Peco PERFORMANCE PRO MULTI-FAN Quick Start Manual

Page 1
QUICK START GUIDE
SET CLOCK, YEAR, MONTH, DAY
1
1. Press ▲/ ▼ to select 12 or 24 HR mode, then press Next.
2. Press ▲/ ▼to select hour, then press Next.
3. Press ▲/▼to select minutes, then press Next.
4. Press ▲/ ▼ to select current year, then press Next.
5. Press ▲/ ▼ to select current month, press Next.
7. Press Done to complete operation. Note: Select More > Clock, to access after setup.
ACCESS SERVICE MENUS
2
PERFORMANCE PRO MULTI-
CONFIGURE SERVICE MENUS
3
The following Service Menus (SM) commonly require confi guration. Please verify that these are set for your specifi c application. Additional confi guration may be required. Refer to Table 2 for all available Service Menus.
• SM 100 = Programmable or Nonprogrammable
• SM 110 = System Type
• SM 121 = Number of Fan Speeds
• SM 130 = Reversing Valve
• SM 135 = W1 heat output NO or NC
• SM 170 = Remote Sensors
• SM 265 = Single or Dual Setpoint Operation
4
WIRING: TERMINAL DESIGNATIONS
1. Connect wires for appropriate system type (Table 1).
!
(24 VAC).
WARNING: DISCONNECT POWER BEFORE BEGINNING INSTALLATION.
• CAUTION: Use copper wire only. Insulate or wire-nut all unused leads.
• Use care to avoid electrostatic discharge to thermostat
• CAUTION: Do not connect unused wires together
• ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C
FAN
1. Hold lower right and lower left keys for fi ve seconds.
2. Press Next or Go Back button to select a Service Menu.
3. Press ▲/ ▼ to select option.
4. Press Done when complete.
Service
Menu
Current
option
TABLE 1. TERMINAL BLOCK DESIGNATIONS
Fan Coil (Conventional) Heat Pump
C 24 VAC, Unswitched side C 24 VAC, Unswitched side
W1 Stage 1 Heat B/O Reversing Valve
W2 Stage 2 Heat AUX Auxiliary Heat (Stage 2 or 3)
G FAN High G FAN High
A FAN Medium A FAN Medium
E FAN Low E FAN Low
Y1 Stage 1 Cool Y1 Compressor Stage 1
Y2 Stage 2 Cool Y2 Compressor Stage 2
RH
RC
SC Sensor Common SC Sensor Common
S1 Indoor Remote Sensor S1 Indoor Remote Sensor
S2 Occupancy Sensor S2 Occupancy Sensor
S3
24 VAC Power for heating, switched side
24 VAC Power for cooling, switched side
Seasonal Changeover Switch OPEN=Cooling in Summer CLOSED=Heating in Winter
24 VAC Power for heating,
RH
switched side
24 VAC Power for cooling,
RC
switched side
S3 NA
© COPYRIGHT 2013 PECO, INC. ALL RIGHTS RESERVED. P/N 70864 3220-2318 REV 00
Page 2
FAN LOW
TYPICAL FAN COIL WIRING DIAGRAM
5
6
FAN SPEED SELECTION
C
WI
Y1
G
A
E
RH
RC
SC
S1
S2
24 VAC Unswitched
Heat Valve
Cool Valve
FAN HIGH
FAN MED
FAN LO
24 VAC Switched Side
Sensor Common
Remote Sensor
OCC Sensor
Fan Speed icon
1. Press the Fan button to select speed/operation. Note: Fan Speed is noted as follows:
24 VAC
FAN HIGH
FAN MED
Aquastat
S3
OPEN= Summer CLOSED = Winter
TABLE 2. ADVANCED CONFIGUR ATION: SERVICE MENUS
Some Service Menus may not be available, depending on system type (SM 110).
