1. Press ▲/ ▼ to select 12 or 24 HR mode, then
press Next.
2. Press ▲/ ▼to select hour, then press Next.
3. Press ▲/▼to select minutes, then press Next.
4. Press ▲/ ▼ to select current year, then press Next.
5. Press ▲/ ▼ to select current month, press Next.
6. Press ▲/ ▼ to select the calendar day number.
7. Press Done to complete operation.
Note: Select More > Clock, to access after setup.
ACCESS SERVICE MENUS
2
PERFORMANCE PRO MULTI-
CONFIGURE SERVICE MENUS
3
The following Service Menus (SM) commonly require
confi guration. Please verify that these are set for your
specifi c application. Additional confi guration may be
required. Refer to Table 2 for all available Service Menus.
• SM 100 = Programmable or Nonprogrammable
• SM 110 = System Type
• SM 121 = Number of Fan Speeds
• SM 130 = Reversing Valve
• SM 135 = W1 heat output NO or NC
• SM 170 = Remote Sensors
• SM 265 = Single or Dual Setpoint Operation
4
WIRING: TERMINAL DESIGNATIONS
1. Connect wires for appropriate system type
(Table 1).
!
▲
(24 VAC).
WARNING: DISCONNECT POWER BEFORE BEGINNING INSTALLATION.
• CAUTION: Use copper wire only. Insulate or wire-nut all unused leads.
• Use care to avoid electrostatic discharge to thermostat
• CAUTION: Do not connect unused wires together
• ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C
FAN
1. Hold lower right and lower left keys for fi ve
seconds.
2. Press Next or Go Back button to select a
Service Menu.
3. Press ▲/ ▼ to select option.
4. Press Done when complete.
Service
Menu
Current
option
TABLE 1. TERMINAL BLOCK DESIGNATIONS
Fan Coil (Conventional) Heat Pump
C24 VAC, Unswitched side C24 VAC, Unswitched side
W1Stage 1 HeatB/OReversing Valve
W2Stage 2 HeatAUXAuxiliary Heat (Stage 2 or 3)
GFAN HighGFAN High
AFAN MediumAFAN Medium
EFAN LowEFAN Low
Y1Stage 1 CoolY1Compressor Stage 1
Y2Stage 2 CoolY2Compressor Stage 2
RH
RC
SCSensor CommonSCSensor Common
S1Indoor Remote SensorS1Indoor Remote Sensor
S2Occupancy SensorS2Occupancy Sensor
S3
24 VAC Power for heating,
switched side
24 VAC Power for cooling,
switched side
Seasonal Changeover Switch
OPEN=Cooling in Summer
CLOSED=Heating in Winter
1 = Single speed Fan (G terminal)
2 = 2-speed Fan (G and A Terminals)
3 = 3-speed Fan (G,A and E Terminals)
4 = 3-speed Staged Fan
0 = (O) Active with cooling
1 = (B) Active with heating
Normally Open).
0 = NC Operation
1 = NO Operation
1 = Backlight always on (low intensity, 24V only)
0 = No Remote Sensors
1 = Remote Indoor Sensor Only
2 = Not Used
3 = Not Used
4 = Not Used
5 = Not Used
6 = S3 Input with Aquastat Only
7 = S3 Input with Aquastat and S1 with Remote Indoor Sensor
8 = Not Used
4 = 4 events per day (Selections Occ1-UnOcc1-Occ2- UnOcc2)
24 = 24-hour clock mode
1 = Fahrenheit
0 = Dual Setpoint (Heat and Cool)
1 = Single Override Setpoint (Single Setpoint with auto changeover algorithm)
50°F (10°C)
90°F (32°C)
55°F (13°C)Temperature setpoint thermostat will Heat to when in Setback mode (Off sets Heating to ~45F Setback).
90°F (32°C)Temperature setpoint thermostat will Cool to when in Setback mode. (Off sets Cooling to ~150F in
0°F (18 °C)Adjusts the sensed Zone Temperature displayed, allowing calibration in the eld.
