Peco T158, TA158 Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
1. Install the T158 with the two furnished mounting screws to a standard 4-11/16" x 2-1/8" square device box with a 2" x 4" adapter ring.
2. For wall installations, mount the thermostat on an inside wall approximately 5 feet above the floor. The location should provide circulation at average room temperature. Avoid direct sunlight or sources of hot or cold air in the room or wall.
3. Remove the cover. Mount thermostat base assembly to the outlet box using the screws provided, tighten the screws evenly but do not over tighten. Connect wires as shown in the appropriate wiring diagram for your thermostat style.
4. To use a remote sensor on units with local sensing capability, remove jumper JP-1 to disable local sensing. Failure to remove JP-1 will cause improper operation of the thermostat.
5. Remove the LCD plastic protective film. Reinstall the cover assembly. Install the cover locking screw provided in the hole at the left side of the control enclosure to complete the installation.
6. Checkout: After wiring and installation are complete, energize the system and check the operation. Adjust the thermostat as necessary to complete at least one cycle. Be sure the thermostat and all other equipment are functioning correctly.
CAUTION
TA158
MICROPROCESSOR THERMOSTAT
On/Off Controller
WARNING
hREAD THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS THERMOSTAT.
hFailure to observe safety information and comply with
instructions could result in PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
hTo avoid electrical shock or damage to equipment,
disconnect power before installing or servicing.
potentially flammable or explosive atmospheres.
hRetain these instructions for future reference. This
product, when installed, will be part of an engineered system whose specifications and performance characteristics are not designed or controlled by PECO. You must review your application and national and local codes to assure that your installation will be functional and safe.
hUse copper wire only, insulate or wire nut all un-used
leads.
hCare should be used to avoid electrostatic discharge to
the microprocessor.
hThis unit has configuration jumpers. You may need to re-
configure this thermostat for your application. See page 2.
1
2
3
4
LINE VOLTAGE
CONNECTIONS
5
6
7
10
11
12
13
14
15
LOW VOLTAGE
CONNECTIONS
16
17
L1 (HOT)
LO
MED
HIGH
OR SINGLE SPEED FAN
24 VAC 1
24 VAC 2
SETBACK INPUT
MAIN 1
SEC 1
SECONDARY
1 OUTPUT
L2 OR NEUTRAL
FAN
MAIN 1
OUTPUT
REMOTE PROBE
PIPE SENSOR
VOLTAGE
RATING
24 VAC
120 VAC
240 VAC
277 VAC
24 VAC XFMR
FAN AND SYSTEM SWITCHES
INDUCTIVE
FLA
NA NA NA 24 VA
5.8 34.8 6.0 125 VA
2.9 17.4 5.0 125 VA
2.4 14.4 4.2 125 VA
LRA
RESISTIVE
AMPS
PILOT DUTY
THERMOSTATIC
SWITCHING
(Pilot Duty)
10 VA
N.A.
N.A.
N.A.
TA158 OPERATION
Off at
N/A
N/A
ON - OFF
On With Demand
Temperature
Summer: On With
Heat Demand
Winter: Disabled
On at
Demand
N/A
N/A
OUTPUT
Off With Demand
MAIN 1
(Terminal 10)
MAIN 2
(Terminal 12)
SECONDARY
1
(Terminal 11)
SECONDARY
2
(Terminal 13)
* Operation is determined by configuration. See Dip Switch Configuration Table.
Temperature
Demand
Summer: Off With
Heat Demand
Winter: Disabled
WIRING DIAGRAM FOR ON/OFF OUTPUT
CONFIGURATION
© COPYRIGHT 2005 PECO, INC. ALL RIGHTS RESERVED P/N 68837 3220-1470 Rev 0 Page 1
Page 2
THERMOSTAT OPERATION
These thermostats are designed to control On-Off, N.O. and N.C. valves, relays and Erie® three wire floating valves. These units may include a fan switch with one or more fan speed selections.