MENU FEATURE OPTIONS STD. DEFAULT DESCRIPTION / COMMENTS
100 Schedule Format 0-3 1 Select the schedule format on the T8000 Series. (Menu not available on non-programmable
101 Daylight-Saving
110 System Type 1-13 1 Select the appropriate system con guration (determines available Service Menus).
© COPYRIGHT 2013 PECO, INC. ALL RIGHTS RESERVED. P/N 70864 3220-2318 REV 00
Time
0,1 0 Select daylight-saving time as it follows standard format in U.S.: It begins second Sunday of
2. Press Done when complete.
ON = Continuous Fan Operation AUTO = Fan Cycles with Heating and Cooling
thermostats.) 0 = nonprogrammable 1 = programmable 2 = 5-1-1 schedule 3 = 5-2 schedule
March at 2:00 AM and ends on the  rst Sunday of November at 2:00 AM. 0 = Disabled 1 = Enabled (2007 U.S. Format)
1 = 1 Heat/1 Cool conventional 2 = 1 Heat/1 Cool heat pump 3 = Heat only without fan (2-wire systems) 4 = Heat only with fan 5 = Cool only 6 = 2 Heat/1 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 7 = 2 Heat/2 Cool multistage conventional 8 = 2 Heat/ 1 Cool multistage conventional 9 = 1 Heat/ 2 Cool multistage conventional 10 = 2 Heat/ 2 Cool heat pump (no auxiliary heat) 11= 3 Heat/ 2 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 12 = NA 13= NA
Page 3
MENU FEATURE OPTIONS STD. DEFAULT DESCRIPTION / COMMENTS
121 Fan Speeds 1, 2, 3, 4 3 Allows selection of multiple fan speeds.
130 O/B Reversing
valve
135 W1 Output
Conguration
150 Backlight 0,1 0 0 = Backlight temporarily on
170 Remote Sensor 0-8 0 Select sensor if used. Contact PECO for information on the T8000 Series Indoor Remote Zone Sensor.
240 Number of Program
Periods
250 Clock format 12 or 24 Hours 12 12 = 12-hour clock mode
260 Temperature Format
(°F or °C)
265 Single/Dual Setpoint 0,1 1 Determines if single user override setpoint is used, or if user sets heat and cool setpoints independently.
290 Range Low 50-90 °F or
300 Range High 50-90 °F or
310 Setback Low Off; 50-82°F or
320 Setback High Off; 58-90°F or
330 Zone Temp Offset +/-9°F or +/-
340 Keypad Lockout 0-3 0 Restricts access to certain features of device; Service Menu still available if keypad lockout is enabled.
341 Enable Pin Access 0,1 0 Applies a 3 digit access code to enter Service Menu 342
342 Set PIN 000-999 000 Choose a 3-digit PIN access code.
350 Fan Mode 1-3 3 1 = ON: Fan is always on, regardless of demand
360 System Mode 0-3 1 Allows ability to determine which system modes the occupant can select.
0,1 0 When 0, output is active for cooling. When 1, output is active for heating.
0,1 0 Changes operation of W1 for Active to Open (NC Normally Closed) to Active to Close (NO
2; 4 events 4 2 = 2 events per day (Selections OCC1 and UnOcc1)
0,1 1 0 = Celsius
10-32°C
10-32°C
11-27°C
11-32°C
4.5°C
© COPYRIGHT 2013 PECO, INC. ALL RIGHTS RESERVED. P/N 70864 3220-2318 REV 00
1 = Single speed Fan (G terminal) 2 = 2-speed Fan (G and A Terminals) 3 = 3-speed Fan (G,A and E Terminals) 4 = 3-speed Staged Fan
0 = (O) Active with cooling 1 = (B) Active with heating
Normally Open). 0 = NC Operation 1 = NO Operation
1 = Backlight always on (low intensity, 24V only)
0 = No Remote Sensors 1 = Remote Indoor Sensor Only 2 = Not Used 3 = Not Used 4 = Not Used 5 = Not Used 6 = S3 Input with Aquastat Only 7 = S3 Input with Aquastat and S1 with Remote Indoor Sensor 8 = Not Used
4 = 4 events per day (Selections Occ1-UnOcc1-Occ2- UnOcc2)
24 = 24-hour clock mode
1 = Fahrenheit
0 = Dual Setpoint (Heat and Cool) 1 = Single Override Setpoint (Single Setpoint with auto changeover algorithm)
50°F (10°C)
90°F (32°C)
55°F (13°C) Temperature setpoint thermostat will Heat to when in Setback mode (Off sets Heating to ~45F Setback).
90°F (32°C) Temperature setpoint thermostat will Cool to when in Setback mode. (Off sets Cooling to ~150F in
0°F (18 °C) Adjusts the sensed Zone Temperature displayed, allowing calibration in the eld.
Choose the lowest selectable temperature setpoint value.