Choose the lowest selectable temperature setpoint value.
Choose the highest selectable temperature setpoint value.
0 = Off
50-82°F (11-27°C)
Setback).
0 = Off (disabled)
58-90°F (11-32°C)
0 = No key pad lockout (Default)
1 = Disables Schedule and System keys
2 = Disables Schedule, System, and Fan keys
3 = Disables all keys
0 = Disable
1 = Enable
2 = Auto: Fan is only on with heating or cooling demand
3 = ON or Auto: Occupant can choose either selection
0 = OFF, Auto
1 = OFF, Heat, Cool, Auto
2 = OFF, Heat, Cool
3 = Heat, Cool, Auto
376Purge Duration1-31De nes how long to open the valve to perform the purge function.
377Purge Frequency0-20De nes how long to open the valve to perform the purge function.
380Minimum Deadband
Adjustment
395Temporary Occupied
Duration Limit
480Minimum Off TimeRange:
500Programmable/
Intermittent Fan
501Intermittent Fan On
Time
502Intermittent Fan Off
Time
520Default Display
Icons
530Revision——Upon menu selection the rmware revision, rmware checksum and con guration checksum is
540Factory Default
Reset
600System Test Main
Output (Cool)
610System Test Main
Output (Heat)
620System Fan Test
Output
900Factory Use Only----Factory Use Only
901Factory Use Only----Factory Use Only
902Factory Use Only----Factory Use Only
1-10°F, 0.5-5°C3°FA changeover deadband value prevents short cycling between heating and cooling modes. The value is
0-4 hours0The temporary User Override is limited by the time de ned in this service menu.
0-10 Minutes
0-20In programmable mode, fan will operate continuously during occupied periods or with demand during
1-60 minutes5 minutesDe nes the duration in which fan low will be on. Fan On will be activated after Fan Off time has passed.
0-60 minutes25 minutesDe nes the duration in which fan low will be off. Fan Off will be activated after Fan On time has passed.
0-40Select icons that will be displayed in the Default Display screen.
0,10When Enable is selected the device will return to factory default settings.
0-2
0-30If either stage is enabled it will activate the associated output for 10 minutes. The Fan output will
0-300 = Disabled
4Sets the minimum off time for both the heat and cool output.
0
1 = W1 purge
2 = Y1 Purge
3 = W1 & Y1 purge
1 to 3 minutes
0 = Every 24 Hours
1 = Every 12 Hours
2 = Every 6 Hours
adjustable to meet various HVAC system requirements.
0 = Remainder of time until the next scheduled event.
1 = 1 Hour
2 = 2 Hours
3 = 3 Hours
4 = 4 Hours
unoccupied periods. In intermittent mode, fan will operate based on the on and off times set in menus
501 and 502 whenever there is no call for fan.
0 = Disable
1 = Programmable Fan: Fan operates continuously in occupied periods or with demand in
unoccupied periods.
2 = Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502.
A selection of 0 will result in continuous Fan.
0 = Time, Temp, SP
1 = Time, Temp
2 = Time only
3 = Temp only
4 = No Display
If either stage is enabled it will activate the associated output for 10 minutes. The Fan output will
automatically turn on. If a different service menu is selected the output will be disabled.
0 = Disable
1= Cool Stage 1
2 = Cool Stage 2
automatically turn on if con gured to do so. If a different service menu is selected the output will be
disabled. (Note: Aux heat could be stage 2 or stage 3 based on con guration)
0 = Disable (Default)
1 = Heat Stage 1
2 = Heat Stage 2
3 = Heat Stage 3
1 = Low Speed
2 = Medium Speed
3 = High Speed
WARNING: Service Menu 375 may disable fan operation during valve
!
purge. This feature should be set to 0 (zero) unless outputs are connected
▲
to hydronic heating or cooling valves. Failure to follow this instruction can
result in damage to equipment and/or property.