity
determined by boiler output (Gross I=B=R Output). Applies to most locations in United States and Canada.
Table 1.5B: Burner Mounting Plates
Model
CF2300AKG
CF2300AKB
CF2500
CF3500AKM
CF3500AKL
801CRD 1050FFD 1150FFD
R10.9
R10 R10.1 R10.2
C2 C3
JB2
Boiler Model
86074*
86073
86088
86076
86081
LCE-13
86083*
86073
86088
86076
86081
LCE-14
86083*
86086
86088
86076
86081
LCE-15
86074*
86086
86088
86080 86081
LCE-16
86074*
86087
86088
86080 86081
LCE-17
86083*
86087
86088
86080 86081
LCE-18
86083*
86087
86088
86080 86081
LCE-19
86083*
86087
86088
86080 86081
LCE-20
86080*
86087
86088
86080 86081
LCE-21
86080*
86087
86088
86080 86081
LCE-22
86087
86088
86080 86081
LCE-23
N/A
86088
86080 86081
LCE-24
Beckett
Carlin
Gordon
Piatt
Power
Flame
Webster
* Standard Burner Mounting Plate
Not
Available
Model
Stock
Code
Label
LC-04
LC-05R
LC-05
87000 87000 87000
A A
A LC-06 LC-07 LC-08
87000 87000 87000
A
A
A LC-09 LC-10 LC-11 LC-12
87001 87001 87001 87001
B
B
B
B
LCE-13 LCE-14 LCE-15
87002 87002 87002
C
C
C
LCE-16 LCE-17 LCE-18
87002 87003 87003
C
D
D
LCE-19 LCE-20 LCE-21
87003 87003 87003
D
D
D
LCE-22 LCE-23 LCE-24
87003 87004 87004
D
E
E
Model Stock Code Label
LC-04
Through
LCE-24
88511 Steam
Page 12
10
A. PACKAGED BOILER
1. Remove crate top and sides. Remove any loose cartons. Remove burner support pedestal and nipple, if supplied
2. Lift boiler off crate pallet. Move to location determined in Chapter 1: Preinstallation.
3. Remove lifting frame and hardware.
4. Re-install burner support pedestal and nipple if necessary.
5. Proceed to Chapter 3: Piping the Boiler.
B. ASSEMBLED BLOCK BOILER
1. Move block to location determined in Chapter 1: Preinstallation.
2. Remove lifting frame and hardware.
3. Proceed to Section D: Install Coils or Plates
C. KNOCKDOWN BOILER
1. Place channel rails as shown in Figure 1.4.
2. Open the Section Assembly Kit cartons. These cartons contain the parts needed for assembly of the sections.
3. Place the Back Section on the floor as shown in Figure 2.1.
4. The Back Section combustion chamber area is lined with a ceramic fiber blanket liner. Make sure the liner is in good condition. Minor tears are not a problem, but there should be no holes in the insulation.
PLACE THE BOILER
2. PLACE THE BOILER
Figure 2.1: Lay Sections on Floor and Apply Rope Seal and Gaskets
Page 13
11
5. Clean the area around the flow ports and in the seal recess. Use solvent and a clean cloth to thoroughly clean all of the sealing surfaces. Remove all foreign matter to assure a water tight seal when the sections are drawn together.
6. Place a Flow Port Gasket in each of the three flow port recesses as shown in Figures 2.1 and 2.2.
7. Apply rope adhesive or spray adhesive in the rope groove around the perimeter of the section.
8. Place the sealing rope completely around the rope groove, being careful not to stretch the rope. Extend the rope from 1/4" to 1/2" past the end of the groove on both sides of the cleanout opening on top of the section. This will assure a gas tight seal when the cleanout cover plate is applied.
9. Apply a bead of silicone sealant around each flow port as shown in Figure 2.3. Do not get sealant on the flow port gaskets.
10. Lift up the Rear Section and move into position on the steel channels on the boiler foundation.
11. Screw a 3" pipe at least 30 inches long into the lower 3" tapping on the back of the Rear Section as shown in Figure 2.4. Place a block under the pipe as shown in the figure and use as a brace during assembly.
12. Place a Plain Intermediate Section on the floor and prepare as above.
13. Carefully place the Intermediate Section against the Rear Section and visually line up the flow ports as close as possible.
14. Insert a tie rod with one nut and washer applied into each of the four tie rod lugs. See Figures 2.5 and 2.6.
15. Place the nut and washer on the other end of the tie rod and draw finger tight.
PLACE THE BOILER
Figure 2.3: Apply Silcone Sealant
Gaskets will be damaged by petroleum or its derivatives. Completely remove all solvent residue before placing gaskets.
Do not use petroleum based compounds in the boiler.
CAUTION
Figure 2.2: Flow Port Machining & Gasket
The sections are heavy and must be supported securely.
WARNING
Page 14
12
Figure 2.4: Install Additional Sections. Use level on each section as tie rod bolts are drawn up.
PLACE THE BOILER
Page 15
13 13
PLACE THE BOILER
Figure 2.5: Series LC Boiler Assembly – Right Side View
Page 16
14
PLACE THE BOILER
Figure 2.6: Series LCE Boiler Assembly – Right Side View
Page 17
15
16. To properly assemble LC/LCE sections in the field, the following steps must be followed to ensure that no damage occurs to the tie rod lugs. A 0-100 ft-lbs torque wrench is required.
a. Use a spirit level as shown in Figure 2.4 to check
the alignment of the sections as the nuts are drawn up. Keep the sections plumb.
b. Draw the sections together evenly, in three
rotations. Torque each port to 20 ft-lbs for the first rotation, then to 40 ft-lbs for the second rotation, then to 60 ft-lbs for the third rotation. Use the following sequence until all three ports touch metal-to-metal at 60 ft-lbs. See Figure 2.7 for port reference.
i) First: Lower Top Port
ii) Second: Bottom Port
iii) Third: Upper Top Port
c. Tighten these (3) three locations only to a torque
value of 60 ft-lbs. DO NOT EXCEED.
d. After the three ports have been tightened to 60
ft-lbs, tighten the draw rod at the bumping pads until metal-to-metal contact is reached. This will assure a proper gas tight seal and prevent the products of combustion from migrating into the boiler room.
17. Repeat with the remaining sections. a. Save the LWCO Intermediate with two 1"
tappings (for level control) for use as the section closest to the front section.
b. Place the Intermediate Section with 3" top
tapping (Tapped Intermediate) in the position given in Figure 2.9.
c. LCE ONLY. Save the (3) Top Flue Outlet
Intermediates (with wide opening in top of the flue collector) for use as the sections closest to the LWCO Intermediate Section. See Figure 2.9.
i) The sequence from Front to Rear is:
• Front Section
• 1" Low Water Cut-off Intermediate
• Three (3) Top Flue Outlet Intermediates
ii) The remaining intermediate sections are 3"
Tapped Intermediates or Plain Intermediates as shown in Figure 2.8 and Figure 2.9.
Do not exceed the manufacturer’s torque recommendations.
WARNING
PLACE THE BOILER
Figure 2.7: Torque Specification/Procedure
Figure 2.8: Section Positioning Numbering
Table 2.1: Section Numbering Sequence
LC-04 LC-05 LC-06 LC-07 LC-08 LC-09 LC-10 LC-11
LC-12 LCE-13 LCE-14 LCE-15 LCE-16 LCE-17 LCE-18 LCE-19 LCE-20 LCE-21 LCE-22 LCE-23 LCE-24
Model
Place a Tapped Intermediate
Section at Position
(Numbered Rear to Front)
NA NA NA NA NA NA NA
6 6 8
5, 9 6, 10 6, 11
5, 9, 12 5, 9, 13
5, 9, 14 5, 9, 12, 15 5, 9, 13, 16 5, 9, 13, 17
6, 10, 14, 18 6, 10, 14, 19
Page 18
16
Figure 2.9: LC/LCE Boiler Section Assembly Sequence
PLACE THE BOILER
Page 19
17
D. INSTALL COILS OR PLATES
1. Remove the coil cover plates, gaskets and mounting hardware, located in the Flue Box Carton.
2. Place the cover plates and gaskets over any unused heater openings. Place the cover plate with two 3/4" NPT tappings on the upper flow port opening (Position #2) of the Front Section.