Choose the highest selectable temperature setpoint value.
0 = Off 50-82°F (11-27°C)
Setback). 0 = Off (disabled) 58-90°F (11-32°C)
0 = No key pad lockout (Default) 1 = Disables Schedule and System keys 2 = Disables Schedule, System, and Fan keys 3 = Disables all keys
0 = Disable 1 = Enable
2 = Auto: Fan is only on with heating or cooling demand 3 = ON or Auto: Occupant can choose either selection
0 = OFF, Auto 1 = OFF, Heat, Cool, Auto 2 = OFF, Heat, Cool 3 = Heat, Cool, Auto
Page 4
MENU FEATURE OPTIONS STD. DEFAULT DESCRIPTION / COMMENTS
375 Purge Enable 0-3 0 0 = No Purge
376 Purge Duration 1-3 1 De nes how long to open the valve to perform the purge function.
377 Purge Frequency 0-2 0 De nes how long to open the valve to perform the purge function.
380 Minimum Deadband
Adjustment
395 Temporary Occupied
Duration Limit
480 Minimum Off Time Range:
500 Programmable/
Intermittent Fan
501 Intermittent Fan On
Time
502 Intermittent Fan Off
Time
520 Default Display
Icons
530 Revision Upon menu selection the  rmware revision,  rmware checksum and con guration checksum is
540 Factory Default
Reset
600 System Test Main
Output (Cool)
610 System Test Main
Output (Heat)
620 System Fan Test
Output
900 Factory Use Only -- -- Factory Use Only
901 Factory Use Only -- -- Factory Use Only
902 Factory Use Only -- -- Factory Use Only
1-10°F, 0.5-5°C 3°F A changeover deadband value prevents short cycling between heating and cooling modes. The value is
0-4 hours 0 The temporary User Override is limited by the time de ned in this service menu.
0-10 Minutes
0-2 0 In programmable mode, fan will operate continuously during occupied periods or with demand during
1-60 minutes 5 minutes De nes the duration in which fan low will be on. Fan On will be activated after Fan Off time has passed.
0-60 minutes 25 minutes De nes the duration in which fan low will be off. Fan Off will be activated after Fan On time has passed.
0-4 0 Select icons that will be displayed in the Default Display screen.
0,1 0 When Enable is selected the device will return to factory default settings.
0-2
0-3 0 If either stage is enabled it will activate the associated output for 10 minutes. The Fan output will
0-3 0 0 = Disabled
4 Sets the minimum off time for both the heat and cool output.
0
1 = W1 purge 2 = Y1 Purge 3 = W1 & Y1 purge
1 to 3 minutes
0 = Every 24 Hours 1 = Every 12 Hours
2 = Every 6 Hours
adjustable to meet various HVAC system requirements.
0 = Remainder of time until the next scheduled event. 1 = 1 Hour 2 = 2 Hours 3 = 3 Hours 4 = 4 Hours
unoccupied periods. In intermittent mode, fan will operate based on the on and off times set in menus 501 and 502 whenever there is no call for fan. 0 = Disable 1 = Programmable Fan: Fan operates continuously in occupied periods or with demand in unoccupied periods. 2 = Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502.
A selection of 0 will result in continuous Fan.
0 = Time, Temp, SP 1 = Time, Temp 2 = Time only 3 = Temp only 4 = No Display
displayed.
0 = Disable 1 = Enable Note: Press “Done” key to complete process.
If either stage is enabled it will activate the associated output for 10 minutes. The Fan output will automatically turn on. If a different service menu is selected the output will be disabled. 0 = Disable 1= Cool Stage 1 2 = Cool Stage 2
automatically turn on if con gured to do so. If a different service menu is selected the output will be disabled. (Note: Aux heat could be stage 2 or stage 3 based on con guration) 0 = Disable (Default) 1 = Heat Stage 1 2 = Heat Stage 2 3 = Heat Stage 3
1 = Low Speed 2 = Medium Speed 3 = High Speed
WARNING: Service Menu 375 may disable fan operation during valve
!
purge. This feature should be set to 0 (zero) unless outputs are connected
to hydronic heating or cooling valves. Failure to follow this instruction can result in damage to equipment and/or property.
© COPYRIGHT 2013 PECO, INC. ALL RIGHTS RESERVED. P/N 70864 3220-2318 REV 00