Peco T170 Application Manual

Page 1
T170 Hospitality Thermostat Occupancy Sensing
HVAC System Control
OCCUPANCY
SENSOR
DOOR SWITCH
WINDOW SWITCH
OCCUPANCY OPERATION:
Occupied State:
- Thermostat waits for a door open.
Door Open:
- Thermostat waits for a door close.
- If door is open more than 5 minutes the thermostat turns the HVAC system outputs to OFF.
Door Close:
- On door close the thermostat looks for occupancy.
- If the thermostat find occupancy it goes to Occupied State.
- If thermostat does not find occupancy it goes to Unoccupied State.
- the thermostat goes into unoccupied setback mode, as determined by factory or user settings.
- Thermostat continues to monitor the occupancy sensor and will go to Occupied State if it see occupancy.
Door/ Window Switch Only:
- Thermostat will disable the HVAC outputs if open for longer than 5 minutes.
ISSUES:
- Timing of return to occupied temperature.
- Thermostat display in unoccupied setback mode.
Unoccupied State:
T170 / SB200 Application Guide Issued 1/19/06