3. Install tankless heaters, if used, in openings #1 and #3. (Optional on Rear Section)
4. See Figure 2.10.
5. Steam boilers may have up to two coils installed when supplied with special tankless coil rear seciton.
6. Standard Rear Sections do not have a tankless opening (position #3). This is available only as optional construction. This special rear section is needed to install two coils on a steam boiler.
E. HYDROSTATIC TEST THE BOILER
1. Install a drain valve in the Rear Section, Tapping 13. See Figure 8.2.
2. Provide a water supply line to the boiler.
3. Plug all open tappings in the boiler.
4. Provide a means to vent air as the boiler fills.
5. Fill the boiler with water, venting air as water level rises.
6. Pressurize boiler to:
• 45 psig
DO NOT EXCEED THESE PRESSURES.
a) Maintain pressure while checking all joints and
fittings for leaks.
7. After inspection is complete, drain the boiler and remove plugs from tappings that are to be used.
PLACE THE BOILER
Figure 2.10: Tankless Coil Openings
Page 20
18
Table 2.2: Tankless Coil Ratings
LC-04
LC-05R
LC-05 LC-06 LC-07 LC-08 LC-09 LC-10 LC-11
LC-12 LCE-13 LCE-14 LCE-15 LCE-16 LCE-17 LCE-18 LCE-19 LCE-20 LCE-21 LCE-22 LCE-23 LCE-24
Model
GPM Location
5.5
5.62
5.75
6.25
6.5
7.0
7.25
7.5
8.0 – – – – – – – – – – – – –
1 1 1 1 1 1 1 1 1 – – – – – – – – – – – – –
GPM Location
6.5
7.0
7.75
8.5
9.25
10.0
10.75
11.50
12.25 13 13 13 13 13 13 13 13 13 13 13 13
– 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
GPM Location
– – – –
13.0
13.75
14.5
15.5
16.5
17.5
18.0
18.75
19.5 20 20 20 20 20 20 20 20 20
– – –
– 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
GPM Location
– – – – – –
14.5
15.0
16.0 – – – – – – – – – – – – –
– – – – –
– 1 & 3 1 & 3 1 & 3
GPM Location
– – – – – – –
21.5
23.5
24.5 26 26 26 26 26 26 26 26 26 26 26 26
– – – – – –
– 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3
GPM Location
– – – – – – – – – – – –
33.5
35.5
37.5
39.5 40 40 40 40 40 40
– – – – – – – – – – –
– 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3 1 & 3
Heater No.
X-1020
Heater No.
X-1021
Heater No.
X-1022
Two Heaters No.
X-1020
Two Heaters No.
X-1021
Two Heaters No.
X-1022
Above heater ratings are based on intermittent demand for water from 40
°F to 140°F with 200°F boiler water.
Steam boilers require a special rear section with coil opening in order to use two tankless heaters. DANGER: Install mixing valve in hot water supply piping. Water temperature over 125°F can cause severe burns instantly or death from scalds.
PLACE THE BOILER
Page 21
19
F. APPLY CLEANOUT COVER PLATES
1. Apply the Cleanout Cover Plates on the tops of the section joints as shown in Figure 2.11.
2. Pre-assemble a steel flat washer and steel nut on the carriage bolts. Place a carriage bolt into each side of the cleanout opening as shown in the figure.
3. Tighten the lower nut securely.
4. Press the Cleanout Plate with insulation over the protruding carriage bolts until the insulation lays flush against the cast iron.
5. Apply a flat washer and brass nut to the carriage bolt. Draw the brass nuts down until the insulation presses firmly against the iron.
G. INSTALL FLUE COLLAR
1. (LC) Remove the Flue Collar and Rear Observation Door Assembly from the LC Rear Flue Box Carton. (LCE) Remove the Top Flue Outlet Plate, the Rear Flue Cover Plate and the Rear Observation Door Assembly from the LCE Top Flue Outlet Carton.
2. (LC) Attach the Flue Collar to the Back Section with 5/16" x 1¹⁄₂" studs, flat washers and hex nuts supplied. See Figure 2.12. (LCE) Attach the Rear Flue Cover Plate to the Rear Section with 5/16" x 1¹⁄₂" studs, flat washers and nuts supplied.
3. (LCE) Apply high tack adhesive or spray adhesive (supplied in Section Assembly Kits) to the rope groove on the bottom of the Top Flue Outlet Plate. Place the high temperature rope seal in the groove, overlapping at the ends for a good seal.
a) Place the plate over the opening provided by the
three top flue intermediate sections at the front of the boiler. NOTE: Top flue outlet plate is marked “FRONT” for proper orientation.
b) Secure the plate and compress using the 3/8" tie
down assembly, nuts and washers provided. See Figure 2.13.
c) Inspect the finished seal, particularly where the
plate crosses the section joints.
d) The correct Top Flue Outlet Plate for the LCE
boiler is:
• LCE-13 thru LCE-17 use the 14" flue opening, part number LCE-5007, Carton D
• LCE-18 thru LCE-24 use the 16" flue opening, part number LCE-5007-1, Carton E
4. Attach the Rear Observation Door to the Rear Section with four (4) 5/16"-18 x 3/4" hex head bolts provided.
PLACE THE BOILER
Figure 2.12: Rear Flue Collar Attachment Figure 2.13: Top Flue Collar Attachment
Figure 2.11: Install Cleanout Cover Plates
Page 22
20
H. INSTALL FLUE BAFFLES
1. Remove the Front Cleanout Plate from Front Section.
2. Open Baffles carton. Remove Baffles. For LC Only – Save Ceramic Fiber Liner for Section I. Save Rating Label for Chapter 4. Models LCE-13 through LCE­20 do not require baffles.
3. Place baffles as shown in Figure 2.14. Three of these are special stainless steel baffles, identified with a 1/4" hole punched in each end. These baffles must be placed in the lowest row of tubes.
4. Install the Front Cleanout Plate.
I. INSTALL CHAMBER LINER
1. (LCE) Remove Ceramic Fiber Liner from Jacket Carton E. Place the liner on the floor of the combustion chamber. Place the front end of the liner flush with the inside of the Front Section. The liner is 24 inches wide. It will not extend all the way to the rear of the boiler on all boiler sizes. No adhesive is required, just press the liner down firmly.
PLACE THE BOILER
Figure 2.14: Flue Baffle Locations
Page 23
21
A. PREPARATION
1. The boiler must be pressure tested as outlined in the chapter “Place the Boiler Sections” of this manual.
2. The Supply and Return piping can be installed before installing the jacket. Use nipples long enough to extend through the jacket.
B. SUPPLY AND RETURN PIPING
1. See Figure 3.3 for piping illustration.
2. Install Top connections sized per Table 3.1.
a) Model LC-04 requires one riser off the Rear
Section. Plug the 4" tapping in the top of the Front Section.
b) Models LC-05 through LC-10 require two risers,
one off the Front and one off the Rear Section.
c) Models LC-11 and LC-12 require three risers,
one each off the Front and Rear Sections plus one off the Tapped Intermediate Section.
d) LCE models require three or more risers.
3. Size the Header per Table 3.1. Pipe the header at least 24 inches above the normal boiler water line. See Figure 3.1. This is required to prevent water from carrying over into the header and then to the system.
4. Figure 3.3 shows the Supply and Return piping for Parallel Flow Gravity systems and all Pumped Return Systems.
5. Counterflow Gravity systems require the boiler steam line to enter the top of the steam main. See Figure 3.2 for this special case.
6. Do not reduce the size or number of risers shown. These are required for reliable operation of the boiler. If the risers are undersized or incorrectly placed, a sloped water line can occur in the boiler, causing possible overheating of some sections.
7. Pipe the Header with an offset as shown in the drawings. This offset prevents the expansion and contraction of the Header from damaging the boiler sections.
8. Always locate the Steam Supply take-off
between the Equalizer and the last Boiler Riser. (See PB Heat, LLC's “Steam Installation
Survey” for discussion). Locating the steam supply between the risers will cause water carryover to the system.
9. Do not use a bull head tee to provide steam supply and equalizer connections. This will cause water level bounce and carryover.
C. LOW SYSTEM TEMPERATURE
1. The use of a Hartford loop is recommended in all installations. See Figure 3.1. The loop provides additional reliability for the system.
