'-'1 [_ :lOl:l;_r.*1
Series TC boilers are supplied completely knocked down
for field assembly, completely assembled as packaged
boilers or as assembled blocks of sections. All items
should be inspected for damage upon receipt and any
damage reported to the wholesaler and trucker. All
components should be stored in a clean dry area.
Im]! [o,l:lllVd_'_l::li"dt:'1 I:]:t:d=(e,];llO[,€
Carefully read these instructions, burner and controls
manuals before beginning work. This boiler must be
installed by a qualified contractor. The boiler warranty
can be voided if the boiler is not installed correctly.
:N [I'[e] I] _L,"Jl-'JR;| :[L"[I JW-'_IHi[I] _I.:
1,
2,
All work shall be performed in strict accordance with
the requirements of state and local regulating
agencies and codes dealing with boiler installations.
In the absence of such local requirements the
following should govern:
A.S.M.E. Section IV - "Heating Boilers"
A.S.ME Section VI - "Care and Operation Boilers"
ANSIfNFPA 31 - "Installation of Oil Burning
Equipment"
ANSI!Z223.1 - "National Fuel Gas Code"
ANSI/NFPA 70 "National Electrical Code"
A.SM.E. CSD-1 "Controls and Safety Devices for
Automatically Fired Boilers"
ANSI/NFPA 211 - "Chimneys, Fireplaces, Vents,
and Solid Fuel Burning Appliances"
If this boiler is to installed on combustible flooring.
Consult local building authorities for proper
installation, or in the absence of regulations consult
ANSI/NFPA 31, Section 4-4. Failure to comply with
this warning can result in a fire, severe personal
injury or death!
[OglI:.[o]lll::l:] li[oIo,Y,__l/[O]_
1. The boiler should be installed on a concrete floor or
pad. If a pad is used, it should be at least 2" high
and strong enough to support the boiler's weight. Do
not install electrical conductors of any type under the
boiler or pad. The pad must be as level and fiat as
possible.
Locate the boiler close to the chimney to minimize
the breeching length, but allow adequate clearance
for piping, service, maintenance and tanldass coil
replacement. A clearance of 36" on the sides of the
boiler and 48" in front of the boiler is recommended
for serviceability. The minimum clearance to
combustible materials, based on ANSI!NFPA 31,
Table 4-4.11 Clearances to Combustible Materials, is
as follows:
2
I Sides: 6"
2. Rear of Jacket: 6"
3. Front of Boiler: 24"
4. Top of Jacket: 6"
5. Vent/Chimney/Flue Box: 18"
]. Vent System Inspection:
a) Inspect the existing chimney or vent system.
Make sure it is in good condition.
b) Inspect the chimney liner and repair or replace if
necessary.
2. Vent System Installation:
a) The vent system and installation must be in
accordance with the current edition of the
American National Standard ANSI!NFPA 211,
"Chimneys, Fireplaces, Vents, and Solid Fuel
Burning Appliances" or applicable provisions of
the local building codes.
b) Always extend vent terminations three feet above
the roof line.
c) The breeching connection between the boiler
and chimney should be as short as possible with
a minimum number of elbows. [t should be
pitched upwards 1/4" per foot. The breeching
must be the same diameter as the boiler outlet
up to 16 section boilers and 18" diameter for 17
and 18 section boilers.
d) If extreme length, excessive number of turns or a
reduction in diameter is necessary, consult your
Peerless Heater Company representative for
recommendations.
3. Vent System Operation:
a) The vent system must be sized and installed to
remove all combustion products. If the vent
system is not properly sized, the burner may not
operate properly. This can cause poor
combustion or sooting to occur.
b)
c)
If the vent system terminates in any area where
wind-generated down drafts are likely, install a
suitable vent cap which can control wind effects.
This boiler is designed to fire only with a positive
pressure firebox with no more than 0.1" water
column at the boiler outJet before the slide
damper. If venting conditions cause a greater
back pressure, burner capacity may be reduced.
Consult the Peerless Heater Company for
verification of burner capacity under these
conditions. The breeching and vent may be sized
for negative, neutral, or positive pressure as
desired. However, negative pressure overfire can
cause lifting of the flame and poor combustion or
overheating of the boiler crown sheet.