PEERLESS WV-DV, WV-DV Series, WV-DV-03-075, WV-DV-03-085, WV-DV-03-110 Installation, Operation & Maintenance Manual

...
Page 1
WV-DV
Boilers
Series
Oil
Installation, Operation & Maintenance Manual
As an ENERGY STA R®Partner, PB Heat, LLC has determined that certain firing rates of this product meet the
ENERGY STA R
®
guidelines for energy efficiency.
Page 2
Sidewall Venting
The Peerless WV-DV is designed and built to be vented through a side wall of a building using a stainless steel concentric vent terminal (4 inch diameter tube inside an 8 inch diameter tube). Exhaust gases from combustion contain water vapor. During the cooler months of the year, this water vapor will condense into a visible vapor plume. This water vapor may condense on any surface near the vent terminal. Care must be taken not to locate the vent terminal where the exhaust gas, vapor plume and condensation could cause a hazard or a nuisance. Do not locate terminal under a deck, for instance, as it may create a coating of ice on the deck during the winter months, as well as shorten the life of the deck materials. Refer to Chapter 4 in this manual for specific terminal location requirements. Condensate from a side wall vent terminal may also cause paint on surrounding surfaces to crack and peel. If the boiler is used to heat potable (tap) water, the boiler will cycle year round.The effects of hot exhaust gases and odors must be taken into consideration during summer months.
Side wall vented, oil fired appliances may cause soot staining on wall surfaces surrounding their terminals. To reduce the potential for staining, the boiler must be serviced annually. Soot and scale must be completely removed from the combustion chamber and cast iron heat exchanger flueways. See Chapter 7 in this manual. The oil burner must be completely serviced and set up according to the specifications shown in Chapter 5 of this manual.
NOTICE
Page 3
1
USING THIS MANUAL 2
A. INSTALLATION SEQUENCE . . . . . . . . . . . . .2
B. SPECIAL ATTENTION BOXES . . . . . . . . . . . .2
1. PREINSTALLATION 3
A. ACCESSIBILITY CLEARANCES . . . . . . . . . . .3
B. CLEARANCES FROM COMBUSTIBLE
CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . .3
2. BOILER SET-UP 4
A. SETTING UP THE BOILER . . . . . . . . . . . . . . .4
3. PIPING AND CONTROLS 5
A. BOILER SUPPLY AND RETURN . . . . . . . . . . .5
B. TANKLESS WATER HEATER . . . . . . . . . . . . .6
C. INDIRECT-FIRED WATER HEATER . . . . . . . .6
D. SAFETY RELIEF VALVE . . . . . . . . . . . . . . . . .6
E. CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4. VENTING 7
A. VENT SYSTEM INSTALLATION . . . . . . . . . . .7
5. OIL BURNER 9
A. BURNER INSTALLATION . . . . . . . . . . . . . . . .9
6. ELECTRICAL 11
A. WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
B. ZONED SYSTEM WIRING . . . . . . . . . . . . . .11
7. MAINTENANCE 15
A. CLEANING HEATING SURFACES . . . . . . . .16
8. BOILER DIMENSIONS & RATINGS 17
9. REPAIR PARTS 18
TABLE OF CONTENTS
TABLE OF CONTENTS
Page 4
2
A. INSTALLATION SEQUENCE
Follow the installation instructions provided in this manual in the order shown. The order of these instructions has been set in order to provide the installer with a logical sequence of steps that will minimize potential interferences and maximize safety during boiler installation.
B. SPECIAL ATTENTION BOXES
Throughout this manual you will see special attention boxes intended to supplement the instructions and make special notice of potential hazards. These categories mean, in the judgment of PB Heat, LLC:
Indicates special attention is needed, but not directly related to potential personal injury or property damage.
NOTICE
Indicates a condition or hazard which will or can cause minor personal injury or property damage.
CAUTION
DANGER
Indicates a condition or hazard which will cause severe personal injury, death or major property damage.
USING THIS MANUAL
USING THIS MANUAL
Indicates a condition or hazard which may cause severe personal injury, death or major property damage.