2. A check valve must still be installed on the pump discharge of all pumped return systems.
3. PIPE THE BOILER
Figure 3.1: Supply and Return Connections, Skim Piping, Hartford Loop
PIPE THE BOILER
Page 24
22
3. On pumped return systems, install a boiler cock after the pump to allow throttling of the pump discharge. The pressure after the boiler cock should be no more than 5 psig above the boiler operating pressure. Pumping the water into the boiler too fast will cause collapse of the water level and level control problems.
4. Size the equalizer per Table 3.1. Models LC-11, LC­12 and LCE-13 through LCE 24 require two return connections to the boiler off of the equalizer line.
5. Pipe the Hartford loop tee so the inside top of the close nipple is 2 to 4 inches below the normal boiler water line. See Figure 3.1.
6. If the pump discharge is looped overhead, above the boiler water line, install spring-loaded check valves at both the pump discharge and the connection to the boiler return.
D. MULTIPLE BOILER INSTALLATIONS
1. Figure 3.4 shows typical piping for multiple boiler Gravity Return systems. Figure 3.5 show typical piping for multiple boiler Pumped Return Systems.
2. Provide separate feed lines for multiple boiler pumped return systems. Use either separate feed pumps or solenoid or motorized valves to isolate feeding of the boilers. This is needed to provide reliable level control and avoid nuisance performance problems.
3. Condensate return units are not effective for multiple boiler installations since they do not respond to the needs of the boilers. always use Boiler Feed Units.
4. Install a Float and Thermostatic trap at the boiler water level on each of the mulitple boilers on a pumped return system. This prevents flooding of idle boilers due to condensation of steam.
Figure 3.2: Supply and Return Piping –
Counterflow Gravity Systems
PIPE THE BOILER
Table 3.1: Header, Risers & Equalizer Sizing
Model
I=B=R
Gross
Output
MBH
End Section
Risers
Intermediate Section
Risers
Equalizer
(Inches)
Header
Size
(inches)
Number
Size
(inches)
Number
Size
(inches)
LC-04
LC-05R
LC-05
547 649 707
1 2 2
4 3 3
– – –
– – –
2 2 2
4 5
5 LC-06 LC-07 LC-08
868 1029 1189
2 2 2
4 4 4
– – –
– – –
2 2¹⁄₂ 2¹⁄₂
5 5
6 LC-09 LC-10 LC-11 LC-12
1350 1511 1672 1832
2 2 2 2
4 4 4 4
– – 1 1
– 3 3
2¹⁄₂ 2¹⁄₂
3 3
6 6 6
6 LCE-13 LCE-14 LCE-15
1966 2125 2284
2 2 2
4 4 4
1 2 2
3 3 3
3 3 3
6
8
8 LCE-16 LCE-17 LCE-18
2444 2603 2763
2 2 2
4 4 4
2 3 3
3 3 3
3 4 4
8
8
8 LCE-19 LCE-20 LCE-21
2922 3082 3256
2 2 2
4 4 4
3 4 4
3 3 3
4 4 4
8
8
8 LCE-22 LCE-23 LCE-24
3430 3604 3777
2 2 2
4 4 4
4 4 4
3 3 3
4 4 4
8
8
8
Page 25
23
PIPE THE BOILER
Figure 3.3: Supply and Return Piping – Pumped Return and Parallel Flow Gravity Systems
Page 26
24
PIPE THE BOILER
Figure 3.5: Piping Multiple Boilers, Typical, Pumped Return Systems
Figure 3.4: Piping Multiple Boilers, Typical, Gravity Return Systems
Page 27
25
A. PREPARE THE PARTS
1. Collect all the jacket cartons: Jacket Front & Back Carton plus Jacket Side & Top Cartons. See
the Shipping List in the front of this manual for the jacket cartons required. The cartons contain the jacket parts and screws. The jacket panels are pre­insulated.
2. Remove all needed knockouts from the jacket parts before beginning assembly.
B. APPLY JACKET SIDES AND CORNERS
1. See Figure 4.2 for details.
2. The Side Panels can be used on either side of the boiler.
3. Place the Jacket Side Panels on each side leaned against the Boiler Sections.
4. On Models LC-08 through LC-12, each side uses two panels. Place the panels so the seam is centered on the Tapped Intermediate Section. On LCE models, place panels in the sequence shown in Table 4.1.
5. On boilers with two or more Jacket Side Panels per side, join the panels together with #10 x 1/2" sheet metal screws. Also attach the Jacket Side Panel Reinforcing Angle inside the jacket at the bottom of the seam.
6. Attach the Left Front Corner Panel to the Left Side Panel with #10 x 1/2" sheet metal screws.
7. Attach the Right Front Corner Panel to the Right Side Panel with #10 x 1/2" sheet metal screws.
C. APPLY JACKET FRONT PANELS
1. Attach the Upper Front Panel to the Right and Left Front Corner Panels with #10 x 1/2" sheet metal screws.
2. Attach the Middle Front Panel and Lower Front Rail in the same manner.
3. Position the Jacket Assembly with the front panels pushed up against the front section. You will need the jacket in this position to install the Burner Front Plate.
D. APPLY JACKET REAR PANEL
1. Attach the Rear Jacket Panel to the Jacket Side Panels with #10 x 1/2" sheet metal screws.
E. APPLY JACKET TOP PANELS
1. Attach the Top Front Panel to the Sides and Upper Front Panel with #10 x 1/2" sheet metal screws.
2. Models LC-08 through LC-12 use two Jacket Top Panels. Place them on top with the seam at the same point as the side panels. Join them at their seam with #10 x 1/2" sheet metal screws. On LCE models, place panels in the sequence shown in Table 4.1.
3. Attach the Jacket Top Panel to the Jacket Top Front Panel with #10 x 1/2" sheet metal screws.
4. Attach the Top Rear Panel to the Jacket Top Panel with #10 x 1/2" sheet metal screws.
5. Finish by placing #10 x 1/2" sheet metal screws in the remaining holes along the Jacket Top Panel flanges, into the Jacket Side Panels.
F. APPLY PLATES AND LABELS
1. Mount Boiler Rating Plates and Agency Plates on the Upper Jacket Front Panel as shown in Figure 4.1.
2. Secure metal plates with #6 x 1/4" sheet metal screws. Apply all adhesive-backed labels.
4. ASSEMBLE THE JACKET
Figure 4.1: Location of Rating, Agency and
Instruction Plates on Jacket Front Top Panel
Table 4.1: Jacket Top & Side Panel Placement
LCE-13 LCE-14 LCE-15 LCE-16 LCE-17 LCE-18 LCE-19 LCE-20 LCE-21 LCE-22 LCE-23 LCE-24
Model
Locate Jacket Top and Side Panels in
the Position Below
(Numbers are from Rear to Front)
5
(Front)
432
1
(Rear)
– – – – – – – E E E E E
– – – – E E
E A A B B C
E E E E A B C A B B B B
B B B C B B B B B B B B
A B C C B B B B B B C C
ASSEMBLE THE JACKET
Page 28
26
ASSEMBLE THE JACKET
Figure 4.2: Jacket Assembly
Page 29
27
VENTING/INSTALL THE BURNER
5. VENTING
Refer to Chapter 1, P
reinstallation, Section D. Chimney or Vent for installation requirements. Refer to Chapter 9, Star
ting the Boiler, Section C. Run Burner
Check Out
for damper settings and draft requirements.
6. INSTALL THE BURNER
A. BURNER APPLICATION
1. Refer to Burner Spec and Data Sheets for the Oil and Gas/Oil Burners pre-tested with Series LC/LCE boilers.
2. Make sure the nozzle sizing and spray pattern match those given in the spec and data sheets.
3. See Figure 6.1 and Table 6.1 for combustion chamber dimensions.
B. INSTALL BURNER MOUNTING PLATE
1. The Burner Mounting Plate is made to fit the burner being used. Burners vary in bolt pattern for the flange, burner tube diameter, insertion length and near-tube configuration. Make sure the front plate is correct for your burner if purchased separately from the boiler.
