Peerless Industries CMJ 300, CMJ 310 User Manual

Installation and Assembly - Peerless Unistrut® and Structural Ceiling Plate
IMPORTANT! Read entire instruction sheet before you start installation and assembly.
Before you start make sure all parts listed
Parts List
PART # QTY . DESCRIPTION
A 100-1007 1 4" x 4" ceiling plate (Model CMJ 300)
100-1008 1 8" x 8" ceiling plate (Model CMJ 310)
B 520-9560 1 10-32 x 1/2" self-tapping screw
are included with your product.
Available Accessories: Concrete Anchor Kit - order accessory kit ACC 210. Call Peerless Customer Service.
Models: CMJ 300, CMJ 310
Attach plate (A) to existing Unistrut using four existing spring nuts and 3/8" (max.) screws (not included).
Note: For concrete ceiling installation go to page 2.
A
Once ceiling plate (A) is in desired position, tighten screws. When attaching the ceiling plate (A) to flush mount tube or extension column, tighten at least four complete turns ending with one of the small threaded holes aligned with slot in the end of flush mount tube or extension column. Insert and tighten one #10-32 screw (B) to lock tube position (shown below on right side).
B
A
1 of 2
Visit the Peerless Web Site at www.peerlessmounts.com For customer care call 1-800-729-0307 or 708-865-8870.
ISSUED: 12-05-00 SHEET #: 100-9001-3 04-27-06
Note: Fasteners for concrete ceilings are not included, order ACC 210 accessory kit.
For Concrete Ceilings use ceiling plate (A) as a template, drill four 5/16" (8 mm) dia. holes to a minimum depth of 1-3/4" (45 mm). Attach using concrete expansion anchors as shown. Tighten to 80 in. • lb (9 N.M.) maximum torque.
WARNING
• Make sure that the supporting surface will safely support the combined load of the equipment and all attached hardware and components.
• Never exceed the Maximum Load Capacity of 250 lb (1 13.4 kg).
A
ACC 210
Align hole in ceiling plate (A) with hole in ceiling. Gently hammer in concrete anchor as shown.
Use a 10 mm wrench (not provided) to tighten concrete anchor to 80 in. • lb (9 N.M.) maximum torque as shown.
WARNING
• Tighten concrete anchor bolt firmly , but do not over­tighten. Overtightening can damage the bolt, greatly reducing its holding power.
• Never tighten in excess of 80 in. • lb (9 N.M.).
FOR PRODUCT SAFETY USE ONL Y RA WL™ #5005 OR HILTI™ HL814 CONCRETE ANCHORS. Order ACC 210 accessory kits, each contains four .312" x
1.625" (8 mm x 41 mm) concrete expansion anchors. Concrete expansion anchors are not intended for
attachment to concrete covered with a layer of plaster, drywall, or other finishing material.
A
WARNING
• Always attach concrete expansion anchors directly to load-bearing concrete.
• Never attach concrete expansion anchors to concrete covered with plaster, drywall or other finishing material. If mounting to concrete surfaces covered with a finishing surface is unavoidable, the finishing surface must be counterbored as shown in Figure 1.
2 of 2
Visit the Peerless Web Site at www.peerlessmounts.com For customer care call 1-800-729-0307 or 708-865-8870.
© 2006 Peerless Industries, Inc. All rights reserved. Peerless is a registered trademark of Peerless Industries, Inc. All other brand and product names are trademarks or registered trademarks of their respective owners.
ISSUED: 12-05-00 SHEET #: 100-9001-3 04-27-06