WARNING
Page 5
A. ACCESSIBILITY CLEARANCES
To provide for reasonable conditions of accessibility, the following minimum clearances are recommended: Alcove Installation.
1. 12" from left side
2. 24" from top
3. 24" from front
4. 9" from right side and rear
B. CLEARANCES FROM COMBUSTIBLE
CONSTRUCTION
The design of this boiler is certified for the following clearances from combustible construction:
1. 0" from rear
2. 0" from right and left sides
3. 0" from top
4. 0" from vent pipe
5. 0" from vent connector
6. 0" from vent terminal
7. 24" from front
3
PREINSTALLATION
1. PREINSTALLATION
Read carefully, study these instructions before beginning work. It will save time. Study the included drawings. Save these instructions for reference.
This boiler must be installed by a qualified contractor.
The boiler warranty can be voided if the boiler is not installed, maintained and serviced correctly.
The equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made, including the current edition of NFPA-31. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
NOTICE
Do not tamper with boiler or controls.
CAUTION
NEVER BURN GARBAGE OR PAPER IN THE UNIT, AND NEVER LEAVE COMBUSTIBLE MATERIAL AROUND IT.
CAUTION
Do not use this appliance if any part has been under water. Improper or dangerous operation may result. Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any control which has been under water.
WARNING
Page 6
4
BOILER SET-UP
A. SETTING THE BOILER
1. Prepare sketches and notes of the layout of the installation. Include boiler location, venting system, existing piping and wiring. Show existing equipment that may interfere with installation of new equipment. See Section 4-A. “Vent System Installation,” Page 7, and Figure 4.1.
2. Provide a level foundation, located as close as possible to the center of the heating system.
3. This boiler is suitable for use on combustible flooring, provided the boiler is not set on carpet and a metal drip pan is placed under the appliance.
4. See exploded view (Figure 9.1). After uncrating boiler and setting it on foundation, open burner mounting plate (Item 5) and make certain the target wall (Item 2) is seated in the back of the combustion chamber. (WV-DV-04) Ceramic fiber blanket base liner (Item 3) should be lying flat on bottom of combustion chamber between target wall and burner mounting plate. Close burner mounting plate.
2. BOILER SET-UP
Page 7
5
A. BOILER SUPPLY AND RETURN
1. See Figure 3.1 for suggested piping to the boiler.
2. Make up cold water supply connection to the boiler.
3. Plug all open tappings in the boiler and fill with water. Apply approximately thirty (30) psi pressure. Check to make certain that all joints and fittings are water tight.
4. After all joints and connections have been proven water tight, remove cold water supply and plugs from all tappings that are to be used. See Figure 8.1 for tapping locations.
5. Return water piping must be done in such a manner to allow clearance from the burner mounting plate to other piping when opening and closing the burner mounting plate.
3. PIPING AND CONTROLS
PIPING AND CONTROLS
6. The supply and return connections should be sized to suit the system. A 1-1/2" to 1-1/4" reducing coupling may be used on the return where the system piping is 1-1/2". The supply should be out of the top of the back section and return to the bottom of the front section. There is a 3/4" tapping in the top of the back section for air elimination.
Figure 3.2
Note: If boiler is to be used in conjunction with a refrigeration
system, the chilled medium shall be piped in parallel with boiler and proper valves applied to prevent the chilled medium from entering the boiler. Refer to Figure 3.2.
When the boiler is connected to heating coils located in air handling units, the boiler piping system must be equipped with flow control valves or other automatic devices to prevent gravity circulation of the boiler water during the cooling cycle.
Figure 3.1
Page 8
6
B. TANKLESS WATER HEATER
C. INDIRECT-FIRED WATER HEATER
1. If a water boiler is to be used in conjunction with an indirect-fired water heater refer to Figure 3.4 for typical piping. Also refer to additional instructions supplied with tank.
D. SAFETY RELIEF VALVE
1. Remove safety relief valve and 3/4" x 3" nipple from parts bag. Install nipple and safety relief valve in top or rear tapping. See Figure 8.1. If rear tapping is used, installer must supply an elbow so that safety relief valve is installed in vertical position.