2. Remove the Burner Mounting Plate and Hardware Bag from the crate.
3. Screw (7) 3/8"-16 x 2 1/4" studs into the holes in the front section around the chamber opening.
4. Secure the Burner Mounting Plate to the front section with the flat washers and hex nuts.
C. MOUNT THE BURNER
1. Remove the Burner from its crate. Read the burner instructions.
2. Insert (4) 3/8"-16 x 1 1/4" studs supplied with Burner Mounting Plate into the front plate holes.
3. Place the high temperature gasket on the burner front plate and secure the burner to the front plate with 3/8" flat washers and hex nuts.
4. If the burner is supplied with a pedestal, install it to the burner per the Burner Manufacturer’s Instructions. The pedestal provides additional support and prevents the burner from sagging.
Page 30
28
INSTALL THE BURNER
Figure 6.1: Combustion Chamber Layout – See Table 6.1 for Dimensions
Table 6.1: Combustion Chamber Dimensions
LC-04
LC-05R
LC-05 LC-06 LC-07 LC-08 LC-09 LC-10 LC-11
LC-12 LCE-13 LCE-14 LCE-15 LCE-16 LCE-17 LCE-18 LCE-19 LCE-20 LCE-21 LCE-22 LCE-23 LCE-24
Model
Chamber
Length
“A”
(Inches)
Burner Front Plate Extension Past Jacket (Inches)
Beckett Carlin
Gordon-
Piatt
Power
Flame
Webster
18⁷⁄₈ 23¹⁵⁄₁₆ 23¹⁵⁄₁₆
29
34¹⁄₁₆
39¹⁄₈
44³⁄₁₆
49¹⁄₄
54⁵⁄₁₆
59³⁄₈
64⁷⁄₁₆
69¹⁄₂
74⁹⁄₁₆
79⁵⁄₈ 84¹¹⁄₁₆
89³⁄₄ 94¹³⁄₁₆
99⁷⁄₈
104¹⁵⁄₁₆
110
115¹⁄₁₆
120¹⁄₈
6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈
1¹⁄₈ N/A N/A
6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈
N/A
6¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈
6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈
6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 6¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈ 1¹⁄₈
Page 31
29
A. GENERAL
1. Read the Burner Instruction Manual, supplied with the boiler or with the burner if purchased separately. Review applicable code requirements for burner and fuel piping installations.
2. Install piping to allow removal of burner and access to combustion chamber for cleaning or service.
B. INSTALL FUEL OIL PIPING
1. Place the fuel oil tank and install the piping in accordance with NFPA-31 and all other applicable codes.
2. General Guidelines for Oil Piping
a) Follow the guidelines in the Burner Manual for
sizing oil lines. Never use smaller than 1/2" OD copper tubing.
b) Install manual shut-off valves on the suction line
at the burner and at the oil line entrance to the building. If installing a shut-off valve on the return line, you must provide an oil pressure relief valve piped ahead of the shut-off valve and discharged to the tank to prevent over-pressure conditions.
c) Install a two-pipe oil distribution system when
possible. It will improve the reliability of the oil delivery to the burner.
d) Use flare fittings when using copper tubing.
e) Provide an oil line filter in the suction line. Size
the filter for the suction gear capacity of the burner oil pump if running a two-pipe system.
f) If burner is above the top of the fuel oil tank,
install a check valve on the oil suction line at the burner to prevent oil from evacuating the line. If burner is below the top of the tank, install an anti-siphon device to prevent oil flow should the oil line break.
C. INSTALL GAS SUPPLY PIPING
1. Size the piping as required by the National Fuel Gas Code, ANSI Z223.1 or as required by local codes.
a) Use Table 7.1 for sizing of natural gas for a
system pressure drop of 0.3 inch water column.
2. The standard gas train is designed for a maximum pressure of 1/2 psig (14 inches water column). Make sure the system regulator will not allow a higher pressure to the Gas Control Train under any conditions.
3. The minimum gas supply pressure is listed on the Burner Rating Plate. Make sure the system regulator and the piping are sized and adjusted properly to provide this pressure under all conditions.
4. Install a Service Valve, Sediment Trap and Ground Joint Union at the supply connection to the Gas Control Train as shown in Figure 7.1. These are not supplied with the boiler. Install them in accordance with local codes.
5. Use only pipe joint compounds rated for use with Liquefied Petroleum Gases.
D. TEST GAS SUPPLY PIPING
1. ISOLATE THE BOILER GAS CONTROL TRAIN FROM THE SYSTEM DURING TEST:
a) Test pressure 1/2 psig or less – Close the Manual
Shut-Off Valve on the Boiler Gas Control Train.
b) Test pressure over 1/2 psig – Disconnect the gas
supply piping upstream of the Boiler Manual Shut-Off Valve.
CONNECT FUEL PIPING
7. CONNECT FUEL PIPING
Figure 7.1: Gas Supply Connection to Boiler
Do not expose the Gas Control Train to excessive pressure. The gas valves can be damaged. This could result in explosion hazard and severe personal injury or death.
Do not test gas supply piping with open flame. Use a soap suds mixture brushed onto the pipe joints to test for leaks.
WARNING
Page 32
30
CONNECT FUEL PIPING
Table 7.1: Capacity of Gas Supply Pipe in Cubic Feet Per Hour of Natural Gas for Pressure Drop of
0.3 inch Water Column.
10
20
30
40
50
60
70
90
100
150
1050
730
590
500
440
400
350
320
305
250
1600
1100
890
760
670
610
560
490
460
380
3050
2100
1650
1450
1270
1150
1050
930
870
710
4800
3300
2700
2300
2000
1850
1700
1500
1400
1130
8500
5900
4700
4100
3600
3250
3000
2600
2500
2000
17500
12000
9700
8300
7400
6800
6200
5400
5100
4100
44000
31000
25000
22000
20000
18000
17000
15000
14000
11500
Pipe Length
(Feet)
1-1/4"
Pipe
1-1/2"
Pipe
2"
Pipe
2-1/2"
Pipe
3"
Pipe
4"
Pipe
6"
Pipe
Above ratings based on natural gas with specific gravity of 0.60 allowing pressure drop of 0.3 inches water column. No allowance is needed for pipe fittings. Use the following multipliers on above capacities for specific gravity other than 0.60:
Specific Gravity
Multiply Capacity by: 1.10
0.50
1.04
0.55
1.00
0.60
0.962
0.65
0.926
0.70
Page 33
31
A. INSTALL SAFETY VALVES
1. Pipe the Pop Safety Valve on a tee mounted in the 2¹⁄₂" tapping located on the upper left side of the Rear Section. Make sure the relief valve sizing meets local code requirements.
2. Install a 2" ball valve for skimming off the end of the tee as shown in the piping drawings in this manual.
B. INSTALL BLOWDOWN VALVES
1. Install a 1¹⁄₂" full port ball valve off of the return connection as shown in the “Pipe the Boiler” section of this manual. See Figure 8.1.
2. Pipe the valve discharge to a floor drain if available or apply a nipple and cap to close off when not in use.
C. INSTALL LOW WATER CUTOFF(S)
1. Mount a float type Low Water Cutoff and Gauge Glass in the tappings provided in the side of the front section or the side and top of the first intermediate section.
2. Do not apply piping which would raise or lower the location of the cutoff relative to the tappings in the boiler. Raising the water level over the design height will cause water carryover to the system.
3. For correct location of typical low water cutoff/feeder or low water cutoff/pump control, see Figures 8.4 through 8.7.
4. See Figure 8.2 for the location of control connection tappings.
5. Provide each float low water cutoff with a blowdown valve. Pipe the blowdown away from traffic to a floor drain if available. The blowdown valve is required for proper maintenance of the control.
6. Maintain a height of 46¹⁄₂" from boiler foundation to the normal water level.
7. When using Multiple Float Type Controls: Always pipe the controls off of the same tappings to the boiler. Do not mount on different ends of the boiler or in different tappings. This can cause erratic operation and nuisance problems with the controls.
D. INSTALL PRESSURE CONTROLS
1. Pipe the Steam Pressure Gauge and Boiler Limit and Operating Pressure Controls as shown in Figure 8.3. Connect the control assembly to the 1/2" tapping in the front section.
E. PIPE TANKLESS HEATER(S)
1. Connect piping to any installed tankless heaters. See Figure 8.8 for suggested piping for single coils and Figure 8.9 for suggested piping for dual coils.
F. CONNECT SUPPLY WIRING
1. Install all wiring in accordance with local codes, the National Electrical Code and other controlling agencies or governing bodies.