MODE BUTTON OPERATION OFF All thermostat outputs are off, fan is still operational if
connected to manual fan speed switch. AUTO The thermostat automatically selects heating or cooling mode depending on the set point and room temperature. The appropriate HEAT or COOL indicator is enabled in addition to AUTO. A 3°F dead-band is provided to prevent short cycling between heating and cooling modes. After change-over the control points automatically shift so that the heating off point or the cooling off point equals the set point temperature. COOL The thermostat operates as a cooling only thermostat. The heating outputs are disabled. HEAT The thermostat operates as a heating only thermostat. The cooling outputs are disabled. If constructed without a mode button, the thermostat operates in Auto mode, subject to configuration of the 2/4 pipe jumper and pipe sensor input.
FAN SPEED SWITCH OPERATION
Fan speed is determined by manual selection from fan switch OFF to HIGH, MEDIUM and/ or LOW. In units with the Cycling Fan Option (demand output), the Fan operation (CYCLING vs. CONTINUOUS) is determined by application connections. In OFF position all outputs are off and display blank.
UP/ DOWN ARROW OPERATION
A first touch of either arrow will display the set point (a single set point is employed for both heating and cooling). Continued pressure on either arrow will scroll the set point to new values. After three seconds with no pressure on either arrow, the selected set point becomes effective and the display of the room temperature resumes.
SETBACK OPERATION
Connection of the Setback Input to 24 VAC 1 will force the control into un-occupied mode (see wiring diagram). Pressing an arrow key or the mode button on the thermostat cover will disable the setback input for one hour.
PIPE SENSOR OPERATION
If cold water is detected, the system will operate in summer mode and the Main output will be cooling. If hot water is detected, the system will operate in winter mode, the Main output will be heating and First Stage Secondary Output will be disabled. In the case of an ambiguous reading, neither hot or cold, the thermostat will initiate a purge cycle.
DIP SWITCH CONFIGURATION
SECONDARY 1 OFF WITH DEMAND
MAIN 1 OFF WITH DEMAND
CENTIGRADE DISPLAY
OPERATING POSITION
OPERATING POSITION
85 F/ 60 F SETBACK
Example: This Dip Switch Is Configured For On With Demand, °F Display, On-Off Operation And 90/50 F Setback.
NOTE: Thermostat power must be cycled for changes in dip switch configuration to take effect.
AUTO
ON
10 11 12 13
11 22 33 44 55 66
SECONDARY 1 ON WITH DEMAND
MAIN 1 ON WITH DEMAND
FAHRENHEIT DISPLAY
N/A
N/A
90 F/ 50 F SETBACK
DIP SWITCH
JP4
15 16 17
5 6 7
ON
1
2 3
4 5 6
1 2 3 4
JP1
CIRCUIT BOARD JUMPER CONFIGURATION
Jumper
Designation
JP1
JP4
* Disables the Secondary 1 Output
Application Notes
1. When no pipe sensor is used the main output controls cooling and the secondary output controls heating.
2. The pipe sensor should be mounted on the main coil input for water system operation and in the main duct system for forced air operation.
3. The set point and operating mode will be retained on a loss of power.
4. When using either a remote probe or pipe sensor, run wiring away from any electrical motors or power wiring.
Jumper Installed
ON
Local Sensing
2 Pipe System*
Jumper Removed
OFF
Remote Sensing
4 Pipe System
Service Menu: Access: Press UP and DOWN arrows for 5 seconds. Menu Selection: Select 1 to 5 by pressing the mode button
or by pressing the UP and DOWN arrows simultaneously. Adjust Value: Use UP or DOWN arrow.
Item # Function Range Default
1 Zone Temp Offset -5.1F to 5.1F 0F 2 Valve Stroke Time 30 sec. To 5 min. 120 sec. 3 Fan Delay to OFF 0 to 10 Minutes 0 Sec. 4 Compressor
30 Sec. To 10 min. 120 Sec.
Minimum Off Time
5 Purge Cycle 0 = Time Based
1 = Temperature Based
For more information see: www.pecomanufacturing.com
© COPYRIGHT 2005 PECO, INC. ALL RIGHTS RESERVED P/N 68837 3220-1471 Rev 0 Page 2
Power-Up Operating Sequence
Upon application of power, a TA158 will go directly to normal operation.