E. CONTROLS
1. For complete information on servicing and adjustment of controls, refer to the attached control specification sheets.
Figure 3.3
Figure 3.4
Install mixing valve in hot water supply piping. Water temperature above 125°F can cause severe burns instantly or death from scalds.
DANGER
PIPING AND CONTROLS
Pipe the discharge of the safety relief valve to prevent injury in the event of pressure relief. Pipe the discharge to a drain. Provide piping that is the same size as the relief valve.
CAUTION
Note: X-1019R, X-1020R and PP-1011R Coils installed in
WV-DV boilers have internal flow controls installed. Do not use external flow controls with these coils.
Page 9
A. VENT SYSTEM INSTALLATION
1. Determine vent terminal location: a. Vent length must be between 3' and 20' long.
See paragraph 3 and Figure 4.1 for air intake requirements.
b. No clearance is required between vent terminal
and combustible construction.
c. Vent terminal extends 12" beyond outside wall
surface and at least 16" beyond inside wall surface. See Figure 4.1.
d. Provide 3' clearance above any forced air inlet
within 10'.
e. Provide 4' clearance below, 4' beside, or 1' above
any door, window, or gravity air inlet into any building.
f. On multiple boiler installations, provide 18"
clearance between vent terminals. Located terminals on same horizontal plane.
g. Provide 1' clearance between bottom of vent
terminal and ground level or between bottom of vent terminal and normal snow lines.
h. Provide 4' horizontal clearance from, and in no
case above or below, unless a 4' horizontal clearance is maintained, from electric meters, gas meters, gas regulators, and gas relief equipment.
i. Provide 5' clearance to the vent outlet of a fuel
oil supply tank.
j. Provide 1' clearance to the soffit of the roof and
3' clearance to an inside corner of an L-shaped building.
k. Do not locate vent terminal over public walkways
where condensate could create a nuisance or hazard.
l. When adjacent to a public walkway, locate vent
terminal at least 7' above grade.
7
4. VENTING
VENTING
Figure 4.1: Venting
This boiler is shipped with a Flex-L International Vent Terminal carton, and a Flex-L International Venting Components Kit. The following components from these two cartons must be used in the installation of this boiler:
·
CeraFlex Oil Vent Terminal
·
CeraFlex Vent Pipe
·
CeraFlex Appliance Adapter
·
CeraFlex Terminal Adapter
· CeraFlex Sealant
NOTICE
This Oil-Fired Unit Shall be Connected to a Direct Vent System, to Assure Safe Proper Operation of the Unit.
CAUTION
Table 4.1
Page 10
8
2. Use Flex-L International Inc. 4" diameter CeraFlex
Vent Pipe.
3. For air intake, use 4" diameter galvanized smoke
pipe or 4" diameter flexible corrugated aluminum pipe. Maximum equivalent length of galvanized smoke pipe is 40'. Allow 5 equivalent feet for each 90° elbow used. (Example: No more than 20' straight smoke pipe can be used with four 90° elbows.) To connect air intake to Riello BF5 burner, use burner air adapter from trim bag to connect 4" air intake to 3" opening on top of burner. See Figure 4.1.
4. For specific installation and maintenance instructions
for the Flex-L Vent Terminal, Appliance Adapter, Terminal Adapter, Burner Air Adapter (Riello only), and Sealant that are included with the boiler, as well as instructions for installation of flexible vent pipe and air intake pipe, refer to Flex-L Manual #Y4-CF12 included in vent kit.
PB Heat, LLC requires that the vent slopes down 1/4" per foot towards the vent terminal.This takes precedence over the requirements shown in the Flex-L manual.
NOTICE
VENTING
Page 11
9
A. BURNER INSTALLATION
1 The oil burner is supplied with a mounting flange
fixed in position.
2. BE SURE HI TEMP GASKET IS BETWEEN THE
BURNER MOUNTING FLANGE AND THE COMBUSTION CHAMBER COVER PLATE.
3. Care must be taken when routing the oil lines so not
to interfere with the opening and closing of the burner mounting plate. Flexible oil lines or flared copper disconnects with valves (when copper lines are used) may be installed to assure full opening of the burner mounting plate when servicing.
Note: Two-pipe oil supply for Riello burner requires a sep-
arate kit. Order part #C7001026 from Riello dealer.