2. Use #14 gauge or heavier wire for supply wiring. Protect the circuit with a fused disconnect switch (by others) and a grounded neutral.
3. Mount an electrical junction box on the boiler Front Panel for connection of supply wiring and distribution to the boiler controls.
4. Follow the instructions in the Burner Manual and the Wiring Diagrams supplied with the burner and the boiler.
INSTALL CONTROLS, TRIM & WIRING
8. INSTALL CONTROLS, TRIM & WIRING
Pipe the discharge of the Safety Relief Valve away from any traffic area, preferably to a floor drain. This is necessary to prevent injury should the valve discharge.
Pipe the discharge full size of valve outlet.
CAUTION
Make sure that the ignition system components, electrical controls, junction boxes and electrical panels are protected from water (dripping, spraying, rain, etc.) during boiler operation and service (trap servicing, control replacements or other).
CAUTION
The boiler/burner must be electrically grounded in accordance with the requirements of the authority having jurisdiction, or in the absence of such requirements, with the current edition of the National Electrical Code, ANSI/NFPA Number 70.
NOTICE
Page 34
32
G. INSTALL CONTROL WIRING
1. Wire the boiler according to the wiring diagrams supplied with the burner and the boiler (in the Boiler Envelope).
2. Low Energy Safety Control wiring, if used, must follow the contour of the boiler. Some local codes may require that all wiring, even low voltage, be routed in conduit.
3. Install line voltage wiring in conduit.
4. Do not install single pole switches, including safety controls, in a grounded line.
INSTALL CONTROLS, TRIM & WIRING
Figure 8.1: Blowdown Valve, Safety Valve and Skim Valve Piping
Page 35
33
INSTALL CONTROLS, TRIM & WIRING
Figure 8.2: Control and Pipe Tapping Locations
Page 36
34
INSTALL CONTROLS, TRIM & WIRING
Figure 8.3: Control and Pipe Tapping Locations
Page 37
35
INSTALL CONTROLS, TRIM & WIRING
Figure 8.5: Optional Model 47-2 Low Water Cutoff/Feeder – Use only up to Model LC-07
Figure 8.4: Optional Model 67PE2 Float Low Water Cutoff
Page 38
36
INSTALL CONTROLS, TRIM & WIRING
Figure 8.6: Optional Float Type Pump Control/Low Water Cutoff, Model 157
Page 39
37
INSTALL CONTROLS, TRIM & WIRING
Figure 8.7: Optional Feeder/Low Water Cutoff, Type 51-2
Page 40
38
INSTALL CONTROLS, TRIM & WIRING
Figure 8.9: Suggested Piping – Dual Tankless Coil Installation
Figure 8.8: Suggested Piping – Single Tankless Coil Installation
Page 41
39
A. CHECK THE PIPING
1. Steam Piping a) The Boiler must have been hydrostatically tested.
b) Check the attached piping for joint tightness.
c) Continue monitoring as you proceed through
start up.
2. Gas Piping a) Make sure the gas system piping and the
connections to the boiler Gas Control Train(s) have been leak tested.
b) After the boiler is in operation, check the
tightness of all joints in the boiler gas piping with a soap suds solution.
c) Purge the gas piping of all air up to the boiler
Gas Control Train.
3. Oil Piping a) Check the oil piping visually. Make sure all joints
are tight.
b) When the burner is firing, check the suction line
and return line pressures.
c) If the pressure exceeds the allowable pressure in
the Burner Manual or if the suction line vacuum is higher than allowable, correct the piping as needed to bring the suction line and return line pressures within acceptable range.
d) Excess pressure can cause pump seal failures.
Excess vacuum will cause fuel flow problems with the burner oil pump.
B. FILL THE BOILER
1. Fill the boiler to the normal water line. a) Gravity Systems and Pumped Return with
Condensate Units – Fill to 46¹⁄₂" above the boiler foundation (center of gauge glass).
b) Pumped Return with Boiler Feed Unit - Fill the
boiler using the boiler feed unit. Fill level will depend on the control being used, but should be 46¹⁄₂" above the boiler foundation (just below center of gauge glass) when the pump stops.
C. RUN BURNER CHECK-OUT
1. Before firing the burner, slide the Slide Gate Damper
on the rear flue box all the way down (full open) on LC’s or open the LCE Draft Damper until the handle is parallel to the vent pipe (full open).
2. Follow the instructions in the Burner Manual for
starting the burner, adjusting air openings and fuel rates. Perform ignition system and flame supervisory control test and checkout as described in the manual.
3. After burner is set at rate, close the damper until the
pressure reading at the test opening in the rear flue box or draft damper is between 0" wc and 0.1" wc positive. See Table 9.1 for typical overfire pressure (measured at the burner front plate) and boiler draft loss.
When a barometric draft regulator is installed in the venting system, adjust the boiler damper for 0" wc pressure reading at the damper. Adjust the draft regulator for -0.05" wc draft between the boiler damper and the draft regulator.
4. Adjust the burner as needed for a CO
2
reading of:
a) Oil burners: CO
2
approximately 12.5% or 1% less than the level at which the smoke reading goes above a trace on the Bacharach scale.
b) Gas burners: 9% to 10% with CO less than 50 ppm.
5. Inspect all flue gas joints (sections, attachments, breeching and vent) for gas tightness. Remove the jacket panels in order to thoroughly inspect all rope seal joints between the sections.
D. CHECK BOILER CONTROLS
1. Limit and Operating Temperature Controls
a) Lower the setting of each control until the burner
shuts down.
2. Low Water Cutoffs
a) Test probe type controls by using the Push-to-Test
Button.
b) Test float type controls.
3. Follow additional instructions in the Burner Manual for proving the burner component operation.
4. Check all controls to make sure they function correctly.
5. After all controls have been proven, set the Operating and High Limit Temperature Controls to the temperatures desired.
E. CLEAN THE BOILER
1. Clean the boiler as described below no later than one week after the initial start-up. Cleaning will be more effective if the boiler operates a day or two to loosen sediment and impurities in the system.
9. STARTING THE BOILER
STARTING THE BOILER
Cleaning the boiler requires the use of very hot water and corrosive chemicals. Use care when handling to prevent injury.
WARNING
On installations with high draft, do not leave the boiler with a negative draft reading at the rear flue box or draft damper. High negative draft can pull the flame up into the boiler crown sheet and overheat the iron. This can result in cracked sections or shortened boiler life.
CAUTION
Page 42
40
2. The boiler must be cleaned to remove any accumulation of oil, grease, sludge, etc. that may be in the system. These substances can cause foaming and surging of the boiler water, producing unstable water line and water carryover to the system.
3. The piping for a 2" Skim Valve must be done as shown in this manual, with the skim valve mounted off the Pop Safety Valve tee on the rear of the boiler.
4. Use common washing soda (such as Arm and Hammer Super Washing Soda). Mix the soda with water in a 10 quart pail. Use a proportion of one pound of washing soda for each 800 square feet EDR net boiler rating. Remove the Pop Safety Valve and pour the washing soda solution into the boiler through the Pop Safety Valve tee. Replace Pop Safety Valve.
5. Connect a 2 inch drain line off of the Skim Valve, run to a point of safe discharge.
6. Close all valves to the system. Provide a means of continuous fresh water to the boiler for the cleaning process.
7. Open the Skim Valve. Fill the boiler until water begins to flow out of the valve.
8. Turn burner on and allow the boiler water to heat up to just below steaming (180° to 200° F). Cycle the burner to maintain temperature during skimming. Do not allow the boiler to steam. Steaming mixes up the contaminants in the water instead of floating them at the surface.
9. Open the make-up water valve to continuously feed water to the boiler. Allow water to flow out the skim tapping.
10. Continue skimming the boiler until the water flowing from the skim tapping flows clear. This will take some time, possibly several hours for a dirty system.
11. After skimming is complete, close the skim valve and turn off the boiler.
12. Close the make-up water valve and open the boiler blowdown valves.
13. Drain the boiler completely, then refill and drain again one or two times to make sure all of the soda has been washed out.
14. Restore piping to normal. Pipe a nipple and cap in the skim valve.
15. Note: If the gauge glass becomes dirty again, this indicates more contaminants have worked loose in the system. Repeat the cleaning and skimming process as needed to clean the system.
STARTING THE BOILER
Table 9.1: Typical Combustion Chamber Pressure and Boiler Draft Loss
LC-04
LC-05R
LC-05 LC-06 LC-07 LC-08 LC-09 LC-10 LC-11
LC-12 LCE-13 LCE-14 LCE-15 LCE-16 LCE-17 LCE-18 LCE-19 LCE-20 LCE-21 LCE-22 LCE-23 LCE-24
+ 0.22 + 0.22 + 0.24 + 0.26 + 0.27 + 0.28 + 0.29 + 0.30 + 0.31 + 0.32 + 0.24 + 0.25 + 0.26 + 0.27 + 0.28 + 0.29 + 0.30 + 0.31 + 0.31 + 0.31 + 0.32 + 0.32
Model
Boiler Draft Loss
(Inches w.c.)
Combustion Chamber Pressure
with 0.1" w.c. at Rear Flue Box Test Port
(Inches w.c.)
0.12
0.12
0.14
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.21
0.21
0.22
0.22
NOTE: Actual chamber pressure and draft loss readings may vary with each boiler and installation due to variation in the heat exchanger, deposits in the flueways, actual burner firing rate and excess air conditions. Use the above numbers as a general guide only. If the measured draft loss is considerably higher than the above, check the flueways for deposits and confirm the burner firing rate.
Do not leave the boiler unattended while firing.
Take great care not to allow the water level to drop below the bottom of the gauge glass or to allow fresh water make-up to flow in too fast. This will avoid the possibility of causing the boiler sections to fracture.
CAUTION
Page 43
WARNING
Product Safety Information
Refractory Ceramic Fiber Product
This appliance contains materials made from refractory ceramic fibers (RCF). Airborne RCF, when inhaled, have been classified by the International Agency for Research on Cancer (IARC), as a possible carcinogen to humans. After the RCF materials have been exposed to temperatures above 1800°F (982°C), they can change into crystalline silica, which has been classified by the IARC as carcinogenic to humans. If particles become airborne during service or repair, inhalation of these particles may be hazardous to your health.
Avoid Breathing Fiber Particulates and Dust
Suppliers of RCF recommend the following precautions be taken when handling these materials:
Precautionar
y Measures: Provide adequate ventilation. Wear a NIOSH/MSHA approved respirator. Wear long sleeved, loose fitting clothing and gloves to prevent skin contact. Wear eye goggles. Minimize airborne dust prior to handling and removal by water misting the material and avoiding unnecessary disturbance of materials. Wash work clothes separately from others. Rinse washer thoroughly after use. Discard RCF materials by sealing in an airtight plastic bag.
Fir
st Aid Procedures: Inhalation: If breathing difficulty or irritation occurs, move to a location with fresh clean air. Seek immediate medical attention if symptoms persist. Skin Contact: Wash affected area gently with a mild soap and warm water. Seek immediate medical attention if irritation persists. Eye Contact: Flush eyes with water for 15 minutes while holding eyelids apart. Do not rub eyes. Seek immediate medical attention if irritation persists. Ingestion: Drink 1 to 2 glasses of water. Do not induce vomiting. Seek immediate medical attention.
41
10. MAINTENANCE
MAINTENANCE
Page 44
42
A. PLACING BOILER IN OPERATION
1. Start up the Burner/Boiler per the Burner Manual and the instructions in this manual on starting the boiler.
2. Prove the correct operation of all controls on the boiler and burner as outlined below.
3. Check the operation of the ignition and flame proving controls as described in the Burner Manual.
4. Test the limit and operating controls to assure they are operating correctly.
5. Inspect and test all low water cutoffs.
6. Test the safety relief valve(s) using the procedure given by the valve manufacturer on the valve tag.
7. Visually inspect the burner and pilot flames (if applicable).
B. TO SHUT DOWN THE BOILER
1. Turn off Burner.
2. Open main line power disconnect switch to boiler/burner.
3. Close fuel shut-off valves.
4. To take boiler out of service if the boiler and system are not to be used when temperatures are below freezing:
a) Drain the boiler and system completely and shut
off make-up water supply.
b) Open main line power disconnect switch to
boiler/burner. Remove the fuses or secure the switch so that the power cannot be turned on accidentally.
c) Be certain that the boiler and system are refilled
before returning to service. Follow the Instructions in this manual and the Lighting Instructions to operate.
d) The system may be filled with a 50% inhibited
propylene glycol solution for protection down to
-35°F. Use only antifreeze solutions specifically designed for hydronic use.
C. MAINTENANCE – ANNUAL
1. Before the start of each heating season, inspect and make all necessary adjustments to insure proper boiler and burner operation. Use the maintenance and inspection procedures following.
2. Inspect the Venting System
a) Check the chimney or vent to make sure it is
clean and free from cracks or potential leaks.
b) All joints must be tight and sealed.
c) The vent connector must extend into, but not
beyond the inside edge of the chimney or vent.
3. Inspect the Boiler Area
a) The boiler area must be clean and free from
combustible materials, gasoline or any other flammable liquids or vapors.
b) The combustion air openings and the area
around the boiler must be unobstructed.
4. Inspect boiler flueways and burner for cleanliness. If cleaning is required, use the following procedure.
a) Turn off all electrical power to the boiler.
b) Remove Jacket Middle Front Panel and Jacket
Top Panels. Remove Front Cleanout Plate and Cleanout Cover Plates on each flueway. On LCE boilers, remove the top flue outlet plate and vent piping as necessary to access the top of the sections.
c) Brush the boiler tube spaces both horizontally
(through cleanout openings on ends) and vertically (from top of boiler through cleanout openings at flueways).
MAINTENANCE
Do not store or allow combustible or flammable materials near the boiler. Substantial fire or explosion hazard could result, causing risk of personal injury, death or property damage.
Do not use this boiler if any part of it has been under water. Immediately call a qualified service technician to inspect the boiler. Any part of the control system, any gas control or any burner or gas component which has been under water must be replaced.
Should overheating occur or the fuel supply fail to shut off: Shut off the fuel supply at a location external to the boiler. Do not turn off or disconnect the electrical supply to the pump. Immediately call a qualified service technician to inspect the boiler for damage and defective components.
WARNING
Before servicing the boiler:
• Turn off all electrical power to the boiler.
• Close the Gas Service Valve and Oil Shut-Off Valve.
• Allow the boiler to cool if it has been operating.
• Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
CAUTION
Page 45
43
d) Remove the Burner and Burner Mounting Plate.
Remove any scale or soot from the combustion chamber by means of vacuum cleaning or other available means. Take care not to damage the chamber floor liner or target wall liner.
e) Replace the Front Cleanout Plate, Burner
Mounting Plate, Burner and all Cleanout Cover Plates on top of the sections. Make sure all sealing rope and seals are in good condition. Replace sealing rope if necessary.
f) Replace all Jacket Panels.
5. Inspect the boiler and piping for signs of leaks. Check to see if there are signs of heavy make-up water addition to the system.
6. When placing boiler into operation, follow Burner Manual, all instructions supplied with the boiler and the instructions in this chapter.
7. Test the operation of all limit controls, float controls and ignition components as described in Part A, “Placing Boiler in Operation”, of this chapter.
D. MONTHLY MAINTENANCE
1. Inspect the burner and pilot flames as for the annual inspection.
2. Inspect the boiler and system for any signs of leakage or excessive make-up water usage.
3. Inspect and check the operation of the venting system.
E. DAILY MAINTENANCE
1. Inspect the boiler area to make sure the area is free from combustible or flammable materials and that there are not obstructions to the flow of air to the boiler or combustion air openings to the room.
2. Make sure there are no signs of abnormal operation, such as overfilling or leakage.
MAINTENANCE
Be very careful when adding water to a hot boiler. Add very slowly or, if possible, allow the boiler to cool naturally before adding water.
If an excessive loss of water occurs, check for a leak in the piping and correct the problem. Excessive make-up water will cause corrosion and damage to the boiler.
CAUTION
Page 46
44
BOILER RATINGS & DIMENSIONS
11. BOILER RATINGS & DIMENSIONS
Table 11.1: Series LC/LCE Boiler Ratings
1 Burner input based on No. 2 fuel oil with a heating value of 140,000 Btu per gallon. 2 Net I=B=R water ratings based on an allowance of 1.15. 3 Net I=B=R steam ratings based on an allowance for LC-04 to LC-08=1.333, LC-09=1.323, LC-10=1.310, LC-11=1.298, LC-12=1.290,
LCE-13 to LCE-24=1.288.