4. Oil Burner Specifications:
For information pertinent to the oil burner such as nozzle sizing, fuel supply piping, adjusting or servicing, refer to the charts below and the burner installation manual.
5. Sampling tapping in CeraFlex Appliance Adapter must
be used for CO², smoke and flue pressure readings.
6. Burner should start automatically when thermostat is turned up and main boiler service switch is turned on. If burner does not start, check to be sure there is oil in the tank and push reset button on burner control: (Beckett) square red button; (Carlin) round red button; (Riello) round red button inside clear flexible cover on back of burner cover. If burner still does not start, contact serviceman.
7. Burner and boiler can be shut down by turning down the thermostat and moving the main boiler service switch to the “off” position.
8. Post-purge timing on Riello BF5 burner is controlled by 3/8" diameter dial near top right corner of AL1009 circuit board inside burner cover. Post-purge duration must be a minimum of one minute. Adjust dial so arrow is pointing directly to the right (toward mounting screw for AL1009 bracket). Check post­purge timing to confirm it is at least one minute long.
5. OIL BURNER
OIL BURNER
BURN ONLY #2 FUEL OIL IN THIS APPLIANCE. DO NOT USE GASOLINE, CRANKCASE DRAININGS OR ANY OIL CONTAINING GASOLINE.
CAUTION
Do not attempt to start the burner when excess oil has accumulated, when the unit is full of vapor, or when the combustion chamber is very hot.
CAUTION
Always keep the manual fuel supply valve shut off if the burner is shut down for an extended period of time.
CAUTION
Page 12
10
Table 5.1
Beckett NX Burner Specifications
Boiler Model No. Burner Model Nozzle Manufacturer, Size Pump Pressure (psig) Head/Air Setting Low Fire Baffle
WV-DV-03-075 NX70LB Delavan 0.60 60° W¹ 175 2.25 Ye s WV-DV-03-085 NX70LB Delavan 0.65 60° W 175 3.00 Ye s WV-DV-03-110 NX70LB Hago 0.85 60° B¹ 175 3.75 No WV-DV-04-115 NX70HB Hago 0.85 60° B 170 1.50 Ye s WV-DV-04-130 NX70HB Hago 1.00 60° B¹ 170 1.50 No
Table 5.2
Table 5.3
Carlin EZ1-HP Burner Specifications
Boiler Model No. Delavan Nozzle Size Pump Pressure (psig) Air Boot Setting Head Bar
WV-DV-03-075 .60 70° A¹ 150 0.5 0.75 WV-DV-03-085 .65 70° A¹ 150 0.6 0.75 WV-DV-03-110 .85 70° A 150 0.85 1.10 - 1.25 WV-DV-04-115 Hago 1.00 60° B¹ 140 1.00 1.10 - 1.25 WV-DV-04-130 Hago 1.10 60° B 140 1.25 1.10 - 1.25
Riello BF5 Burner Specifications
Boiler Model No. Nozzle Size Pump Pressure (psig) Turbulator Setting Air Damper Setting
WV-DV-03-075 Delavan .60 80° B¹ 165 1 3.3 WV-DV-03-085 Delavan .65 80° B¹ 165 1 3.8 WV-DV-03-110 Delavan .90 80° B 165 2 5.0 WV-DV-04-115 Hago .85 60° B¹ 180 2 5.0 WV-DV-04-130 Hago 1.10 60° B 140 4 5.0
Start-up and adjustment recommendations: Above Turbulator, Pin, Air Damper, and Air Dial settings are start-up settings only. Adjust burner for highest CO²(no more than 13%) while maintaining a 0 smoke spot. Pressure or draft over fire and in flue cannot be adjusted. However, draft and/or pressure measurements must be taken in these two locations and recorded for reference. All adjustments and measurements must be made using suitable instruments such as those found in a Bacharach Combustion Test Kit.
Factory Installed Nozzles are indicated in Boldface.
1. Shipped Loose
OIL BURNER
Page 13
11
ELECTRICAL
A. WIRING
1. All electrical wiring shall be done in accordance with the National Electrical Code and Local Requirements. Single Pole Switches including those of Safety Controls or Protective Devices shall not be wired in a grounded line.
B. ZONED SYSTEM WIRING
1. Wire zone circulators as shown in Figures 6.4 and
6.5. Wire zone valves as shown in Figure 6.6.
6. ELECTRICAL
Do not connect power supply to Aquastat. To assure service switch interrupts power to all boiler controls, power supply must be connected to junction box as shown below.
CAUTION
Figure 6.2: Beckett/Carlin Burner
Figure 6.1: Connecting Incoming Power
Page 14
12
ELECTRICAL
Figure 6.3: Riello Burner
Figure 6.4: Zoning With Circulators, Honeywell L8148 Aquastat
Page 15
13
ELECTRICAL
Figure 6.5: Zoning With Circulators, Honeywell L8124A, C Aquastat
Figure 6.6: Zoning With Zone Valves
Page 16
14
Figure 6.7: Partner with Circulator (Non-priority)
ELECTRICAL
Page 17
15
MAINTENANCE
7. MAINTENANCE
WARNING
Product Safety Information
Refractory Ceramic Fiber Product
This appliance contains materials made from refractory ceramic fibers (RCF). Airborne RCF fibers, when inhaled, have been classified by the International Agency for Research on Cancer (IARC), as a possible carcinogen to humans. After the RCF materials have been exposed to temperatures above 1800°F, they can change into crystalline silica, which has been classified by the IARC as carcinogenic to humans. If particles become airborne during service or repair, inhalation of these particles may be hazardous to your health.
Avoid Breathing Fiber Particulates and Dust
Suppliers of RCF recommend the following precautions be taken when handling these mate­rials:
Precautionar
y Measures: Provide adequate ventilation. Wear a NIOSH/MSHA approved respirator. Wear long sleeved, loose fitting clothing and gloves to prevent skin contact. Wear eye goggles. Minimize airborne dust prior to handling and removal by water misting the material and avoiding unnecessary disturbance of materials. Wash work clothes separately from others. Rinse washer thoroughly after use. Discard RCF materials by sealing in an airtight plastic bag.
Fir
st Aid Procedures: Inhalation: If breathing difficulty or irritation occurs, move to a location with fresh clean air. Seek immediate medical attention if symptoms persist. Skin Contact: Wash affected area gently with a mild soap and warm water. Seek immediate medical attention if irritation persists. Eye Contact: Flush eyes with water for 15 minutes while holding eyelids apart. Do not rub eyes. Seek immediate medical attention if irritation persists. Ingestion: Drink 1 to 2 glasses of water. Do not induce vomiting. Seek immediate medical attention.
Page 18
16
MAINTENANCE
A. CLEANING HEATING SURFACES
TO CLEAN:
1. Turn off all electrical power to the boiler before beginning cleaning operation.
2. Remove top jacket panel and flue collector cover plate, Item 11.
3. Brush the flue passages thoroughly from the top with a wire brush. If unit is extremely dirty, brushing up from the combustion chamber area also may be necessary. The target wall is made of a soft ceramic fiber. Care must be taken not to damage this material during cleaning.
4. Remove any scale or soot from the combustion chamber area by vacuum cleaning or any other available means.
5. Replace oil burner and flue collector cover plate making sure all gaskets are in place.
6. Replace jacket top panel.
7. Inspect venting system.
Entire heating system, including boiler, burner and venting system, must be inspected at least once a year by a qualified heating professional. Boiler is to be cleaned at least once a year. To thoroughly clean the boiler it must be brushed down from the top. Alternately, for limited space or minimum clearance to combustible installations, cleaning the heat exchanger from the combustion chamber side is acceptable.
NOTICE
Combustion chamber cover plate must be opened to facilitate this operation.
NOTICE
Combustion chamber and flue collector may be under pressure when burner is running. Flue collector cover plate and combustion chamber must be completely sealed before boiler is returned to operation.
CAUTION
All Cover Plates, Enclosures, and Guards must be maintained in place at all times, except during maintenance and servicing.