4 Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping
systems, etc.
5 Combustion efficiency determined in accordance with The Hydronics Institute’s Testing and Rating Standard for Heating Boilers.
Gross
I=B=R
Output
Mbh
Boiler
Model
Number
LC-04
LC-05R
LC-05 LC-06 LC-07 LC-08 LC-09 LC-10 LC-11
LC-12 LCE-13 LCE-14 LCE-15 LCE-16 LCE-17 LCE-18 LCE-19 LCE-20 LCE-21 LCE-22 LCE-23 LCE-24
547 649 707
868 1029 1189 1350 1511 1672 1832 1966 2125 2284 2444 2603 2763 2922 3082 3256 3430 3604 3777
16.3
19.4
21.1
25.7
30.7
35.5
40.3
45.1
49.9
54.7
58.7
63.5
68.2
73.0
77.8
82.5
87.3
92.1
97.3
102.5
107.7
112.8
4.75
5.60
6.10
7.50
8.80
10.20
11.60
12.80
14.20
15.60
17.00
18.40
19.80
21.00
22.50
24.00
25.00
26.50
28.00
29.50
31.00
32.50
Boiler
H.P.
Oil
GPH
I=B=R Burner Capacity
686 808
881 1077 1273 1469 1664 1860 2056 2252 2464 2657 2850 3043 3236 3429 3622 3815 4027 4239 4451 4663
Gas MBH
1708 2029 2208 2713 3217 3717 4250 4804 5367 5917 6358 6875 7388 7908 8421 8938 9454
9971 10533 11096 11658 12217
Steam
Sq. Ft.
I=B=R Net Ratings
410 487 530 651 772
892 1020 1153 1288 1420 1526 1650 1773 1898 2021 2145 2269 2393 2528 2663 2798 2932
Steam
MBH
476 564 615 755
895 1034 1174 1314 1454 1593 1710 1848 1986 2125 2263 2403 2541 2680 2831 2983 3134 3284
Water
MBH
83.7
83.7
83.7
83.7
83.6
83.6
83.6
83.6
83.6
83.6
83.5
83.5
83.5
83.5
83.5
83.5
83.5
83.5
83.6
83.6
83.7
83.7
Oil
Combustion Efficiency
81.2
81.2
81.2
81.1
81.1
81.1
81.1
81.1
81.1
81.1
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.1
81.1
81.2
81.2
Gas
SERIES LC/LCE BOILER RATINGS
Figure 11.1: Tankless Coil Pressure Drops
Page 47
BOILER RATINGS & DIMENSIONS
Figure 11.2: Series LC Dimensional Diagram
Figure 11.3: Series LCE Dimensional Diagram
45
Page 48
46
BOILER RATINGS & DIMENSIONS
SERIES LC/LCE BOILER DIMENSIONS
Boiler
Model
Number
Jacket Supply Piping
Return
Piping
Riser Tapping Locations*
Burner
Center
Line
Vent Location Vent
Width
“A”
Length
“B”
Height
“C”
Risers Size
Recom.
Header
End Sect.
Tappings
Intermediate Section Tapping
“D” “E”
Diameter
“F”
Minimum
Height
Equalizer “G1” “G2” “G3” “G4”
LC-04 37" 25-15/16" 63" 1 4" 4" 2" 16-1/2" 18-1/2" 18-1/4" 54-1/8" 9" 3'
LC-05R 37" 31" 63" 2 3" 5" 2" 21-9/16" 18-1/2" 18-1/4" 54-1/8" 9" 3'
LC-05 37" 31" 63" 2 3" 5" 2" 21-9/16" 18-1/2" 18-1/4" 54-1/8" 9" 3'
LC-06 37" 36-1/16" 63" 2 4" 5" 2" 26-5/8" 18-1/2" 18-1/4" 54-1/8" 10" 3'
LC-07 37" 41-1/8" 63" 2 4" 5" 2-1/2" 31-11/16" 18-1/2" 18-1/4" 54-1/8" 10" 3'
LC-08 37" 46-5/16" 63" 2 4" 6" 2-1/2" 36-13/16" 18-1/2" 18-1/4" 54-1/8" 10" 3'
LC-09 37" 51-3/8" 63" 2 4" 6" 2-1/2" 41-7/8" 18-1/2" 18-1/4" 54-1/8" 12" 3'
LC-10 37" 56-7/16" 63" 2 4" 6" 2-1/2" 46-15/16" 18-1/2" 18-1/4" 54-1/8" 12" 3'
LC-11 37" 61-1/2" 63" 2, 1 4", 3" 6" 3" (2 Ret.) 52" 26" 18-1/2" 18-1/4" 54-1/8" 12" 3'
LC-12 37" 66-9/16" 63" 2, 1 4", 3" 6" 3" (2 Ret.) 57-1/8" 26" 18-1/2" 18-1/4" 54-1/8" 12" 3'
LCE-13 37" 71-3/4" 63" 2, 1 4", 3" 6" 3" 62-3/16" 36-3/16" 18-1/2" 16" 20-1/2" 14" 3'
LCE-14 37" 76-13/16" 63" 2, 2 4", 3" 8" 3" 67-1/4" 20-15/16" 20-5/16" 18-1/2" 16" 20-1/2" 14" 3'
LCE-15 37" 81-7/8" 63" 2, 2 4", 3" 8" 3" 72-5/16" 26" 20-5/16" 18-1/2" 16" 20-1/2" 14" 3'
LCE-16 37" 86-15/16" 63" 2, 2 4", 3" 8" 3" 77-7/16" 26" 25-7/16" 18-1/2" 16" 20-1/2" 14" 3'
LCE-17 37" 92-1/8" 63" 2, 3 4", 3" 8" 4" 82-1/2" 20-15/16" 20-5/16" 15-1/4" 18-1/2" 16" 20-1/2" 14" 3'
LCE-18 37" 97-3/16" 63" 2, 3 4", 3" 8" 4" 87-9/16" 20-15/16" 20-5/16" 20-5/16" 18-1/2" 16" 20-1/2" 16" 3'
LCE-19 37" 102-1/4" 63" 2, 3 4", 3" 8" 4" 92-5/8" 20-15/16" 20-5/16" 25-7/16" 18-1/2" 16" 20-1/2" 16" 3'
LCE-20 37" 107-7/16" 63" 2, 4 4", 3" 8" 4" 97-3/4" 20-15/16" 20-5/16" 15-1/4" 15-1/4" 18-1/2" 16" 20-1/2" 16" 3'
LCE-21 37" 112-1/2" 63" 2, 4 4", 3" 8" 4" 102-3/16" 20-15/16" 20-5/16" 20-5/16" 15-1/4" 18-1/2" 16" 20-1/2" 16" 3'
LCE-22 37" 117-9/16" 63" 2, 4 4", 3" 8" 4" 107-7/8" 20-15/16" 20-5/16" 20-5/16" 20-5/16" 18-1/2" 16" 20-1/2" 16" 3'
LCE-23 37" 122-5/8" 63" 2, 4 4", 3" 8" 4" 112-15/16" 26" 20-5/16" 20-5/16" 20-5/16" 18-1/2" 16" 20-1/2" 16" 3'
LCE-24 37" 127-11/16" 63" 2, 4 4", 3" 8" 4" 118-1/16" 26" 20-5/16" 20-5/16" 26" 18-1/2" 16" 20-1/2" 16" 3'
*These dimensions are approximate.
Table 11.2: Series LC/LCE Boiler Dimensions
Page 49
47
REPAIR PARTS
12. REPAIR PARTS
Figure 12.1: Series LC Boiler Assembly
Repair parts are available from your installer or by contacting PB Heat, LLC, P.O. Box 447, New Berlinville, PA 19545-0447. Use the Figures and Tables on pages 47-52 to assist in ordering parts.
Note: Remember to include boiler model number and serial number when ordering parts.
Page 50
48
REPAIR PARTS
Table 12.1A: Series LC Repair Parts
Item
No.
Description Part Selection Information
Stock
Code
1 Front Section See Table 1.3 for Stock Code
2 Intermediate Section w/1" Tapping See Table 1.3 for Stock Code
3 Intermediate Section See Table 1.3 for Stock Code
4 Back Section See Table 1.3 for Stock Code
5 Tapped Intermediate Section See Table 1.3 for Stock Code
Upper Flow Port Gasket 2 Required per Flueway 51671
Lower Flow Port Gasket 1 Required per Flueway 51672
6 Tie Rod 4 Required per Flueway 51721
5/8" Diameter High Temp Rope 13 Feet Required per Flueway 55723
7 Ceramic Fiber Base Liner Models LC-04 through LC-12 50862
8 Ceramic Fiber Target Wall 50854
9 Front Cleanout Plate (C.I.) 51162
10 5/16"-18 x 1-1/4" Studs w/Brass Nuts 4 Required
11 Steel Cover Plate 51776
12 Steel Cover Plate 51777
13 Tankless Heater Location 1 Specify Heater Model Number
14 Tankless Heater Location 2 Not Used On Steam
15 Tankless Heater Location 3 Specify Heater Model Number
16 Rubber Gasket Specify Quantity 51800
17 3/8"-16 x 3/4" SS Hex Head Cap Screw Specify Quantity
18 Rear Observation Assembly 90923
19 5/16"-18 x 3/4" Hex Head Cap Screw Specify Quantity
20 Burner Mounting Plate Specify Burner Model
21 3/8"-16 x 2-1/4" Studs with Nuts
22 Flame Observation Assembly 90922
23 3/8"-16 x 1" Studs for Burner Mounting 4 Required
24 1/4"-20 x 1/2" Hex Head Machine Screw 4 Required
25 Cleanout Cover Plate (Steel) 1 Required per Flueway 51772
26 Rear Flue Box w/9" Flue Outlet Models LC-04 and LC-05 86040
Rear Flue Box w/10" Flue Outlet Models LC-06, LC-07 and LC-08 86041
Rear Flue Box w/12" Flue Outlet Models LC-09, LC-10, LC-11 and LC-12 86042
27 Rear Flue Box Stud 5/16"-18 x 1-1/2" 7 Required
28 Rear Flue Box Hi Temp Rope, 1/4" Diameter x 65" Long
29 Side Jacket Panel LC-6000 For Models LC-04 and LC-08
Side Jacket Panel LC-6001 For Models LC-05, LC-08, LC-09 and LC-10
Side Jacket Panel LC-6002 For Models LC-06, LC-10, LC-11 and LC-12
Side Jacket Panel LC-6003 For Models LC-07 and LC-12
30 Left Front Jacket Corner Panel LC-6011
31 Right Front Jacket Corner Panel LC-6010
32 Upper Front Jacket Panel LC-6007
33 Middle Front Jacket Panel LC-6008
34 Lower Front Jacket Rail LC-6009
35 Back Jacket Panel LC-6012
36 Side Jacket Panel Support Angle LC-6014
37 Front Top Jacket Panel LC-6005
Page 51
49
REPAIR PARTS
Table 12.1B: Series LC Repair Parts (continued)
38
39
Top Jacket Panel LC-6004
Top Jacket Panel LC6004-1
Top Jacket Panel LC-6004-2
Top Jacket Panel LC-6004-3
Rear Top Jacket Panel LC-6006
Single Rib Flue Baffle, Aluminized Steel LC-1018
Triple Rib Flue Baffle, Aluminized Steel LC-1019
Single Rib Flue Baffle, Stainless Steel LC-1020
Triple Rib Flue Baffle, Stainless Steel LC-1021
Item
No.
Description
For Models LC-04 and LC-08
For Models LC-05, LC-08, LC-09 and LC-10
For Models LC-06, LC-10, LC-11 and LC-12
For Models LC-07 and LC-12
Specify Boiler Model Number
Specify Boiler Model Number
Specify Boiler Model Number
Specify Boiler Model Number
Part Selection Information
Stock
Code
Page 52
50
REPAIR PARTS
Figure 12.2: Series LCE Boiler Assembly
Page 53
51
REPAIR PARTS
Table 12.2A: Series LCE Repair Parts
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
Front Section
Top Flue Outlet Intermediate Section
Intermediate Section w/1" Tapping
Intermediate Section
Back Section (Closed Back)
Back Section w/Tankless Coil Opening
Tapped Intermediate Section
Upper Flow Port Gasket
Lower Flow Port Gasket
Tie Rod
5/8" Diameter High Temp Rope
Ceramic Fiber Base Liner
Ceramic Fiber Target Wall
Front Cleanout Plate (C.I.)
5/16"-18 x 1-1/4" Studs w/Brass Nuts
Steel Cover Plate
Steel Cover Plate
Tankless Heater Location 1
Tankless Heater Location 2
Tankless Heater Location 3
Rubber Gasket
3/8"-16 x 3/4" SS Hex Head Cap Screw
Rear Observation Assembly
5/16"-18 x 3/4" Hex Head Cap Screw
Burner Mounting Plate
3/8"-16 x 2-1/4" Studs with Nuts
Front Observation Assembly
3/8"-16 x 1" Studs for Burner Mounting
1/4"-20 x 1/2" Hex Head Machine Screw
Cleanout Cover Plate (Steel)
Rear Flue Cover Plate
Rear Flue Cover Stud 5/16"-18 x 1-1/2"
Rear Flue Cover Hi Temp Rope, 1/4" Dia. x 65" Long
Side Jacket Panel LC-6000
Side Jacket Panel LC-6001
Side Jacket Panel LC-6002
Left Front Jacket Corner Panel LC-6011
Right Front Jacket Corner Panel LC-6010
Upper Front Jacket Panel LC-6007
Middle Front Jacket Panel LC-6008
Lower Front Jacket Rail LC-6009
Back Jacket Panel LC-6012
Side Jacket Panel Support Angle LC-6014
Front Top Jacket Panel LC-6005
Top Jacket Panel LC-6004
Top Jacket Panel LC-6004-1
Item
No.
Description
86022
86036
86008
51671
51672
51721
55723
50862
50854
51162
51776
51777
51800
90923
90922
51772
51131
See Table for Stock Code
2 Required per Flueway
1 Required per Flueway
4 Required per Flueway
13 Feet Required per Flueway
For All LCE Boilers
4 Required
Specify Heater Model Number
Not Used On Steam
Specify Heater Model Number
Specify Quantity
Specify Quantity
Specify Quantity
Specify Burner Model
7 Required
4 Required
4 Required
1 Required per Flueway
For All LCE Boilers
5 Required
For Models LCE-13, -17, -20 & -21
For Models LCE-13 to LCE-15, LCE-17 to LCE-24
For All LCE Boilers
For Models LCE-13, -17, -20 & -21
For Models LCE-13 to LCE-15, LCE-17 to LCE-24
Part Selection Information
Stock
Code
Page 54
52
REPAIR PARTS
Table 12.2B: Series LCE Repair Parts (continued)
38
40
39
41
42
43
44
Top Jacket Panel LC-6004-2
Top Jacket Panel with Flue Opening LC-6022
Rear Top Jacket Panel LC-6006
Top Flue Outlet Plate (14" Flue)
Top Flue Outlet Plate (16" Flue)
5/8" Diameter High Temperature Rope
3/8" Diameter Tie Down Assembly
Draft Damper, 14"
Draft Damper, 16"
Baffles
Item
No.
Description
51132
51133
55723
51604
90523
90524
86113
For Models LCE-15, -16, -19, -23 & -24
For All LCE Boilers
For Models LCE-13 through LCE-17
For Models LCE-18 and Larger
For Top Flue Outlet Plate, 6 Feet
For Top Flue Outlet Plate, 4 Required
For Models LCE-13 through LCE-17
For Models LCE-18 and Larger
Models LCE-21 through LCE-24 Only
Part Selection Information
Stock
Code
Page 55
LC/LCE
Gas/Oil Boilers Steam
Series
Oil, Gas &
Installation, Operation & Maintenance Manual
TO THE INSTALLER:
This manual is the property of the owner and must be affixed near the boiler for future reference.
TO THE OWNER:
This boiler should be inspected annually by a Qualified Service Agency.
LC8046 R6 (4/06-1.5M)
Printed in U.S.A.
©2006
HI Division
of gama
ASME
PB HEAT, LLC
PO BOX 447 • NEW BERLINVILLE, PA 19545-0447
Loading...