NOTICE
Page 19
17
BOILER DIMENSIONS & RATINGS
8. BOILER DIMENSIONS & RATINGS
Table 8.1: WV-DV Ratings
1. Boiler Model No. may have the following suffix letters: a. W–Water, b. P–Packaged, c. C–Circulator, d. T–Tankless Coil
2. Heating Capacity ratings are based on U.S. Government standard tests, with
13.0% CO².
3. The water ratings are based on piping pick-up allowance of 1.15. Consult factory
before selecting a boiler for gravity hot water installations and installations having unusual piping and pick-up requirements, such as intermittent system operation, extensive piping systems, etc.
4. Firing rate is based on a fuel oil with a heating value of 140,000 BTU per gallon.
Burner input based on maximum altitude of 2,000 ft. – for other altitudes consult factory.
(1) Boiler Model
Number
(2)
Heating
Capacity
BTU/Hr.
(3)
Net I=B=R Ratings
BTU/Hr.
Water
(4)
I=B=R
Firing
Rate G.P.H. WV-DV-03-075 92,000 80,000 0.75 WV-DV-03-085 103,000 90,000 0.85 WV-DV-03-110 131,000 114,000 1.10 WV-DV-04-115 141,000 122,000 1.15 WV-DV-04-130 158,000 137,000 1.30
Model A B
WV-DV-03
14¹⁄₈" 7¹⁄₁₆"
WV-DV-04
18¹⁄₈" 9¹⁄₁₆"
Figure 8.1: WV-DV Boiler Views
Page 20
18
REPAIR PARTS
9. REPAIR PARTS
Figure 9.1: Repair Parts
Repair parts are available from your installer or by contacting PB Heat, LLC, P.O. Box 447, New Berlinville, PA 19545-0447.
Note: Remember to include boiler model number and serial number when ordering parts.
5a
5b
5c
5d
5e
Page 21
19
Table 9.1: Repair Parts**
**See Figure 9.1
REPAIR PARTS
Item
No.
Description
Additional
Information
Stock Code
WV-DV-03
Stock Code
WV-DV-04
1
Block Assembly Water WPCT
90183 90184
Block Assembly Water WPC
90186 90187
2
Target Wall
50795 50795
3
Base Liner
50857
4
Swing Door Hinge
3903 3903
5
Burner Mounting Plate Assembly
PP1051 PP1051
Burner Mounting Plate Insulation
50794 50794
Flame Observation Assembly
90754 90754
5a
Flame Observation Cover Plate
SC1007P SC1007P
5b
Face Gasket
50230 50230
5c
Pyrex Observation Window
51681 51681
5d
Ring Gasket
50229 50229
5e
Observation Glass Holder
X1138P X1138P
6
Burner Mounting Plate Rope Seal 51210 51210
7
Steel Cover Plate (Front) Water 99812 99812
8
Rubber Gasket (Front Plate) 51800
51800
9
Tankless Coil 90637
90534
10
Flue Collector Plate Blanket Seal 90999
90999
11
Flue Collector Cover Plate 50245
50253
12
Rope Seal 51209
51209
13
Rear Outlet Cover Plate 90563
90563
15
Jacket Assembly 90098
90418
Oil Burner
Specify Brand Name
and Boiler Size
Temperature-Pressure Gauge
Aquastat
Drain Valve
Relief Valve
Boiler Vent Adapter
CFAA44P 7612 7612
Flexible Pipe Termination Adapter
CFAT44 7613 7613
Riello Burner Adapter
CFBA34-RL 7615 7615
Tube of Sealant
XMMSC5 7616 7616
Concentric Vent Termination Kit
CFT4 91776 91776
Page 22
20
NOTES
Page 23
21
NOTES
Page 24
HI Division
of gama
ASME
PP8076 R5 (2/06-3M)
Printed in U.S.A.
©2006
WV-DV
Boilers
Series
Oil
Installation, Operation & Maintenance Manual
TO THE INSTALLER:
This manual is the property of the owner and must be affixed near the boiler for future reference.
TO THE OWNER:
This boiler should be inspected annually by a Qualified Service Agency.
Service Information
PB HEAT, LLC
P.O. BOX 447 • NEW BERLINVILLE, PA 19545-0447
Name:
Address:
Phone:
Loading...